battery notes
TRANSCRIPT
-
8/12/2019 Battery Notes
1/9
Different types of battery used for auxiliary power supply in substations and power plants
In industrial or substation applications mainly three types of batteries are used namely:
Vented / Flooded Lead Acid batteries
Sealedmaintenance free batteries/Valve Regulated Lead Acid
Nickel Cadmium (Ni-cd) batteries
For UPS applications batteries are the most popular and hence are widely used. Hence, in this
detailing, mainly emphasize has been put on these type of batteries.
Vented / Flooded Lead Acid Batteries
http://electrical-engineering-portal.com/maintenance-for-ups-systemshttp://electrical-engineering-portal.com/maintenance-for-ups-systems -
8/12/2019 Battery Notes
2/9
Vented / Flooded Lead Acid Batteries
There are two types for vented or flooded lead acid batteries namely tubular and Plante. The
difference between the two is the construction. For tubular battery normal life is 8-10 years. The
Plante battery is both mechanically and electrically more durable. The normal life for Plante
batteries is 15-20 years. Because this type of battery generates corrosive fumes when charging
and because the sulfuric acid electrolyte does evaporate to some extent, these batteries must
be used in a special room, which is well ventilated to the outside and kept away from delicate
electronic equipments.
It needs separate room/racks with acid proof tiles for installation. Because of evaporation, it
needs regular maintenance to check specific gravity, to add water and acid. These batteries can
withstand high temperature, voltage, and deep discharge with minimum damage to itself. A
notice should be exhibited in the battery room prohibiting smoking and use of naked flames.
These batteries cannot be transported in charged condition and therefore need charging at site.
Typical initial charging of the battery will take about 55 to 90 hours. Nominal cell voltage is
2V/cell. The charger for this battery should be able to provide the first charge at 2.6 to 2.7 V/cell.
Tubular Type Lead acid battery
These types of batteries are typically used for UPS Systems of very high rated capacity,
typically engaged for plant application, wherein maintenance and space is not really an issue.
-
8/12/2019 Battery Notes
3/9
Sealed Maintenance Free batteries (SMF)
VRLA/SMF type Lead acid battery
These are also known asValve Regulated Lead Acid (VRLA) batteries. These batteries are the
most popular for usage with UPS systems for computer or commercial application. Being
sealed, these batteries do not emit any fumes and hence can be very well installed next to
electronic equipment. These batteries also can be housed in a close enclosure if necessary.These batteries are also maintenance free and avoid any hassles of checking specific gravity,
adding water or acid, etc.
These batteries have a relatively lesser life of approx. 3-5 years. The life expectancy typically
depends on the number of charge/discharge cycle experienced by the batteries and the ambient
temperature in which the batteries are used. These batteries are primarily the most popular for
commercial applications due to Install and forget approach.
The Performance and service life of these batteries can be maximized by observing the
following guidelines:
1. Permissible operating temperature range of SMF batteries is 15 deg C to 50 deg C, but using
within an operating range 5 C to 35 C will extend service life. Below15 deg C, the battery
changes its chemical composition and cannot hold a charge. You will enjoy longer service life, if
batteries are operated in ambient temperature range of 20 deg C to 25 deg C (68F to 77F). At
lower temperature they have longer life and lower capacity while at higher temperature they
have higher capacity and lower life.
2. A good rule of thumb when determining battery service life in relation to temperature is that
for every 8.3 deg C (15F) average annual temperature above 25 deg C (77F), the life of the
battery is reduced by 50%. Therefore warranty of the battery should be ideally reduced to 50%
for every 8.3 deg C (15F) increase in operating temperature above 25 deg C (77F).
3. SMF batteries are designed to have a float voltage of 2.3 V/cell. This means that a 12 V
battery (with 6 internal cells) has a float voltage of 13.8 Volts. Most of the battery manufacturers
recommend float voltage of 2.252.3 volts per cell. When there are more cells (generally >120)
in series, to compensate for higher temperatures, float voltage should be decreased by approx.
3 mV per cell per deg C above 25 deg C. It should be increased by the same amount when
http://electrical-engineering-portal.com/battery-monitoring-and-maintenancehttp://electrical-engineering-portal.com/battery-monitoring-and-maintenance -
8/12/2019 Battery Notes
4/9
operated at a temperature less than 25 deg C to avoid undercharge. The Cutoff voltage is 1.67
V/cell for high rate of discharge (
4. It is recommended that SMF batteries should not be left in totally discharged state more than
72 hrs. The batteries may get partially or fully damaged due to SULPHATION if charging does
not start within 72 Hrs from totally discharged state. Sulphation is the formation of lead sulphate
on negative plates which acts as an insulator and has a detrimental effect on charge
acceptance.
