battery maintenance manual
TRANSCRIPT
-
7/29/2019 battery maintenance manual.
1/83
FACILITIES INSTRUCTIONS,STANDARDS, AND TECHNIQUES
VOLUME 3-6
STORAGE BATTERYMAINTENANCE AND PRINCIPLES
Internet version of This Manual Created
June, 1998
HYDROELECTRIC RESEARCH AND
TECHNICAL SERVICES GROUP
The Appearance of the Internet Version of ThisManual May Differ from the Original but the Content does not
UNITED STATES DEPARTMENT OF THE INTERIORBUREAU OF RECLAMATION
DENVER, COLORADO
-
7/29/2019 battery maintenance manual.
2/83
TABLE OF CONTENTSSection Page
Flooded, wet cell, lead-acid battery maintenance schedule (last updated 12/31/97) . . . . . . . . . . . . . . . . 11 Condensed instru ctions: lead-acid batteries (last upd ated 12/31/97) . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.1 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21.2 Battery charging and spec ific gravity t emperature cor rect ion . . . . . . . . . . . . . . . . . . . . 21.3 Voltage readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.4 Specific gravity readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.5 Temperature readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61.6 Connection resistance readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61.7 Visual inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81.8 Battery care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81.9 Chargers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81.10 Records . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.11 Battery troubles sum mar ized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 1.12 Recommended actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 1.13 Cell replacemen t . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2 Lead-acid batter y principles (last upd ated 12/31/97) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.1 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.2 Full charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.3 Appearance of normal cells . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.4 Chemical changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 2.5 Internal self-discharge and effect of impurities on floating voltage . . . . . . . . . . . . . . . 13 2.6 Temperature characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 2.7 Proper amount of charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 2.8 High-rate overch arging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 2.9 Low-rate overch arging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 2.10 Undercharging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 2.11 Over discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 2.12 Sedimentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 2.13 Replacement water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 2.14 Water replacem en t rate for lead-an tim on y cells . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 2.15 Water replacem en t rate for lead-calciu m cells . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 2.16 Water replacemen t for lead-seleniu m cells . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 2.17 Adjustin g specific gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 2.18 Hydrometer readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 2.19 Constan t voltage char ging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 2.20 Battery life for differen t types an d services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 2.21 Cleanliness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 2.22 In ternal shorts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 2.23 Normal sulfate and over sulfation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 2.24 Elimination of over sulfation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 2.25 Water treatment for over sulfation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3 Battery testing (last upd ated 12/31/97) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 3.1 Acceptan ce testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 3.2 Capacity tests to determine replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4 Optional instru ctions lead-calcium batte ries (last upd ated 12/31/97) . . . . . . . . . . . . . . . . . . . . . . . . 22 4.1 Float charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 4.2 In itial charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
i
-
7/29/2019 battery maintenance manual.
3/83
TABLE OF CONTENTSCCCONTINUED
Section Page
4.3 Voltage readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224.4 Specific gravity readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234.5 Heavy discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234.6 Water replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Valve regulated lead-acid battery (gel cell) maintenance schedule (last updated 12/31/97) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5 Condensed in struc tionsvalve regulated lead-acid batteries (gel cells) (last upda ted 12/31/97) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255.2 Float charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255.3 Equalizing charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265.4 Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265.5 Battery main tenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265.6 Visual inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265.7 Voltage readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275.8 Temperature readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275.9 Connection resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285.10 In ternal resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285.11 Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Vented n icke l cadmium ba ttery main tenance schedule ( last upda ted 12/31/97) . . . . . . . . . . . . . . . . . . 316 Ven ted n icke l cad miu m batter y pr in ciples ( last u pd ate d 12/31/97) . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2
6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326.2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326.3 Chemical reactions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326.4 Upon installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336.5 Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336.6 Voltage readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346.7 Temperature readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356.8 Visual inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356.9 Battery discharge testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356.10 Electrolyte . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 366.11 Electrolyte level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376.12 Specific gravity readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376.13 Electrolyte renewal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 386.14 General care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 396.15 Battery records . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 396.16 Wall card records . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7 Batter ies for microwave and VHF radio equipment ( last upda ted 12/31/97) . . . . . . . . . . . . . . . . . . . 397.1 Lead-acid batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 397.2 Nickel-cadmium batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
8 Battery safety (last updated 12/31/97) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 408.1 Explosive hazard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 408.2 Electrolyte hazard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
ii
-
7/29/2019 battery maintenance manual.
4/83
8.3 Flame arresters purpose and cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Section Page
8.4 Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 8.5 Battery rooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 8.6 Safety mee tings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
9 Battery charging equipment (last updated 12/31/97) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 9.1 Motor-generator sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 9.2 Static rectifier char gers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
10 Replacement storage battery sizing (last updated 12/31/97) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 11 Standards (last updated 12/31/97) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
TABLES
Table
1 Flooded, wet cell, lead-acid battery main tenance schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Comm on voltage ran ges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 3 Valve regulated lead-acid battery main tenance schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 4 Vented nickel cadmium battery maintenan ce schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
FIGURES
Figure
1 Water consu mpt ion for lead-acid battery sizes and types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 2 Placement of meter probes for connection resistance measurem ents . . . . . . . . . . . . . . . . . . . . . 73 Percent capacity of batteries with pasted and plante type plates for various
discharge rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 4 Effect of concentr ation of electrolyte on cell capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 5 Final voltage at various rates after char ge is fully completed . . . . . . . . . . . . . . . . . . . . . . . . . . 71 6 Per cen t local action in 1.280 electr olyte versus specific gravity of elect rolyte . . . . . . . . . . . . . . 73 7 Approximate variation of local action in lead-acid storage cells with changes in
specific gravity of electrolyte an d ch anges in tem peratu re . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 8 Approximate variation of capacity with tem peratu re in lead-acid chloride-
accumulator type storage cells . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 9 Typical rech arge cur ves at constan t voltages following 100-percent discharges . . . . . . . . . . . . 77
10 Voltage probe placemen t for nickel-cadmium cells with different type conn ectors . . . . . . . . . 79
iii
-
7/29/2019 battery maintenance manual.
5/83
TABLE OF CONTENTSCCCONTINUED
REPORT FORMS
Form Page
POM-133A Flooded lead-acid battery maintenance report (last updated 12/31/97) . . . . . . . . . . . . 51POM-133B Valve regulated lead-acid battery main ten ance report (last updated
12/31/97) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 POM-133C Nickel-cadmium bat tery maintenance report ( last updated 12/31/97) . . . . . . . . . . . . . 55 POM-134A Flooded lead acid batter conn ection resistance annu al report
(last updated 12/31/97) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 POM-134B Valve regulated lead-acid battery conn ection and intern al resistance
annual report (last updated 12/31/97) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59POM-157 Lead-acid storage ba tt ery data ( last upda ted 12/31/97) . . . . . . . . . . . . . . . . . . . . . 61 POM-159 Nickel cadmium storage bat tery data ( last updated 12/31/97) . . . . . . . . . . . . . . . . 63
iv
-
7/29/2019 battery maintenance manual.
6/83
TABLE 1. - FLOODED, WET CELL, LEAD-ACID BATTERY
MAINTENANCE SCHEDULE
1
Mainten anc e New Battery Shift Monthly 3-Month Ann ual 5-Year
Visual Also See 1.10C &D Flame
Inspection Arresters
See 1.7 See 8.3
Battery Float Panel Meter Battery Terminals Compare Panel
Voltage Float Voltage with Digital Mete r to Digital
See 1.3 See 1.3A Voltmete r Voltmete r
Cell Float All Cells Pilot Cells All Cells
Voltages with Digital with Digital with Digital
See 1.3 Voltmete r Voltmete r Voltmete r
Specific Gravity All Cells Pilot Cells 10 Per cen t of All Cells
Readings all Cells
See 1.4
Temperature Pilot Cells 10 Percent of
Read ings All Cells
See 1.5
Conn ection All All Conn ections
Resistance Connections
See 1.6
Battery Testing Accepta nce Yearly Capac ity Capac ity
See 3.0 Te st After Tests if 5-Year Dischar ge
1 week Test < 90 Percent Test
Check Safety Wash Equipment;
Equipm ent Protective Clothing;
See 1.7 & 8.0 Fire Extinguisher s,
Etc.
See section 1.11H for sur face charge phen omenon (initial voltage drop u nder load).
-
7/29/2019 battery maintenance manual.
7/83
1. CONDENSED INSTRUCTIONS: LEAD-ACID BATTERIES
E1.1 PURPOS11. PURPOSE
The purpose of this section is to outline the duties and responsibilities for
routine operation and care of vent ed lead-acid batteries. Section 2 contains
detailed information on lead-acid battery principles.
