Page 1: BBConn Cloud Help

BBconn CloudUser's Guide

Customer Product ManualPart 1129243_01

Issued 06/20

NORDSON CORPORATION • DULUTH, GEORGIA • USAwww.nordson.com

This document contains important safety information.Be sure to read and follow all safety information in thisdocument and any other related documentation.

Page 2: BBConn Cloud Help

Part 1129243_01 � 2021 Nordson CorporationAll rights reserved

Nordson Corporation welcomes requests for information, comments, and inquiries about its products. General informationabout Nordson can be found on the Internet using the following address: http://www.nordson.com.

Address all correspondence to:

Nordson CorporationAttn: Customer Service11475 Lakefield Drive

Duluth, GA 30097

Notice

This is a Nordson Corporation publication which is protected by copyright. Original copyright date 2021.No�part�of�this�document may be photocopied, reproduced, or translated to another language without the prior written

consent of Nordson�Corporation. The�information�contained in this publication is subject to change without notice.

Trademarks

4800 INTEGRA, Allegro, Apogee, Artiste, Asymtek, Automove, Avex, BaitGun, BKG, Blue Box, BM-32, BM-58, BM-63, Bowtie,Build‐A‐Part, CF, Century, CleanSleeve, CleanSpray, Color‐on‐Demand, ColorMax, Conexis, Connections to Life, Contour, Control�Coat,

Coolwave, Cross‐Cut, CrystallCut, Dage, Dial‐A‐Dose, Dima, DispenseJet, DispenseMate, DuraBlue, DuraDrum, DuraPail, e.dot,e-stylized, EasyCoat, Easymelt, Ecodry, Econo‐Coat, EDI, EFD, Eliminator, Encore, Equatherm, Excel 2000, Fibrijet, Flextrak, Fluidmove,FoamMelt, FoamMelt - stylized, FoamMix, Freedom, Fulfill, HDLV, Heli‐flow, iControl, iDry, iFlow, IntelliJet, Isocore, Iso‐Flo, iTrax, KISS,

Lean�Cell, LogiComm, March, Matrix, MatriX, Maverick, Measuring the Invisible, MEG, Meltex, MicroCoat, MicroMark, Micromedics,Micro‐Meter, Microshot, Millennium, MiniBlue, Mini Squirt, NexJet, No-Drip, Nordson, Nordson - stylized, Nordson and Arc, NYTVision,OptiMix, Optima, Optimum, Package of Values, Paragon, PermaFlo, PICO, PicoPulse Plasmod, Poly-Check, Polymer Solution Casting,

Porous�Coat, Posi‐Dose, PowderGrid, Precisecoat, PrintPlus, ProBlue, ProBlue Liberty, Prodigy, Pro‐Flo, Program‐A‐Bead,Program‐A‐Shot, Program‐A‐Stream, Program‐A‐Swirl, Pro‐Meter, Pulsar, Quantum, Ratio‐Pak, RBX, RediSet, Rhino, Saturn,

Saturn with Rings, Scoreguard, Sealant Equipment & Engineering, Inc., SEE (and design), See‐Flo, Select�Charge, Select�Coat,Select Cure, Servo‐Flo, Shot‐A‐Matic, Signature - stylized, Slautterback, Smart‐Coat, Smart-Gun, SolderPlus, Spectrum, Speed‐Coat,StediFlo, Stratablend, SureBead, Sure Coat, SureWrap, Symphony, Tip-Seal, TRAK, Tribomatic, Trilogy, TrueBlue, TrueCoat, Turbo,

Ultra, u‐TAH, Value Plastics, Vantage, Vention Medical, Vention Medical Advancing Your Innovations For Health, VersaBlue, Versa‐Coat,VersaDrum, VersaPail, Versa‐Spray, VP stylized, When you expect more., X-Plane, Xaloy, Xaloy - stylized, YesTech, and

2 Rings (design) are registered trademarks of Nordson Corporation.

Accubar, Active Nozzle, Advanced Plasma Systems, AeroDeck, AeroWash, AirShield, AltaBlue, AltaSlot, Alta Spray, ATS, Auto‐Flo,Autoflex, AutoScan, Axiom, BBconn, Best Choice, Better Dispensing, Blue Series, Bravura, CanPro, Champion, Check Mate, Classic IX,ClassicBlue, Clean�Coat, Cobalt, Concert, ContourCoat, Control Weave, Controlled Fiberization, CPX, cScan+, cSelect, Cyclo‐Kinetic,

DispensLink, Dry Cure, DuraBraid, DuraCoat, DuraPUR, e.dot+, Emerald, E‐Nordson, Easy Clean, EasyOn, EasyPW, Eclipse, EcoBead,EdgeControl, Equalizer, Equi=Bead, FillEasy, Fill�Sentry, FlexSeam, Flow Coat, FluxPlus, G‐Net, G‐Site, Genius, Get Green with Blue,

Horizon, Inspire, iON, Iso‐Flex, iTrend, JetStream, Lacquer Cure, LightTite, LoadermoveTouch, Maxima, Mesa, MicroDot, MicroFin,MicroMax, MicroSpray, Mikros, MiniEdge, Minimeter, MiniPUR, Multifill, MultiScan, Myritex, Nano, OmniScan, OptiStroke, Optix,

Partnership+Plus, PatternJet, PCI, PharmaLok, PicoDot, PicoTouch, Pinnacle, Powder�Pilot, Powder Port, Powercure, Process Sentry,Pulse Spray, PURBlue, PUReOne, PURJet, Qadence, Ready Coat, RediCoat, RollVIA, Royal Blue, Select�Series, Sensomatic,

Shaftshield, SheetAire, Smart, Smart Tune, Smartfil, SolidBlue, Spectral, SpeedKing, Spray Works, StediTherm, StrokeControl, Summit,SureFoam, Sure�Mix, SureSeal, Swirl�Coat, TAH, Trade�Plus, ThruCoat, ThruCure, ThruWave, Trio, TruFlow, Ultraflex, Ultrasaver,

Ultrasmart, Unity, UNITYMotion, Universal, Ultra FoamMix, UltraMax, ValueMate, Versa, VersaPUR, Vista, VP Quick Fit, VP Quick‐Fit stylized, WaferLock, Web Cure, 781Mini, and 787Mini are�trademarks of Nordson�Corporation.

