back up protection

Upload: tigrillo

Post on 14-Apr-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/30/2019 Back Up Protection

    1/17

    Page

    Discrimination and Back-up Protection

    Introduction 12/2

    Discrimination 12/3Current discrimination, time discrimination 12/4Back-up protection 12/5

    Discrimination limits

    Series circuit-breakers miniature circuit-breakers 12/6Series circuit-breakers circuit-breakers 12/10

    Back-up protection values

    Series circuit-breakers miniature circuit-breakers 12/24

    Discrimination miniature circuit-breakers 12/26

    td

    = 80 ms

    NSK-8274b

    A

    Q1

    E

    K2

    A

    Q2

    E

    K1

    A

    E

    Q3

    Q4 Q5

    A A

    E E

    tzss

    = 50 ms

    td

    = 150 ms

    tzss

    = 50 ms

    td

    = 0 ms

    tzss

    = td

    td

    = 0 ms

    tzss

    = td

  • 7/30/2019 Back Up Protection

    2/17

    Discrimination and Back-up Protection

    Introduction

    It is not the performance of an individual

    component that determines the reliability of

    a low-voltage system, but rather the team-

    work of all such components.Optimal cooperation of switching devices

    depends on discriminative line and deviceprotection. Each feeder and each device

    must be protected as well as possible

    against overload and short-circuit, withoutbeing adversely affected by any switching

    operations intended to protect the rest of

    the system.

    When a system is planned, it is customary

    to select protective devices with breaking

    capacities to suit the maximum possible

    short-circuit currents at the points of installa-tion.

    VDE and IEC standards allow back-up pro-tection of a switching device by one of the

    upstream protective devices with an appro-

    priate switching capacity, if thereby boththe feeder and the downstream protective

    device are protected.

    This means in practical terms that at a

    point in the distribution system with a

    possible short-circuit current of e.g. 50 kA,

    a cost-effective protective device with a

    breaking capacity of only 20 kA can also

    be used, entailing however other advan-

    tages (e.g. less space required and better

    protection), if it is given back-up protectionby an upstream device with a breaking ca-

    pacity of at least 50 kA.

    Discriminative switching with SIEMENS de-

    vices means: maximum possible availa-

    bility of supply, with at the same time a

    high degree of system and device pro-tection by way of specific shutdown of

    the faulty circuit without affecting the

    other loads.

    12/2 Siemens NS PS 1999

  • 7/30/2019 Back Up Protection

    3/17

    Discrimination and Back-up Protection

    In series-connection of circuit-breakers, pro-

    tection against overload and short-circuit is

    referred to as discriminative if, in the direc-

    tion of power flow, only that device up-stream of the fault is tripped.

    Current discrimination

    With overload, the discrimination can be

    worked out from a comparison of the

    time/current characteristics. With short-

    circuit, this comparison produces values

    that are too low. The reason for this is the

    behaviour of the releases in the event ofshort-circuit currents, which deviates from

    the behaviour in the long-time range, i.e. inthe event of overload (see diagram below).

    With adequately different short-circuitcurrents at the installation points of two cir-

    cuit-breakers, the instantaneous short-cir-cuit releases can generally be set so that in

    the event of short-circuit after the down-stream switch, only the latter operates.

    With almost identically high short-circuitcurrents at the installation points of the cir-

    cuit-breakers, grading of the operating cur-rents of the short-circuit releases allows dis-

    crimination only up to a certain short-circuit

    current. This current is referred to as thediscrimination limit.

    The limit values for discrimination are

    shown in the tables on Pages 12/8 to 12/25.

    If the value worked out from the short-

    circuit calculation (e.g. to VDE 0102) at theinstallation point of the downstream switch

    lies below the discrimination limit read offfrom the table for the chosen combination,

    discrimination is assured for all possibleshort-circuit occurrences at the installation

    point.

    If the short-circuit current worked out at the

    installation point lies above the discrimina-

    tion limit, discriminative tripping by thedownstream switch is assured only up to

    the value in the table. The planner must

    assess whether the value can be con-sidered adequate, as the probability of, for

    example, the maximum short-circuit currentoccurring is low. Otherwise a switch combi-

    nation must be selected, with a discrimina-

    tion limit higher than the maximum short-

    circuit current.