1.21.2 BATTE RY CHARGING AND SPECIFIC GRAVITY TEMPERATURE CORRE CTIONBATTERY CHARGING AND SPECIFIC GRAVITY TEMPERATURE CORRECTION
A.A. Initial Fresh en ing Char geInitial Freshening Charge
To establish a reference, give each new battery, or reinstalled battery stored
for more than 3 mon ths, an initial freshening charge. Use the equalizing
voltage given by the manufacturer for the type cell, but do not exceed the
maximum voltage of othe r loads conn ected to the charger. Apply th is charge
un til each cell gasses freely and equally and specific gravity (sp.gr.) stops
rising. Just before the en d of the initial charge, record th e voltage of eachcell. About 20 m inutes after th e end of the charge, record the specific
gravity of each cell, corrected to 77 EF. For every 3 EF above 77EF, add one
point (0.001) to the reading. For every 3 EF below 77EF, subtract one point
(0.001) from the reading. Use form POM-133A for these records and keep
them for the life of the battery.
ell.CPilot.1A.1 Pilot Cell.After the initial char ge or to begin a yearly cycle, ch oose a pilot
cell from on e of the lowest specific gravity an d lowest voltage cells. Th is cell
is used as a representa tive for readings, for one year. Each year a new pilot
cell is chosen.
eB. Float Cha rg.B F loa t Ch ar ge
Charge batteries continu ously at the float voltage r ecomm ended by the
manufacturer . Monthlyy take the voltage across the overall battery terminalswith an accurate digital mete r and compare t his reading with the ch arger
and bus voltmete rs. If needed, adjust the charger float voltage based on th e
digital mete r. Adjust the char ger an d/or bus voltmete rs to agree with th edigital meter if needed.
A battery is said to float when charging voltage is slightly greater than the
open circu it voltage of the battery. Floating current required to keep lead-
calcium cells at full charge is about one-four th to one-third t hat of lead-an timony cells, but lead-calcium cells usually mu st be floated a t a slight ly
higher voltage. Lead-selen ium cells require float voltages slight ly above
those of lead-calcium.
The oper ation of a batt ery by float m eth od is based on overa ll voltage applied
to the battery term inals. The voltmeter used m ust be very accurate. An
inaccurate meter can result in either over or u ndercharge and resulting
problems, which redu ce life an d service of the battery. See section 1.3.
Rev.12/31/97 2
-
7/29/2019 battery maintenance manual.
8/83
-
7/29/2019 battery maintenance manual.
9/83
discharge temperature increases.
Rev.12/31/97 4
-
7/29/2019 battery maintenance manual.
10/83
D.D. Unatten ded StationsUnattended Stations
The equalizing charge may be term inated au tomatically by a timer. Use the
man ufacture rs recommen ded charge time for the cell type. Set the timer to
switch off the equalizing charge and to reconnect the float charge. In th e
event that th e m anu facturer does not provide a recommen ded charge time,
3 days (72 hou rs) may be used as the charge time.
A "check charge" for batteries at unattended locations may be used to determine ifequalization is necessary. With a "check char ge, the batter y is placed on
charge at th e equ alizing rate. After allowing 15 or 20 m inutes for the rate to
stabilize, the voltages of individual cells are measured . If the highest an d
lowest ce ll voltages (while on charge at the equ alizing rate) d iffer by no
more th an 0.04 volt, the battery does not require equalizing. The battery
shou ld be equalized if the voltage differences exceed 0 .04 volt. Use a digital
me ter accur ate to 0.01 volt. The test described above is effective in
determining equality of cell charge. However, the test cannot be substituted
for a hydrometer in determining state of charge. All cells must be within 5F,the r eason is described in paragraph 2.6, and the temperature mu st not
be below 55 F.
1.31.3 . VOLTAGE READINGSVOLTAGE READINGS
Voltage readings should be taken in accordance with the following
instructions. NNote: Accurate voltmeters are critical for extending batter y life.Provide a digital voltmeter accurate to 0.01 volt re served on ly for sta tion
battery duty and calibrate it or send it out for calibration at least once a year.
This voltmete r m ust be treated with extra care; do not use a shop m eter or
electrician s genera l-use meter for batte ry voltages.
A.A. Each Shift (Attended Stations) or DuringEach Shift (Attended Stations) or During Routine In spections (Unatten ded Stations)Routine Inspections (Un attended Stations)
Check the voltmeter on the control panel to determine if the battery is being
charged at th e proper voltage. Adjust the battery charging voltage if
necessary.
B.B. When Taps Are ChangedWhen Taps Are Changed
Check the voltage on th e control panel when taps are ch anged on power or
station-service tran sform ers. Adjust the batt ery charging voltage if
necessary.
C.C. Dur ing Equ alizing Char geDur ing Equalizing Ch arge
Just before term inating the equalizing charge, measure the voltages of the
highest voltage ce ll and th e lowest voltage cell of the battery to the nearest 0.01volt with an accu rate digital voltmeter. The equalizing charge should be
continued if the voltage differen ce between the two cells is more than that
recorded for th e initial char ge.
Rev.12/31/97 5
-
7/29/2019 battery maintenance manual.
11/83
D.D. Mon t h lyMonthly
With the charger in service, check the overall float voltage across the battery
term inals with an accurate digital mete r an d record on form POM-133A.
E.E. MonthlyMonthly
Che ck the pilot cell float voltage with an accu rate digital voltmeter an d
record on form POM-133A.
F.F. QuarterlyQuarterly
Check the float voltage on a ll individual cells to the nearest 0.01 volt with an
accu rate digital voltmeter. Take the se readings as rapidly as possible and
record them on form POM-133A. At the en d of the year ly cycle, use these
readings to determ ine th e pilot cells for the n ext year.
1.41.4 SPECIFIC GRAVITY READINGSSPECIFIC GRAVITY READINGS
Specific gravity readings of vented lead-acid batteries must be taken in
accordance with the following instructions. Note: All specific gravity read ingsmu st be corrected to 77EF before recording (see 2.18). Do not attem pt to
take an y specific gravity reading after add ing water to a cell. The electrolyte
takes several hou rs to mix after water is added.
A.A. MonthlyMonthly
Take th e specific gravity reading of the pilot cell and record it on form POM
133A.
B.B. QuarterlyQuarterly
Take specific gravity readings of 10 percent of the total number of cells and
record them on form POM-133A. Rotate these cells so that r eadings are
taken on differen t cells each quarter.
C.C. AnnuallyAnnually
Take specific gravity readings of every cell and r ecord them on form POM
133A.
D.D. After Equa lizing Ch argeAfter Equalizing Charge
About 15 minutes after heavy gassing stops, take th e specific gravity readings
of every cell and record th em on form POM-133A. If two cells with the
lowest specific gravity (ch ecked over the last one-eighth of the charging
period) have n ot stopped rising, continue the equalizing charge.
Rev.12/31/97 6
-
7/29/2019 battery maintenance manual.
12/83
1.51.5 TEMPE RATURE READINGSTEMPE RATURE READINGS
All cells of a battery should be at the sam e am bient temper ature. Heat
sources such as sun light, portable heate rs, etc. mu st be blocked so they do
not raise the tem peratu re of individual cells. Record the room ambient
temperature before cell temperatures are taken.
Note: An accu rate infrared (IR) cam era m ay be used for tem peratu res;however, the camera calibration mu st be checked at least once each year. If
possible, take the an nu al temperatu re readings of the cells just after cam era
calibration. If the temper ature spread of the cells exceeds 5 F (i.e., upper
rows are warmer) th e room ven tilation m ay be inadequa te.
A.A. MonthlyMonthly
Record the pilot cell temperatures on form POM-133A.
B.B. QuarterlyQuarterly
Record temperatu re r eadings of 10 percen t of all the ce lls; rotate the subject
cells each quar ter.
C.C. AnnuallyAnnually
If an accurate IR camera is available, take the tem peratu re of the battery
conn ections du ring a load or discharge test, i.e., while cur ren t is flowing. If
one or more of the connections are loose or dirty, the ir temperatu res will be
higher than the other connections.
1.61.6 CONNECTION RESIS TANCE READINGSCONNECTION RESISTANCE READINGS
A.A. After In sta llationAfter In stallation
Using an accurate micro-ohm meter, record the resistance of each
connection on form POM-134A. The readings should be on the order of a
few micro-ohm s (less than 100). Record the r eadings as a baseline on form
POM-134A. For additional informa tion see IEEE 450-1995Maintenance,Testing , and Replacement of Vented Lead-acid Batteries, Annex D and F. See belowfor detailed instructions.
B.B. AnnuallyAnnually
Repeat resistance ch ecks of the connections ch ecked in step A above an d
compare values. If any conne ction resistance has increased more than 20
percen t, clean, apply no-ox grease, retorque the connections, an d retest.
Fill out both as foun d and as left colum ns on form POM-134A.
