base paper upfc
TRANSCRIPT
-
8/19/2019 Base Paper UPFC
1/10
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 11, NOVEMBER 2014 5813
Line Loss Minimization in Isolated Substations and
Multiple Loop Distribution Systems Using the UPFCMahmoud A. Sayed , Member, IEEE , and Takaharu Takeshita , Member, IEEE
Abstract—This paper presents the line loss minimum conditionin isolated substations and same substation multiple loop distribu-tion systems by using the unified power flow controller (UPFC).In each case, the mathematical model is presented and the lineloss minimum conditions are obtained based on the line param-eters of the distribution feeders. Since multiple loop distributionsystem is fed from same substation, the line loss minimization canbe achieved by compensating the summation of the line reactancevoltage drop. In an isolated substation loop distribution system,the line loss minimization can be achieved by compensating thesummation of the line reactance voltage drop in addition to thevoltage difference of the substations. Realization of both cases canbe achieved if the loop current is eliminated from the loop system.
The series compensation technique applied by the UPFC is used toeliminate the loop current from the loop distribution system andhence minimize the total line loss. Theeffectiveness of theproposedcontrol schemes of the UPFC have been verified experimentally.
Index Terms—FACTS, line loss minimization, loop distributionsystem, series compensation, unified power flow controller(UPFC),voltage regulation.
I. INTRODUCTION
GREENHOUSE gas emissions are considered one of the
most important problems that affect our environment and
causes climate change. Electrical Energy supplies are consid-
ered as oneof themain contributors in globalwarming since they
emit carbon dioxide (CO2 ), which is the most abundant green-
house gas. Therefore, concerns over global warming problems
have led to change the operation and design standards for dis-
tribution networks. The most important of these is the energy
saving. Line loss minimization in distribution systems is the
most efficient solution in order to achieve energy saving. In ad-
dition, line loss minimization enhances the voltage profile along
the distribution feeders [1], [2].
Distribution networks are mainly classified as either radial
or loop. The radial system is commonly used because it has
simple and inexpensive protection schemes. Also, its voltage
profile can be controlled easily. However, radial systems are of-
ten quite weak because of the long distances involved and thehigh resistance-to-inductance ratio of the lines that are used,
Manuscript received July 13, 2013; revised October 23, 2013 and December3, 2013; accepted January 8, 2014. Date of publication January 29, 2014; dateof current version July 8, 2014. Recommended for publication by AssociateEditor P. Barbosa.
M. A. Sayed is with the Department of Electrical Engineering, Fac-ulty of Engineering, South Valley University, 83523 Qena, Egypt (e-mail:
[email protected]).T. Takeshita is with the Department of Electrical and Computer Engi-
neering, Nagoya Institute of Technology, 466-8555 Nagoya, Japan (e-mail:[email protected]).
Digital Object Identifier 10.1109/TPEL.2014.2301833
Fig. 1. Configuration of the distribution system.
and the continuous increasing of the power demand. Hence, as
the demand power increases on these networks, power quality
issues such as high power loss often become a significant prob-
lem. Ideally, the power loss in electrical systems should not be
more than 6%. However, in developed countries, the power loss
is more than 10%, whereas in developing countries, it is more
than 20% [3]. Therefore, distribution system engineers haveproposed a loop system to achieve the merits of line loss reduc-
tion and to enhance the load voltage profile along the feeders.
Although, the loop distribution system requires complex pro-
tection schemes [4], [5], it is also more reliable service that is
offered for critical loads such as hospitals. As a result, much
of recent research works have considered reconfiguring the ra-
dial distribution system to loop one in order to achieve these
objectives [6]–[9].
Reconfiguration of radial distribution systems to the closed-
loop lines, using the existing infrastructure, is done in the
medium voltage by connecting the ends of adjacent radial feed-
ers. Based on the feeder substation, two different types of the
loop system may result. These types are the isolated substationsloop system and multiple loop system [8], [10], as shown in
Fig. 1. The isolated substations loop system results from re-
configuring two radial feeders fed from different substations
to perform one loop, whereas the multiple loop system results
from reconfiguring more than two radial feeders fed from same
substation to perform at least two adjacent loops. In the isolated
substations loop system, a loop current may results from the
voltage difference between substation voltages in addition to
the asymmetrical line parameters of the feeders. In a multiple
loop system, a loop current may results from the asymmetrical
line parameters of the feeders, only, since its feeders are fed
from the same substation.
0885-8993 © 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
-
8/19/2019 Base Paper UPFC
2/10
5814 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 11, NOVEMBER 2014
Recent research in distribution networks has been focused
on the minimizing power loss and enhance the load voltage
profile along the feeders by using power electronics technolo-
gies [11]–[18]. The idea given in [11]–[15] has been achieved
using STATCOM, SSSC, and active filters-based shunt and se-
ries power converters to compensate the reactive power in dis-
tribution systems, and hence, control the power flow. In [16]
and [17], power balancing between feeders using a back-to-
back converter has been proposed to reduce the loop power loss
and improve the load voltage profile. In [18], a loop power con-
troller has been used to reconfigure two radial systems to loop
in order to reduce the power loss and mitigate power flow over-
loading. In [19]–[21], the authors have proposed the line loss
minimum conditions in loop distribution systems, and experi-
mentally achieved these conditions by using the unified power
flow controller (UPFC). In [20], the authors proposed load volt-
age regulation to be equal in the magnitude to the source volt-
age under line loss minimum condition. However, the proposed
technique cannot guarantee the other load voltages to be within
the permissible voltage range. In [21], the authors proposed anew technique for controlling all load voltages to be within the
permissible voltage range under line loss minimum condition
by controlling both the load voltage magnitude and phase an-
gle to follow reference values. The reference load phase angle
was calculated from the line loss minimum condition, whereas
the reference voltage magnitude was calculated based on the
voltage magnitude of each load in the loop system. Line loss
minimization can be achieved if the loop current is eliminated
from the loop system. This condition can be achieved if, at least,
the line parameters of all loop lines have the same ratio between
the resistance and inductance. This can be realized in the same
substation loop distribution system since it has only one substa-tion for the whole loop, whereas in an isolated substations loop
system this condition cannot be realized due to the voltage dif-
ference between them, which may result from small difference
in the magnitude or phase angle. The difference between the
substation voltages results in an excessive loop current that will
flow in the loop lines even if the loop line parameter ratios are
same.