    Discrimination

    In = 10 A

    I"k = 20 kA

    Ue = 400 V

    = 1600= 120

    = 120 A

    = 1600 AI>

    I>

    3RV

    3VF

    NSK-8220a

    In = 160 A

    I"k = 6 kA

    I

    I>

    3RV

    I>

    3VF

    Discrimina-tion limitworked outby tests5 kA

    Opening time

    Current

    A

    Discrimination limit fromcomparison of characteristics1600 - 20% = 1280 A

    Fig. 12/1 Example of the effect of discrimination on the selection of circuit-breakers

    Tripping characteristics forcircuit breakers

    In = rated currentIk = short-circuit currentI> = response current

    1

    Siemens NS PS 1999 12/3

  • 7/30/2019 Back Up Protection

    4/17

    Discrimination and Back-up Protection

    Current discrimination, time discrimination

    Fig. 12/2 Fig. 12/3

    Q4 Q2 Q1

    150 ms

    80 ms50 ms

    NSK-8221a

    Opening time

    Current

    A

    td = 80 ms

    NSK-8222a

    A

    Q1

    E

    K2

    A

    Q2

    E

    K1

    A

    E

    Q3

    Q4 Q5

    A A

    E E

    tzss = 50 ms

    td = 150 ms

    tzss = 50 ms

    td = 0 ms

    tzss = td

    td = 0 ms

    tzss = td

    3VF current-limiting circuit-breakers

    for distribution system protection toIEC 60 947

    The 3VF circuit-breakers are available invarious short-circuit breaking capacities. Toeliminate the need to create a table for

    every breaking capacity where the discrimi-

    nation limit is dependant on the breaking

    capacity, the discrimination limit is given inthe sequence e.g. 40/70/100 kA. The corre-

    sponding value is dependant upon thebreaking capacities of the upstream and

    downstream breakers. Decisive is always

    the smallest value.

    Time discrimination

    Another method of assuring discrimination

    in the event of almost identically high short-

    circuit currents at the installation points istime discrimination. The upstream breakerrequires time-delay short-circuit releases,

    so that in the event of a fault only the down-

    stream breaker isolates the part of the sys-

    tem affected by the fault.

    Both the release delays and the operating

    currents of the short-circuit releases aregraded.

    In order to avoid undesirably long tripping

    times with series-connection of several cir-cuit-breakers, SIEMENS has developed

    microprocessor-driven short-time gradingcontrol (ZSS) for the 3WN/3WS circuit-

    breakers.

    This control permits reduction of the trip-

    ping delay time to a maximum of 50 ms for

    the breaker upstream of the short-circuit.

    Upstream

    circuit-breaker

    kA 100 70 40 70

    Downstreamcircuit-breaker

    kA 40 100 100 70

    Discriminationlimit

    kA 40 70 40 70

    td = Maximum operative timeof the blocking signal ordelay time in the event ofnon-activated short timegrading control.

    tZSS = Delay time of all switcheswhich sense the short-circuit and receive noblocking signal.

    A: Output,transmits blocking signal

    E: Input,receives blocking signal

    Communication lines

    Function:A short-circuit at point K1 issensed by Q4, Q2 and Q1.When the ZSS is activated,Q1 and Q2 are temporarilyblocked by Q4 and Q2 respec-tively.As Q4 receives no blockingsignal, it trips after 10 ms.

    A short-circuit at point K2 issensed only by Q1; as Q1receives no blocking signal,it trips after 50 ms. WithoutZSS, tripping would not takeplace until after 150 ms.

    12/4 Siemens NS PS 1999

  • 7/30/2019 Back Up Protection

    5/17

    Discrimination and Back-up Protection

    Back-up protection

    When a circuit-breaker or miniature circuit-

    breaker is selected, it is mandatory that thebreaker be able to handle the short-circuit

    current I"k at the installation point, either onits own or with the assistance of an up-

    stream protective device (back-up protec-

    tion). This means that by virtue of the back-

    up protection, the breaking capacity of thedownstream breaker is allowed to be lowerthan the short-circuit current at the installa-

    tion point. This represents a degree of plan-

    ning freedom, which makes above all for

    economical system design and also op-timizes component protection.

