back up protection
TRANSCRIPT
-
7/30/2019 Back Up Protection
1/17
Page
Discrimination and Back-up Protection
Introduction 12/2
Discrimination 12/3Current discrimination, time discrimination 12/4Back-up protection 12/5
Discrimination limits
Series circuit-breakers miniature circuit-breakers 12/6Series circuit-breakers circuit-breakers 12/10
Back-up protection values
Series circuit-breakers miniature circuit-breakers 12/24
Discrimination miniature circuit-breakers 12/26
td
= 80 ms
NSK-8274b
A
Q1
E
K2
A
Q2
E
K1
A
E
Q3
Q4 Q5
A A
E E
tzss
= 50 ms
td
= 150 ms
tzss
= 50 ms
td
= 0 ms
tzss
= td
td
= 0 ms
tzss
= td
-
7/30/2019 Back Up Protection
2/17
Discrimination and Back-up Protection
Introduction
It is not the performance of an individual
component that determines the reliability of
a low-voltage system, but rather the team-
work of all such components.Optimal cooperation of switching devices
depends on discriminative line and deviceprotection. Each feeder and each device
must be protected as well as possible
against overload and short-circuit, withoutbeing adversely affected by any switching
operations intended to protect the rest of
the system.
When a system is planned, it is customary
to select protective devices with breaking
capacities to suit the maximum possible
short-circuit currents at the points of installa-tion.
VDE and IEC standards allow back-up pro-tection of a switching device by one of the
upstream protective devices with an appro-
priate switching capacity, if thereby boththe feeder and the downstream protective
device are protected.
This means in practical terms that at a
point in the distribution system with a
possible short-circuit current of e.g. 50 kA,
a cost-effective protective device with a
breaking capacity of only 20 kA can also
be used, entailing however other advan-
tages (e.g. less space required and better
protection), if it is given back-up protectionby an upstream device with a breaking ca-
pacity of at least 50 kA.
Discriminative switching with SIEMENS de-
vices means: maximum possible availa-
bility of supply, with at the same time a
high degree of system and device pro-tection by way of specific shutdown of
the faulty circuit without affecting the
other loads.
12/2 Siemens NS PS 1999
-
7/30/2019 Back Up Protection
3/17
Discrimination and Back-up Protection
In series-connection of circuit-breakers, pro-
tection against overload and short-circuit is
referred to as discriminative if, in the direc-
tion of power flow, only that device up-stream of the fault is tripped.
Current discrimination
With overload, the discrimination can be
worked out from a comparison of the
time/current characteristics. With short-
circuit, this comparison produces values
that are too low. The reason for this is the
behaviour of the releases in the event ofshort-circuit currents, which deviates from
the behaviour in the long-time range, i.e. inthe event of overload (see diagram below).
With adequately different short-circuitcurrents at the installation points of two cir-
cuit-breakers, the instantaneous short-cir-cuit releases can generally be set so that in
the event of short-circuit after the down-stream switch, only the latter operates.
With almost identically high short-circuitcurrents at the installation points of the cir-
cuit-breakers, grading of the operating cur-rents of the short-circuit releases allows dis-
crimination only up to a certain short-circuit
current. This current is referred to as thediscrimination limit.
The limit values for discrimination are
shown in the tables on Pages 12/8 to 12/25.
If the value worked out from the short-
circuit calculation (e.g. to VDE 0102) at theinstallation point of the downstream switch
lies below the discrimination limit read offfrom the table for the chosen combination,
discrimination is assured for all possibleshort-circuit occurrences at the installation
point.
If the short-circuit current worked out at the
installation point lies above the discrimina-
tion limit, discriminative tripping by thedownstream switch is assured only up to
the value in the table. The planner must
assess whether the value can be con-sidered adequate, as the probability of, for
example, the maximum short-circuit currentoccurring is low. Otherwise a switch combi-
nation must be selected, with a discrimina-
tion limit higher than the maximum short-
circuit current.
