base paper upfc

Upload: bhargav-reddy

Post on 07-Aug-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/19/2019 Base Paper UPFC

    1/10

    IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 11, NOVEMBER 2014 5813

    Line Loss Minimization in Isolated Substations and

    Multiple Loop Distribution Systems Using the UPFCMahmoud A. Sayed , Member, IEEE , and Takaharu Takeshita , Member, IEEE 

     Abstract—This paper presents the line loss minimum conditionin isolated substations and same substation multiple loop distribu-tion systems by using the unified power flow controller (UPFC).In each case, the mathematical model is presented and the lineloss minimum conditions are obtained based on the line param-eters of the distribution feeders. Since multiple loop distributionsystem is fed from same substation, the line loss minimization canbe achieved by compensating the summation of the line reactancevoltage drop. In an isolated substation loop distribution system,the line loss minimization can be achieved by compensating thesummation of the line reactance voltage drop in addition to thevoltage difference of the substations. Realization of both cases canbe achieved if the loop current is eliminated from the loop system.

    The series compensation technique applied by the UPFC is used toeliminate the loop current from the loop distribution system andhence minimize the total line loss. Theeffectiveness of theproposedcontrol schemes of the UPFC have been verified experimentally.

     Index Terms—FACTS, line loss minimization, loop distributionsystem, series compensation, unified power flow controller(UPFC),voltage regulation.

    I. INTRODUCTION

    GREENHOUSE gas emissions are considered one of the

    most important problems that affect our environment and

    causes climate change. Electrical Energy supplies are consid-

    ered as oneof themain contributors in globalwarming since they

    emit carbon dioxide (CO2 ), which is the most abundant green-

    house gas. Therefore, concerns over global warming problems

    have led to change the operation and design standards for dis-

    tribution networks. The most important of these is the energy

    saving. Line loss minimization in distribution systems is the

    most efficient solution in order to achieve energy saving. In ad-

    dition, line loss minimization enhances the voltage profile along

    the distribution feeders [1], [2].

    Distribution networks are mainly classified as either radial

    or loop. The radial system is commonly used because it has

    simple and inexpensive protection schemes. Also, its voltage

    profile can be controlled easily. However, radial systems are of-

    ten quite weak because of the long distances involved and thehigh resistance-to-inductance ratio of the lines that are used,

    Manuscript received July 13, 2013; revised October 23, 2013 and December3, 2013; accepted January 8, 2014. Date of publication January 29, 2014; dateof current version July 8, 2014. Recommended for publication by AssociateEditor P. Barbosa.

    M. A. Sayed is with the Department of Electrical Engineering, Fac-ulty of Engineering, South Valley University, 83523 Qena, Egypt (e-mail:

    [email protected]).T. Takeshita is with the Department of Electrical and Computer Engi-

    neering, Nagoya Institute of Technology, 466-8555 Nagoya, Japan (e-mail:[email protected]).

    Digital Object Identifier 10.1109/TPEL.2014.2301833

    Fig. 1. Configuration of the distribution system.

    and the continuous increasing of the power demand. Hence, as

    the demand power increases on these networks, power quality

    issues such as high power loss often become a significant prob-

    lem. Ideally, the power loss in electrical systems should not be

    more than 6%. However, in developed countries, the power loss

    is more than 10%, whereas in developing countries, it is more

    than 20% [3]. Therefore, distribution system engineers haveproposed a loop system to achieve the merits of line loss reduc-

    tion and to enhance the load voltage profile along the feeders.

    Although, the loop distribution system requires complex pro-

    tection schemes [4], [5], it is also more reliable service that is

    offered for critical loads such as hospitals. As a result, much

    of recent research works have considered reconfiguring the ra-

    dial distribution system to loop one in order to achieve these

    objectives [6]–[9].

    Reconfiguration of radial distribution systems to the closed-

    loop lines, using the existing infrastructure, is done in the

    medium voltage by connecting the ends of adjacent radial feed-

    ers. Based on the feeder substation, two different types of the

    loop system may result. These types are the isolated substationsloop system and multiple loop system [8], [10], as shown in

    Fig. 1. The isolated substations loop system results from re-

    configuring two radial feeders fed from different substations

    to perform one loop, whereas the multiple loop system results

    from reconfiguring more than two radial feeders fed from same

    substation to perform at least two adjacent loops. In the isolated

    substations loop system, a loop current may results from the

    voltage difference between substation voltages in addition to

    the asymmetrical line parameters of the feeders. In a multiple

    loop system, a loop current may results from the asymmetrical

    line parameters of the feeders, only, since its feeders are fed

    from the same substation.

    0885-8993 © 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See http://www.ieee.org/publications standards/publications/rights/index.html for more information.

  • 8/19/2019 Base Paper UPFC

    2/10

    5814 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 11, NOVEMBER 2014

    Recent research in distribution networks has been focused

    on the minimizing power loss and enhance the load voltage

    profile along the feeders by using power electronics technolo-

    gies [11]–[18]. The idea given in [11]–[15] has been achieved

    using STATCOM, SSSC, and active filters-based shunt and se-

    ries power converters to compensate the reactive power in dis-

    tribution systems, and hence, control the power flow. In [16]

    and [17], power balancing between feeders using a back-to-

    back converter has been proposed to reduce the loop power loss

    and improve the load voltage profile. In [18], a loop power con-

    troller has been used to reconfigure two radial systems to loop

    in order to reduce the power loss and mitigate power flow over-

    loading. In [19]–[21], the authors have proposed the line loss

    minimum conditions in loop distribution systems, and experi-

    mentally achieved these conditions by using the unified power

    flow controller (UPFC). In [20], the authors proposed load volt-

    age regulation to be equal in the magnitude to the source volt-

    age under line loss minimum condition. However, the proposed

    technique cannot guarantee the other load voltages to be within

    the permissible voltage range. In [21], the authors proposed anew technique for controlling all load voltages to be within the