Rev.12/31/97 7
-
7/29/2019 battery maintenance manual.
13/83
C.C. Recomm en ded Method For Taking Ann ual Micro-Ohm met er Readings Across BatteryRecomm en ded Meth od For Taking Ann ua l Micro-Ohm me ter Read ings Across Batter y
ConnectionsConnections
Figure 2. - Placement of meter probes for connection resistance measurements.
Caution: Never place probes across a cell or cells (between positive an dnegative posts), with th e mete r set on ohms. The m eter m ay be destroyedand arcing may occur at the battery.
1. Make sure the battery is on float charge before beginning the readings.Obtain an accurate digital micro-ohmm eter, an d set it to the lowest scale.
2. On cell No. 1 take the first reading between the connector lug and thefirst post (see fig. 2). This reading will be the resistance between the
post and connect or lug and will be about one-half the m iddle readings.
Record a ll readings on form POM-134A.
3. Take the second reading between opposite polarityposts (not connectors) ofcells No. 1 and No. 2. Following readings will be between positive an dnegative posts of adjacent cells. These middle readings will include the resistance of two connections (one on each post) and the intercelllead(see fig. 2). These readings will be about double the first and last.
4. Take the rem aining middle readings as in step 4, proceeding from cell tocell.
5. Take the last reading between the last post on the last cell and theconnector lug as shown.
6. If high resistance is found , take readings from each post to its conn ectorto determ ine which of the two connections is bad. Mark this and all
high-resistance connec tions for later repair.
7. After readings are complete, disconnect the charger and loads from th ebattery. Caution: do not remove or make connections while current is flowing.Clean problem conn ections, re torque to man ufacturers specifications,
and apply no-ox grease. Retest the repaired connections and record the
resistance in the as-left column on form POM-134A.
Rev.12/31/97 8
-
7/29/2019 battery maintenance manual.
14/83
1.71.7 VISUAL INSP ECTIONSVISUAL INSPECTIONS
Visual inspections are made to assess the general condition of the battery,
battery room, and safety equipmen t. See below and section 1.10 and r ecord
on form 133-A.
A.A. MonthlyMonthly
Check for gene ral cleanliness of the battery, moun ting rack, and battery
room. Check for electrolyte leaks and cracks in cells, and take corrective
action if any are found. Check for corrosion at terminals, conn ectors, racks,
and cabinets. Check the ambient tem peratu re and make sure ventilation
devices (fans and ven ts) are operable. Check all the electrolyte levels and
correct if necessary.
Check for availability and con dition of all safety equipmen t, gloves, apr ons,
face shields, etc. (see sect ion 8). Check for a full gallon of labeled
neut ralizing solution, an d operability of eyewash sta tion or portable eyewashequipmen t. Check for operation an d cleanliness of body wash station.
Check for a class C fire extinguisher an d check that it h as been inspected
and tested according to schedu le. Check for availability of insu lated tools
and uten sils so short circuits can be avoided. Check the hydrometer for
cleanliness an d cracking of rubber parts.
1.81.8 BATTERY CAREBATTERY CARE
A.A. Adjustm en t of Specific GravityAdjustm en t of Specific Gravity
Do not add or remove acid in any cell except when following instructions in
paragraph 2.17.
B.B. TemperatureTemperature
Never intentionally allow electrolyte temperature to exceed 100 EF.
C.C. CleanlinessCleanliness
Keep th e battery room or cabinet clean and well ven tilated. Keep cells,
especially the tops, clean, dry, and free of electrolyte and corrosion residue.
D.D. Spilled Electr olyteSpilled Elect rolyte
At each batter y room or cabine t, provide a labeled gallon jar of solut ion
consisting of 1 poun d baking soda to 1 gallon of water . Neu tralize spilled
electrolyte with soda solut ion, rinse with water, an d wipe dry. Do not allow
any solut ion to enter the cells. Keep vent plugs tight and gas ven ts open.
Any missing or worn ven t plug gaskets shou ld be rep laced.
1.91.9 CHARGERSCHARGERS
Rev.12/31/97 9
-
7/29/2019 battery maintenance manual.
15/83
Chargers serve two important fun ctions. The m ain function is to provide d
c station power and to keep the battery charged. The second fun ction is to
be able to replace the battery if the need arises. Two main types available
are silicon-controlled rect ifier (SCR) an d ferro-resonan t. The two types
differ greatly. SCR chargers consist of a tran sform er with an SCR bridge
and filtering. All cont rol and protection in these chargers is electron ic.
These chargers are usually the cheapest type because the manufacturer can
buy SCRs and electronics off the she lf. Ferro-resonan t cha rgers uses a
tran sformer specifically designed for each application. When extreme
conditions occur, th ese tran sformers satu rate and limit, by design, th e
maximum cu rren t and voltage. Additional electronics are not needed. This
feature m akes the char gers more du rable and depen dable in a power plant
environm ent . The ferro-resonan t type charger is ther efore recommended.
Chargers norm ally are bought and operated in pairs to shar e the load. Both
chargers operating, with all safety featu res activated on both , will less likely
have a double failure than if one is operating and one is in stan d-by mode.
In an emergency, a cha rger on standby trying to power u p and assume theduties of a failed charger may exceed its current or voltage limits before
safety circuits are enabled. The r esult may be two failed char gers. The best
way to avoid this problem is to opera te both chargers in para llel at all times,
each supplying half the load.
The size of the chargers is very important to the life and service of the
battery. The chargers mu st have enough capacity to easily gas the battery
un der ch arging conditions. Chargers with too little capacity redu ce battery
life. A smaller charger, though cheaper initially, can be the m ost expensive
on a long term basis.
A.A. Ever y Sh iftEvery Sh ift
Check the panel voltmeter to see if the correct float voltage is being used for
charging.
B.B. QuarterlyQuarterly
Check each charger by turning off one , then the other, and see if each
charger will carry the total load.
C.C. AnnuallyAnnually
Check the accu racy of the charger panel voltmeter with the digital mete r.
1.101.10 RECORDSRECORDS
Post a battery data card form POM-157 in a conspicuous location n ear th e
battery, and keep accu mu lated forms in a perm anent file.
Loss of capacity over time is shown by a gradu al change in specific gravity of
Rev.12/31/97 10
-
7/29/2019 battery maintenance manual.
16/83
the ce lls. Keeping accurate records in th e battery room is important.
Comparison can be made easily between cu rren t and ear lier readings. A
copy of forms POM-133A and POM-134A are included in the forms sect ion
and are available from Reclamations Technical Service Cen ter in Den ver.
Four POM-133A quarterly reports and one POM-134A connection
resistance report ar e requ ired for a 60-cell battery each year. Special care is
necessary to protect data sheets. Keep cur ren t records on clip boards or in a
log book near the battery and transfer th em to a perman ent file at the en d of
the year.
Rev.12/31/97 11
-
7/29/2019 battery maintenance manual.
17/83
1.111.11 BATTERY TROUBLES SU MMARIZEDBATTERY TROUBLES SUMMARIZED
A.A. Lack of GassingLack of GassingLack of gassing while on charge may indicate an internal short between
plates, i.e., the cell discha rges interna lly as fast as it is being charged.
B.B. Specific Gravity or VoltageSpecific Gravity or Voltage
Specific gravity or voltage of a ce ll lower than othe r ce lls is an indication of
excessive inte rnal losses an d m ay result from con sistent un derch arging.
C.C. ColorColor
Color or appearan ce of plates or sedimen t differen t from other cells is
addressed below:
1. Patches of white lead sulfate on either the positive or negative plates:caused by standing idle or un derch arging for extended periods.2. Antimony deposit dark-slate patches on negative plates (usually near the
term inal): caused by charging at too high a rate or an aged cell nearing
the en d of its service life.
3. Top layer of sedimen t white: caused by underchar ging.4. Lumpy brown sediment: caused by overcharging.5. All white sediment n o visible layers: caused by overcharging after
prolonged low float voltage.
6. Large flaking on th e inte rplate collector bar : caused by being on floatcharge for extended periods at insufficient float voltage without
equalizing charging being performed.
D. D. Plate Problem sPlate Problem sIf any checks below are excessive, capacity tests must be run to determine if
individual cells or th e en tire battery should be replaced. See section 3.
1.
Cracks on the edges of the positive plate grids.
2. Light-colored sulfating spots on edges of plates below cracks men tionedin check No. 1 above.
3. Excessive sedimen t in th e bottom of the case.4. Mossing or treeing on the tops of negative plates.
Rev.12/31/97 12
-
7/29/2019 battery maintenance manual.
18/83
E.E . Wat erWater
1. Cell uses excessive water (ch eck fig. 1 for typical water consu mpt ion):caused by excess charging rates, h igh operating temperatu res, or leaking
cell.