    The tables on pages 12/26 and 12/27 show

    the increased permissible short-circuit cur-

    rents for all breaker combinations, madepossible by back-up protection.

    Appraisal of the back-up protection for thecircuit-breakers to IEC 60 947 and for theminiature circuit-breakers according toIEC 60 898 was based on the breaking

    capacity test with test sequence Icu, in

    according to IEC 60 947-2.

    Fig. 12/4 Example of the effect of back-up protection on the selection of circuit-breakers

    3VF3

    5SX

    NSK-8223a

    Icn = 40 kA

    In = 160 A

    I"k = 28 kA

    Icn = 10 kA

    In = 16 A

    5SX

    Icn = 10 kA

    In = 16 A

    3VF3

    Icn = 40 kA

    In = 160 A

    I"k = 28 kA

    I"k = 9 kA I"k = 14 kA

    Overload and short-circuit protectivewithout advantage of back-up protectionIn Rated currentI"k Short-circuit currentIcn Rated short-circuit

    breaking capacity

    Overload and short-circuit protectivetaking into account back-up protectionin accordance with the tableon page 12/26 and 12/27.

    Back-up-protectedup to 15 kA

    1

    Siemens NS PS 1999 12/5

  • 7/30/2019 Back Up Protection

    6/17

  • 7/30/2019 Back Up Protection

    7/17

  • 7/30/2019 Back Up Protection

    8/17

    S. 10-11

    Discrimination limits

    Series-connection circuit-breakers miniature circuit-breakers AC 400 V, 50 Hz1)

    Downstream circuit-breakers Upstream circuit-breakers

    3RV1.1 3RV1.2

    In (A) 1 1.25 1.6 2 2.5 3.2 4 5 6.3 8 10 12 1 1.25 1.6 2 2.5 3.2

    I > (A) 12 15 19 24 30 38 48 60 76 96 120 144 12 15 19 24 30 38

    Icn (kA) 100 100 100 100 100 100 100 100 100 50 50 50 100 100 100 100 100 100

    Discrimination limits (kA)

    3RV1.1 1 12 100 0.1 0.1 0.2 0.3 0.6 50 50 0.1

    1.25 15 100 0.1 0.1 0.1 0.2 0.3 0.4 0.8 0.1

    1.6 19 100 0.1 0.1 0.1 0.1 0.2 0.3 0.3 0.1

    2 24 100 0.1 0.1 0.1 0.1 0.2 0.2 0.3

    2.5 30 100 0.1 0.1 0.1 0.1 0.2 0.2

    3.2 38 100 0.1 0.1 0.1 0.1 0.2 0.2

    4 48 100

    5 60 100 6.3 76 100

    8 96 50

    10 120 50

    12 144 50

    3RV1.2 1 12 100 0.1 0.1 0.1 0.6 50 50 50 0.1

    1.25 15 100 0.1 0.1 0.2 0.2 0.6 30 50 0.1

    1.6 19 100 0.1 0.1 0.1 0.2 0.3 0.4

    2 24 100 0.1 0.1 0.1 0.2 0.3 0.5

    2.5 30 100 0.1 0.1 0.1 0.2 0.2 0.3

    3.2 38 100 0.1 0.1 0.1 0.1 0.2 0.2

    4 48 100

    5 60 100

    6.3 76 100

    8 96 100

    10 120 100

    12.5 150 100

    16 192 50

    20 240 50

    22 264 50

    25 300 50

    3RV1.3 16 192 50

    20 240 50

    25 300 50

    32 384 50

    40 480 50

    45 540 50

    50 600 50

    3RV1.4 16 192 100

    20 240 100

    25 300 100

    32 384 100

    40 480 100

    50 600 100

    63 756 100

    75 900 100

    90 1080 100

    100 1140 100

    In = Rated current

    I> = Response current for instantaneous short-circuit releases

    Icn = Rated short-circuit breaking capacity acc. to IEC 60 947-2 for mccbs

  • 7/30/2019 Back Up Protection

    9/17

    S. 12-13

    Discrimination limits

    Series-connection circuit-breakers miniature circuit-breakers AC 400 V, 50 Hz1)