    permissible voltage range under line loss minimum condition

    by controlling both the load voltage magnitude and phase an-

    gle to follow reference values. The reference load phase angle

    was calculated from the line loss minimum condition, whereas

    the reference voltage magnitude was calculated based on the

    voltage magnitude of each load in the loop system. Line loss

    minimization can be achieved if the loop current is eliminated

    from the loop system. This condition can be achieved if, at least,

    the line parameters of all loop lines have the same ratio between

    the resistance and inductance. This can be realized in the same

    substation loop distribution system since it has only one substa-tion for the whole loop, whereas in an isolated substations loop

    system this condition cannot be realized due to the voltage dif-

    ference between them, which may result from small difference

    in the magnitude or phase angle. The difference between the

    substation voltages results in an excessive loop current that will

    flow in the loop lines even if the loop line parameter ratios are

    same.

    In this paper, the mathematical model of the isolated substa-

    tions and the same substation multiple loop distribution system

    is presented. Also, the line loss minimum condition is inves-

    tigated by using the UPFC in both loop systems. The UPFC

    shunt converter is used to regulate the dc-link voltage, whereas

    the series converter is used to control the power flow in order toachieve line loss minimum condition. Since the series converter

    performs the main function of the UPFC, its proposed control

    schemes in both cases are presented. The effectiveness of the

    proposed control schemes are investigated experimentally using

    a laboratory prototype of 200 V, 6 kVA.

    II. MODEL OF THE ISOLATED SUBSTATIONS LOOP

    DISTRIBUTION SYSTEM WITH THE UPFC

    The UPFC is used in a loop distribution system as a series

    compensator to control the power flow in the loop lines in order

    to achieve line loss minimum condition. Fig. 2 shows a simple

    Fig. 2. Model of the isolated substations loop distribution system.

    model of the isolated substations loop distribution system with

    the UPFC equivalent circuit. Since the UPFC shunt converter is

    used to regulate the dc-link voltage, its current is very small andcan be neglected. Therefore, the UPFC is simplified as a series

    voltage source that represents the series converter voltage.

    The loop system is represented by three distribution lines

    (Line 1, Line 2, and Line 3). Each line has its resistance (Ri) andinductance (Li ), where  i   is the line number  (i = 1, 2, 3). Theline impedance is represented by  Ż i  = Ri  +  jωLi . Since theloop system is isolated substations, it is supplied from different

    substations represented by two voltage sources ( V̇ 1  and  V̇ 2 ). Thesystem feeds two loads represented by constant current sources

    ( İ L1   and  İ L2 ). The line current of each line in the loop systemflows in the same direction. The UPFC series injected voltage

    is represented by the voltage source ( V̇ c).

     A. Before Installing the UPFC 

    The line currents  İ i   (i = 1, 2, 3), that flow in each line of the loop system, before installing the UPFC, can be formulated

    using Superposition theorem as follows:

    İ 1  =  ( Ż 2  +  Ż 3 ) İ L1  +  Ż 2  İ L2  + ( V̇ 1 −  V̇ 2 )

    Ż loop

    İ 2  = − Ż 1  İ L1 −  ( Ż 1  +  Ż 3 ) İ L2  + ( V̇ 1 −  V̇ 2 )

    Ż loop

    İ 3  =  − Ż 1  İ L1  +  Ż 2  İ L2  + ( V̇ 1 −  V̇ 2 )Ż loop

    (1)

    where

    Ż loop =3

    i=1

    Ż i , Rloop =3

    i=1

    Ri , Lloop =3

    i=1

    Li . (2)

    According to the line loss minimization theory in the loop

    distribution system [19]–[21], the line currents can be divided

    into two currents. The first one is the current flow in each line

    during the line loss minimum condition [ İ mi , (i = 1, 2, 3)], andthe second one is the loop current  İ loop   that circulates in the

    loop lines, as shown in Fig. 2. Therefore, the line current can be

  • 8/19/2019 Base Paper UPFC

    3/10

    SAYED AND TAKESHITA: LINE LOSS MINIMIZATION IN ISOLATED SUBSTATIONS AND MULTIPLE LOOP DISTRIBUTION SYSTEMS 5815

    Fig. 3. Equivalent circuit of the loop system under line loss minimization.

    formulated as follows:

    İ i  =  İ mi +  İ loop . (3)

    The line currents that flow in each line of the loop system

    during line loss minimization,   [ İ mi ,  (i = 1, 2, 3)], can be for-mulated as follows:

    İ m1  = {(R2  +  R3 ) İ L1  +  R2  İ L2}/Rloop

    İ m2  = {−R1  İ L1 −  (R1  +  R3 ) İ L2}/Rloop

    İ m3  = {−R1  İ L1  +  R2  İ L2}/Rloop

    . (4)

    Considering the voltage difference in substations, the loop

    current  İ loop   that circulates in the loop system lines can beformulated as follows:

    İ loop  = −  1

    Rloop

      3i= 1

     jωLi  İ i + ( V̇ 2 −  V̇ 1 )

    . (5)

    The total power loss in the isolated substation loop systemlines can be formulated as follows:

    P l  =3

    i=1

    Riİ i2

    =

    3i=1

    Riİ mi2 + 2

      3i=1

    (Ri  İ mi)

    · İ loop

    + Rloopİ loop 2 . (6)

    According to (6), the line loss minimum condition can be

    achieved in the loop system if the loop current  İ Loop   is elimi-

    nated from the system. In this case, the line currents that flowin the loop lines after eliminating the loop current are   [ İ mi ,(i = 1, 2, 3)]. Fig. 3 shows the equivalent circuit of the isolatedloop distribution system in case of line loss minimization. There-

    fore, the resultant total line loss can be formulated as follows:

    P lmin   =3

    i= 1

    Riİ mi2 . (7)

    The line loss minimum conditions can be obtained by equat-

    ing the loop current, shown in (5) with zero, as follows:

    3

    i=1

     jωLi  İ i + ( V̇ 2 −  V̇ 1 ) = 0. (8)

    The loop current can be eliminated from the loop system if 

    the summation of the reactance voltage drop in addition to the

    voltage difference between the substation voltages equals zero.