Designations and trademarks stated in this document may be brands that, when used by third parties for their own purposes, could lead to violation of the owners' rights.

EtherNet/IP� is a trademark used under license by ODVA.PROFIBUS and PROFINET are registered trademarks of PROFIBUS and PROFINET International (PI).

Studio 5000 and RSLogix 5000 are trademarks of Rockwell Automation.TIA Portal and STEP 7 are trademarks of Siemens.

Page 3: BBConn Cloud Help

BBconn Cloud User’s Guide 1

Part 1129243_01� 2021 Nordson Corporation

Table of Contents

About BBconn Cloud 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Theory of Operation 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Getting Started 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Creating a BBconn Cloud Account 4. . . . . . . . . . . . . . . . . . . . . . . . . . .Logging into your BBconn Cloud Account 6. . . . . . . . . . . . . . . . . . . . . . . . .

Getting Updates and Help 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Using the MEDIA CENTER 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Using the HELP CENTER 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Contacting Us 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Defining Runtime Settings 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .About Managing .NOR Files 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Using the SETUP TOOL 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Runtime Settings 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .System Settings 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PLC Communication Integration 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Creating and Customizing the ADI Map File 15. . . . . . . . . . . . . . . . . . . .Exporting a .PLC File from BBconn Cloud 17. . . . . . . . . . . . . . . . . . . . . .Modifying an Existing .PLC File 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Programming the PLC to Communicate with the Melter 18. . . . . . . . . .Starter Kits 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Understanding Nordson's Data Mapping System 20. . . . . . . . . . . . . . . . . .BBconn Cloud for the Cyclic Message 21. . . . . . . . . . . . . . . . . . . . . . . . .Acyclic Messages 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Using the Tools 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Viewing the Event Log 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Viewing and Managing System Configurations 24. . . . . . . . . . . . . . . . . .Restoring a Control System to the Factory Default Settings 25. . . . . . . . .

BBconn Cloud Account Management 26. . . . . . . . . . . . . . . . . . . . . . . . .Editing Your Profile 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Changing Your Password 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Registering or Editing Melter Models 27. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Registering a Melter on BBconn Cloud 27. . . . . . . . . . . . . . . . . . . . . . . .Editing a Registered Melter 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Managing Sub Users 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Adding a Sub User 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Editing Sub User Details 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Software Updates 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 4: BBConn Cloud Help

BBconn Cloud User’s Guide 1

Part 1129243_01� 2021 Nordson Corporation

About BBconn Cloud

BBconn Cloud is a web-based application used to configure Nordson controlsystems.

Use BBconn Cloud as follows:

� Account Management

� Register and manage one or more Nordson control systems

� Manage licenses

� Manage users associated with one or more Nordson control systems

� Download software updates

� System Configuration

� Define runtime and system settings

� View and manage the control system configuration code and

accessories

� Define PLC Flexible Map

� Create recipes

� View Logs and Reports

Page 5: BBConn Cloud Help

BBconn Cloud User’s Guide2

Part 1129243_01 � 2021 Nordson Corporation

Theory of Operation

BBconn Cloud is a web-based application that you can use to set up yourcontrol system. A .NOR file is used to export, using a USB drive, the setup ofyour control system and to import recipes and the event log/reports from thecontrol system back to BBconn Cloud for viewing.

This manual details how to use the BBconn Cloud tool. You will need to referto the documentation that came with your control system for specific detailsabout each runtime/system feature and option.

NOTE:

� When transferring files between the control system and BBconn

Cloud, the USB drive must be formatted using FAT or FAT32. Noother format, such as NTFS and exFAT are supported.

Page 6: BBConn Cloud Help

BBconn Cloud User’s Guide 3

Part 1129243_01� 2021 Nordson Corporation

Getting StartedGetting your melter into operation is a two-step process:

Step Refer to… Description

1The Product or Product installationmanual that came with your controlsystem

� Install and connect power to the melter.

� Connect your melter to a PLC or connect the optional

Nordson touchscreen.

2This manual, BBconn Cloud User'sGuide

� Register and set up a BBconn Cloud account.

� Use the BBconn Cloud web-based application to

create a .NOR file which includes system operationsettings and an optional .PLC file for PLC integrationthat you can import to your control system.

� When done, export settings to a .NOR file that you

can import into your control system.

The rest of this manual details the tasks listed in Step 2.

NOTES:

� When transferring files between the control system and BBconn

Cloud, the USB drive must be formatted using FAT or FAT32. Noother format, such as NTFS and exFAT are supported.

� Refer to the documentation that came with your control system for

items listed in step 1. You can view and print the documentation fromthe BBconn Cloud Media Center.