    Downstream circuit-breakers Upstream circuit-breakers

    3RV1.3 3RV1.4

    In (A) 16 20 25 32 40 45 50 16 20 25

    I > (A) 192 240 300 384 480 540 600 192 240 300

    Icn (kA) 50 50 50 50 50 50 50 100 100 100

    Discrimination limits (kA)

    3RV1.1 1 12 100 50 50 50 50 50 50 50 100 100 100

    1.25 15 100 50 50 50 50 50 50 50 100 100 100

    1.6 19 100 0.6 1.5 50 50 50 50 50 0.6 1.5 100

    2 24 100 0.4 0.6 1.2 3 50 50 50 0.4 0.6 1.2

    2.5 30 100 0.3 0.4 0.6 1.2 2 3 5 0.3 0.4 0.6

    3.2 38 100 0.3 0.3 0.5 0.8 1.2 1.5 2 0.2 0.3 0.5

    4 48 100 0.4 0.6 0.8 1 1.2 0.4

    5 60 100 0.4 0.6 0.6 0.8 1 0.46.3 76 100 0.4 0.5 0.6 0.8 0.8 0.4

    8 96 50 0.4 0.5 0.6 0.6 0.8 0.4

    10 120 50 0.4 0.5 0.6 0.6 0.8 0.4

    12 144 50 0.5 0.6 0.6 0.8

    3RV1.2 1 12 100 50 50 50 50 50 50 50 100 100 100

    1.25 15 100 50 50 50 50 50 50 50 100 100 100

    1.6 19 100 6 50 50 50 50 5 0 50 100 100 100

    2 24 100 0.8 2.5 50 50 50 50 50 1.2 8 100

    2.5 30 100 0.5 1 1.5 8 50 50 50 0.6 1.2 4

    3.2 38 100 0.4 0.6 0.6 2 3 6 12 0.4 0 .6 0 .6

    4 48 100 0.4 0.6 1 1.5 2.5 3 0.3 0.5 0.6

    5 60 100 0.4 0.6 0.8 1.5 1.5 0.3 0.4

    6.3 76 100 0.5 0.6 0.6 0.6 0.6 0.3 0.5

    8 96 100 0.4 0.6 0.8 1 1.2 0.4

    10 120 100 0.4 0.6 0.8 1 1 0.4

    12.5 150 100 0.4 0.5 0.6 0.8 1 0.4

    16 192 50 0.5 0.6 0.8 0.8

    20 240 50 0.6 0.8

    22 264 50 0.6

    25 300 50 0.6

    3RV1.3 16 192 50 0.5 0.6 0.6 0.8

    20 240 50 0.5 0.6 0.6 0.8

    25 300 50 0.4 0.5 0.6 0.6

    32 384 50 0.6

    40 480 50 0.6

    45 540 50

    50 600 50

    3RV1.4 16 192 100 0.5 0.6 0.6 0.8

    20 240 100 0.5 0.6 0.6 0.8

    25 300 100 0.4 0.5 0.6 0.6

    32 384 100 0.6

    40 480 100 0.6

    50 600 100

    63 756 100

    75 900 100

    90 1080 100

    100 1140 100

    In = Rated current

    I> = Response current for instantaneous short-circuit releases

    Icn = Rated short-circuit breaking capacity acc. to IEC 60 947-2 for mccbs

    1) In 240/415 V, 50 Hz networks the discrimination limits must be reduced by 10%.

  • 7/30/2019 Back Up Protection

    10/17

  • 7/30/2019 Back Up Protection

    11/17

  • 7/30/2019 Back Up Protection

    12/17

  • 7/30/2019 Back Up Protection

    13/17

    S. 20-21

    Discrimination limits

    Series-connection circuit-breakers circuit-breakers AC 400 V, 50 Hz1)

    Downstream circuit-breakers Upstream circuit-breakers

    3VF5 3VF6 3VF7 3VF

    In (A) 200 250 315 400 315 400 500 630 800 800-1250 16

    I >> (A) 2000 2500 3150 4000 3200 4000 5000 6300 6400 15000

    Icn (kA) 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100

    Discrimination limits (kA)