    The summation of the reactance voltage drop equals zero if the

    resistance-to-inductance ratio in each line of the loop system is

    the same. Therefore, the loop current can be eliminated from

    the loop system if the following conditions have been realized,

    simultaneously:

    R1/L1  = R2/L2  = R3/L3

    V̇ 2 −  V̇ 1  = 0

    . (9)

     B. After Installing the UPFC for Line Loss Minimization

    The UPFC is installed in an isolated substations loop sys-

    tem in order to eliminate the loop current from the system by

    inserting a controlled series voltage that can compensate the

    difference between substation voltages in addition to the sum-

    mation of the reactance voltage drop in loop lines. In order to

    compensate the summation of the reactance voltage drop, two

    control schemes are proposed based on (8) and (9). These con-trol schemes are line inductance compensation and line voltage

    compensation. Both schemes have a common part that is used

    to compensate the difference between the substation voltages.

    In the line voltage compensation scheme, the series converter

    voltage of the UPFC can be formulated as follows:

    V̇ c  =3

    i=1

     jωLi  İ i + ( V̇ 2 −  V̇ 1 ). (10)

    As a function of time, the UPFC series converter voltage can be

    formulated as follows:

    vc  =

    3i= 1

    Lidi

    idt   + (v

    2 −  v1 ).   (11)

    In the line inductance compensation scheme, the UPFC is

    used to insert a virtual inductance,  Lc , which realize same ra-tio between the resistance and inductance in each line of the

    loop system. The inserted inductance Lc  can realize the sameresistance-to-inductance ratio in the loop system as follows:

    R1/(L1  +  Lc) = R2/L2  = R3/L3 . (12)

    Therefore, the inserted inductance  Lc   can be calculated asfollows:

    Lc  = (R1/R2 )L2 −  L1 . (13)

    Based on loop line parameters, the value of the inserted con-

    trolled inductance can be positive or negative [19]. The UPFC

    series converter voltage, for line loss minimization, can be for-

    mulated as follows:

    V̇ c  = − jωLc  İ 1  + ( V̇ 2 −  V̇ 1 ). (14)

    As a function of time, the UPFC series converter voltage can be

    formulated as follows:

    vc  = −Lcdi1dt

      + (v2 −  v1 ). (15)

    It is clear that the line inductance compensation scheme can

    be used in the loop distribution system if there is only one line

  • 8/19/2019 Base Paper UPFC

    4/10

    5816 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 11, NOVEMBER 2014

    Fig. 4. Model of the multiple loop distribution system.

    that has a different resistance-to-inductance ratio. Therefore,

    only this line current in addition to the substation voltages are

    required to obtain the reference voltage of the UPFC series

    converter. On the other hand, the line voltage compensation

    scheme can be used in the loop system if the resistance-to-

    inductance ratio is not the same in, at least, two lines of the loop.

    Also, in both schemes, the line loss minimum condition does

    not need the load information. Both schemes depend on loop

    line currents in addition to line impedance parameters to achieve

    line loss minimization. Therefore, the system performance will

    not be affected by load type.

    III. MODEL OF THE SAME SUBSTATION  MULTIPLE LOOP

    DISTRIBUTION SYSTEM WITH THE UPFC

    Fig. 4 shows the model of the same substation multiple loop

    distribution system. It consists of three radial feeders fed from

    the same substation. The loads fed from the radial lines are con-

    nected in parallel in order to obtain two adjacent loop systems.

    For mathematical model simplification, the loads are assumed

    to be adjacent. Therefore, the impedance parameters of the line

    connecting them are neglected. Line 1 has a step voltage regula-

    tor (SVR), a common device used to compensate load voltages

    along distribution feeders. It is assumed that the UPFC is in-

    stalled in series with line 1 to achieve line loss minimization by

    controlling the loop current in the two adjacent loop systems.

    The line currents in loop lines should flow in the same direction.

    Therefore, it is assumed that the currents  İ 1   and  İ 2  flow in the

    counter clockwise direction, whereas the currents  İ 2 and  İ 3 flowin the clockwise direction.

     A. Before Installing the UPFC 

    Considering that the UPFC output voltage is zero, the three

    load currents ( İ L1 ,  İ L2 , and  İ L3 ) can be lumped together ina single load current ( İ L ). According to the location of theSVR in line 1, the line parameter will be determined referred

    to the secondary side. Fig. 5 shows the equivalent circuit of the

    multiple loop system, shown in Fig. 4. The line currents in each

    feeder of the loop distribution system model, shown in Fig. 5,

    Fig. 5. Equivalent circuit of the multiple loop system.

    can be formulated as follows:

    İ 1   =  1

    Ż 1 +Ż 2  Ż 3

    Ż 2 + Ż 3

     Ż 2  Ż 3

    Ż 2 + Ż 3İ L  + (n−1) V̇ s

    İ 2   =   −1Ż 2 +

    Ż 1  Ż 3

    Ż 1 + Ż 3

      ˙Z 1

      ˙Z 3

    Ż 1 + Ż 3İ L−

    ˙Z 3

    Ż 1 + Ż 3(n−1) V̇ s

    İ 3   =  1

    Ż 3 +Ż 1  Ż 2

    Ż 1 + Ż 2

     Ż 1  Ż 2

    Ż 1 + Ż 2İ L−

    Ż 2

    Ż 1 + Ż 2(n−1) V̇ s

    (16)

    where

    Ż 1  = R1  +  jωL1

    R1  = n2R1a  +  R1b

    L1  = n2L1a  +  L1b

    (17)

    İ L  =  İ L1  +  İ L2  +  İ L3 . (18)

    Since the distribution system is connected to perform two

    adjacent loop systems, the line currents in each feeder can be

    divided into the loop circulating currents ( İ loop1   and  İ loop2 ) in

    addition to the currents at line loss minimum condition ([ İ mi ,(i = 1, 2, 3)]). Therefore, the line current can be formulated asfollows:

    İ 1  =  İ m1  +  İ loop1İ 2  =  İ m2  +  İ loop1  +  İ loop2İ 3  =  İ m3  +  İ loop2

    . (19)

    The loop circulating current in each loop system can be for-

    mulated as follows:

    İ loop1 =

    −V̇ m1 + V̇ m2 −(n−1) V̇ s

    +

    Ż 2

    Ż 2 + Ż 3( V̇ m2 + V̇ m3 )

    Ż 1 +Ż 2  Ż 3

    Ż 2 + Ż 3

    İ loop2 =

    Ż 2

    Ż 1 + Ż 2

    V̇ m1 + V̇ m2 −(n−1) V̇ s

    −( V̇ m2 + V̇ m3 )

    Ż 3 +Ż 1  Ż 2

    Ż 1 + Ż 2

    (20)

    V̇ mi  =  Ż i  İ mi(i = 1, 2, 3). (21)

  • 8/19/2019 Base Paper UPFC

    5/10

    SAYED AND TAKESHITA: LINE LOSS MINIMIZATION IN ISOLATED SUBSTATIONS AND MULTIPLE LOOP DISTRIBUTION SYSTEMS 5817

    Fig. 6. Equivalent model at line loss minimum condition.

    Line loss minimization in the loop distribution system can

    be achieved if the loop current is eliminated from the loop

    system. This can be realized by compensating the inductance

    voltage drop in each feeder constituting the loop system by

    using a series compensator. Therefore, the equivalent circuit of 

    the loop distribution system, shown in Fig. 5, in case of line

    loss minimization can be represented by a feeder resistanceonly as shown in Fig. 6. The line currents of each feeder in the

    system shown in Fig. 6, at line loss minimum condition, can be

    formulated as follows:

    İ m1  =  1

    R1  +  R2R3R2 +R3

      R2R3R2 +R3

    İ L

    İ m2  =  −1

    R2  +  R1R3R1 +R3

      R1R3R1 +R3

    İ L

    İ m3  =  1

    R3  +  R1R2R1 +R2

      R1R2R1 +R2

    İ L

    . (22)

    Based on (19), (20), and (22), the loop current in each loop

    system ( İ loop1  and  İ loop2 ) can be formulated as follows:

    İ loop1 =−V̇ 1 + V̇ 2 −(n−1) V̇ s

    +

      R2R2 +R3

    ( V̇ 2 + V̇ 3 )

    R1 +  R2R3R2 +R3

    İ loop2 =

    R2R1 +R2

    V̇ 1 + V̇ 2 −(n−1) V̇ s

    −( V̇ 2 + V̇ 3 )

    R3 +  R1R2R1 +R2

    (23)

    ˙V i  = jωLi

     ˙I i   (i = 1, 2, 3). (24)

    In this case, the total power loss can be formulated as a function

    of the line currents and the loop currents as follows:

    P l  =3

    i= 1

    Riİ i2

    =

    3i= 1

    Riİ mi2 + 2(R1  İ m1  +  R2  İ m2 ) ·  İ loop1

    + 2(R2  İ m2  +  R3  İ m3 ) ·  İ loop2  +  R1

    İ loop1

    2

    + R2İ loop1  +  İ loop2

    2+ R3

    İ loop2

    2. (25)

    According to (25), the line loss minimum condition can be

    achieved if both loop currents ( İ loop1  and  İ loop2 ) are eliminatedfrom the system. In this case, the resultant total power loss can

    be formulated as follows:

    P lmin   =3

    i= 1

    Riİ mi2

    . (26)

    It is clear from (23) that eliminating both loop currents from

    the loop system, in order to realize line loss minimum condition,

    can be achieved if the following two conditions are realized,

    simultaneously:

    V̇ 1 + V̇ 2 −(n−1) V̇ s  = 0

    V̇ 2 + V̇ 3  = 0

    . (27)

     B. After Installing the UPFC for Line Loss Minimization

    The main objective of installing the UPFC in the same sub-

    station multiple loop distribution system is to realize the line

    loss minimum condition by controlling the loop power flow,using the series compensation scheme, provided by the inserted

    controlled series converter voltage. Fig. 7(a) shows the multiple

    loop distribution system with the UPFC in case of line loss min-

    imization. The voltages (V 1 , V 2 , and V 3 ) represent the inductivevoltage drop in each line (Line 1, Line 2, and Line 3). Using

    Thevenin’s theorem, the system can be approximated as shown

    in Fig 7 (b) and (c) in order to obtain the reference voltage of the

    UPFC series converter. The parallel feeders (Line 2 and Line 3)

    are approximated by a resistor  Ż 0  in series with a voltage sourceV̇ 0 , which can be formulated as follows:

    Ż 0  =

      R2R3R2 +R3

    V̇ 0  =  R3R2 +R3

    V̇ 2 −  R2R2 +R3

    V̇ 3

    . (28)