Discrimination
In = 10 A
I"k = 20 kA
Ue = 400 V
= 1600= 120
= 120 A
= 1600 AI>
I>
3RV
3VF
NSK-8220a
In = 160 A
I"k = 6 kA
I
I>
3RV
I>
3VF
Discrimina-tion limitworked outby tests5 kA
Opening time
Current
A
Discrimination limit fromcomparison of characteristics1600 - 20% = 1280 A
Fig. 12/1 Example of the effect of discrimination on the selection of circuit-breakers
Tripping characteristics forcircuit breakers
In = rated currentIk = short-circuit currentI> = response current
1
Siemens NS PS 1999 12/3
-
7/30/2019 Back Up Protection
4/17
Discrimination and Back-up Protection
Current discrimination, time discrimination
Fig. 12/2 Fig. 12/3
Q4 Q2 Q1
150 ms
80 ms50 ms
NSK-8221a
Opening time
Current
A
td = 80 ms
NSK-8222a
A
Q1
E
K2
A
Q2
E
K1
A
E
Q3
Q4 Q5
A A
E E
tzss = 50 ms
td = 150 ms
tzss = 50 ms
td = 0 ms
tzss = td
td = 0 ms
tzss = td
3VF current-limiting circuit-breakers
for distribution system protection toIEC 60 947
The 3VF circuit-breakers are available invarious short-circuit breaking capacities. Toeliminate the need to create a table for
every breaking capacity where the discrimi-
nation limit is dependant on the breaking
capacity, the discrimination limit is given inthe sequence e.g. 40/70/100 kA. The corre-
sponding value is dependant upon thebreaking capacities of the upstream and
downstream breakers. Decisive is always
the smallest value.
Time discrimination
Another method of assuring discrimination
in the event of almost identically high short-
circuit currents at the installation points istime discrimination. The upstream breakerrequires time-delay short-circuit releases,
so that in the event of a fault only the down-
stream breaker isolates the part of the sys-
tem affected by the fault.
Both the release delays and the operating
currents of the short-circuit releases aregraded.
In order to avoid undesirably long tripping
times with series-connection of several cir-cuit-breakers, SIEMENS has developed
microprocessor-driven short-time gradingcontrol (ZSS) for the 3WN/3WS circuit-
breakers.
This control permits reduction of the trip-
ping delay time to a maximum of 50 ms for
the breaker upstream of the short-circuit.
Upstream
circuit-breaker
kA 100 70 40 70
Downstreamcircuit-breaker
kA 40 100 100 70
Discriminationlimit
kA 40 70 40 70
td = Maximum operative timeof the blocking signal ordelay time in the event ofnon-activated short timegrading control.
tZSS = Delay time of all switcheswhich sense the short-circuit and receive noblocking signal.
A: Output,transmits blocking signal
E: Input,receives blocking signal
Communication lines
Function:A short-circuit at point K1 issensed by Q4, Q2 and Q1.When the ZSS is activated,Q1 and Q2 are temporarilyblocked by Q4 and Q2 respec-tively.As Q4 receives no blockingsignal, it trips after 10 ms.
A short-circuit at point K2 issensed only by Q1; as Q1receives no blocking signal,it trips after 50 ms. WithoutZSS, tripping would not takeplace until after 150 ms.
12/4 Siemens NS PS 1999
-
7/30/2019 Back Up Protection
5/17
Discrimination and Back-up Protection
Back-up protection
When a circuit-breaker or miniature circuit-
breaker is selected, it is mandatory that thebreaker be able to handle the short-circuit
current I"k at the installation point, either onits own or with the assistance of an up-
stream protective device (back-up protec-
tion). This means that by virtue of the back-
up protection, the breaking capacity of thedownstream breaker is allowed to be lowerthan the short-circuit current at the installa-
tion point. This represents a degree of plan-
ning freedom, which makes above all for
economical system design and also op-timizes component protection.