In this paper, the mathematical model of the isolated substa-
tions and the same substation multiple loop distribution system
is presented. Also, the line loss minimum condition is inves-
tigated by using the UPFC in both loop systems. The UPFC
shunt converter is used to regulate the dc-link voltage, whereas
the series converter is used to control the power flow in order toachieve line loss minimum condition. Since the series converter
performs the main function of the UPFC, its proposed control
schemes in both cases are presented. The effectiveness of the
proposed control schemes are investigated experimentally using
a laboratory prototype of 200 V, 6 kVA.
II. MODEL OF THE ISOLATED SUBSTATIONS LOOP
DISTRIBUTION SYSTEM WITH THE UPFC
The UPFC is used in a loop distribution system as a series
compensator to control the power flow in the loop lines in order
to achieve line loss minimum condition. Fig. 2 shows a simple
Fig. 2. Model of the isolated substations loop distribution system.
model of the isolated substations loop distribution system with
the UPFC equivalent circuit. Since the UPFC shunt converter is
used to regulate the dc-link voltage, its current is very small andcan be neglected. Therefore, the UPFC is simplified as a series
voltage source that represents the series converter voltage.
The loop system is represented by three distribution lines
(Line 1, Line 2, and Line 3). Each line has its resistance (Ri) andinductance (Li ), where i is the line number (i = 1, 2, 3). Theline impedance is represented by Ż i = Ri + jωLi . Since theloop system is isolated substations, it is supplied from different
substations represented by two voltage sources ( V̇ 1 and V̇ 2 ). Thesystem feeds two loads represented by constant current sources
( İ L1 and İ L2 ). The line current of each line in the loop systemflows in the same direction. The UPFC series injected voltage
is represented by the voltage source ( V̇ c).
A. Before Installing the UPFC
The line currents İ i (i = 1, 2, 3), that flow in each line of the loop system, before installing the UPFC, can be formulated
using Superposition theorem as follows:
İ 1 = ( Ż 2 + Ż 3 ) İ L1 + Ż 2 İ L2 + ( V̇ 1 − V̇ 2 )
Ż loop
İ 2 = − Ż 1 İ L1 − ( Ż 1 + Ż 3 ) İ L2 + ( V̇ 1 − V̇ 2 )
Ż loop
İ 3 = − Ż 1 İ L1 + Ż 2 İ L2 + ( V̇ 1 − V̇ 2 )Ż loop
(1)
where
Ż loop =3
i=1
Ż i , Rloop =3
i=1
Ri , Lloop =3
i=1
Li . (2)
According to the line loss minimization theory in the loop
distribution system [19]–[21], the line currents can be divided
into two currents. The first one is the current flow in each line
during the line loss minimum condition [ İ mi , (i = 1, 2, 3)], andthe second one is the loop current İ loop that circulates in the
loop lines, as shown in Fig. 2. Therefore, the line current can be
-
8/19/2019 Base Paper UPFC
3/10
SAYED AND TAKESHITA: LINE LOSS MINIMIZATION IN ISOLATED SUBSTATIONS AND MULTIPLE LOOP DISTRIBUTION SYSTEMS 5815
Fig. 3. Equivalent circuit of the loop system under line loss minimization.
formulated as follows:
İ i = İ mi + İ loop . (3)
The line currents that flow in each line of the loop system
during line loss minimization, [ İ mi , (i = 1, 2, 3)], can be for-mulated as follows:
İ m1 = {(R2 + R3 ) İ L1 + R2 İ L2}/Rloop
İ m2 = {−R1 İ L1 − (R1 + R3 ) İ L2}/Rloop
İ m3 = {−R1 İ L1 + R2 İ L2}/Rloop
. (4)
Considering the voltage difference in substations, the loop
current İ loop that circulates in the loop system lines can beformulated as follows:
İ loop = − 1
Rloop
3i= 1
jωLi İ i + ( V̇ 2 − V̇ 1 )
. (5)
The total power loss in the isolated substation loop systemlines can be formulated as follows:
P l =3
i=1
Riİ i2
=
3i=1
Riİ mi2 + 2
3i=1
(Ri İ mi)
· İ loop
+ Rloopİ loop 2 . (6)
According to (6), the line loss minimum condition can be
achieved in the loop system if the loop current İ Loop is elimi-
nated from the system. In this case, the line currents that flowin the loop lines after eliminating the loop current are [ İ mi ,(i = 1, 2, 3)]. Fig. 3 shows the equivalent circuit of the isolatedloop distribution system in case of line loss minimization. There-
fore, the resultant total line loss can be formulated as follows:
P lmin =3
i= 1
Riİ mi2 . (7)
The line loss minimum conditions can be obtained by equat-
ing the loop current, shown in (5) with zero, as follows:
3
i=1
jωLi İ i + ( V̇ 2 − V̇ 1 ) = 0. (8)
The loop current can be eliminated from the loop system if
the summation of the reactance voltage drop in addition to the
voltage difference between the substation voltages equals zero.