    According to the approximated loop system shown in Fig. 7,

    the reference voltage of the UPFC series converter can be for-

    mulated as follows:

    V̇ c  =  V̇ 1 + V̇ 0 −(n−1) V̇ s . (29)

    Therefore, inserting a controlled series voltage by the UPFC

    series converter as given in (29) results in loop currents  İ loop1

    and  İ loop2  to be as follows:

    İ loop1  = 0

    İ loop2  = −V̇  2  +  V̇ 

     3

    R2  +  R3

    (30)

    where

    V̇  i   = jωLi İ i

    İ 1  =  İ m1

    İ 2  =  İ m2  +  İ loop2

    İ 3  =  İ m3  +  İ loop2

    . (31)

  • 8/19/2019 Base Paper UPFC

    6/10

    5818 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 11, NOVEMBER 2014

    Fig. 7. Multiple loop system with the UPFC and its equivalent circuit. (a)

    Model of the multiple loop distribution system with the UPFC. (b) Thevenin’sequivalent circuit of line 2 and line 3. (c) Equivalent circuit of the multiple loopsystem with the UPFC.

    Since the two loops are adjacent, the loop currents  İ loop1  and

    İ loop2   affect each other. The inserted controlled series voltage

    has theability to eliminate the loop current  İ loop1 , which reduces

    the loop current  İ loop2 . However, the loop current  İ loop2  can be

    eliminated, simultaneously with the loop current  İ loop1 , if itsloop lines have the same resistance-to-inductance ratio. The ref-

    erence voltage of the UPFC series converter can be formulated,

    as a function of time and line parameters, as follows:

    vc  = L1di1dt

      +  R3R2 +R3

    L2di2dt

    −  R2R2 +R3

    L3di3dt

      − (n−1)vs . (32)

    Based on the line loss minimum conditions in both isolated sub-

    stations and same substation multiple loop distribution system,

    it is clear that the controlled series voltage depends mainly on

    the line currents or line parameters. The change in line param-

    eters due to the temperature is very small and it will be in all

    line parameters, simultaneously. Therefore, it will not affect the

    system performance. However, detecting all line currents of the

    Fig. 8. Configuration of the UPFC.

    loop system is difficult. Line currents in the loop system can be

    estimated as given in [22]. Moreover, the protection schemes of 

    the loop system add another challenge in the practical system.

    Since the short-circuit current in loop distribution systems is

    high, recent research works focus on protective devices for fault

    isolation and fault location detecting methods [23], [24].

    IV. EXPERIMENTAL  RESULTS

    Two laboratory prototype systems have been carried out in

    order to demonstrate the effectiveness of the line loss minimiza-

    tion in isolated substations and same substation multiple loop

    distribution systems. In both systems, the UPFC is installed to

    achieve line loss minimum condition. Experimental waveforms

    of the line currents in all studied cases have been captured.

    Bar charts have been presented to compare theoretical and ex-

    perimental results in order to demonstrate the accuracy of the

    experimental system and the proposed control schemes. All the

    line currents, voltages, and total power loss are measured byusing Digital Power Meters (Yokogawa WT1600) that are con-

    nected simultaneously in the sending and receiving ends of each

    line in addition to the input and output of the UPFC converter

    in the experimental system. The power loss in each line is cal-

    culated from the difference between the sending and receiving

    powers.

     A. UPFC Circuit Configuration

    One of the most promising FACTS devices is the UPFC,

    which has been introduced by Gyugiy in 1991 [25]. Fig. 8

    shows the configuration of the UPFC used in the experimen-

    tal system. It consists of combined series and shunt convertersconnected back to back to each other through a common dc-

    link capacitor. The series converter, which acts as a controllable

    voltage source  vc , is used to inject a controlled voltage in series

    with the distribution line and thereby to force the power flow to

    a desired value. In general, the series converter exchanges the

    active and reactive power with the line while performing this

    duty. The reactive power is electronically provided by the series

    converter itself, whereas the active power is transmitted to the

    dc terminals. The main function of the shunt converter, which

    acts as a controllable current source  ic , is to regulate the dc-link 

    voltage by adjusting the amount of the active power drawn from

    the distribution line to meet the real power needed by the series

  • 8/19/2019 Base Paper UPFC

    7/10

    SAYED AND TAKESHITA: LINE LOSS MINIMIZATION IN ISOLATED SUBSTATIONS AND MULTIPLE LOOP DISTRIBUTION SYSTEMS 5819

    Fig. 9. Experimental configuration of the isolated substations loop system.

    converter. In addition, the shunt converter has the capability of 

    controlling the reactive power [26]–[29].

    The UPFC series and shunt converters, shown in Fig. 8,

    have been built as a three-phase pulse width modulation con-

    verter with IGBT SKM100GB124D as the power device. The

    Expert-III DSP system-based TMS320VC33 is selected as the

    controller for both converters. The shunt converter is connected

    in parallel with the distribution line via a three-phase trans-

    former. The series converter, multilevel converter [30], [31],

    consists of three single-phase H-bridge converters. The ac ter-

    minals of each H-bridge converter are connected in series with

    the distribution line through a single-phase transformer. The

    switching and sampling frequency for series and shunt convert-

    ers are 2.45 and 4.9 kHz, respectively.

    The main function of the UPFC series converter is to realize

    line loss minimization in the isolated substations and multiple

    loop distribution systems by injecting a controlled series voltage

    based on the line lossminimum condition in each case. The main

    function of the shunt converter is to regulate the dc-link voltage.

    Therefore, in the following discussion, the shunt converter is

    disregarded because its current,  ic , is very small.