The tables on pages 12/26 and 12/27 show
the increased permissible short-circuit cur-
rents for all breaker combinations, madepossible by back-up protection.
Appraisal of the back-up protection for thecircuit-breakers to IEC 60 947 and for theminiature circuit-breakers according toIEC 60 898 was based on the breaking
capacity test with test sequence Icu, in
according to IEC 60 947-2.
Fig. 12/4 Example of the effect of back-up protection on the selection of circuit-breakers
3VF3
5SX
NSK-8223a
Icn = 40 kA
In = 160 A
I"k = 28 kA
Icn = 10 kA
In = 16 A
5SX
Icn = 10 kA
In = 16 A
3VF3
Icn = 40 kA
In = 160 A
I"k = 28 kA
I"k = 9 kA I"k = 14 kA
Overload and short-circuit protectivewithout advantage of back-up protectionIn Rated currentI"k Short-circuit currentIcn Rated short-circuit
breaking capacity
Overload and short-circuit protectivetaking into account back-up protectionin accordance with the tableon page 12/26 and 12/27.
Back-up-protectedup to 15 kA
1
Siemens NS PS 1999 12/5
-
7/30/2019 Back Up Protection
6/17
-
7/30/2019 Back Up Protection
7/17
-
7/30/2019 Back Up Protection
8/17
S. 10-11
Discrimination limits
Series-connection circuit-breakers miniature circuit-breakers AC 400 V, 50 Hz1)
Downstream circuit-breakers Upstream circuit-breakers
3RV1.1 3RV1.2
In (A) 1 1.25 1.6 2 2.5 3.2 4 5 6.3 8 10 12 1 1.25 1.6 2 2.5 3.2
I > (A) 12 15 19 24 30 38 48 60 76 96 120 144 12 15 19 24 30 38
Icn (kA) 100 100 100 100 100 100 100 100 100 50 50 50 100 100 100 100 100 100
Discrimination limits (kA)
3RV1.1 1 12 100 0.1 0.1 0.2 0.3 0.6 50 50 0.1
1.25 15 100 0.1 0.1 0.1 0.2 0.3 0.4 0.8 0.1
1.6 19 100 0.1 0.1 0.1 0.1 0.2 0.3 0.3 0.1
2 24 100 0.1 0.1 0.1 0.1 0.2 0.2 0.3
2.5 30 100 0.1 0.1 0.1 0.1 0.2 0.2
3.2 38 100 0.1 0.1 0.1 0.1 0.2 0.2
4 48 100
5 60 100 6.3 76 100
8 96 50
10 120 50
12 144 50
3RV1.2 1 12 100 0.1 0.1 0.1 0.6 50 50 50 0.1
1.25 15 100 0.1 0.1 0.2 0.2 0.6 30 50 0.1
1.6 19 100 0.1 0.1 0.1 0.2 0.3 0.4
2 24 100 0.1 0.1 0.1 0.2 0.3 0.5
2.5 30 100 0.1 0.1 0.1 0.2 0.2 0.3
3.2 38 100 0.1 0.1 0.1 0.1 0.2 0.2
4 48 100
5 60 100
6.3 76 100
8 96 100
10 120 100
12.5 150 100
16 192 50
20 240 50
22 264 50
25 300 50
3RV1.3 16 192 50
20 240 50
25 300 50
32 384 50
40 480 50
45 540 50
50 600 50