2. Cell requires very little water: cau sed by insufficient ch arging.FF . Buckling of Plate sBuckling of Plate sBuckling of positive plates ind icates excessive su lfation caused by
un derch arging or excessive temper ature. See sections 2.10, 2.22, and 2.23.
GG. Failure to Su pply Rated Ampe re-Hou r LoadsFailure to Su pply Rated Ampe re-Hou r LoadsFailure to supply rated ampere hours indicates dischar ged condition,
excessive su lfation, or loss of active material from positive plates. Cells may
be worn out or act ive ma ter ial may be gone from positive plates. See sec tion3 for testing.
H.H. Surface Charge Phen omenonSurface Charge PhenomenonWhen a battery has been on float charge for a long time and is put u nde r
load with the ch argers off, the voltage will drop rapidly. Th is drop is caused
by plugging of some of the pores on the surface of the plates, which part ially
blocks the tran sfer of ions. The voltage may drop below the low-voltage
alarm and trip settings. After th is initial drop, the voltage will usually
increase to a level above the low-voltage alarm an d trip settings. The battery
will then operate normally until its capacity is exhausted.
If the battery is exercised (partially discharged) on a routine basis, the
voltage dip can be reduced or eliminated. Turning off both chargers and
allowing the battery to take the load for at least 15 minutes exercises the
battery. The first few times th is procedure is performed, disconnect th e low
voltage trip relay to prevent an inadverten t trip. The first time th e battery is
exercised, th e procedu re should be performed several times in succession
un til the voltage drop stays above th e alarm setting. Always give th e
chargers time t o reduce ch arging cur ren t to float value before tu rn ing off the
chargers again for the next cycle.
Each battery has its own cha racteristics, and th e frequen cy of exercisingshould be adjusted so that the voltage drop does not cause the low voltage
alarm. Start at a m onthly cycle and experiment with increasing the time
between exercises. The proper time between exercises exists when the
voltage dr op is just above th e alarm relay setting.
1.121.12 RECOMMENDED ACTIONSRECOMMENDED ACTIONS
If any cells seem to be in trouble, the whole battery shou ld be given an
Rev.12/31/97 13
-
7/29/2019 battery maintenance manual.
19/83
equalizing charge, and then specific gravity readings should be taken on all
cells. Ifall cells gas evenly and specific gravity ofevery cell is normal, all thebattery needed was the cha rge. Otherwise, all low gravities shou ld be
recorded, an d an extra thorough charge, as described in section 1.2C should
be given. The t emper ature of all cells should be compared by ther mometer
or IR camera with th e rest of the cells. Sulfated cells will run hot en ough to
cau se dam age if not corr ected. Any cells that still will not gas with the extra
charging should be investigated for impu rities an d inspected for inte rnal
short circu its. See section 3 for testing.
Additional informa tion may be obtained from IEEE Standard 450-
1995Maintenance, Testing, and Replacement of Vented Lead-Acid Batteries. If thisstandard does not help solve a problem, record the voltage of each cell and
the specific gravity of 10 per cen t of all the cells. Also, record the electr olyte
temperature an d the ambient temperature, then contact the battery
manufacturer for assistance.
1.131.13 CELL REPLACEMEN TCELL REPLACEMENT
A faulty cell may be replaced by one in good condition of the same make,
type, rat ing, and approximate age. A new cell shou ld not be insta lled in
series with older ce lls except as a last resort. A battery may be operated
without severa l cells by proper adjustm en t of float and equalizing voltages,
provided discharge capacity requ iremen ts can be met.
2. LEAD-ACID BATTERY PRINCIPLES
2.12.1 PURPOSEPURPOSE
This section describes th e pr inciples of lead-acid battery care an d h ow to
determ ine if the care is adequate and correct. The most importan t part of
battery care is a proper charging program . Keeping and comparing accura te
records of physical conditions and m easured data assists in determ ining
whether the charging program is correct. Correct charging is critical for
long battery life and reliability of service.
The following discussion describes cell conditions with both proper and
improper operation and mainten ance . These principles do not take
preceden ce over the man ufacture r's instructions, but provide explana tions
and details.
2.22.2 FULL CHARGEFULL CHARGE
Knowing when a ce ll is fully charged is importan t. A cell is fully charged
when , charging at the equ alizing rate, the ce ll is gassing, specific gravity has
stopped r ising, and specific gravity rem ains constan t for two successive
readings. Hydromete r readings must be corrected for any changes in cell
temperatu re that have occur red between readings. These two readings
should be taken dur ing the last one-eighth of the charging period.
Rev.12/31/97 14
-
7/29/2019 battery maintenance manual.
20/83
2.32.3 APPE ARANCE OF NORMAL CELLSAPPEARANCE OF NORMAL CE LLS
Edges of positive plates do not give much in formation. Edges of negative
plates should be uniformly gray; they should be examined with a non
me tallic flash light for sparkling from lead su lfate c rystals. Correc t float
charging will cau se no lead sulfate crystals. See sect ion 1.10 for more
informa tion on cell appearan ce.
Rev.12/31/97 15
-
7/29/2019 battery maintenance manual.
21/83
No visible change occurs when the ce ll is discharged a normal amount. If
the charging program is correct, sediment accumulates very slowly and
should never be white or lumpy. The ch arging program may require
chan ges to produce a very scanty, fine , dark-brown sediment . The electrolyteshould be at th e m arked level, midway between top of the case an d top of
the plates.
2.42.4 CHEMICAL CHANGESCHEMICAL CH ANGES
A fully charged ce ll has brown lead peroxide on positive plates and gray
sponge lead on n egative plates.
On discharge, electric current converts active materials of positive and
negative plates to norm al lead su lfate an d u ses up su lfuric acid to
man ufacture lead sulfate. This process leaves the acid weak at the en d of
the d ischarge. Lead sulfate is white in color but cann ot be seen on plates
un less the cell is over-discharged, which produ ces over sulfation. This
condition makes the plates first lighter in color and finally mott led white inpatches or white all over.
Charging the cell reverses this process, converting lead sulfate in the plates
to lead peroxide an d sponge lead and producing sulfur ic acid, which restores
the specific gravity to norm al. Chemical reac tions in a storage cell are :
Battery Discharged Battery Char ged
(+ plate) (- plate) (solutio (+ plate) (- plate) (solution)
n
PbSO4 PbSO4 2H 2O PbO2 + Pb 2H2 SO 4+ + +
(lead sulfate) (lead sulfate) (water) (lead peroxide) (lead) (sulfuric acid)
As the charge nears completion little lead sulfate remains to convert to lead.
The charging curren t begins to separate water into oxygen and hydrogen,
which bubbles to the top of the electrolyte and forms a mixture of very
explosive gases.
Quan tity of ampere-hou rs available from a cell decreases with an increasing
rate of discharge. Available ampere-hou rs are m uch less at rapid rates ofdischarge (see fig. 3). The amper e h ours also decrease for cells with weaker
specific gravity (see fig. 4).
2.52.5 INTE RNAL SELF-DISCHARGE AND EFF ECT OF IMPURITIE S ON FLOATINGINTERNAL SELF-DISCHARGE AND EFFECT OF IMPURITIES ON FLOATING
VOLTAGEVOLTAGE
Lead-calcium and lead-selenium cells have th e advantage of low internal
losses, which rem ain constan t for the life of the cell. Lead-selen ium cells
Rev.12/31/97 16
-
7/29/2019 battery maintenance manual.
22/83
contain little antimony and do not have antimony migration like lead-
an timony cells.
Fully charged lead-antimony cells discharge internally by an action between
active mater ial and th e grid. Impu rities may hasten this action and m ay
result in visible or invisible changes on the plates depending on the types of
impurities presen t. No metals should be put into the electrolyte at any time, except acadmium test electrode. Impur ities may prevent a proper floating voltage fromkeeping up th e charge and m ay prevent an equalizing charge from
equalizing voltage, so a higher floating voltage m ay be requ ired.
The ra te of self-discharge is decreased by using a lower specific gravity. The
rate increases as the cell temperatu re rises, as may be seen on th e cur ves of
figures 5 and 6. The charge will not be lost if a small charging curren t, just
equal to the self-discharge rate, is given to the ce ll. Th is charge is known as
a tr ickle charge an d is usu ally made a little larger t han necessary so as to
gradually restore losses caused by small loads connected to the battery.
Self-discha rge increases with age to perhaps five times the initial rate. This
process is believed to be caused by the antimony being deposited on the
negative plate in a form th at behaves as an impu rity. Many batteries use
calcium instead of antimony as the alloying material, which redu ces the
intern al dischar ge as indicated on figure 7.