     B. Isolated Substations Loop Distribution System

    Fig. 9 shows the 6-kVA, 200-V laboratory prototype of thedistribution system and the UPFC converters. The distribution

    system consists of two radial feeders fed from different sources

    that have same magnitude but a difference of 10◦ in the phase

    angle. The two radial feeders can be transformed to the loop

    system by connecting the loads in parallel. The parameters of 

    the whole system are listed in Table I. The proposed line in-

    ductance compensation scheme and line voltage compensation

    scheme have been used, respectively, to control the UPFC se-

    ries converter in order to realize line loss minimization. In each

    control scheme, all line currents and loop current in addition

    to the source voltage difference are measured before and after

    installing UPFC.

    TABLE IPARAMETERS OF THE ISOLATED SUBSTATIONS LOOP SYSTEM

    Fig. 10. Experimental waveforms using theline voltage compensation schemein the isolated substations loop system.

    1) Controlling the UPFC Using the Line Voltage Compen-

    sation Scheme:  In order to control the UPFC series converter

    using the line voltage compensation scheme, all line currentsand source voltages are detected to calculate the reference volt-

    age as given in (11). In this scheme, the UPFC is considered as

    a voltage source to compensate the line inductance voltage drop

    in addition to the difference in source voltages. Fig. 10 shows

    the experimental waveforms of source voltages difference  ∆v,reference voltage of the UPFC series converter (vc), line 1 cur-

    rent (i1 ), line 2 current (i2 ), and loop current (iloop ) of the loop

    system before and after installing the UPFC. It is clear that after

    installing the UPFC, the loop current is eliminated from the loop

    system, and hence, the line loss minimum condition is realized.

    The total power loss in the UPFC converters is 83.58 W.

    2) Controlling the UPFC Using the Line Inductance Com-

     pensation Scheme:   In order to control the UPFC series con-verter using the line inductance compensation scheme, only the

    UPFC line current and the source voltages are detected to cal-

    culate the reference voltage as given in (15). In this scheme, the

    UPFC is considered as an inductance (Lc ) in series with a volt-age source. The inductance (Lc ) compensates the loop systemline parameters in order to achieve equal ratio of the resistance

    to inductance for all loop lines, whereas the additional voltage

    source compensates the difference in source voltages. Accord-

    ing to (13), the inserted inductance Lc  = 0.13mH. Fig. 11 showsthe experimental waveforms of the source voltages difference

    ∆v, reference voltage of the UPFC series converter (vc ), line

    1 current (i1 ), line 2 current (i2 ), and loop current (iloop ) of 

  • 8/19/2019 Base Paper UPFC

    8/10

    5820 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 11, NOVEMBER 2014

    Fig. 11. Experimental waveforms using the line inductance compensationscheme in the isolated substations loop system.

    Fig. 12. Comparison between theoretical and experimental results for radial,isolated substations loop system without the UPFC, and isolated substations

    loop system with the UPFC.

    the loop system before and after installing the UPFC. Exper-

    imental results show that after installing the UPFC, the loop

    current is eliminated from the loop system, and hence, the lineloss minimum condition is realized. The total power loss in the

    UPFC converters is 80.95 W. Also, it is clear that the experimen-

    tal results obtained by both schemes coincide with each other

    since they provide the same function for the same system with

    different control techniques.

    The bar chart shown in Fig. 12 presents a comparison be-

    tween theoretical and experimental results of the experimental

    system that works as radial, isolated substations loop before in-

    stalling the UPFC, and isolated substations loop after installing

    the UPFC controlled by the line voltage and line inductance

    compensation schemes. In both control schemes, after installing

    the UPFC, the total line loss is reduced by 37.3% compared with

    Fig. 13. Experimental configuration of the same substation multiple loop

    system.

    TABLE I I

    PARAMETERS OF THE  SAME SUBSTATION MULTIPLE LOOP SYSTEM

    loop before installing the UPFC, and reduced by 16.5% com-

    pared with radial.

    C. Same Substation Multiple Loop Distribution System

    Fig. 13 shows the 6-kVA, 200-V laboratory prototype of the

    same substation distribution system that consists of three radial

    feeders, which can be reconfigured to loop by connecting the

    loads in parallel. SVR is taken into consideration by installing

    in series with line 1. The parameters of the whole system are

    listed in Table II. The UPFC is installed in the loop system as

    shown in Fig. 13 to achieve the line loss minimum condition

    by eliminating the loop currents from the two mesh circuits. In

    order to achieve that, the UPFC has been controlled to insert a

    reference series voltage as given in (32).

    Fig. 14 shows the experimental waveforms of the UPFC series

    converter voltage vc , line 1 current on both side of the SVR (i1aand   i1b ), line 2 current  i2 , line 3 current  i3 , and the two loop

    currents (iloop1 and iloop2 ) before and after installing the UPFC.

    Before installing the UPFC, the difference in the resistance-to-

    inductance ratio in the line parameters of loop 1 causes the loop

    current to pass in this loop (I loop1  = 2.05 A). Although the lineparameters of loop 2 have the same resistance-to-inductance

    ratio, there is a loop current (I loop2  = 1.04 A), which resultsfrom the effect of loop 1 current. Since the injected power of 

    the UPFC is small, the total power loss in the UPFC converter is

    20 W. It is clear that after installing the UPFC, both loop currents

    have been diminished from the distribution system, and hence,

    the line loss minimum condition has been realized.

  • 8/19/2019 Base Paper UPFC

    9/10

    SAYED AND TAKESHITA: LINE LOSS MINIMIZATION IN ISOLATED SUBSTATIONS AND MULTIPLE LOOP DISTRIBUTION SYSTEMS 5821

    Fig. 14. Experimentalwaveforms of thesamesubstation multiple loop system.