Page 7: BBConn Cloud Help

BBconn Cloud User’s Guide4

Part 1129243_01 � 2021 Nordson Corporation

Creating a BBconn Cloud Account BBconn Cloud is a web application that you can use from most any browser-enabled device. Supported browsers include:

Browser MacintoshVersion

Windows Version Iphone Droid Devices

Apple Safari 10.12 Sierra andhigher

Not available 10.12 Sierra andhigher

Not available

Google Chrome Version 79.0 andhigher

Version 79.0 andhigher

Version 79.0 andhigher

Version 79.0 andhigher

Microsoft InternetExplorer

Not supported Not supported

Not supported Not supported

Mozilla Firefox Version 68.0 andhigher

Version 68.0 andhigher

Edge

Version 44.18362and higher

Version -44.18362 andabove, Browserengine -EdgeHTML18.1836

UC Browser Version - 7.0 andhigher

Version - 7.0 andhigher

NOTE:

� A BBconn Cloud account can include multiple sub users. Refer to

Adding a Sub User for more information.

1. Locate and write down the Serial Number and Unique Identification ofyour melter. Typically this information is located somewhere on thebottom frame of the unit. You will need this information when creatingyour BBconn Cloud account.

2. Open a supported browser and enter the following URL:https://bbconncloud.nordson.com.

3. Select Sign Up and enter the required information. When done, selectCONTINUE.Notes:

� When entering your phone number, make sure to enter numbers only-

no hyphens or parentheses. You country code is automaticallyincluded based on you country selection.

� You may want to write down your username and password.

� The Configuration Code field auto-populates after you enter the

Serial and Unique ID Numbers.

Page 8: BBConn Cloud Help

BBconn Cloud User’s Guide 5

Part 1129243_01� 2021 Nordson Corporation

� You must Agree to Nordson Terms of Service and Privacy Policy

to create your account. Click on the links to view details.

4. To complete the registration, select Accept and Sign Up. An email willbe sent to your registered email. If you do not receive an email [email protected] in your inbox, check your bulk or Spamfolder.

� Open the message and click on the Confirm the email link.

� A new browser opens to Nordson BBconn Cloud Click the

CONFIRM YOUR EMAIL button again, then select the LOG INTOTHE SYSTEM button to start setting up your melter.

NOTE: Refer to the next section, Logging into your BBconn CloudAccount.

Page 9: BBConn Cloud Help

BBconn Cloud User’s Guide6

Part 1129243_01 � 2021 Nordson Corporation

Logging into your BBconn Cloud Account1. Open a supported browser and enter the following URL:

https://bbconncloud.nordson.com.

2. Enter your Email Address and Password.

TIP: Select the Remember me? option to save your login information soyou do not have to enter your login information each time you want toaccess your BBconn Cloud account.

3. Select SIGN IN. The BBconn Cloud Home page appears. Refer to thefollowing table for a detailed explanation of each option.

Model Registration

Sub User Account

Setup Tool

Media Center

Manage Licenses

Help Center

Recently Viewed Event Log Files

Welcome (user name)

Thanks for using our BBconn Cloud, your dashboard is ready to use.DASHBOARD

Recently Created or Imported Setting Files

Figure 1 BBconn Cloud Home page

NOTE: Refer to the section, Defining Runtime Settings to continue.

Page 10: BBConn Cloud Help

BBconn Cloud User’s Guide 7

Part 1129243_01� 2021 Nordson Corporation

Icon Description What you can do ….

Dashboard Return to the your Dashboard page.

ModelRegistration

� Add additional control systems to this account. There is no limit

to the number of control systems you can manage.

� View and Edit the melter Serial Number, UID. and Description.

� View, Edit, Edit as New File, and Delete .NOR files or edit the

.NOR file description.Note: .NOR files contain system settings and recipes that youcan edit and export to other same-model/same-configurationmelters. You can also view logs and various reports. Similarly,you can also import .NOR files from a melter into BBconn Cloudfor troubleshooting or to edit configuration and recipes.

� Download an existing .NOR file to a USB drive so you can upload

it to other same-model/same-configuration control systems.

Sub UserAccount

Add users to this BBconn Cloud account. You can decide to give auser Read/Write or Read-Only access.

Notes:

� An email is sent to the new user to confirm and to set up a

password.

� Sub user email (user login name) must be unique.

Setup Tool Create or modify system and operational settings which are saved to.NOR file. You can select from one of the following:

� Load from USB/Computer: Modify an exported .NOR file from

a melter.

� Use Previous File: Modify the most recent BBconn Cloud

version of the .NOR file.

� Create New: Generate a .NOR file based on factory defaults.

Notes:

� The .NOR filename structure is [control system name]

_2019-09-29_220813.nor, where 2019-09-29 is the date and220813 is the time (including seconds).

� You can also select the Recently Created or Imported

Setting Files link on the Home page to view a chronologicallist of .NOR files that you have recently created or modified.You can edit or download the .NOR file to a FAT or FAT32formatted USB drive.

Media Center � Download the latest control system software update.

� Download the latest control system documentation.

ManageLicenses

Purchase one or more licenses for new features or options as theybecome available.

Note:

� Some licenses require additional hardware.

Page 11: BBConn Cloud Help

BBconn Cloud User’s Guide8

Part 1129243_01 � 2021 Nordson Corporation

What you can do ….DescriptionIcon

Help Center View help on how to use the BBconn Cloud application.

Page 12: BBConn Cloud Help

MEDIA CENTER

HELP CENTER

BBconn Cloud User’s Guide 9

Part 1129243_01� 2021 Nordson Corporation

Getting Updates and Help

Using the MEDIA CENTER

Once you log into your account, select MEDIA CENTER to access thefollowing:

� The latest software updates

� Related documentation including manuals, instruction sheets, data

sheets, press releases, and video tutorials

Using the HELP CENTER

Once you log into your account, select HELP CENTER to access BBconnCloud help.