3RV1.4 16 192 100
20 240 100
25 300 100
32 384 100
40 480 100
50 600 100
63 756 100
75 900 100
90 1080 100
100 1140 100
In = Rated current
I> = Response current for instantaneous short-circuit releases
Icn = Rated short-circuit breaking capacity acc. to IEC 60 947-2 for mccbs
-
7/30/2019 Back Up Protection
9/17
S. 12-13
Discrimination limits
Series-connection circuit-breakers miniature circuit-breakers AC 400 V, 50 Hz1)
Downstream circuit-breakers Upstream circuit-breakers
3RV1.3 3RV1.4
In (A) 16 20 25 32 40 45 50 16 20 25
I > (A) 192 240 300 384 480 540 600 192 240 300
Icn (kA) 50 50 50 50 50 50 50 100 100 100
Discrimination limits (kA)
3RV1.1 1 12 100 50 50 50 50 50 50 50 100 100 100
1.25 15 100 50 50 50 50 50 50 50 100 100 100
1.6 19 100 0.6 1.5 50 50 50 50 50 0.6 1.5 100
2 24 100 0.4 0.6 1.2 3 50 50 50 0.4 0.6 1.2
2.5 30 100 0.3 0.4 0.6 1.2 2 3 5 0.3 0.4 0.6
3.2 38 100 0.3 0.3 0.5 0.8 1.2 1.5 2 0.2 0.3 0.5
4 48 100 0.4 0.6 0.8 1 1.2 0.4
5 60 100 0.4 0.6 0.6 0.8 1 0.46.3 76 100 0.4 0.5 0.6 0.8 0.8 0.4
8 96 50 0.4 0.5 0.6 0.6 0.8 0.4
10 120 50 0.4 0.5 0.6 0.6 0.8 0.4
12 144 50 0.5 0.6 0.6 0.8
3RV1.2 1 12 100 50 50 50 50 50 50 50 100 100 100
1.25 15 100 50 50 50 50 50 50 50 100 100 100
1.6 19 100 6 50 50 50 50 5 0 50 100 100 100
2 24 100 0.8 2.5 50 50 50 50 50 1.2 8 100
2.5 30 100 0.5 1 1.5 8 50 50 50 0.6 1.2 4
3.2 38 100 0.4 0.6 0.6 2 3 6 12 0.4 0 .6 0 .6
4 48 100 0.4 0.6 1 1.5 2.5 3 0.3 0.5 0.6
5 60 100 0.4 0.6 0.8 1.5 1.5 0.3 0.4
6.3 76 100 0.5 0.6 0.6 0.6 0.6 0.3 0.5
8 96 100 0.4 0.6 0.8 1 1.2 0.4
10 120 100 0.4 0.6 0.8 1 1 0.4
12.5 150 100 0.4 0.5 0.6 0.8 1 0.4
16 192 50 0.5 0.6 0.8 0.8
20 240 50 0.6 0.8
22 264 50 0.6
25 300 50 0.6
3RV1.3 16 192 50 0.5 0.6 0.6 0.8
20 240 50 0.5 0.6 0.6 0.8
25 300 50 0.4 0.5 0.6 0.6
32 384 50 0.6
40 480 50 0.6
45 540 50
50 600 50
3RV1.4 16 192 100 0.5 0.6 0.6 0.8
20 240 100 0.5 0.6 0.6 0.8
25 300 100 0.4 0.5 0.6 0.6
32 384 100 0.6
40 480 100 0.6
50 600 100
63 756 100
75 900 100
90 1080 100
100 1140 100
In = Rated current
I> = Response current for instantaneous short-circuit releases
Icn = Rated short-circuit breaking capacity acc. to IEC 60 947-2 for mccbs
1) In 240/415 V, 50 Hz networks the discrimination limits must be reduced by 10%.