5. In normal float / equalize use (2.25 to 2.35V/cell), gas generated inside battery is recombined
into negative plates, and return to water content of the electrolyte. Thus electrical capacity is not
lost because of this recombination. There is no need to add external water, but due the
corrosion of the electrodes battery will eventually lose capacity.
6. At ambient temperature of 3040 deg C, the shelf life of batteries is 5-6 months only. A
freshening charge must be given to the batteries every 6 months, if needed to be stored for
longer periods. Batteries should be kept in dry, cool place. At ambient temperature of 20 deg C
(68F), the self-discharge rate is 3-4% (approx.) of rated capacity per month. The self-discharge
rate varies with ambient temperature.
7. SMF batteries are equipped with a safe, low pressure venting system, which operates at 7 psi
to 10 psi (can vary slightly from manufacturer to manufacturer), automatically releasing excess
gas in the event that gas pressure rises to a level above the normal rate ensuring no excessive
buildup of gas in the batteries. Resealing is automatic once the pressure is returned to normal.
8. Cyclic life of the battery depends on ambient operating temperature, the discharge rate, the
depth of discharge, and the manner in which the battery is recharged. The most important factor
is the depth of discharge. At a given discharge rate and time, the shallower the depth of
discharge, the longer is the cyclic life.
9. Failure mode at the end of life includes:
Capacity decrease
Internal short circuit
Damage to container/lid
Terminal corrosion
Reduced open circuit voltage.
10. The IEEE defines B (Bend of useful life) for a UPS battery as being the point when it can
no longer supply 80 percent of its rated capacity in ampere-hours (AH). The relationship
between AH capacity and runtime time is not linear, a 20% reduction in capacity results in a
much greater reduction in runtime. When battery reaches 80% of its ratedcapacity,the aging
process accelerates and the battery should be replaced. Some UPS/ Battery manufacturers
http://electrical-engineering-portal.com/supercapacitor-the-future-of-energy-storagehttp://electrical-engineering-portal.com/supercapacitor-the-future-of-energy-storage -
8/12/2019 Battery Notes
5/9
define B (Bend of useful life) for a UPS battery when battery capacity reaches 50-60% of its
rated capacity.
11. Mixed use of batteries with different capacities, different makes should be avoided as it will
cause accelerated aging of the whole string.
12. If two or more battery groups are to be used, connected in parallel, they must be connected
to the UPS through lengths of wires, cables or busbars that have the same loop line resistance
as each other. This makes sure that each parallel bank of batteries presents the same
impedance to the UPS as any other of the parallel banks thereby ensuring correct equalization
of the source to allow for maximum energy transfer to the UPS load.
13. The normal life SMF battery will support approx. 200 charge/discharge cycles at 25 deg C
(77F) and 100% depth of discharge.
14. The term B (Bend of useful life) for a UPS battery refers to the fact that these batteries do
not require fluid. But preventive maintenance like checking for cracks and deformation of the
container & lid, electrolyte leakage/spills tightening of the connection etc, particularly for higherAH capacity batteries should be done to prevent any damage.
Nickel Cadmium Batteries (Ni-Cd)
Ni-cd batteries do emit hydrogen and oxygen gas, products of electrolysis, but there are no
corrosive gases as lead acid batteries, so these can be installed near electronic equipment.
Water consumption is relatively low and so therefore maintenance is low. Normal service life is
20-25 years. These are most expensive of the various types of batteries previously discussed.
Initial cost may be approximately three times that of lead acid battery depending upon their AH
capacity.
These batteries do not experience the severe shortening of life when operated at elevated
temperatures and perform better at low temperatures than do the lead acid batteries. Nominal
cell voltage is 1.2 V/cell. The battery chargers and inverters have to be designed to operate with
low end cell cutoff voltages and higher recharging voltages needed for such batteries.
These batteries occasionally demand boost charging and typically find their applications
wherein UPSs support critical equipment in hazardous environment such as chemical, fertilizer,
cement industry.
Merits/demerits
As spelled earlier, all the above discussed types of batteries have their own merits and
demerits. Let us now look at them individually.
A) Vented / flooded Lead acid batteries
-
8/12/2019 Battery Notes
6/9
Merits
Most economical among three types of batteries.
Life is higher than SMF batteries.
Robust- not much sensitive to temperature.
Demerits
Needs periodic maintenance- twice a month.
Emits corrosive fumes.
Needs special battery room with acid proof tilling.
Cannot be transported in charged condition, initial charging takes 55 to 90 hours.
Needs specially trained persons for handling due highly hazardous sulphuric acid.
B) Sealed maintenance free batteries / Valve Regulated Lead Acid
Merits
No maintenance as far as water filling, specific gravity check etc is concerned.
Can be shipped in charged conditions so ready to use.
User friendly.
Demerits
Leaving batteries in discharged state for longer life will reduce life significantly or can damage
them permanently.