The summation of the reactance voltage drop equals zero if the
resistance-to-inductance ratio in each line of the loop system is
the same. Therefore, the loop current can be eliminated from
the loop system if the following conditions have been realized,
simultaneously:
R1/L1 = R2/L2 = R3/L3
V̇ 2 − V̇ 1 = 0
. (9)
B. After Installing the UPFC for Line Loss Minimization
The UPFC is installed in an isolated substations loop sys-
tem in order to eliminate the loop current from the system by
inserting a controlled series voltage that can compensate the
difference between substation voltages in addition to the sum-
mation of the reactance voltage drop in loop lines. In order to
compensate the summation of the reactance voltage drop, two
control schemes are proposed based on (8) and (9). These con-trol schemes are line inductance compensation and line voltage
compensation. Both schemes have a common part that is used
to compensate the difference between the substation voltages.
In the line voltage compensation scheme, the series converter
voltage of the UPFC can be formulated as follows:
V̇ c =3
i=1
jωLi İ i + ( V̇ 2 − V̇ 1 ). (10)
As a function of time, the UPFC series converter voltage can be
formulated as follows:
vc =
3i= 1
Lidi
idt + (v
2 − v1 ). (11)
In the line inductance compensation scheme, the UPFC is
used to insert a virtual inductance, Lc , which realize same ra-tio between the resistance and inductance in each line of the
loop system. The inserted inductance Lc can realize the sameresistance-to-inductance ratio in the loop system as follows:
R1/(L1 + Lc) = R2/L2 = R3/L3 . (12)
Therefore, the inserted inductance Lc can be calculated asfollows:
Lc = (R1/R2 )L2 − L1 . (13)
Based on loop line parameters, the value of the inserted con-
trolled inductance can be positive or negative [19]. The UPFC
series converter voltage, for line loss minimization, can be for-
mulated as follows:
V̇ c = − jωLc İ 1 + ( V̇ 2 − V̇ 1 ). (14)
As a function of time, the UPFC series converter voltage can be
formulated as follows:
vc = −Lcdi1dt
+ (v2 − v1 ). (15)
It is clear that the line inductance compensation scheme can
be used in the loop distribution system if there is only one line
-
8/19/2019 Base Paper UPFC
4/10
5816 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 11, NOVEMBER 2014
Fig. 4. Model of the multiple loop distribution system.
that has a different resistance-to-inductance ratio. Therefore,
only this line current in addition to the substation voltages are
required to obtain the reference voltage of the UPFC series
converter. On the other hand, the line voltage compensation
scheme can be used in the loop system if the resistance-to-
inductance ratio is not the same in, at least, two lines of the loop.
Also, in both schemes, the line loss minimum condition does
not need the load information. Both schemes depend on loop
line currents in addition to line impedance parameters to achieve
line loss minimization. Therefore, the system performance will
not be affected by load type.
III. MODEL OF THE SAME SUBSTATION MULTIPLE LOOP
DISTRIBUTION SYSTEM WITH THE UPFC
Fig. 4 shows the model of the same substation multiple loop
distribution system. It consists of three radial feeders fed from
the same substation. The loads fed from the radial lines are con-
nected in parallel in order to obtain two adjacent loop systems.
For mathematical model simplification, the loads are assumed
to be adjacent. Therefore, the impedance parameters of the line
connecting them are neglected. Line 1 has a step voltage regula-
tor (SVR), a common device used to compensate load voltages
along distribution feeders. It is assumed that the UPFC is in-
stalled in series with line 1 to achieve line loss minimization by
controlling the loop current in the two adjacent loop systems.
The line currents in loop lines should flow in the same direction.
Therefore, it is assumed that the currents İ 1 and İ 2 flow in the
counter clockwise direction, whereas the currents İ 2 and İ 3 flowin the clockwise direction.
A. Before Installing the UPFC
Considering that the UPFC output voltage is zero, the three
load currents ( İ L1 , İ L2 , and İ L3 ) can be lumped together ina single load current ( İ L ). According to the location of theSVR in line 1, the line parameter will be determined referred
to the secondary side. Fig. 5 shows the equivalent circuit of the
multiple loop system, shown in Fig. 4. The line currents in each
feeder of the loop distribution system model, shown in Fig. 5,
Fig. 5. Equivalent circuit of the multiple loop system.