Contacting Us

For BBconn Cloud Technical Support only, click on the bottom right-handcorner of any page. Enter your name, email and, in the message field, yourquestion for the BBconn Cloud administrator.

Contact your field representative or Nordson Technical Support for controlsystem related questions and issues.

Page 13: BBConn Cloud Help

BBconn Cloud User’s Guide10

Part 1129243_01 � 2021 Nordson Corporation

Defining Runtime SettingsTo proceed, you must have already completed the following:

� Unpacked and installed your control system

� Installed any optional hardware

� Created a BBconn Cloud account

� Logged into BBconn Cloud and selected SETUP TOOL

As previously described, the .NOR file includes all runtime and systemsettings your control system requires for production. When done, you mustdownload the .NOR file to a USB drive and import the .NOR file into yourcontrol system. This process is detailed later in this manual.

The following section details how to use the .NOR file with BBconn Cloud.

NOTE:

� When transferring files between the control system and BBconn

Cloud, the USB drive must be formatted using FAT or FAT32. Noother format, such as NTFS and exFAT are supported.

Page 14: BBConn Cloud Help

BBconn Cloud User’s Guide 11

Part 1129243_01� 2021 Nordson Corporation

About Managing .NOR Files

Log into your BBconn Cloud account, and do the following to continue:

To create, view/edit or download… Then…

10 most recently viewed or edited.NOR files

From the Home page, click Recently Created or ImportedSetting Files.

� Select the appropriate link corresponding to the .NOR file you

want to View (edit) or Download. The 10 most recent .NORfiles are listed. The most recent is listed first.

� Select the icon to permanently remove the .NOR file from

your account.

Previously created or imported .NORfile

(all previously viewed or edited .NORfiles)

From the Home page, select MODEL REGISTRATION, thenselect corresponding to the melter (serial number, UID) toview all .NOR files created for this melter.

� Select corresponding to .NOR file you want to either EDIT,

EDIT AS NEW FILE, or DELETE.

� Select DOWNLOAD to save a copy to your /downloads folder

on your computer. You can then copy the .NOR file to a USBdrive so you can import it into your melter.

Load (upload) an exported .NOR fileonto a USB drive from a melter

� Refer to the section titled Backing Up and Restoring the Melter

for more information.

� From the Home page, select SETUP TOOL then LOAD

FROM USB/COMPUTER, then navigate to the location of the.NOR file on the USB drive or computer.

� Enter a brief description, such as which melter this is from or

intended changes. Click SUBMIT to load the .NOR file forviewing/editing.

Open the most recent .NOR file youviewed or edited

� From the Home page, select SETUP TOOL, then USE

PREVIOUS FILE.

� Confirm the .NOR file name, then click SUBMIT to load the

.NOR file for viewing/editing.

Create a new .NOR file with factorydefaults

� From the Home page, select SETUP TOOL then CREATE

NEW.

Download current .NOR file When you are done modifying settings, select the DOWNLOADNOR FILE link located in the lower left-hand side of the page.

� The .NOR file is saved to your /downloads folder on your

computer. You can then copy the .NOR file to a USB drive soyou can import it into your melter.

NOTE: When a .NOR file is uploaded, BBconn Cloud automatically addsthe .NOR file to its associated, registered melter. If you upload a .NOR filethat is not from a melter already registered in your account, BBconn Cloudadds the melter to the Model Registration list.

Page 15: BBConn Cloud Help

SETUP TOOL

LOAD FROM USB/COMPUTER

USE PREVIOUS FILE

CREATE NEW

Please select how to load a configuration file

SETUP TOOL

LOAD FROM USB/COMPUTER

USE PREVIOUS FILE

CREATE NEW

Please select how to load a configuration file

RUNTIME SETTINGS

BBconn Cloud User’s Guide12

Part 1129243_01 � 2021 Nordson Corporation

Using the SETUP TOOL

Once you log into your account, and either create or open an existing .NORfile, you can then view and define the following:

� Runtime Settings

� System Settings

� Communication Settings

� Tools

� Recipes

The following sections detail each SETUP TOOL in greater detail.

NOTE: Refer to the documentation that came with your control system fordetailed information about each control and option.

Runtime Settings

Use Runtime Settings to define specific settings unique for control systemand product production, such as Pressure, Temperature, and Flow Settings.

Refer to the documentation that came with your control system for detailedinformation about each control and option.

NOTE: Runtime Settings can be optionally saved to a recipe. Refer toManaging Recipes for more information.

Page 16: BBConn Cloud Help

BBconn Cloud User’s Guide 13

Part 1129243_01� 2021 Nordson Corporation

System Settings

Use System Settings to define typically one-time system settings that are notincluded in a recipe, but needed for normal control system operation. Forexample, Preferences, Language, Temperature Units, Time/Date Format andNetwork and System I/O Settings to name a few.

Refer to the documentation that came with your control system for detailedinformation about each control and option.

Page 17: BBConn Cloud Help

BBconn Cloud User’s Guide14

Part 1129243_01 � 2021 Nordson Corporation

PLC Communication Integration

Monitoring in real time and managing your control system using your PLC is afive-step procedure:

Step Description

1

Define your network and PLC settings - SETUP TOOLS | SYSTEM SETTINGS /NETWORKING

Virtually all melter data is available through one of the many network protocols, such as Profinetand Ethernet IP to allow the parent machine to control most or all aspects of control systemoperation.

2

Download the appropriate PLC Starter Kit for your control system and PLCmanufacturer from the MEDIA CENTER.