    Fig. 15. Comparison between theoretical and experimental results for radial,same substation multiple loop system without the UPFC, and same substationmultiple loop system with the UPFC.

    Fig. 15 shows a comparison between theoretical and exper-

    imental results of both loop currents and total line loss for the

    system that works as radial, same substation multiple loop with-

    out the UPFC, and same substation multiple loop after installing

    the UPFC. It is clear that after installing the UPFC, the total line

    loss is reduced by 12.5% compared with loop before installing

    the UPFC, and reduced by 24.6% compared with radial.

    V. CONCLUSION

    This paper has presented the line loss minimum condition

    and the power flow control schemes of the UPFC to realize line

    loss minimization in the isolated substations and the same sub-

    station multiple loop distribution systems, along with a detailed

    mathematical analysis of both systems. The line loss minimum

    condition has been realized in the loop distribution system bycompensating the line reactance voltage drop in addition to the

    difference of substation voltages in the case of isolated sub-

    stations loop system. Two control schemes of the UPFC series

    converter have been proposed to achieve line loss minimum

    condition in loop systems. These control schemes are the line

    inductance compensation and line voltage compensation. The

    effectiveness of the proposed control schemes has been verified

    experimentally using a laboratory prototype 6 kVA, 200 V. A

    comparison between experimental and theoretical results has

    been presented to evaluate the accuracy of the results and the

    validity of line loss minimum condition theory. Theoretical and

    experimental results agree well. Experimental results prove that

    the UPFC has a great capability to achieve line loss minimiza-

    tion in isolated substations and the same substation multiple

    loop distribution systems.

    REFERENCES

    [1] N. Okada, H. Kobayashi, K. Takigawa, M. Ichikawa, and K. Kurokawa,“Loop power flow control and voltage characteristics of distribution sys-tem for distributed generation including PV system,” in Proc. 3rd World Conf. Photovoltaics Energy Convers., 2003, pp. 2284–2287.

    [2] N. Okada, “Verification of control method for a loop distribution systemusing loop power flow controller,” in  Proc. IEEE Power Syst. Conf. Expo. ,2006, pp. 2116–2123.

    [3] N. Suman and R. Somnath, “Network reconfiguration for electrical lossminimization,”  Int. J. Instrum., Control Autom., vol. 2, pp. 22–28, Feb.2011.

    [4] A. Thirumalai, X. Liu, and G. Karady, “Ultra fast pilot protection of a

    looped distribution system,” in Proc. IEEE Trondheim PowerTech, 2001,pp. 1–8.

    [5] M. Rezaei and A. Huang, “Ultra fast protection of radial and loopedelectric power grid using a novel solid-state protection device,” in  Proc.

     IEEE Energy Convers. Congr. Expo., 2012, pp. 610–614.[6] N. Rugthaicharoencheep and S. Sirisumrannukul, “Feeder reconfiguration

    for loss reduction in three phase distribution system under unbalancedloading conditions,” in   Proc. 45th Int. Univ. Power Eng. Conf., 2010,pp. 1–6.

    [7] W.-T. Huang and S.-T. Chen, “Line loss reduction by distribution systemupgrading from radial to normally closed-loop arrangement,” in  Proc. 9th

     Int. Conf. Hybrid Intell. Syst., 2009, pp. 334–339.[8] T.-H. Chen, W.-T. Huang, J.-C. Gu, G.-C. Pu, Y.-F. Hsu, and T.-Y. Guo,

    “Feasibility study of upgrading primary feedersfrom radialand open-loopto normally closed-loop arrangement,”  IEEE Trans. Power Syst., vol. 19,no. 3, pp. 1308–1316, Aug. 2004.

    [9] R. Simanjorang,Y.Miura, T. Ise, andS. Sugimoto,“A methodfor effectiveutilization of power distribution apparatus in industrial park by loopingdistribution lines,” IEEJ Trans. Power Energy, vol. 127-B, pp. 1127–1136,Nov. 2007.

    [10] T.-L.Lee andS.-H.Hu, “Discretefrequency-tuning active filter to suppressharmonic resonances of closed-loop distribution power systems,”   IEEE 

    Trans. Power Electron., vol. 26, no. 1, pp. 137–148, Jan. 2011.[11] R. Gupta, A. Ghosh, and A. Joshi, “Performance comparison of VSC-

    based shunt and series compensators used for load voltage control indistribution systems,”   IEEE Trans. Power Del., vol. 26, no. 1, pp. 268–

    278, Jan. 2011.[12] A. Jain, K. Joshi, A. Behal, and N. Mohan, “Voltage regulation with

    STATCOMs: Modeling, control and results,”  IEEE Trans. Power Del.,

    vol. 21, no. 2, pp. 726–735, Apr. 2006.

  • 8/19/2019 Base Paper UPFC

    10/10

    5822 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 11, NOVEMBER 2014

    [13] Z. Xi, B. Parkhideh, and S. Bhattacharya, “Improving distribution systemperformance with integrated STATCOM and supercapacitor energy stor-

    age system,” in Proc. IEEE Power Electron. Spec. Conf. , 2008, pp. 1390–1395.

    [14] H. Fujita and H. Akagi, “Voltage-regulation performance of a shunt activefilterintended for installationon a power distribution system,” IEEE Trans.Power Electron., vol. 22, no. 3, pp. 1046–1053, May 2007.

    [15] Z. ZhiHua, X. BingYin, and C. Qing, “Preliminary research on the powerflow control method of thedistribution network with normally closed-loop

    operation based on the SSSC,” in Proc. Int. Conf. Adv. Power Syst. Autom.Protect., 2011, pp. 818–821.