can be formulated as follows:
İ 1 = 1
Ż 1 +Ż 2 Ż 3
Ż 2 + Ż 3
Ż 2 Ż 3
Ż 2 + Ż 3İ L + (n−1) V̇ s
İ 2 = −1Ż 2 +
Ż 1 Ż 3
Ż 1 + Ż 3
˙Z 1
˙Z 3
Ż 1 + Ż 3İ L−
˙Z 3
Ż 1 + Ż 3(n−1) V̇ s
İ 3 = 1
Ż 3 +Ż 1 Ż 2
Ż 1 + Ż 2
Ż 1 Ż 2
Ż 1 + Ż 2İ L−
Ż 2
Ż 1 + Ż 2(n−1) V̇ s
(16)
where
Ż 1 = R1 + jωL1
R1 = n2R1a + R1b
L1 = n2L1a + L1b
(17)
İ L = İ L1 + İ L2 + İ L3 . (18)
Since the distribution system is connected to perform two
adjacent loop systems, the line currents in each feeder can be
divided into the loop circulating currents ( İ loop1 and İ loop2 ) in
addition to the currents at line loss minimum condition ([ İ mi ,(i = 1, 2, 3)]). Therefore, the line current can be formulated asfollows:
İ 1 = İ m1 + İ loop1İ 2 = İ m2 + İ loop1 + İ loop2İ 3 = İ m3 + İ loop2
. (19)
The loop circulating current in each loop system can be for-
mulated as follows:
İ loop1 =
−V̇ m1 + V̇ m2 −(n−1) V̇ s
+
Ż 2
Ż 2 + Ż 3( V̇ m2 + V̇ m3 )
Ż 1 +Ż 2 Ż 3
Ż 2 + Ż 3
İ loop2 =
Ż 2
Ż 1 + Ż 2
V̇ m1 + V̇ m2 −(n−1) V̇ s
−( V̇ m2 + V̇ m3 )
Ż 3 +Ż 1 Ż 2
Ż 1 + Ż 2
(20)
V̇ mi = Ż i İ mi(i = 1, 2, 3). (21)
-
8/19/2019 Base Paper UPFC
5/10
SAYED AND TAKESHITA: LINE LOSS MINIMIZATION IN ISOLATED SUBSTATIONS AND MULTIPLE LOOP DISTRIBUTION SYSTEMS 5817
Fig. 6. Equivalent model at line loss minimum condition.
Line loss minimization in the loop distribution system can
be achieved if the loop current is eliminated from the loop
system. This can be realized by compensating the inductance
voltage drop in each feeder constituting the loop system by
using a series compensator. Therefore, the equivalent circuit of
the loop distribution system, shown in Fig. 5, in case of line
loss minimization can be represented by a feeder resistanceonly as shown in Fig. 6. The line currents of each feeder in the
system shown in Fig. 6, at line loss minimum condition, can be
formulated as follows:
İ m1 = 1
R1 + R2R3R2 +R3
R2R3R2 +R3
İ L
İ m2 = −1
R2 + R1R3R1 +R3
R1R3R1 +R3
İ L
İ m3 = 1
R3 + R1R2R1 +R2
R1R2R1 +R2
İ L
. (22)
Based on (19), (20), and (22), the loop current in each loop
system ( İ loop1 and İ loop2 ) can be formulated as follows:
İ loop1 =−V̇ 1 + V̇ 2 −(n−1) V̇ s
+
R2R2 +R3
( V̇ 2 + V̇ 3 )
R1 + R2R3R2 +R3
İ loop2 =
R2R1 +R2
V̇ 1 + V̇ 2 −(n−1) V̇ s
−( V̇ 2 + V̇ 3 )
R3 + R1R2R1 +R2
(23)
˙V i = jωLi
˙I i (i = 1, 2, 3). (24)
In this case, the total power loss can be formulated as a function
of the line currents and the loop currents as follows:
P l =3
i= 1
Riİ i2
=
3i= 1
Riİ mi2 + 2(R1 İ m1 + R2 İ m2 ) · İ loop1
+ 2(R2 İ m2 + R3 İ m3 ) · İ loop2 + R1
İ loop1
2
+ R2İ loop1 + İ loop2
2+ R3
İ loop2
2. (25)
According to (25), the line loss minimum condition can be
achieved if both loop currents ( İ loop1 and İ loop2 ) are eliminatedfrom the system. In this case, the resultant total power loss can
be formulated as follows:
P lmin =3
i= 1
Riİ mi2
. (26)
It is clear from (23) that eliminating both loop currents from
the loop system, in order to realize line loss minimum condition,
can be achieved if the following two conditions are realized,
simultaneously:
V̇ 1 + V̇ 2 −(n−1) V̇ s = 0
V̇ 2 + V̇ 3 = 0
. (27)
B. After Installing the UPFC for Line Loss Minimization
The main objective of installing the UPFC in the same sub-
station multiple loop distribution system is to realize the line
loss minimum condition by controlling the loop power flow,using the series compensation scheme, provided by the inserted
controlled series converter voltage. Fig. 7(a) shows the multiple
loop distribution system with the UPFC in case of line loss min-
imization. The voltages (V 1 , V 2 , and V 3 ) represent the inductivevoltage drop in each line (Line 1, Line 2, and Line 3). Using
Thevenin’s theorem, the system can be approximated as shown
in Fig 7 (b) and (c) in order to obtain the reference voltage of the
UPFC series converter. The parallel feeders (Line 2 and Line 3)
are approximated by a resistor Ż 0 in series with a voltage sourceV̇ 0 , which can be formulated as follows:
Ż 0 =
R2R3R2 +R3
V̇ 0 = R3R2 +R3
V̇ 2 − R2R2 +R3
V̇ 3
. (28)
According to the approximated loop system shown in Fig. 7,
the reference voltage of the UPFC series converter can be for-
mulated as follows:
V̇ c = V̇ 1 + V̇ 0 −(n−1) V̇ s . (29)
Therefore, inserting a controlled series voltage by the UPFC
series converter as given in (29) results in loop currents İ loop1
and İ loop2 to be as follows:
İ loop1 = 0
İ loop2 = −V̇ 2 + V̇
3
R2 + R3
(30)
where
V̇ i = jωLi İ i
İ 1 = İ m1
İ 2 = İ m2 + İ loop2
İ 3 = İ m3 + İ loop2
. (31)
-
8/19/2019 Base Paper UPFC
6/10
5818 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 11, NOVEMBER 2014
Fig. 7. Multiple loop system with the UPFC and its equivalent circuit. (a)
Model of the multiple loop distribution system with the UPFC. (b) Thevenin’sequivalent circuit of line 2 and line 3. (c) Equivalent circuit of the multiple loopsystem with the UPFC.