To speed development for the PLC engineer, Nordson has developed Starter Kits for mostcontrol systems. These Starter Kits contain useful data and tools to facilitate control systemintegration into the parent machine as quickly as possible.Parent Machine integration (PMI) Starter Kits contain the following tools:

� Add-On Instructions (AOI) for Allen Bradley or function blocks for Siemens

� Supports only the pre-configured cyclic map. You must use the Nordson-supplied custom

cyclic map. Otherwise, the Add-On Instructions (AOI) will not work.

� Quick start guide and video

� Programmer manual and all applicable GSD/GSDML files, sample code, and sample HMI

screen.

3

Use BBconn Cloud to create a .PLC file containing the ADI map.

Refer to:

� The next section, Creating and Customizing the ADI Map File

� The section, Understanding Nordson's Data Mapping System

4Export the .PLC file from BBconn Cloud to your control system.

Refer to Exporting a .PLC File from BBconn Cloud later in this manual.

5Program the .PLC to communicate with the control system.

Refer to the PLC starter kit for your control system and PLC manufacturer.

The following sections detail steps 3 and 4.

NOTES:

� You must use BBconn Cloud to view, create, and modify .PLC files.

� Your control system comes with a default cyclic map, referred to as

an ADI map. The map is designed with a pre-configured section thatis Nordson’s best estimation of what most customers will select fortheir HMI, and a free section for custom data.

� When used in a network system, Nordson melters always act as

slaves.

Page 18: BBConn Cloud Help

SETUP TOOL

LOAD FROM USB/COMPUTER

USE PREVIOUS FILE

CREATE NEW

Please select how to load a configuration file

PLC COMMUNICATIONS

COMMUNCATION SET­TINGS

BBconn Cloud User’s Guide 15

Part 1129243_01� 2021 Nordson Corporation

Creating and Customizing the ADI Map File

The control system comes with a default cyclic map, referred to as anApplication Data Identifier (ADI) map. The map is designed with apre-configured section of entries, but you can include other elements that youwant.

1

3

2

Fill

SAVE

Flow

General

READ AREA CFG (TO PLC) WRITE AREA CFG (TO PLC)

WORD ADI NUMBER WORD ADI NUMBER

0

1

2

3

4

5

6

7

8

9

Fill Status

Fill

WORDS READ WRITE ADI NUMBER

Fill Control

Actual Fill Level

Target Fill Level

Maximum Fill Time

Lid Open Alert Time

Fill Enable

4

4

1

1

1

1

1

YES

NO

YES

YES

YES

YES

YES

NO

YES

NO

YES

YES

YES

YES

1300

1301

1302

1303

1304

1305

1306

Motor/Pump

Temperature

WORDS READ WRITE ADI NUMBER

0

1

2

3

4

5

6

7

8

9

PLC Mapping and Interface Setup

4

IMPORT EXPORT

Figure 2 PLC Mapping and Interface Setup screen

1. WORDS, READ, WRITE, and ADINUMBER column heads

2. Parameter groups

3. Read/Write data maps

4. Expanded parameter group(Fill group shown)

1. Log into your BBconn Cloud account, then do the following:

� Select SETUP TOOL - create or load a .NOR file.

� Select SYSTEM SETTINGS | PLC COMMUNICATIONS. The PLC

Mapping and Interface Setup screen appears.

2. Select the down arrow � next to each parameter group to expand theselection (For example, General and Temperature).

Page 19: BBConn Cloud Help

Incorrect drag and drop operation

Correct drag and drop operation

BBconn Cloud User’s Guide16

Part 1129243_01 � 2021 Nordson Corporation

3. Select the ADI number, then drag and drop it either into the Read AreaCFG (To PLC) or the Write Area CFG (From PLC) column.

The system automatically fills rows depending on the number of wordsrequired for each parameter.

� READ settings must be dropped only into the the READ area.

� WRITE settings must be dropped into the WRITE area.

� If a setting is both READ and WRITE, such as Target Fill Level

(13003), then you can add it to BOTH the READ and WRITE areas.BBconn Cloud ignores unallowable actions.

� If you try to drop an item into an area that is not available, or if the

cursor is not in the correct location, a red circle with a red lineappears.

� When a drag-and-drop is accepted, a copy icon appears to indicate

that you can release the left click button.

4. Select Save to save the changes, or Cancel to exit without saving.

When you select Save, BBconn Cloud names the .PLC file and saves (orprompts you to save, depending on your browser settings) the file to yourcomputer's \Downloads folder. The .PLC filename structure is a randomset of numbers.

5. Do the following to continue:

� Refer to Exporting a .PLC File from BBconn Cloud.

� Refer to the documentation that came with your control system for

importing the .PLC file.

NOTES:

� You cannot have duplicates in the same AREA. For example, Fill

Status cannot occur twice in the READ area. BBconn Cloud ignoresunallowable actions.

� BBconn Cloud automatically places ADI mapping requests in

sequential order. For example, if nothing is entered in the READ areaand you attempt to drag and drop Fill Status (13000) into thenumber�9 slot, BBconn Cloud automatically places the entry intoslot�0, or the first available slot.

� To delete an ADI entry, left-click inside the field you want to delete

and use the backspace key to delete all the numbers; left-clickanywhere on the screen to exit the field. The ADI entry is cleared.

Page 20: BBConn Cloud Help

SETUP TOOL

LOAD FROM USB/COMPUTER

USE PREVIOUS FILE

CREATE NEW

Please select how to load a configuration file

PLC COMMUNICATIONS

COMMUNCATION SET­TINGS

BBconn Cloud User’s Guide 17

Part 1129243_01� 2021 Nordson Corporation

Exporting a .PLC File from BBconn Cloud

Depending on your control system, you can export the .PLC file by:

� Selecting Save from the PLC Mapping and Interface Setup page.