2.62.6 TEMPE RATURE CHARACTERISTICSTEMPE RATURE CHARACTERISTICS
Operating tem pera ture grea tly affects performan ce of storage cells. Capacity
is greatly reduced when cold, as shown by figure 8. The self-discharge rate
is increased at warm tem peratu res, as shown by figure 7. The tem peratu re
at which the electrolyte will freeze an d bur st cells is lowered a s specificgravity rises. Little dan ger of freezing exists if the battery is kept well
charged.
If charging cu rrent is kept constant , charging voltage will rise to a final value
and is one indication th at full char ge has been reach ed. This final voltage
increasesgreatly as the cell gets colder, as shown by figure 5. For th is reason,do not try to term inate an equalizing charge by a re lay that operates at a
constan t voltage. This procedur e would only work correctly for one
tem peratu re. Relays are available where operat ing voltage varies with
temperatu re. This charge control mu st be subject to the same am bien t
temperature as the battery.
If charging voltage is held constant, final charging current increases with
temperatu re, as also shown in figure 5. This condition is needed to offset
the incr easing intern al self-discharge current. The constant voltage char ge
meth od automatically keeps the cu rren t at the value the battery needs for
replacing both the self discharge and load discharges.
2.72.7 PROPER AMOUNT OF CHARGEPROPE R AMOUNT OF CHARGE
Rev.12/31/97 17
-
7/29/2019 battery maintenance manual.
23/83
If cells of either lead-antimony or lead-calcium are undercharged, service willbe poor and battery life short . Ifovercharged, service with eithe r cell type willbe good, but excessive overcharging will shorten life. Proper charging,
means slight overcharging to cause the least possible sedimentation and a minimum ofheavy gassing. This condition requ ires very little makeup water . Noperceptible sedimentation or buckling of plates occurs during charge at high
or low rates if cells are not a llowed to gas vigorously. Sedim en tation star ts
with gassing and is proportional to the total amoun t of gas liberated. Lead-
selen ium cells do not have th e grid growth or the lead-antimony cell
problems. Typical curves of recharge times after 100-percent dischar ge at
the 8-hour rate ar e shown in figure 9.
2.82.8 HIGH -RATE OVERCH ARGINGHIGH-RATE OVERCHARGING
After a battery is fully charged, continuation of charging current at a high
rate dam ages positive plates. Violen t gassing takes place, bu bbles form in
the interior of the active m aterial, and th e re sulting pressure forces bubbles
through the porous active mater ial. The active mater ial restrains thebubbles sufficiently so that many particles of plate material are broken out.
These particles rise with the bubbles and result in a m uddy red or brown
color of the electrolyte. Some of this fine sedimen t settles on n egative plates
where it short circuits. The sedimen t is converted to gray sponge lead and
results in a growth of moss-like sediment deposited on top edges of the
negative plates. This deposit indicates that high-ra te overcha rging
previously occur red . The battery will overh eat on susta ined heavy charge
rates. The t emper ature of the cells should never inten tionally be allowed to
exceed 100 F.
2.92.9 LOW-RATE OVERCHARGINGLOW-RATE OVERCHARGING
At lower rates of overcharge, bubbling is reduced and sediment falls to the
bottom of the cell. Overcharging at a very slow rate disturbs electrolyte so
little th at fine brown sedime nt falls in a vertical line, forming tiny ridges on
top of the sedimen t. Ridged sedimen t is a good indication that th e recen t
overcharging was not at h igh rates. Obviously, overch arging shou ld be kept
at a m inimum , and r idges should be small.
2.102.10 UNDERCHARGINGUNDERCHARGING
If the battery gets too little charging, unconverted sulfate remains on the
plates too long and harden s. The longer plates stay in less-than-full-chargecondition, th e harder the sulfate becomes an d the m ore difficult it is to
reconvert. When n ew, the sulfate is easily converted back to soft active
mate rials by a n ormal ch arge, but a long overch arge is required to rem ove it
after becoming hard. Sulfate accumu lates un noticed, a little on each
charge, if charging is not en ough to eliminate all the sulfate. This residue
build-up con tinues un til a substantial portion of ampere -hour capacity is
lost. The rem edy is to increase charging to give a slight overcharge. Thisprocedure m ust be pu t into practice while the battery is new and followed
Rev.12/31/97 18
-
7/29/2019 battery maintenance manual.
24/83
-
7/29/2019 battery maintenance manual.
25/83
2.132.13 REPLACEMENT WATERREPLACEMEN T WATER
As batteries are charged, a small quantity of water in the electrolyte is
broken down in to hydrogen and oxygen by the charging curren t. The gases
are dissipated th rough open ings in ven t plugs. As this process takes place,
electrolyte level gradually lowers u nt il distilled water mu st be added .
Comm ercially available "dem ineralized" water has been found by test to be
equal or super ior to commercial or "in plant" distilled water . Referen ces
throughout this bulletin to "distilled water" do not preclude the use of
"dem ineralized water. Do not add water in excess of the maximu m level
mark. Never store distilled water in a meta llic container. Use glass, plastic,
or rubber containers.
Water consu mption of batteries is indicated on figure 1. Take an average of
the am oun t of water added over several month s and compare with the
amounts given on figure 1.
2.142.14 WATER REPLACEMEN T RATE FORWATER REPLACEMENT RATE FOR LEAD-ANTIMONY CELLSLEAD-ANTIMONY CELLS
Lead-an timony cells begin the ir lives with low water consumption, which
increases as m uch as five times toward th e en d of their lives (see fig. 1).
Capped ce lls evaporate very little water, and loss is caused by gassing an d is
proportiona l to the amount of charge the battery rece ives. Heavy gassing
requ ires frequent additions of distilled water. The water should be added
just before or at th e beginn ing of a ch arge so that gassing will en su re
thorough mixing before specific gravity readings are taken . Proper charging
minimizes distilled water replacement by limiting the amount of gas
gene rated to a small quan tity. This method is mu ch easier than
overcharging and having to refill cells frequ en tly. It also exten ds the life of
the battery.
2.152.15 WATER REPLACEMEN T RATE FORWATER REPLACEMENT RATE FOR LEAD-CALCIUM CE LLSLEAD-CALCIUM CELLS
Frequ ent additions of distilled water in small amoun ts are not desirable.
Water add itions two or thr ee times a year will probably be sufficient a t most
installations. The electrolyte in all cells shou ld be maint ained within 1/4
inch be low the high level mark. Calcium ce lls, becau se of greater pu rity of
their components, require only about one tenth the water needed by
equivalent size an timony cells. This low requirem ent r emains constant
dur ing the entire battery life. See figure 1 for water consum ption r ate.
2.162.16 WATER REPLACEMENT FOR LEAD-SELEN IUM CELLSWATER REPLACEMEN T FOR LEAD-SELENIUM CELLS
Water r eplacemen t should only be necessary every 12 to 18 mon ths if the
battery is not subjected to many dischar ges. If several discharges are
experienced, water replacement should be performed as with the lead-
calcium cells in paragraph 2 .15 above. Water consumption is low
throughout the life of these cells.
Rev.12/31/97 20
-
7/29/2019 battery maintenance manual.
26/83
2.172.17 ADJUSTING SPECIFIC GRAVITYADJUSTING SPECIFIC GRAVITY
Specific gravity should nevernever be adjusted un til the gravity is definitelyestablished to be wrong. Before adjusting for low gravity, make su re th at th e
gravity can not be raised by equalizing (see 1.2 C). Continue th e charge
un til the specific gravity shows no rise, an d th en charge for 3 more hour s.
Hydrometer readings must be taken as indicated in 2.18 below. Never make agravity adjustment on a cell that does not gas on charge. Remove some electrolytefrom the cell and replace it with pure, 1.300-gravity sulfuric acid, which
consists of 30-percen t concen trated acid and 70-percent distilled water by
volum e. Recharge un til all cells gas for an hou r. Repeat the procedu re if
the gravity is still not norm al. To lower the gravity, rep lace some of theelectrolyte with distilled water .
2.182.18 HYDROMETE R READINGSHYDROMETER READINGS
Provide two hydrometers of high accuracy and sensitivity and check them
against each other frequen tly. The h ydrometer s should be replaced every 2to 3 years. The hydrometer must be held vert ically for accu rate specific
gravity readings. Do not take readings after adding water (or acid) un til the
electrolyte h as had time to m ix thoroughly (not less than 1 hour when
gassing or 2 days if not gassing for an timony cells, an d severa l weeks for
calcium cells in floating service). Use a long nozzle syringe and take
samples several inch es down to minimize errors. Bubbles in the elect rolyte
cause err ors, and r eadings should not be taken sooner th an 15 m inutes after
gassing has stopped.
Specific gravity of electrolyte mu st be correcte d for temperature. Subtract
one point (0.001) from the specific gravity reading for each 3 EF the
temperatu re is below 77 F, and add one point (0 .001) for each 3 EF thetemperatu re is above 77 F. The r ecomm ended specific gravity spread
between all cells is 0.010.