Since the two loops are adjacent, the loop currents İ loop1 and
İ loop2 affect each other. The inserted controlled series voltage
has theability to eliminate the loop current İ loop1 , which reduces
the loop current İ loop2 . However, the loop current İ loop2 can be
eliminated, simultaneously with the loop current İ loop1 , if itsloop lines have the same resistance-to-inductance ratio. The ref-
erence voltage of the UPFC series converter can be formulated,
as a function of time and line parameters, as follows:
vc = L1di1dt
+ R3R2 +R3
L2di2dt
− R2R2 +R3
L3di3dt
− (n−1)vs . (32)
Based on the line loss minimum conditions in both isolated sub-
stations and same substation multiple loop distribution system,
it is clear that the controlled series voltage depends mainly on
the line currents or line parameters. The change in line param-
eters due to the temperature is very small and it will be in all
line parameters, simultaneously. Therefore, it will not affect the
system performance. However, detecting all line currents of the
Fig. 8. Configuration of the UPFC.
loop system is difficult. Line currents in the loop system can be
estimated as given in [22]. Moreover, the protection schemes of
the loop system add another challenge in the practical system.
Since the short-circuit current in loop distribution systems is
high, recent research works focus on protective devices for fault
isolation and fault location detecting methods [23], [24].
IV. EXPERIMENTAL RESULTS
Two laboratory prototype systems have been carried out in
order to demonstrate the effectiveness of the line loss minimiza-
tion in isolated substations and same substation multiple loop
distribution systems. In both systems, the UPFC is installed to
achieve line loss minimum condition. Experimental waveforms
of the line currents in all studied cases have been captured.
Bar charts have been presented to compare theoretical and ex-
perimental results in order to demonstrate the accuracy of the
experimental system and the proposed control schemes. All the
line currents, voltages, and total power loss are measured byusing Digital Power Meters (Yokogawa WT1600) that are con-
nected simultaneously in the sending and receiving ends of each
line in addition to the input and output of the UPFC converter
in the experimental system. The power loss in each line is cal-
culated from the difference between the sending and receiving
powers.
A. UPFC Circuit Configuration
One of the most promising FACTS devices is the UPFC,
which has been introduced by Gyugiy in 1991 [25]. Fig. 8
shows the configuration of the UPFC used in the experimen-
tal system. It consists of combined series and shunt convertersconnected back to back to each other through a common dc-
link capacitor. The series converter, which acts as a controllable
voltage source vc , is used to inject a controlled voltage in series
with the distribution line and thereby to force the power flow to
a desired value. In general, the series converter exchanges the
active and reactive power with the line while performing this
duty. The reactive power is electronically provided by the series
converter itself, whereas the active power is transmitted to the
dc terminals. The main function of the shunt converter, which
acts as a controllable current source ic , is to regulate the dc-link
voltage by adjusting the amount of the active power drawn from
the distribution line to meet the real power needed by the series
-
8/19/2019 Base Paper UPFC
7/10
SAYED AND TAKESHITA: LINE LOSS MINIMIZATION IN ISOLATED SUBSTATIONS AND MULTIPLE LOOP DISTRIBUTION SYSTEMS 5819
Fig. 9. Experimental configuration of the isolated substations loop system.
converter. In addition, the shunt converter has the capability of
controlling the reactive power [26]–[29].
The UPFC series and shunt converters, shown in Fig. 8,
have been built as a three-phase pulse width modulation con-
verter with IGBT SKM100GB124D as the power device. The
Expert-III DSP system-based TMS320VC33 is selected as the
controller for both converters. The shunt converter is connected
in parallel with the distribution line via a three-phase trans-
former. The series converter, multilevel converter [30], [31],
consists of three single-phase H-bridge converters. The ac ter-
minals of each H-bridge converter are connected in series with
the distribution line through a single-phase transformer. The
switching and sampling frequency for series and shunt convert-
ers are 2.45 and 4.9 kHz, respectively.
The main function of the UPFC series converter is to realize
line loss minimization in the isolated substations and multiple
loop distribution systems by injecting a controlled series voltage
based on the line lossminimum condition in each case. The main
function of the shunt converter is to regulate the dc-link voltage.
Therefore, in the following discussion, the shunt converter is
disregarded because its current, ic , is very small.
B. Isolated Substations Loop Distribution System
Fig. 9 shows the 6-kVA, 200-V laboratory prototype of thedistribution system and the UPFC converters. The distribution
system consists of two radial feeders fed from different sources
that have same magnitude but a difference of 10◦ in the phase
angle. The two radial feeders can be transformed to the loop
system by connecting the loads in parallel. The parameters of
the whole system are listed in Table I. The proposed line in-
ductance compensation scheme and line voltage compensation
scheme have been used, respectively, to control the UPFC se-
ries converter in order to realize line loss minimization. In each
control scheme, all line currents and loop current in addition
to the source voltage difference are measured before and after
installing UPFC.