    3VF4 125 1250 40/70/100 2 2 2.5 3.4 3.4 4 4 5.1 5.1 33 4

    for line protection 160 1600 40/70/100 2 2 2.5 3.4 3.4 4 4 4.9 4.9 33 4

    200 2000 40/70/100 2.5 3.4 3.4 4 4 4.9 4.9 33 4

    250 2500 40/70/100 2.5 3.4 3.4 4 4 4.9 4.9 33 4

    3VF4 125 2000 70 3 4 5 5 6 6 27

    for starter 160 2500 70 3 4 5 5 6 6 27

    combinations 200 3000 70 3 5 5 6 6 27

    3VF4 250 3000 40/70 3 5 5 6 6 27

    Non-automatic

    circuit-breakers

    3VF5 200 2000 45/70/100 2.4 3.4 3.4 4 4 4 4 30 4

    for line protection 250 2500 45/70/100 2.4 3.4 3.4 4 4 4 4 28 4

    315 3150 45/70/100 3.4 4 4 4 4 28 4

    400 4000 45/70/100 4 4 28 4

    3VF5

    for motor proteciton 315 4800 40/65 5 5 27

    3VF5 200 3000 65 3.4 5 5 5 5 27

    for starter 250 3800 65 5 5 5 27

    combinations 315 4800 65 5 5 27

    3VF5

    Non-automatic 315 4800 40/65 5 5 27

    circuit-breakers

    3VF6 315 3200 45/70/100 4.4 4.4 21

    for line protection 400 4000 45/70/100 4.4 4.4 21

    500 5000 45/70/100 21 630 6300 45/70/100 21

    800 6400 50

    3VF6

    for motor protection 500 7500 40/65 17

    3VF6 315 4800 65 17

    for starter 400 6000 65 17

    combinations 500 7500 65 17

    3VF6

    Non-automatic 500 7500 40/65

    circuit-breakers

    3VF7 800 15000 50/70/100

    fo r l ine p ro tect ion 1250 15000 50/70/100

    3VF7 800 15000 50/70

    Non-automatic 1250 15000 50/70

    circuit-breakers

    3VF8 1600 20000 70/100

    fo r l ine p ro tect ion 2000 20000 70/100

    3VF8 1600 20000 65

    Non-automatic 2000 20000 65

    circuit-breakers

    In = Rated current

    I>= Response current for instantaneous short-circuit releases

    Icn = Rated short-circuit breaking capacity acc. to IEC 60 947-2 for mccbs

    1) In 240/415 V, 50 Hz networks the discrimination limits must be reduced by 10%.

    The discrimination values apply for adjustable releases at maximum setting.

  • 7/30/2019 Back Up Protection

    14/17

  • 7/30/2019 Back Up Protection

    15/17

    S. 24-25

    Back-up protection values

    Series-connection circuit-breakers-miniature circuit-breakers AC 400 V, 50 Hz

    AC 230/400 V, 50 Hz

    D ow ns tre am c ir cui t- br ea ke rs U ps tre am c ir cui t- br eak er s

    3VF3 3VF3 3VF4 3VF5

    adjustable fixed setting

    In (A) 50 63 80 100 125 160 50 63 80 100 125 160 125 160 200 250 200 250

    I >> (A) 500 630 800 1000 1250 1600 400 500 630 800 1000 1280 1250 1600 2000 2500 2000 2500

    Icn ( kA)

    40/70

    100

    40/70

    100

    40/70

    100

    40/70

    100

    40/70

    100

    40/70

    100

    40/70

    100

    40/70

    100

    40/70

    100

    40/70

    100

    40/70

    100

    40/70

    100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/1

    Back-up protection up to (kA)

    5SX2 0.5-2 6kA/ 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

    5SX4 3 10kA 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35

    A-Characteristics 4 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35

    B-Characteristics 6 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

    C-Characteristics 8 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

    D-Characteristics 13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

    16 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

    20 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

    25 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

    32 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15

    40 10 10 10 10 10 10 10 10 10 10 10 10 8/10 8/10 8/10 8/10 8/10 8/10

    50 10 10 10 10 10 10 10 10 10 10 8/10 8/10 8/10 8/10 8/10 8/10

    In = Rated current

    I >= Response current for instantaneous short-circuit releases

    Icn = Rated short-circuit breaking capacity acc. to IEC 60 947-2 for mccbs

  • 7/30/2019 Back Up Protection

    16/17

    S. 26

    Discrimination miniature circuit-breakers

    In distribution networks without any fuses, mcbs provide selectivity between themselves within close limits. This is dependentpeak current of the downstream mcb and the tripping current of the upstream mcb.