-
7/30/2019 Back Up Protection
10/17
-
7/30/2019 Back Up Protection
11/17
-
7/30/2019 Back Up Protection
12/17
-
7/30/2019 Back Up Protection
13/17
S. 20-21
Discrimination limits
Series-connection circuit-breakers circuit-breakers AC 400 V, 50 Hz1)
Downstream circuit-breakers Upstream circuit-breakers
3VF5 3VF6 3VF7 3VF
In (A) 200 250 315 400 315 400 500 630 800 800-1250 16
I >> (A) 2000 2500 3150 4000 3200 4000 5000 6300 6400 15000
Icn (kA) 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100
Discrimination limits (kA)
3VF4 125 1250 40/70/100 2 2 2.5 3.4 3.4 4 4 5.1 5.1 33 4
for line protection 160 1600 40/70/100 2 2 2.5 3.4 3.4 4 4 4.9 4.9 33 4
200 2000 40/70/100 2.5 3.4 3.4 4 4 4.9 4.9 33 4
250 2500 40/70/100 2.5 3.4 3.4 4 4 4.9 4.9 33 4
3VF4 125 2000 70 3 4 5 5 6 6 27
for starter 160 2500 70 3 4 5 5 6 6 27
combinations 200 3000 70 3 5 5 6 6 27
3VF4 250 3000 40/70 3 5 5 6 6 27
Non-automatic
circuit-breakers
3VF5 200 2000 45/70/100 2.4 3.4 3.4 4 4 4 4 30 4
for line protection 250 2500 45/70/100 2.4 3.4 3.4 4 4 4 4 28 4
315 3150 45/70/100 3.4 4 4 4 4 28 4
400 4000 45/70/100 4 4 28 4
3VF5
for motor proteciton 315 4800 40/65 5 5 27
3VF5 200 3000 65 3.4 5 5 5 5 27
for starter 250 3800 65 5 5 5 27
combinations 315 4800 65 5 5 27
3VF5
Non-automatic 315 4800 40/65 5 5 27
circuit-breakers
3VF6 315 3200 45/70/100 4.4 4.4 21
for line protection 400 4000 45/70/100 4.4 4.4 21
500 5000 45/70/100 21 630 6300 45/70/100 21
800 6400 50
3VF6
for motor protection 500 7500 40/65 17
3VF6 315 4800 65 17
for starter 400 6000 65 17
combinations 500 7500 65 17
3VF6
Non-automatic 500 7500 40/65
circuit-breakers
3VF7 800 15000 50/70/100
fo r l ine p ro tect ion 1250 15000 50/70/100
3VF7 800 15000 50/70
Non-automatic 1250 15000 50/70
circuit-breakers
3VF8 1600 20000 70/100
fo r l ine p ro tect ion 2000 20000 70/100
3VF8 1600 20000 65
Non-automatic 2000 20000 65
circuit-breakers
In = Rated current
I>= Response current for instantaneous short-circuit releases
Icn = Rated short-circuit breaking capacity acc. to IEC 60 947-2 for mccbs
1) In 240/415 V, 50 Hz networks the discrimination limits must be reduced by 10%.
The discrimination values apply for adjustable releases at maximum setting.
-
7/30/2019 Back Up Protection
14/17
-
7/30/2019 Back Up Protection
15/17
S. 24-25
Back-up protection values
Series-connection circuit-breakers-miniature circuit-breakers AC 400 V, 50 Hz
AC 230/400 V, 50 Hz
D ow ns tre am c ir cui t- br ea ke rs U ps tre am c ir cui t- br eak er s
3VF3 3VF3 3VF4 3VF5
adjustable fixed setting
In (A) 50 63 80 100 125 160 50 63 80 100 125 160 125 160 200 250 200 250
I >> (A) 500 630 800 1000 1250 1600 400 500 630 800 1000 1280 1250 1600 2000 2500 2000 2500
Icn ( kA)
40/70
100
40/70
100
40/70
100
40/70
100
40/70
100
40/70
100
40/70
100
40/70
100
40/70
100
40/70
100
40/70
100
40/70
100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/1
Back-up protection up to (kA)
5SX2 0.5-2 6kA/ 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
5SX4 3 10kA 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
A-Characteristics 4 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
B-Characteristics 6 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
C-Characteristics 8 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
D-Characteristics 13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
16 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
20 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
25 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
32 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
40 10 10 10 10 10 10 10 10 10 10 10 10 8/10 8/10 8/10 8/10 8/10 8/10
50 10 10 10 10 10 10 10 10 10 10 8/10 8/10 8/10 8/10 8/10 8/10
In = Rated current
I >= Response current for instantaneous short-circuit releases
Icn = Rated short-circuit breaking capacity acc. to IEC 60 947-2 for mccbs
-
7/30/2019 Back Up Protection
16/17
S. 26
Discrimination miniature circuit-breakers
In distribution networks without any fuses, mcbs provide selectivity between themselves within close limits. This is dependentpeak current of the downstream mcb and the tripping current of the upstream mcb.