    [16] R. Simanjorang, Y. Miura, and T. Ise, “A series type BTB converter forcontrolling voltage profile in loop distribution system with distributedgenerations,” IEEJ Trans. Power Energy, vol. 128-B, pp. 769–778, May2008.

    [17] R. Simanjorang, Y. Miura, and T. Ise, “Distributed-series compensatorfor controlling voltage in distribution line with clustered distributed gen-erations,”   IEEJ Trans. Electr. Electron. Eng., vol. 4, pp. 404–415, Apr.2009.

    [18] C.-S. Chen, C.-T. Tsai, C.-H. Lin, W.-L. Hsieh, and T.-T. Ku, “Load-ing balance of distribution feeders with loop power controllers consid-ering photovoltaic generation,”  IEEE Trans. Power Syst., vol. 26, no. 3,pp. 1762–1768, Aug. 2011.

    [19] M. Sayed, N. Inayoshi, T. Takeshita, and F. Ueda, “Line loss minimizationof loop distribution systems usingUPFC,” IEEJ Trans.Ind. Appl.,vol.128-

    D, pp. 508–515, Apr. 2008.[20] M. Sayed and T. Takeshita, “Voltage regulation and line loss minimization

    of loop distribution systems usingUPFC,” IEEJ Trans.Ind. Appl.,vol.129-D, pp. 1118–1125, Nov. 2009.

    [21] M. Sayed and T. Takeshita, “All nodes voltage regulation and line lossminimization in loop distribution systems using UPFC,”   IEEE Trans.Power Electron., vol. 26, no. 6, pp. 1694–1703, Jun. 2011.

    [22] R. Saino,T.Takeshita, N.Izuhara,and F. Ueda,“Power flowestimationandline-loss-minimizationcontrol usingUPFC in loop distribution system,” inProc. IEEE Power Electron. Motion Control Conf., 2009, pp. 2426–2431.

    [23] C.-J. Chouand C.-W. Liu, “Assessment of risks from ground fault transferon closed-loop HV underground distribution systems with cables runningin a common route,”  IEEE Trans. Power Del., vol. 28, no. 2, pp. 1015–1023, Apr. 2013.

    [24] J.-F. Moon and J.-S. Kim, “Voltage sag analysis in loop power distribu-tion system with SFCL,”   IEEE Trans. Appl. Supercond., vol. 23, no. 3,

    pp. 5601504–5601504, Jun. 2013.

    [25] L. Gyugyi, “Unified power-flow control concept for flexible ac trans-mission systems,”   IEE Proc. C Generat., Transmiss. Distrib., vol. 139,pp. 323–331, Jul. 1992.

    [26] L. Gyugyi, C. Schauder, S. Williams, T. Rietman, D. Torgerson, andA. Edris, “The unified power flow controller: A new approach to powertransmission control,” IEEE Trans. Power Del., vol. 10, no. 2, pp. 1085–1097, Apr. 1995.

    [27] H. Fujita, H. Akagi, and Y. Watanabe, “Dynamic control and performanceof a unified power flow controller for stabilizing an ac transmission sys-tem,”   IEEE Trans. Power Electron., vol. 21, no. 4, pp. 1013–1020, Jul.2006.

    [28] J. Verveckken, F. Silva, D. Barros, and J. Driesen, “Direct power control

    of series converter of unified power-flow controller with three-level neu-tral point clamped converter,”   IEEE Trans. Power Del., vol. 27, no. 4,pp. 1772–1782, Oct. 2012.

    [29] Z. Yuan, S. de Haan, J. Ferreira, and D. Cvoric, “A FACTS device: Dis-tributed power-flow controller (DPFC),”   IEEE Trans. Power Electron.,vol. 25, no. 10, pp. 2564–2572, Oct. 2010.

    [30] H. Abu-Rub, A. Iqbal, and J. Guzinski, High Performance Control of AC  Drives With MATLAB/Simulink Models. New York, NY, USA: Wiley-Interscience, 2012.

    [31] Z. Shu, X. He, Z. Wang, D. Qiu, and Y. Jing, “Voltage balanc-ing approaches for diode-clamped multilevel converters using auxiliarycapacitor-based circuits,”   IEEE Trans. Power Electron., vol. 28, no. 5,

    pp. 2111–2124, May 2013.

    Mahmoud A. Sayed (M’09) was born in Qena Pre-fecture, Egypt, in 1974. He received the B.Sc. andM.Sc. degrees in electrical engineering from MiniaUniversity, El-Minia, Egypt, in 1997 and 2001, re-spectively, and the Ph.D. degree from the NagoyaInstitute of Technology, Nagoya, Japan, in 2010.

    Since 1999, he has been with the Department of Electrical Engineering, Faculty of Energy Engineer-ing, Aswan University, Aswan, Egypt, first as an Ad-

    ministrator and since 2001 as a Research Assistant.Currently, he is an Assistant Professor in the Depart-

    ment of ElectricalEngineering,Faculty of Engineering, SouthValley University,Qena, Egypt. His research interests include series and shunt compensation of 

    electrical distribution systems for voltage regulation and loss reduction usingseries and shunt PWM converters in addition to renewable energy applicationsand machine drives.

    Dr. Sayed is a Member of the IEEE Power Electronics Society.

    Takaharu Takeshita   (M’92) was born in Aichi,

    Japan, on August 23, 1959. He received the B.S.

    and M.S. degrees in electrical engineering from theNagoya Institute of Technology, Nagoya Japan, in1982 and 1984, respectively, and the Ph.D. degreefrom Nagoya University, Nagoya, Japan, in 1990.

    Since 1991, he has been with the Nagoya Instituteof Technology, where he is currently a Full Professorandis engaged in research on power convertersystemand motor control.

    Dr. Takeshita is a Member of the Society of In-strument and Control Engineers.