TABLE IPARAMETERS OF THE ISOLATED SUBSTATIONS LOOP SYSTEM
Fig. 10. Experimental waveforms using theline voltage compensation schemein the isolated substations loop system.
1) Controlling the UPFC Using the Line Voltage Compen-
sation Scheme: In order to control the UPFC series converter
using the line voltage compensation scheme, all line currentsand source voltages are detected to calculate the reference volt-
age as given in (11). In this scheme, the UPFC is considered as
a voltage source to compensate the line inductance voltage drop
in addition to the difference in source voltages. Fig. 10 shows
the experimental waveforms of source voltages difference ∆v,reference voltage of the UPFC series converter (vc), line 1 cur-
rent (i1 ), line 2 current (i2 ), and loop current (iloop ) of the loop
system before and after installing the UPFC. It is clear that after
installing the UPFC, the loop current is eliminated from the loop
system, and hence, the line loss minimum condition is realized.
The total power loss in the UPFC converters is 83.58 W.
2) Controlling the UPFC Using the Line Inductance Com-
pensation Scheme: In order to control the UPFC series con-verter using the line inductance compensation scheme, only the
UPFC line current and the source voltages are detected to cal-
culate the reference voltage as given in (15). In this scheme, the
UPFC is considered as an inductance (Lc ) in series with a volt-age source. The inductance (Lc ) compensates the loop systemline parameters in order to achieve equal ratio of the resistance
to inductance for all loop lines, whereas the additional voltage
source compensates the difference in source voltages. Accord-
ing to (13), the inserted inductance Lc = 0.13mH. Fig. 11 showsthe experimental waveforms of the source voltages difference
∆v, reference voltage of the UPFC series converter (vc ), line
1 current (i1 ), line 2 current (i2 ), and loop current (iloop ) of
-
8/19/2019 Base Paper UPFC
8/10
5820 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 11, NOVEMBER 2014
Fig. 11. Experimental waveforms using the line inductance compensationscheme in the isolated substations loop system.
Fig. 12. Comparison between theoretical and experimental results for radial,isolated substations loop system without the UPFC, and isolated substations
loop system with the UPFC.
the loop system before and after installing the UPFC. Exper-
imental results show that after installing the UPFC, the loop
current is eliminated from the loop system, and hence, the lineloss minimum condition is realized. The total power loss in the
UPFC converters is 80.95 W. Also, it is clear that the experimen-
tal results obtained by both schemes coincide with each other
since they provide the same function for the same system with
different control techniques.
The bar chart shown in Fig. 12 presents a comparison be-
tween theoretical and experimental results of the experimental
system that works as radial, isolated substations loop before in-
stalling the UPFC, and isolated substations loop after installing
the UPFC controlled by the line voltage and line inductance
compensation schemes. In both control schemes, after installing
the UPFC, the total line loss is reduced by 37.3% compared with
Fig. 13. Experimental configuration of the same substation multiple loop
system.
TABLE I I
PARAMETERS OF THE SAME SUBSTATION MULTIPLE LOOP SYSTEM
loop before installing the UPFC, and reduced by 16.5% com-
pared with radial.
C. Same Substation Multiple Loop Distribution System
Fig. 13 shows the 6-kVA, 200-V laboratory prototype of the
same substation distribution system that consists of three radial
feeders, which can be reconfigured to loop by connecting the
loads in parallel. SVR is taken into consideration by installing
in series with line 1. The parameters of the whole system are
listed in Table II. The UPFC is installed in the loop system as
shown in Fig. 13 to achieve the line loss minimum condition
by eliminating the loop currents from the two mesh circuits. In
order to achieve that, the UPFC has been controlled to insert a
reference series voltage as given in (32).
Fig. 14 shows the experimental waveforms of the UPFC series
converter voltage vc , line 1 current on both side of the SVR (i1aand i1b ), line 2 current i2 , line 3 current i3 , and the two loop
currents (iloop1 and iloop2 ) before and after installing the UPFC.
Before installing the UPFC, the difference in the resistance-to-
inductance ratio in the line parameters of loop 1 causes the loop
current to pass in this loop (I loop1 = 2.05 A). Although the lineparameters of loop 2 have the same resistance-to-inductance
ratio, there is a loop current (I loop2 = 1.04 A), which resultsfrom the effect of loop 1 current. Since the injected power of
the UPFC is small, the total power loss in the UPFC converter is
20 W. It is clear that after installing the UPFC, both loop currents
have been diminished from the distribution system, and hence,
the line loss minimum condition has been realized.
-
8/19/2019 Base Paper UPFC
9/10
SAYED AND TAKESHITA: LINE LOSS MINIMIZATION IN ISOLATED SUBSTATIONS AND MULTIPLE LOOP DISTRIBUTION SYSTEMS 5821
Fig. 14. Experimentalwaveforms of thesamesubstation multiple loop system.
Fig. 15. Comparison between theoretical and experimental results for radial,same substation multiple loop system without the UPFC, and same substationmultiple loop system with the UPFC.