The following table specifies up to which short-circuit current in kA, discrimination is provided between mcbs connectedin series at 230 V AC.
Downstream miniature circuit-breakers Upstream miniature circuit-breakers
5SX4-7 5SX7-7 5SX7-8
In (A) 20 25 32 40 50 63 80 100 63 80
I >> (A) 200 250 320 400 500 630 800 1000 945 1200
Icn ( kA) 10 10 10 10 10 10 10 10 10 10
Discrimination limits (kA)
5SX2 6 30 6/10 0.2 0.2 0.3 0.5 0.5 0.5 0.8 1.5 1.5 3
5SX4 10 50 6/10 0.2 0.2 0.3 0.5 0.5 0.5 0.8 1.2 1.5 3
B-Characteristics 13 65 6/10 0.2 0.2 0.3 0.4 0.5 0.5 0.8 1.2 1.5 2
16 80 6/10 0.2 0.2 0.3 0.4 0.5 0.5 0.8 1.2 1.5 2
20 100 6/10 0.2 0.3 0.4 0.5 0.5 0.8 1.2 1.5 2
25 125 6/10 0.4 0.4 0.4 0.6 1.2 1.2 1.5
32 160 6/10 0.4 0.4 0.4 0.6 1.2 1.2 1.5
40 200 6/10 0.4 0.4 0.6 1.2 1.2 1.5
50 250 6/10 0.4 0.6 1 1.2 1.5
5SX2 0.5 5 6/10 0.2 0.3 0.5 0.8 0.8 0.8 1.2 4 5 6/10
5SX4 1 10 6/10 0.2 0.3 0.5 0.8 0.8 0.8 1.2 4 5 6/10
C-Characteristics 1.5 15 6/10 0.2 0.3 0.5 0.8 0.8 0.8 1.2 4 5 6/10
2 20 6/10 0.2 0.3 0.5 0.8 0.8 0.8 1.2 4 5 6/10
3 30 6/10 0.2 0.2 0.3 0.5 0.5 0.5 0.8 1.5 1.5 3
4 40 6/10 0.2 0.2 0.3 0.5 0.5 0.5 0.8 1.5 1.5 3
6 60 6/10 0.2 0.2 0.3 0.5 0.5 0.5 0.8 1.5 1.5 3
8 80 6/10 0.2 0.2 0.3 0.4 0.4 0.4 0.6 1.2 1.5 2.5
10 100 6/10 0.2 0.2 0.3 0.4 0.4 0.4 0.6 1.2 1.5 2.5
13 130 6/10 0.2 0.2 0.3 0.4 0.4 0.4 0.6 1.2 1.2 2
16 160 6/10 0.2 0.2 0.3 0.4 0.4 0.4 0.6 1.2 1.2 2
20 200 6/10 0.2 0.3 0.4 0.4 0.4 0.6 1.2 1.2 2
25 250 6/10 0.3 0.4 0.4 0.6 1 1.2 1.5
32 320 6/10 0.3 0.4 0.4 0.6 1 1.2 1.5
40 400 6/10 0.8 1 1.5
50 500 6/10 0.8 1 1.5
63 630 6/10 0.8 1.2
In = Rated current
I> = Response current for instantaneous short circuit releases
Icn = Rated short-circuit breaking capacity acc. to IEC 60 947-2 for mccbs
-
7/30/2019 Back Up Protection
17/17
S. 26
on the
100
1500
10
5
4
3
3
3
3
3
2.5
2.5
6/10
6/10
6/10
6/10
4
4
4
3
3
3
3
3
2.5
2.5
2
2
1.5