Very sensitive to temperature
Service life lowest among the three types
Costlier than flooded / vented lead acid battery
C) Nickel Cadmium (Ni-cd) batteries
Merits
Moderate maintenance
Higher service life
less sensitive to temperature
Fumes not corrosive so can be installed near electronic equipment
-
8/12/2019 Battery Notes
7/9
Demerits
Most expensive among three types
Cannot be transported in charged conditions.
Compatibility with respect to charger and inverter needed to be considered.
Summary of Techno-Commercial Analysis between Ni-Cd & Lead acid Batteries
No. Description Ni-Cd Lead acid Remarks
1 Reliability Criteria Worst case failure is
cell short circuit.
Result is reduced
performance. The
battery will continue to
support the system.
Worst case failure
is cell open circuit.
Result is complete
loss of battery,
known as sudden
death, resulting in
an unpredicted
system failure.
This point makes
NiCd to be superior in
terms of purpose
2 Requirement of
Air-Conditioning
& additional cost
of Electrical
Energy
Nil Yes Additional Cost due to
Air conditioning
equipment and
running cost-For
VRLA
3 Battery Life as
claimed by UK
manufacturers
(Industrial
Batteries)
20 Years 5-7 Years Replacing cost of
VRLA after every 5-7
years will involve
manufacturing cost
escalation during that
year. Eg.at 6th year,
12th year and 18th
year.
4 Battery Cost Approximately 3 times
than VRLA
- -
5 Relative Costs
Initial & Life
Cycle
Ni-Cd cells have a
higher initial cost than
lead acid but superior
lifetime and
characteristics, giving
Lead Acid has a
low initial cost but a
restricted lifetime.
In many
applications they
-
-
8/12/2019 Battery Notes
8/9
a lower life cycle cost
in many applications.
can have a poor life
cycle cost.
6 Physical Size Ni-Cd cells are
generally larger than
VRLA cells.
In terms of Ah,
Lead acid (VRLA)
is the most
compact battery.
7 Water Topping Occasionally Required Not Required
Summary of Comparison between tubular flooded (ordinary Lead-acid) battery with SMF Lead
Acid Battery
No. Tubular Lead Acid battery VRLA Battery
1 Tubular positive Plates:
The positive active material is held in a
polyester tube. This does not allow the
materials to shed during charge-discharge
cycling resulting in long cyclic life-
minimum 1200 cycles at 80 % depth of
discharge.
Flat pasted positive plates:
The positive active material is a paste form
pasted over a lead alloy grid.? This results in
a shorter cyclic life compared to tubular
construction.- minimum 500 cycles at 80%
depth of discharge
2 Electrolyte:? Stationary batteries of UPS
and Power plant back up works on low
specific gravity (1.200) electrolyte andlarger in volume. This results in less
corrosion of grids and longer life. The
larger volume keeps the battery
comparatively cooler which also adds to
life.
Electrolyte: VRLA batteries work on high
specific gravity electrolyte (1.280 to 1.300)
and less volume. The cells get heated upduring charging and high rate discharges
which affects the service life.
3 Separators: Micro porous poly ethylene
separators are used. This permits the ion
movement and positive to negative plate
separation.
Separators: Adsorptive glass mat separators
are used in these batteries with a closer
spacing between the positive and negative
plates. Chances of cell shorting are
therefore more.
4 Charging compatibility: Tubular stationary
lead acid batteries can be charged with
constant current and constant voltage
mode. Flooded electrolyte batteries can
withstand more abuses during charging.
Water lost in electrolyte during such
Charging compatibility:? VRLA batteries
require constant voltage charging with a
specified limit only specifically to avoid
overcharging.? If by any chance, the
charging conditions are altered, the battery
will get heated up which will deteriorate the
-
8/12/2019 Battery Notes
9/9
abusive overcharging could be easily
made up manually by periodic top-up.
Lagging cells could be brought to normal
life by an extended equalizing charging
without significantly affecting the other
cells.
battery life. Though there is no need to top-
up due to the recombination principle, it is
not always 100% efficient, so some water
loss during use is not avoidable. This results
in a further increase in electrolyte specific
gravity and life reduction. Equalizing(Extended) charging in VRLA batteries
results in some cells getting heated up and
life reduction.
5 Containers: We use transparent SAN
containers. The electrolyte level is easily
seen for topping up needs and ease of
maintenance. Low maintenance.
Not applicable: Cannot monitor Electrolyte
6 Need for temperature control: Due to the
large electrolyte volume the temperature ofthe cells generally do not rise abnormally
during charging. No need for Air
conditioning.
Need for temperature control:? The close
packing arrangement and compactness ofthe stack in the cell assembly rises the
temperature sharply during charging. Due to
this, VRLA battery manufacturers invariably
recommend the need for air conditioned
environment for the battery compartments.
This adds to the cost of maintenance.