BBconn Cloud saves the .PLC file to your computer's \Downloadsfolder.

� The .PLC file is also included in the .NOR file and will be installed on

a system during a restore.

1. Log into your BBconn Cloud account, then do the following:

� Select SETUP TOOL - create or load a .NOR file.

� Select SYSTEM SETTINGS | PLC COMMUNICATIONS. The PLC

Mapping and Interface Setup screen appears.

2. Select EXPORT. The .PLC file is saved to your /DOWNLOADS folder onyour computer. You can then transfer the file to the root of a USB drivethat is formatted for FAT or FAT32, then insert the drive into your controlsystem.

The .PLC filename structure is a random set of numbers.

NOTES:

� For steps needed to import the .PLC file to your control system, refer

to the control system manual.

� When you use the PLC Mapping and Interface Setup tool to

download a .PLC file, it is a standalone file.

� When you download a .NOR file from BBconn Cloud, the .PLC file is

also included in the .NOR file.

� When transferring files between the control system and BBconn

Cloud, the USB drive must be formatted using FAT or FAT32. Noother format, such as NTFS and exFAT are supported.

Page 21: BBConn Cloud Help

SETUP TOOL

LOAD FROM USB/COMPUTER

USE PREVIOUS FILE

CREATE NEW

Please select how to load a configuration file

PLC COMMUNICATIONS

COMMUNCATION SET­TINGS

BBconn Cloud User’s Guide18

Part 1129243_01 � 2021 Nordson Corporation

Modifying an Existing .PLC File

You must use BBconn Cloud to modify an existing .PLC file. You can importthe .PLC by itself, or when you import a .NOR file, as the .PLC is alsoincluded.

1. Log into your BBconn Cloud account, then do the following:

� Select SETUP TOOL - create or load a .NOR file.

� Select SYSTEM SETTINGS | PLC COMMUNICATIONS. The PLC

Mapping and Interface Setup screen appears.

2. Select IMPORT to browse for the .PLC file.

Programming the PLC to Communicate with the Melter

Use the Starter Kit for your control system and PLC manufacturer to programyour PLC to communicate with your control system. You can downloadstarter kits from the MEDIA CENTER.

Page 22: BBConn Cloud Help

MEDIA CENTER

BBconn Cloud User’s Guide 19

Part 1129243_01� 2021 Nordson Corporation

Starter Kits

Nordson has developed Starter Kits for the your control system. TheseStarter Kits contain useful data and tools to facilitate melter integration intothe parent machine as quickly as possible.

Parent Machine Integration (PMI) Starter Kits contain the following tools:

� AOI (add-on instructions) for Allen Bradley or function blocks for

Siemens

‐ Supports only the pre-configured cyclic map

‐ If the programmer makes a custom cyclic map, the AOI will not

work.

� Quick start guide

� Quick start video

� Programmer manual

� GSD/GSDML files as applicable

� Sample code

� Sample HMI screen

PMI Starter Kits are available for the following PLC development software:

� Allen Bradley Studio 5000 for ControlLogix and CompactLogix PLCs.

Refer to the Quick Start Guide for Allen Bradley PLC OverEthernet/IP (P/N�1128649).

� Siemens TIA Portal version 13 and above for Siemens S7 1500 and

1200 PLCs. Refer to the Quick Start Guide for Siemens PLC(Using TIA Portal) Over PROFINET (P/N�1128650).

� Siemens Classic STEP7 V5.5 and above for Siemens S7 400 and

300 PLCs. Refer to the Quick Start Guide for Siemens PLC (UsingClassic STEP 7) Over PROFINET (P/N�1128651).

1. Log into your BBconn Cloud account.

2. Select MEDIA CENTER. Refer to the section PLC Starter Kits to locatethe appropriate kit for your PLC.

Page 23: BBConn Cloud Help

BBconn Cloud User’s Guide20

Part 1129243_01 � 2021 Nordson Corporation

Understanding Nordson's Data Mapping System

The data mapping system for the all Nordson control systems was designedto be simple, efficient, and highly customizable. Each piece of data in themap has a number associated with it called an Application Data Identifier(ADI). This unique identifier makes it simple to configure the data mapneeded for your specific application.

The major advantages of the mapping system are:

� Efficient and customizable mapping system that uses both acyclic

(slow) and cyclic (fast) messages

� Pre-configured cyclic map can be customized by the PLC engineer

through BBconn Cloud.

� Acyclic map is composed of a series of ADI/Value pairs that are easily

parsed by the Flex system.

� Possible to control and monitor the melter through cyclic messages,

acyclic messages, or a combination of both

See Figure 3.

PLC

Cyclic (Fast) Object

Control System Melter Data

Cyclic Messaging Acyclic Messaging

Acyclic (Slow) Object

Figure 3 Example of controlling and monitoring the melter through acyclic messages, cyclic messages, or acombination of both

Page 24: BBConn Cloud Help

BBconn Cloud User’s Guide 21

Part 1129243_01� 2021 Nordson Corporation

BBconn Cloud for the Cyclic Message

The cyclic message is typically used for data that is required in real time. Thisdata can include motor speed (if used), alarms, basic status, etc. Becausethis message is sent at a high repeat rate, it is usually kept very small tominimize bus traffic. It is possible for some systems to forego the cyclicmessage and to use only acyclic messages.

See Figure 4. Setting up the map of the cyclic message can be done throughNordson's BBconn Cloud web application. Use the drop-down menus tochoose the data elements to add to the map, and their respective ADIsappear in the list on the right of the screen. Once this map is complete, themap data can be downloaded from BBconn Cloud and then uploaded to yourcontrol system, at which time it is ready for use by the PLC.