2.192.19 CON STANT VOLTAGE CH ARGINGCONSTANT VOLTAGE CHARGING
Constant voltage ch arging is the preferred meth od because of extended
service life. If charging equ ipmen t is suitable for a continuou sly floating
charge at a constant voltage, the proper floating voltage should be chosen
from the manufactu rer s data. If the voltage is given for a single cell,
mu ltiply th is voltage by the n um ber of cells in the batte ry.
2.202.20 BATTE RY LIFE FOR DIFF ERENTBATTERY LIFE FOR DIFFERENT TYPES AND SERVICESTYPES AND SERVICES
The life of various types of cells can vary markedly. Valve regulated lead-
acid cells have the shortest life. Formed plates of the P lante or Manchex
type on light du ty and floating charge have a longer life, u sually 14 to 18
years. Pasted p late Plante cells may be expected to last in excess of 25 year s
on float ch arge. Form ed plate ce lls, if cycle cha rged, usu ally last only about
9 years. Lead-calcium cells on constan t float charge typically last 12 to 15
Rev.12/31/97 21
-
7/29/2019 battery maintenance manual.
27/83
years. Lead-selen ium cells have a longer life expectation than lead-calcium
or lead-an timony. A batter y is considered worn ou t when it fails to deliver
80 percen t of its original capacity.
2.212.21 CLEANLINESSCLEANLINESS
Battery connections m ust be clean , bright, and free of corrosion for th e
battery to perform. Corrosion tha t is not clean ed off terminals per iodically
will spread in to areas between posts and connectors. Th is condition will
develop into a h igh re sistance connection an d cause h eating and wasted
capacity. The battery and su rroun ding parts should be kept clean, dry, and
free of acid. Su lfur ic acid absorbs moisture, and spilled electrolyte will not
dry up. If electrolyte is spilled or sprayed ou t of the cells on ch arge,
ne ut ralize with a solution of baking soda (1 poun d of soda to 1 gallon of
water), then rinse with distilled water and dry with a soft cloth. A labeled jarof soda solution at least one gallon, must be kept in the battery room. Care should betaken to prevent th e solut ion from getting into the cells. Make sure ven t
plugs are open, flame arresters an d dust caps are in place, and allcomponen ts are in good condition.
2.222.22 INTERNAL SHORTSINTERNAL SHORTS
A short circuit th rough a separ ator may be caused by:
1. Insufficient ch arging causes mater ial in the plates to become mostly leadsulfate. The lead su lfate expan ds and , if the grid does not crack to relieve
the strain, the plate will become distorted. This condition is commonly
known as buckling. The buckling is most pronounced at th e four corn ers
of the positive plates, where sh orts are most likely to occur .
2. Impurities in the solution cau sed by using contaminated water or dirtyutensils.
3. Excessive overcharging causes th e grid specific gravity to be partiallyconverted to lead peroxide, which redu ces mech anical strength and
allows positive an d n egative plate contact.
A short in a cell can be detected by falling specific gravity and falling cell
voltage. In some cases, an oran ge discoloration occur s at the point of the
short . If a shor t is long standing, disin tegration of the positive plate will
occur a t the point of contact with the negative because of the conversion ofpositive plate mater ial to negative.
2.232.23 NORMAL SULFATE AND OVER SULFATIONNORMAL SU LFATE AND OVER SULFATION
During discharge of a battery, "normal" sulfate is formed, which is required
to produce cu rrent . If charging is neglected, the sulfate fills the pores of the
plates and m akes the active mater ial dense and ha rd. This condition is
referr ed to as "over sulfated."
Rev.12/31/97 22
-
7/29/2019 battery maintenance manual.
28/83
Normal lead sulfate formed on discharge is in a form th at a charge will
easily recon vert . When a batter y is "over sulfated," plates are less porous
than norm al and absorb a charge with difficulty. With this condition, an
ordinary charge will not reconvert all the sulfate to sulfuric acid and specific
gravity remains below norm al. Active mater ial of "over su lfated" negative
plates is light in color and either h ard an d den se or granular an d gritty and
easily disint egrated . The negative plates requ ire the prolonged charge
necessary to restore an "over su lfated" battery. An individual cell may
become "over su lfated" by extern al groun ding, by an inter na l short, or by
drying out because of failure to add water. Over sulfation may also be caused
by prolonged low float charging.
2.242.24 ELIMINATION OF OVER SULFATIONELIMINATION OF OVER SULFATION
A battery or ce ll that is "over sulfated" shou ld be ch arged fu lly in the regular
way un til specific gravity stops rising. Then one of the weakest ce lls should
be dischar ged th rough a load resistor at the n ormal 8-hour discharge rate to
a final voltage of 1.75 volts. The batte ry is not over sulfated if therepresen tative cell gives normal capacity, that is, about 100 pe rcen t ra ted
capacity for a fairly new battery or down to 80 percent of initial rated
capacity for a battery nearing the end of its expected life.
If the above capacity is not obtained, possible over sulfation shou ld be
treated as follows:
1. In cases where one or more individual cells have become "over sulfated"and the rest of the battery is in good condition, these cells should be
treated separately after rem oving them from th e circuit.
2. Recharge the removed cells at half the 8-hou r discharge rate. Recordhydrometer readings and tem peratu re at regular intervals (3 to 5 hour s)
during the charge to determine if rising specific gravity has peaked.
Maintain constant electrolyte level by adding water after each reading.
Do not add water before taking readings.
3. Continue the charge, recording the readings un til no furth er specificgravity rise has occurred in any cell for 10 hour s. If the temper ature
reach es 100 F, reduce the cu rren t or temporarily interru pt the ch arge so
as not to exceed this temperatu re. When the specific gravity has reach ed
maximum , terminate th e char ge an d record the hydrometer reading of
each cell.
4. The cells must be replaced if they again fail the capacity check in 2.24.
Rev.12/31/97 23
-
7/29/2019 battery maintenance manual.
29/83
2.252.25 WATER TREATMENT FOR OVER SULFATIONWATER TREATMENT FOR OVER SULFATION
In cases of emergency such as plant power loss or loss of both chargers, a
long discharge to the point of over-discharge may make the batte ry difficult
to recover. Over sulfation may have occurred su ch th at prolonged charging
set forth in section 2.24 m ay not recover th e battery.
The water trea tmen t should only be attempted in an emergency as a lastlastresort after p rolonged charges will not restore the specific gravity.
The pr inciple is to reduce th e specific gravity in steps by removing a portion
of the electrolyte and replacing it with distilled water, then charging the
battery after each step. As the specific gravity is reduced and the ch arge is
applied, th e su lfate is dissolved from th e plate s by lower specific gravity
electrolyte at each step. The e lectrolyte becomes more an d more like pur e
water, making it easier for th e su lfate t o tran sfer off the plates into th e
electrolyte. Once th e sulphates have been dissolved an d rem oved, the
process is reversed to bring the electr olyte back to norm al specific gravity.
The steps are as follows:
1. Redu ce th e specific gravity to about 1 .050 to 1.100 by rem oving some ofthe electrolyte an d replacing it with distilled water.
2. Charge the battery at the equalizing rate until the specific gravity of thepilot cell stops rising for two consecu tive readings. However, do not
charge longer than 48 hour s before the n ext step.
3. Again reduce the specific gravity as in step 1 above and repeat the chargein step 2.
4. Repeat th e above steps u ntil the maximum specific gravity obtained at theend of a charge is less than 1.150.
5. Reverse the above process by removing some of the weakened electrolyteand replacing it with 1.300 specific gravity acid. The amoun t to be
replaced is about the sam e as that in step 1 above. Do not try to speed up
the process by replacing more of electrolyte th an that rem oved in steps 1
through 4.
6.
Charge the batte ry as in step 2 above, ch ecking the specific gravity of 10percen t of the cells.
7. Repeat steps 5 an d 6, increasing the specific gravity un til it is just be lownormal opera ting value. Record th e specific gravity of all the cells on th e
last step.
8. Place the battery back under n ormal float charge an d service.
Rev.12/31/97 24
-
7/29/2019 battery maintenance manual.
30/83
9. After 1 month un der n ormal service, the battery should be given a
capacity test to see if the battery must be replaced (see section 3.2).
Rev.12/31/97 25
-
7/29/2019 battery maintenance manual.
31/83
3. BATTERY TESTING
The purpose of this section is to describe recom men ded testing procedures
and intervals. Inform ation herein con sists of guidelines on ly and is not
intended to replace manu facturers recomm endations. Follow
man ufacture rs informa tion if a conflict between these guidelines and
man ufacturers information is en countered.