Fig. 15 shows a comparison between theoretical and exper-
imental results of both loop currents and total line loss for the
system that works as radial, same substation multiple loop with-
out the UPFC, and same substation multiple loop after installing
the UPFC. It is clear that after installing the UPFC, the total line
loss is reduced by 12.5% compared with loop before installing
the UPFC, and reduced by 24.6% compared with radial.
V. CONCLUSION
This paper has presented the line loss minimum condition
and the power flow control schemes of the UPFC to realize line
loss minimization in the isolated substations and the same sub-
station multiple loop distribution systems, along with a detailed
mathematical analysis of both systems. The line loss minimum
condition has been realized in the loop distribution system bycompensating the line reactance voltage drop in addition to the
difference of substation voltages in the case of isolated sub-
stations loop system. Two control schemes of the UPFC series
converter have been proposed to achieve line loss minimum
condition in loop systems. These control schemes are the line
inductance compensation and line voltage compensation. The
effectiveness of the proposed control schemes has been verified
experimentally using a laboratory prototype 6 kVA, 200 V. A
comparison between experimental and theoretical results has
been presented to evaluate the accuracy of the results and the
validity of line loss minimum condition theory. Theoretical and
experimental results agree well. Experimental results prove that
the UPFC has a great capability to achieve line loss minimiza-
tion in isolated substations and the same substation multiple
loop distribution systems.
REFERENCES
[1] N. Okada, H. Kobayashi, K. Takigawa, M. Ichikawa, and K. Kurokawa,“Loop power flow control and voltage characteristics of distribution sys-tem for distributed generation including PV system,” in Proc. 3rd World Conf. Photovoltaics Energy Convers., 2003, pp. 2284–2287.
[2] N. Okada, “Verification of control method for a loop distribution systemusing loop power flow controller,” in Proc. IEEE Power Syst. Conf. Expo. ,2006, pp. 2116–2123.
[3] N. Suman and R. Somnath, “Network reconfiguration for electrical lossminimization,” Int. J. Instrum., Control Autom., vol. 2, pp. 22–28, Feb.2011.
[4] A. Thirumalai, X. Liu, and G. Karady, “Ultra fast pilot protection of a
looped distribution system,” in Proc. IEEE Trondheim PowerTech, 2001,pp. 1–8.
[5] M. Rezaei and A. Huang, “Ultra fast protection of radial and loopedelectric power grid using a novel solid-state protection device,” in Proc.
IEEE Energy Convers. Congr. Expo., 2012, pp. 610–614.[6] N. Rugthaicharoencheep and S. Sirisumrannukul, “Feeder reconfiguration
for loss reduction in three phase distribution system under unbalancedloading conditions,” in Proc. 45th Int. Univ. Power Eng. Conf., 2010,pp. 1–6.
[7] W.-T. Huang and S.-T. Chen, “Line loss reduction by distribution systemupgrading from radial to normally closed-loop arrangement,” in Proc. 9th
Int. Conf. Hybrid Intell. Syst., 2009, pp. 334–339.[8] T.-H. Chen, W.-T. Huang, J.-C. Gu, G.-C. Pu, Y.-F. Hsu, and T.-Y. Guo,
“Feasibility study of upgrading primary feedersfrom radialand open-loopto normally closed-loop arrangement,” IEEE Trans. Power Syst., vol. 19,no. 3, pp. 1308–1316, Aug. 2004.
[9] R. Simanjorang,Y.Miura, T. Ise, andS. Sugimoto,“A methodfor effectiveutilization of power distribution apparatus in industrial park by loopingdistribution lines,” IEEJ Trans. Power Energy, vol. 127-B, pp. 1127–1136,Nov. 2007.
[10] T.-L.Lee andS.-H.Hu, “Discretefrequency-tuning active filter to suppressharmonic resonances of closed-loop distribution power systems,” IEEE
Trans. Power Electron., vol. 26, no. 1, pp. 137–148, Jan. 2011.[11] R. Gupta, A. Ghosh, and A. Joshi, “Performance comparison of VSC-
based shunt and series compensators used for load voltage control indistribution systems,” IEEE Trans. Power Del., vol. 26, no. 1, pp. 268–
278, Jan. 2011.[12] A. Jain, K. Joshi, A. Behal, and N. Mohan, “Voltage regulation with
STATCOMs: Modeling, control and results,” IEEE Trans. Power Del.,
vol. 21, no. 2, pp. 726–735, Apr. 2006.
-
8/19/2019 Base Paper UPFC
10/10
5822 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 11, NOVEMBER 2014
[13] Z. Xi, B. Parkhideh, and S. Bhattacharya, “Improving distribution systemperformance with integrated STATCOM and supercapacitor energy stor-
age system,” in Proc. IEEE Power Electron. Spec. Conf. , 2008, pp. 1390–1395.
[14] H. Fujita and H. Akagi, “Voltage-regulation performance of a shunt activefilterintended for installationon a power distribution system,” IEEE Trans.Power Electron., vol. 22, no. 3, pp. 1046–1053, May 2007.
[15] Z. ZhiHua, X. BingYin, and C. Qing, “Preliminary research on the powerflow control method of thedistribution network with normally closed-loop
operation based on the SSSC,” in Proc. Int. Conf. Adv. Power Syst. Autom.Protect., 2011, pp. 818–821.
[16] R. Simanjorang, Y. Miura, and T. Ise, “A series type BTB converter forcontrolling voltage profile in loop distribution system with distributedgenerations,” IEEJ Trans. Power Energy, vol. 128-B, pp. 769–778, May2008.