NOTE: Most control systems include a default cyclic map with apre-configured section that is Nordson’s best estimation of what mostcustomers will select for their HMI, and a free section for custom data. Thismap can be used as supplied, without editing it through BBconn Cloud. Forthe complete ADI map, refer to Application Data Identifier (ADI) Map(P/N�1128648).

1

3

2

Fill

SAVE

Flow

General

READ AREA CFG (TO PLC) WRITE AREA CFG (TO PLC)

WORD ADI NUMBER WORD ADI NUMBER

0

1

2

3

4

5

6

7

8

9

Fill Status

Fill

WORDS READ WRITE ADI NUMBER

Fill Control

Actual Fill Level

Target Fill Level

Maximum Fill Time

Lid Open Alert Time

Fill Enable

4

4

1

1

1

1

1

YES

NO

YES

YES

YES

YES

YES

NO

YES

NO

YES

YES

YES

YES

1300

1301

1302

1303

1304

1305

1306

Motor/Pump

Temperature

WORDS READ WRITE ADI NUMBER

0

1

2

3

4

5

6

7

8

9

PLC Mapping and Interface Setup

4

IMPORT EXPORT

Figure 4 PLC Mapping and Interface Setup screen

1. WORDS, READ, WRITE, and ADINUMBER column heads

2. Parameter groups

3. Read/Write data maps

4. Expanded parameter group(Fill group shown)

In BBconn Cloud, all data is selectable from the data list (left side of thescreen) by each word’s unique ADI. Choose the data from the list on the left,then drag and drop the ADI into the Read/Write data area. Refer to ManagingPLC Communications under Using BBconn Cloud for procedures.

Page 25: BBConn Cloud Help

BBconn Cloud User’s Guide22

Part 1129243_01 � 2021 Nordson Corporation

Acyclic Messages

Acyclic messages are not predefined in BBconn Cloud. They are built andsent by the PLC “on-the-fly.”

The acyclic message is created from the same complete ADI list as the cyclicmessage, making the acyclic data channel very full-featured and greatlyreduces the amount of data required in the limited cyclic space.

All acyclic data blocks are transmitted/received as an ADI/Data pair. TheADI, chosen from the ADI list in BBconn Cloud or from this manual, isfollowed by the data. One ADI/Data pair is allowed per acyclic message. Thefrequency and content of the messages can vary according to the needs ofthe system.

Acyclic Message

ADI #1

Flex ADI List

SYSTEM STATUS

HOSE1 TEMP

APPLICATOR2 TEMP

HOSE2 TEMP

ADI #2

ADI #3

ADI #4

ADI #n

ADI #1

Data

Acyclic Message

ADI #2

Data

Acyclic Message

ADI #3

Data

… …

Figure 5 Transmission of ADI pairs

Page 26: BBConn Cloud Help

SETUP TOOL

LOAD FROM USB/COMPUTER

USE PREVIOUS FILE

CREATE NEW

Please select how to load a configuration file

TOOLS

Event Log

BBconn Cloud User’s Guide 23

Part 1129243_01� 2021 Nordson Corporation

Using the Tools This section includes information and tasks for advanced users.

Viewing the Event Log1. Log into your BBconn Cloud account.

2. Open an existing .NOR file. Refer to About Managing .NOR Files.

3. Select TOOLS, then EVENT LOG. You can sort and filter the event log foreasier viewing.

NOTE:

� When transferring files between the control system and BBconn

Cloud, the USB drive must be formatted using FAT or FAT32. Noother format, such as NTFS and exFAT are supported.

Page 27: BBConn Cloud Help

SETUP TOOL

LOAD FROM USB/COMPUTER

USE PREVIOUS FILE

CREATE NEW

Please select how to load a configuration file

TOOLS

SYSTEM CONFIGURATION

BBconn Cloud User’s Guide24

Part 1129243_01 � 2021 Nordson Corporation

Viewing and Managing System Configurations1. Log into your BBconn Cloud account.

2. Open or create a .NOR file. Refer to About Managing .NOR Files.

3. Select SYSTEM CONFIGURATION to do the following:

4. Once you open the .NOR file, you can define the following:

Option Description

SYSTEMINFORMATION

View firmware version for the installed hardwareboards.

LICENSES View the currently purchased licenses.

MANAGEACCESSORIES

View and add purchased accessories for this controlsystem.

CONFIGURATIONCODE

View and change the configuration code for thiscontrol system.

NOTE: You will need to update this configurationcode for those hardware or software purchases thatare not automatically detected by the controlsystem.

NOTE:

� When transferring files between the control system and BBconn

Cloud, the USB drive must be formatted using FAT or FAT32. Noother format, such as NTFS and exFAT are supported.

Page 28: BBConn Cloud Help

SETUP TOOL

CREATE NEW

Please select how to load a configuration file

BBconn Cloud User’s Guide 25

Part 1129243_01� 2021 Nordson Corporation

Restoring a Control System to the Factory Default Settings

You can restore your control system to factory default settings by creating anew .NOR file in BBconn Cloud and then transferring the new file to thecontrol system.

NOTE: Restoring your control system to factory defaults will also reset thePLC mapping.

1. Log into your BBconn Cloud account.

2. Select SETUP TOOL, then select CREATE NEW.

3. Insert a USB drive into your computer.

4. See Figure 6. Select the Download NOR File link, located at the bottomleft of the page. The default location is your \Downloads folder on yourcomputer. Copy the .NOR file to your USB drive. Refer to thedocumentation that came with your control system for importing .NORfiles.