3.13.1 ACCEP TANCE TES TINGACCEPTANCE TESTING
Acceptance testing should be performed n o sooner t han 1 week after th e
battery has had its initial freshening charge (see section 1.2 A). This test
may be done a t the factory before shipping if specified. This test should be
at least a 3-hour d ischarge test an d should provide at least 90 percen t of
rated capacity. An 8-hou r discharge test for acceptance is preferred , and 90
percen t of rated capacity should be required.
3.23.2 CAPACITY TES TS TO DETERMINE REPLACEMEN TCAPACITY TESTS TO DE TERMINE REPLACEMEN T
To establish whether a battery is nearing the end of its useful life, load test
the en tire battery as out lined below at 5-year intervals. This test shou ld be
repeated ann ually if the capacity has dr opped below 90 percent.
A.A. After th e batte ry has been fully charged by equalizing, retu rn it to floatservice for at least 72 h ours, but less than 30 days before pe rforming the
test.
B.B. Check all battery conn ections with a m icro-ohmm eter to en sureconnections are clean an d low resistance. An IR camer a may be used
just after th e disch arge t est has begun to ch eck the con nection s.
Temperatu re will be higher on poor conn ections. If poor conn ections are
foun d, stop the te st and repair the conn ections before continu ing.
C. C. Record the specific gravity and voltage of each cell just prior to th e test.D. D. Record the tem peratu re of the electrolyte of 10 percen t or more of the
cells (an IR camera may be used an d the tem peratu re of cell cases may
be recorded) to establish an average temperatur e.
E. Record the batte ry term inal float voltage. Use an accu rate digitalvoltmeter.
F.F. Take precau tions t o ensu re that a battery failure will not jeopardize otherequipmen t. Discharge the battery through a suitable resistor and an
amm eter for 3 hour s at rated 3-hou r discharge curren t. Leave the
charger in normal float operation and record each cell voltage every half-
hour during discharge. Watch closely dur ing the last hour an d time the
exact end point accu rately. After ambient tem peratu re correction to
77F, if the minimum voltage of 1.75 in any cell is reached before 3 hours
Rev.12/31/97 26
-
7/29/2019 battery maintenance manual.
32/83
has elapsed, the test should be stopped and the amper e-hours discharge
should be computed. Capacity can be de term ined by referring to figure
3. Testing should be done each year if the capacity is less than 90
percen t of the original rating. The entire battery should be replaced as
soon as possible after capacity drops below 80 percen t of original. The
battery cann ot be relied u pon in an emergency if it has deter iorated
below 80-percent capacity.
Rev.12/31/97 27
-
7/29/2019 battery maintenance manual.
33/83
4. OPTIONAL INSTRUCTIONS LEAD-CALCIUM BATTERIES
4.14.1 FLOAT CHARGEFLOAT CHARGE
For a typical, 60-cell, lead-calcium battery floated a t 2.17 volts per cell and
equalized at 2.33 volts per cell, the normal voltage range would be 130.2 to
139.8 volts. At many locations, the h ighe r voltage can not be tolerated for
the 6 or more days required for equalizing, particularly where the battery is
a source of power for electronic equipmen t. Lead-calcium batteries do notrequire equalizing if floated between 2.2 an d 2.25 volts per cell. Th is voltagewould give a 60-ce ll battery a voltage between 132 an d 135 volts. Lead-
calcium batteries have a d istinct advantage when constant voltage is
desirable. To match the battery voltage to the rated voltage of the
equipmen t served, the n um ber of cells should be selected to provide
optimu m voltage when floated to eliminate the equalizing charge. This
procedure should be considered when replacing batteries. The table below
lists some common voltage ranges.
Table 2. - Comm on voltage ranges.
Nu mb Voltage Range
er (volts)
of
Cells
12 26.4 to 27.0
23* 50.6 to 51.75
24 52.8 to 54.0
58* 127.6 to 130.5
59* 129.8 to 132.75
60 132.0 to 135.0
116* 225.2 to 261.0
120 264.0 to 270.0
* The low battery alarm m ust be ca librated to r eflect th e lower n um ber of cells.
4.24.2 INITIAL CHARGEINITIAL CHARGE
An initial charge is not required because the battery will charge properly at
the above voltages. After abou t 2 weeks, initial cell voltages and specific
gravity readings shou ld be recorded on form POM-133A. Increase the
voltage to 2.33 to 2.38 volts per cell (connected equipment permitting) if the
initial charge mu st be completed sooner .
4.34.3 VOLTAGE READINGSVOLTAGE READINGS
A.A. Each Sh ift (Atten ded Stations) or Dur ing Routine Inspections (Unat ten ded Stations)Each Shift (Attended Stations) or During Routine Inspections (Unattended Stations)
Check the ch arger panel voltmete r to determ ine if the battery is being
Rev.12/31/97 28
-
7/29/2019 battery maintenance manual.
34/83
floated at the proper voltage. Adjust the battery charging voltage when
nece ssary, and check when the power or station-service transformer taps are
changed.
Rev.12/31/97 29
-
7/29/2019 battery maintenance manual.
35/83
B.B. Mon t hlyMonthly
Check voltage across the battery terminals with an accurate digital voltmeter
and adjust the panel voltmeter if necessary. Record pilot cell voltages to the
nea rest 0.01 volt, measured with an accur ate digital voltmete r, on form
POM-133A. Batte ry is fun ction ing norm ally if all cells are above 2.14 volts.
C.C. QuarterlyQuarterly
Check voltages across all ind ividual cells and r ecord them on POM-133A.
4.44.4 SPECIFIC GRAVITY READINGSSPECIFIC GRAVITY READINGS
A.A. Month ly (Atten ded Stations) or During Routine Inspections(Un atten ded Stations)Monthly (Attended Stations) or During Routine Inspections(Unattended Stations)
Read th e specific gravity of the pilot cell. For accu rate readings, hold the
hydrometer vertically and use a long nozzle syringe about one-third down
from the top. Record th e pilot cell specific gravity, correc ted fortemperatu re, on form POM-133A.
B.B. Quar te rlyQuarterly
Read the specific gravity of 10 percent all cells and record, corrected for
temperatu re, on form POM-133A.
C.C. AnnuallyAnnually
Read the specific gravity of 100 percen t of the ce lls, correc ted for
temperatu re, and record on form POM-133A.
4.54.5 HEAVY DIS CH ARGEHEAVY DIS CH ARGE
The battery should be recharged as quickly as possible following a h eavy
dischar ge. This rech arge can be done by raising the charging voltage to the
maximum allowed by other circu it components but n ot greater than the
ran ge of 2.33 to 2.38 volts per cell. The battery should be retu rned to
norm al voltage after the capacity been restored.
4.64.6 WATER REPLACEMEN TWATER REPLACEMENT
Add water only when the water level approach es th e low level mar k or priorto an equ alizing charge. This step shou ld be needed every 2 or 3 year s with
a proper charging program .
Rev.12/31/97 30
-
7/29/2019 battery maintenance manual.
36/83
TABLE 3. - VALVE REGULATED LEAD-ACID BATTERY (GEL CELL)
MAINTENANCE SCHEDULE
31
Mainten anc e New Battery Shift Monthly 3-Month 6-Month Ann ual
Visual General
Inspection Inspection
See 5.6
Batter y Float Pane l Meter Battery Float Voltage
Voltage Float with Digital Voltmeter
See 5.7 Voltage
Cell Float All Cells Pilot Cells All Cells
Voltage with Digital with Digital with Digital
See 5.7 Voltmeter Voltmeter Voltmete r
Tem perat ure All All
Readings Cells Cells
See 5.8
Conne ction All 25 Perce nt All
Resistance Conne ctions of All Conne ctions
See 5.9 Connections
In ter na l All All
Resistance Cells CellsSee 5.10
Battery Accept anc e Capacity Test 6
Testing Capacity mont hs if 1-year
See 5.11 Testing test < 90 percent
Safety Wash Equipment
Equipment Protective Clothing
See 5.6 & 8.0 Fire Extinguisher , etc.
-
7/29/2019 battery maintenance manual.
37/83
5. CONDENSED INSTRUCTIONSCC
VALVE REGULATED LEAD-ACID BATTERIES (GEL CELLS)
5.15.1 GENERALGENERAL
Valve regulated lead-acid batt eries (VRLA) are u sually manu factured inmu lti-cell blocks, (called modules) rathe r than single cells. The cases are
often made of ABS plastic material and do not permit visual inspection of
plates or electrolyte levels. They are called starved electrolyte or absorbed
electrolyte cells and operate u nde r a positive pressure . The h ydrogen and
oxygen ar e not expelled but recombined. Cells are sealed and requ ire no
water addition or spec ific gravity readings. These ce lls are typically lead
calcium pasted-plate type cells with the electrolyte retained in gel or
fiberglass mats.
These batteries are normally used for emergency lighting,
telecommunications, and other u ninter rupted power supply (UPS) service.