    The following table specifies up to which short-circuit current in kA, discrimination is provided between mcbs connectedin series at 230 V AC.

    Downstream miniature circuit-breakers Upstream miniature circuit-breakers

    5SX4-7 5SX7-7 5SX7-8

    In (A) 20 25 32 40 50 63 80 100 63 80

    I >> (A) 200 250 320 400 500 630 800 1000 945 1200

    Icn ( kA) 10 10 10 10 10 10 10 10 10 10

    Discrimination limits (kA)

    5SX2 6 30 6/10 0.2 0.2 0.3 0.5 0.5 0.5 0.8 1.5 1.5 3

    5SX4 10 50 6/10 0.2 0.2 0.3 0.5 0.5 0.5 0.8 1.2 1.5 3

    B-Characteristics 13 65 6/10 0.2 0.2 0.3 0.4 0.5 0.5 0.8 1.2 1.5 2

    16 80 6/10 0.2 0.2 0.3 0.4 0.5 0.5 0.8 1.2 1.5 2

    20 100 6/10 0.2 0.3 0.4 0.5 0.5 0.8 1.2 1.5 2

    25 125 6/10 0.4 0.4 0.4 0.6 1.2 1.2 1.5

    32 160 6/10 0.4 0.4 0.4 0.6 1.2 1.2 1.5

    40 200 6/10 0.4 0.4 0.6 1.2 1.2 1.5

    50 250 6/10 0.4 0.6 1 1.2 1.5

    5SX2 0.5 5 6/10 0.2 0.3 0.5 0.8 0.8 0.8 1.2 4 5 6/10

    5SX4 1 10 6/10 0.2 0.3 0.5 0.8 0.8 0.8 1.2 4 5 6/10

    C-Characteristics 1.5 15 6/10 0.2 0.3 0.5 0.8 0.8 0.8 1.2 4 5 6/10

    2 20 6/10 0.2 0.3 0.5 0.8 0.8 0.8 1.2 4 5 6/10

    3 30 6/10 0.2 0.2 0.3 0.5 0.5 0.5 0.8 1.5 1.5 3

    4 40 6/10 0.2 0.2 0.3 0.5 0.5 0.5 0.8 1.5 1.5 3

    6 60 6/10 0.2 0.2 0.3 0.5 0.5 0.5 0.8 1.5 1.5 3

    8 80 6/10 0.2 0.2 0.3 0.4 0.4 0.4 0.6 1.2 1.5 2.5

    10 100 6/10 0.2 0.2 0.3 0.4 0.4 0.4 0.6 1.2 1.5 2.5

    13 130 6/10 0.2 0.2 0.3 0.4 0.4 0.4 0.6 1.2 1.2 2

    16 160 6/10 0.2 0.2 0.3 0.4 0.4 0.4 0.6 1.2 1.2 2

    20 200 6/10 0.2 0.3 0.4 0.4 0.4 0.6 1.2 1.2 2

    25 250 6/10 0.3 0.4 0.4 0.6 1 1.2 1.5

    32 320 6/10 0.3 0.4 0.4 0.6 1 1.2 1.5

    40 400 6/10 0.8 1 1.5

    50 500 6/10 0.8 1 1.5

    63 630 6/10 0.8 1.2

    In = Rated current

    I> = Response current for instantaneous short circuit releases

    Icn = Rated short-circuit breaking capacity acc. to IEC 60 947-2 for mccbs

  • 7/30/2019 Back Up Protection

    17/17

    S. 26

    on the

    100

    1500

    10

    5

    4

    3

    3

    3

    3

    3

    2.5

    2.5

    6/10

    6/10

    6/10

    6/10

    4

    4

    4

    3

    3

    3

    3

    3

    2.5

    2.5

    2

    2

    1.5