Figure 6 Downloading a .NOR file from a System Settings screen (TemperatureSettings screen shown)

Page 29: BBConn Cloud Help

User Name

Profile

Sign Out

User Name

Profile

Sign Out

BBconn Cloud User’s Guide26

Part 1129243_01 � 2021 Nordson Corporation

BBconn Cloud Account Management

Editing Your Profile

Your Profile includes your contact information.

1. Log into your BBconn Cloud account.

2. Select your user name in the top right-hand corner and select Profile.

NOTE: To exit the Profile screen at this point, press Escape.

3. Select Edit Profile and enter any changes you want to make. Thisscreen includes the following fields:

� Full name

� Company name

� Address

� Phone

� Plant name

� Company type (OEM, End user, or Nordson)

4. Select Save, or select Cancel to exit the screen without saving.

NOTE: You cannot change your email through BBconn Cloud. To changeyour email, select the Get In Touch link to submit a request to the BBconnCloud Administrator.

Changing Your Password

Password change is accomplished through the Profile screen.

1. Select your user name in the top right corner and select Profile.

2. Select Change Password.

3. Enter your current password.

4. Enter a new password twice.

NOTE: Passwords must be a minimum of 8 characters and can be amaximum of 64 characters.

5. Select Change Password.

NOTE: To exit the screen without changing the password, select theback button for your browser or on the BBconn Cloud page.

Page 30: BBConn Cloud Help

MODEL REGISTRATION

ADD MODEL

MODEL REGISTRATION

ADD MODEL

MODEL REGISTRATION

BBconn Cloud User’s Guide 27

Part 1129243_01� 2021 Nordson Corporation

Registering or Editing Melter Models

Most any Nordson control system can be added to your BBconn Cloudaccount. For each control system added to BBconn Cloud, you can view andmanage all the data (.NOR files) associated with it.

Registering a Melter on BBconn Cloud 1. Log into your BBconn Cloud account.

2. Select Model Registration. The Model Registration screen opens,showing all registered melters.

3. Select Add Model. The Add Model window opens.

4. Enter the following required information for your melter:

� Model (select from drop-down menu)

� Serial Number

� UID (Unique Number)

NOTES:

‐ Refer to the manual that came with the control system to help you

locate the Serial Number and UID.

‐ The Configuration Code / Name field auto-populates after you

enter a valid Serial Number and UID.

‐ The Description field is not required, but Nordson recommends

entering a user-specific description for your control system.

‐ To close the window without adding equipment, select Cancel.

Editing a Registered Melter 1. Log into your BBconn Cloud account.

2. Select Model Registration. The Model Registration screen opens,showing all registered equipment.

3. Select the edit icon � next to the registered equipment to edit. The EditEquipment Details screen opens.

4. Make the needed changes. This screen includes the following fields:

� Model Name (select from the drop-down menu)

� Serial Number

� UID (Unique Number)

� Configuration Code / Name (read only)

� Description

5. Select Save to save the changes, or select Cancel to exit the screenwithout saving.

Page 31: BBConn Cloud Help

ADD SUB USER

SUB USER ACCOUNT

SUB USER ACCOUNT

BBconn Cloud User’s Guide28

Part 1129243_01 � 2021 Nordson Corporation

Managing Sub Users

You can add an unlimited number of sub users to your BBconn Cloudaccount. Sub users can have either read only-access, or full read/writeaccess.

NOTE: You cannot remove a sub user, but you can change a sub user'semail address to prevent a sub user from accessing the account.

Adding a Sub User 1. Log into your BBconn Cloud account.

2. Select Sub User Account. The Manage Sub User Account screenopens, showing all existing sub users.

3. Select Add Sub User. The Add Sub User window opens. To exit withoutadding a sub user, select Cancel.

4. Enter the following information about the sub user:

� Full name

� Email

� Access (Read/Write or Read Only)

NOTE: Sub users with Read/Write access have the same level of accessas the account owner. Sub users with read-only access can view anyscreen and download files but cannot make any changes.

5. Select Add to save, or select Cancel to exit without saving.

When you add a sub user, the system sends a confirmation email to thesub user. To complete the process, the sub user must select the link inthe email to confirm the registration and set up a password.

Editing Sub User Details

NOTE: Account owners can edit any sub user detail. Sub users can edit onlytheir name and access details.

1. Log into your BBconn Cloud account.

2. Select Sub User Account. The Manage Sub User Account screenopens, showing all existing sub users.

3. Select the edit icon � next to the sub user details to edit. The Edit SubUser Details screen opens.

4. Edit any of the following information about the sub user:

� Full name

� Email (can be edited only by the account owner)

� Access (Read/Write or Read Only)

5. Select Save to save the changes, or select Cancel to exit the screenwithout saving.

Page 32: BBConn Cloud Help

MEDIA CENTER

BBconn Cloud User’s Guide 29

Part 1129243_01� 2021 Nordson Corporation

Software Updates

Use the MEDIA CENTER for the latest software for your control system, aswell as for other related documentation.

1. Log into your BBconn Cloud account and select MEDIA CENTER.

2. Locate the software update link located at the top of the MEDIA CENTERpage.

3. Download the .DAT file to the root of your USB drive. When done, insert itinto your control system. The upgrade process should automatically start.Refer to the documentation that came with your control system for moreinformation.

NOTES:

� When transferring files between the control system and BBconn

Cloud, the USB drive must be formatted using FAT or FAT32. Noother format, such as NTFS and exFAT are supported.

� It is recommended that you read the details of the upgrade. You may

need to export your current configuration (.NOR) file to a USB driveand open it up in BBconn Cloud to make any necessary changes tothe configuration.