They are best applied where long slow dischar ges are n eeded. Heavy shortdischarges required for breaker operations are n ot recomm ended for th is
type batter y. The life has been foun d to be only 18 mon ths to 10 years in
actual service.
These cells are not flooded and do not effectively dissipate heat. Thischar acteristic can lead to therm al runaway if ambient an d battery
temperatu res are n ot carefully controlled (see 5.2 below). Cases have
occurred in which the battery has burst into flame . Maintaining the cells as
close as possible t o 77 EF is imperative. Ambient tem peratu re should bemaintained as close as possible to 72 EF. Air circu lation must be sufficient
to eliminat e any ambient temperatu re differences. The maximu m cell
temperatu re spread (h ottest to coldest cell) should not exceed 5 EF, and the
hottest cell should not be more than 5EF above am bient. Colder
temperatures reduce capacity, and higher temperatures greatly reduce service life.About 50 pe rcent of the service life will be lost for every 15 EF above 77EF.
Do not allow sun light or other h eat sources to raise the temperatu re of
individual cells. These cells are not recommended for station service because of thesecharacteristicscharacteristics.
VRLA modu les/cells are typically shipped fully charged and do not require
initial charge.
5.25.2 FLOAT CHARGEFLOAT CHARGE
VRLA cells are typically floated at 2.25 to 2.30 volts depending on the
manufactu rer . Correct battery float voltage is critical for valve-regulated
cells. The float voltage mu st be within the m anu facturers recommended
limits compen sated for temperatu re. See the man ufacture rs literatu re for
temperature compensation of float voltages.
When VRLA cells are operated on float at normal full charge, no net
Rev.12/31/97 32
-
7/29/2019 battery maintenance manual.
38/83
chem ical reaction occur s and almost all the overcharge energy results in
heat generation. If the en vironmen t is such that th e heat produced can be
dissipated, no therm al runaway problem occur s. If the r ate of hea t
gene rated exceeds the dissipated rate, the battery temperatu re rises and
more cu rren t is requ ired to maintain the float voltage. The additional
current results in more heat generation, which raises the battery
temperatu re furth er, and the cycle is repeated. Ther mal runaway and
destruc tion of the battery result. Elevated am bient temperature (above 72F)
or cell and/or charger malfunction will aggravate this condition.
Ven tilation an d tem pera ture con trol is critical for VRLA cells, and th e
battery should reach t hermal equilibrium at no more than 5F above
ambient for the hottest cell.
As cells approach fu ll cha rge, battery voltage rises to approach the ch arger
output voltage, and charging curren t decreases. The battery is fully charged
when the ch arging curren t has n ot changed more than 10 percen t for more
than 3 hou rs. If the charging voltage has been set h ighe r than float voltage
to redu ce th e ch arging time, redu ce th e ch arging voltage to n ormal floatvalue after th e ch arging cur ren t has stabilized. Caution: Never exceed themaximum charging voltage recommended by the manufacturer.
5.35.3 EQUALIZING CHARGEEQUALIZING CHARGE
Equ alizing charge is not n orma lly per form ed on VRLA cells. An equa lizing
charge m ay be n ecessary if a low float voltage is indicated or if a fast
rech arge is needed. The battery man ufacture r should be consulted before
proceeding if an equalizing charge is needed. The exact voltages and charge
times indicated by the man ufacture r m ust be followed ca refully.
5.45.4 CHARGERCHARGER
A VRLA cell char ger mu st have at least two capabilities: (1) extra e lectrical
filtering to protect the cells from AC ripple, which may lead to thermal run
away, and (2) temperatu re compensation to prevent therm al run-away. Do
not try to charge these cells with a charger designed for afloodedlead-acidcells.
5.55.5 BATTE RY MAINTEN ANCEBATTERY MAINTENANCE
The regimen described below is strongly recommen ded to maximize
performance an d life expectancy. See man ufacture rs data and IEEE 1188-1996Recommended Practice for Maintenance, Testing, and Replacement of Valve-RegulatedLead-Acid (VRLA) Batteries for Stationary Application for further information.
5.65.6 VISUAL INSPECTIONSVISUAL INSPECTIONS
Visual inspections are made to assess the general condition of the battery,
moun ting rack and battery room, and safety equipmen t.
Rev.12/31/97 33
-
7/29/2019 battery maintenance manual.
39/83
A.A. MonthlyMonthly
Check for gene ral cleanliness of the battery, moun ting rack, and battery
room. Check for electrolyte leaks and cover integrity, and take corrective
action if needed. Check for corrosion at term inals, connectors, racks, and
cabinet s. Check the ambient tem peratu re and m ake sure all ventilation
equipmen t (fans, vents, etc.) is operable.
Check for availability and con dition of all safety equipmen t, gloves, apr ons,
face shields, etc. Check for a full gallon of labeled neu tra lizing solut ion.
Check for cleanliness and operability of eyewash station or portable eyewash
equipmen t and body wash station (see section 8.2). Check for a class C fire
extinguisher and ensu re tha t it has been inspected an d tested according to
schedu le. Carbon dioxide (CO2) fire extinguishers are not recommended
becau se of the cooling effect they will have on th e battery. Check for
availability of insu lated tools and u ten sils so short circu its can be avoided.
5.75.7 VOLTAGE READINGSVOLTAGE READINGS
An accu rate digital voltmeter is critical for exten ded life of the batte ry (see
section 1.3). At a constan t float voltage, the charging cur ren t will increase
as the tem peratu re of the electrolyte increases. The refore, cells of higher
tem peratu re will indicate a lower cell voltage. See figur e 10 for proper
mete r probe placement. Place the probes across the posts of the ce ll so as
not to include the voltage dr ops across the intercell connections.
A.A. Initial VoltageIn itial Voltage
Readings of all cells should be taken and recorded about 24 h ours after
placing the batter y in float. Select th e cell/modu le with the lowest floatvoltage as the pilot cell for futu re r eadings. Use form POM-133B for all
voltage readings.
B.B. Each ShiftEach Shift
Check th e voltmete r on the charger and adjust th e float voltage if necessary.
C.C. When Taps Are ChangedWhen Taps Are Changed
When taps are changed on the power or station service tran sformers, check
the float voltage on the charger panel and adjust if necessary.
D.D. MonthlyMonthly
Check and record the voltage of the pilot cell with an accurate digital
voltmeter.
E.E. MonthlyMonthly
Rev.12/31/97 34
-
7/29/2019 battery maintenance manual.
40/83
-
7/29/2019 battery maintenance manual.
41/83
and compare them with the previous readings. Rotate the measured
connections each quarter. Repair those that have increased 20 percent in
resistance.
C. C. AnnuallyAnnuallyRecord the resistance of all the con nections as in step A above an d compare
them with the previous readings. Repair those that h ave increased 20
percent in resistance.
D. D. Dur ing Discha rgeDur ing Dischar geConnection integrity may be checked with an accurate IR camera.
Temperatu re of the h igher resistance conn ections will be noticeably higher
and should be repaired.
5.105.10 INTE RNAL RESIS TANCEINTE RNAL RESISTANCE
Internal resistance is a good indication of the state of charge and substitutes
for specific gravity readin gs taken on flooded, lead-acid type ce lls.
Measuring the inte rnal resistance of a modu le monitors the two main failure
modesgrid corrosion and dryout. The man ufactu rer s litera ture will list
the n ormal expected values. This test should not be done un til after the
connection resistances of the cells are ch ecked and repaired a s in 5.9 above.
Elevated connection re sistance will appear as inte rnal resistance and make
cells appea r fau lty. Int ern al resistan ce can be checked as follows:
1. While the battery is fully charged and operating on float, check andrecord voltage an d cu rren t for the cell being tested.
2. Apply a n orma l load across th e ce ll.3. Again check and r ecord the voltage and cu rren t.4. The intern al resistance can t hen be calculated by dividing the chan ge in
voltage by the ch ange in cu rren t.
Commercial test sets are available to measur e inter nal resistance, which
saves time and effort. Consider purch asing a test set if maintain ing more
than one VRLA battery.
A.A. Upon InstallationUpon InstallationAfter the battery has reach ed equ ilibrium (1 to 3 days) on float, perform theintern al resistance ch eck on each ce ll/module and r ecord the r esults on
form POM-134B as a baseline for futu re comparisons.
B.B. Quar te rlyQuarterly
Perform the internal resistance check on each cell and compare the results
with th e initial records. Chan ges in th e intern al resistance of 20 percen t or
greater should be considered significant. Contact the battery man ufacture r
Rev.12/31/97 36
-
7/29/2019 battery maintenance manual.
42/83
and follow their recomm endations.
5.115.11 TESTINGTESTING
A.A. Upon InstallationUpon InstallationAcceptance capacity testing should be performed within 1 week after the
battery has reached equilibrium in charge and temperatu re. Oper