[17] R. Simanjorang, Y. Miura, and T. Ise, “Distributed-series compensatorfor controlling voltage in distribution line with clustered distributed gen-erations,” IEEJ Trans. Electr. Electron. Eng., vol. 4, pp. 404–415, Apr.2009.
[18] C.-S. Chen, C.-T. Tsai, C.-H. Lin, W.-L. Hsieh, and T.-T. Ku, “Load-ing balance of distribution feeders with loop power controllers consid-ering photovoltaic generation,” IEEE Trans. Power Syst., vol. 26, no. 3,pp. 1762–1768, Aug. 2011.
[19] M. Sayed, N. Inayoshi, T. Takeshita, and F. Ueda, “Line loss minimizationof loop distribution systems usingUPFC,” IEEJ Trans.Ind. Appl.,vol.128-
D, pp. 508–515, Apr. 2008.[20] M. Sayed and T. Takeshita, “Voltage regulation and line loss minimization
of loop distribution systems usingUPFC,” IEEJ Trans.Ind. Appl.,vol.129-D, pp. 1118–1125, Nov. 2009.
[21] M. Sayed and T. Takeshita, “All nodes voltage regulation and line lossminimization in loop distribution systems using UPFC,” IEEE Trans.Power Electron., vol. 26, no. 6, pp. 1694–1703, Jun. 2011.
[22] R. Saino,T.Takeshita, N.Izuhara,and F. Ueda,“Power flowestimationandline-loss-minimizationcontrol usingUPFC in loop distribution system,” inProc. IEEE Power Electron. Motion Control Conf., 2009, pp. 2426–2431.
[23] C.-J. Chouand C.-W. Liu, “Assessment of risks from ground fault transferon closed-loop HV underground distribution systems with cables runningin a common route,” IEEE Trans. Power Del., vol. 28, no. 2, pp. 1015–1023, Apr. 2013.
[24] J.-F. Moon and J.-S. Kim, “Voltage sag analysis in loop power distribu-tion system with SFCL,” IEEE Trans. Appl. Supercond., vol. 23, no. 3,
pp. 5601504–5601504, Jun. 2013.
[25] L. Gyugyi, “Unified power-flow control concept for flexible ac trans-mission systems,” IEE Proc. C Generat., Transmiss. Distrib., vol. 139,pp. 323–331, Jul. 1992.
[26] L. Gyugyi, C. Schauder, S. Williams, T. Rietman, D. Torgerson, andA. Edris, “The unified power flow controller: A new approach to powertransmission control,” IEEE Trans. Power Del., vol. 10, no. 2, pp. 1085–1097, Apr. 1995.
[27] H. Fujita, H. Akagi, and Y. Watanabe, “Dynamic control and performanceof a unified power flow controller for stabilizing an ac transmission sys-tem,” IEEE Trans. Power Electron., vol. 21, no. 4, pp. 1013–1020, Jul.2006.
[28] J. Verveckken, F. Silva, D. Barros, and J. Driesen, “Direct power control
of series converter of unified power-flow controller with three-level neu-tral point clamped converter,” IEEE Trans. Power Del., vol. 27, no. 4,pp. 1772–1782, Oct. 2012.
[29] Z. Yuan, S. de Haan, J. Ferreira, and D. Cvoric, “A FACTS device: Dis-tributed power-flow controller (DPFC),” IEEE Trans. Power Electron.,vol. 25, no. 10, pp. 2564–2572, Oct. 2010.
[30] H. Abu-Rub, A. Iqbal, and J. Guzinski, High Performance Control of AC Drives With MATLAB/Simulink Models. New York, NY, USA: Wiley-Interscience, 2012.
[31] Z. Shu, X. He, Z. Wang, D. Qiu, and Y. Jing, “Voltage balanc-ing approaches for diode-clamped multilevel converters using auxiliarycapacitor-based circuits,” IEEE Trans. Power Electron., vol. 28, no. 5,
pp. 2111–2124, May 2013.
Mahmoud A. Sayed (M’09) was born in Qena Pre-fecture, Egypt, in 1974. He received the B.Sc. andM.Sc. degrees in electrical engineering from MiniaUniversity, El-Minia, Egypt, in 1997 and 2001, re-spectively, and the Ph.D. degree from the NagoyaInstitute of Technology, Nagoya, Japan, in 2010.
Since 1999, he has been with the Department of Electrical Engineering, Faculty of Energy Engineer-ing, Aswan University, Aswan, Egypt, first as an Ad-
ministrator and since 2001 as a Research Assistant.Currently, he is an Assistant Professor in the Depart-
ment of ElectricalEngineering,Faculty of Engineering, SouthValley University,Qena, Egypt. His research interests include series and shunt compensation of
electrical distribution systems for voltage regulation and loss reduction usingseries and shunt PWM converters in addition to renewable energy applicationsand machine drives.
Dr. Sayed is a Member of the IEEE Power Electronics Society.
Takaharu Takeshita (M’92) was born in Aichi,
Japan, on August 23, 1959. He received the B.S.
and M.S. degrees in electrical engineering from theNagoya Institute of Technology, Nagoya Japan, in1982 and 1984, respectively, and the Ph.D. degreefrom Nagoya University, Nagoya, Japan, in 1990.
Since 1991, he has been with the Nagoya Instituteof Technology, where he is currently a Full Professorandis engaged in research on power convertersystemand motor control.
Dr. Takeshita is a Member of the Society of In-strument and Control Engineers.