  • Dr B Pahlavanpour

    Senior Techncal Co-ordinator

    Nynas Naphthenics LTD

    UK

  • IEC specification and maintenance guide for

    mineral insulating oil Dr B Pahlavanpour

    Nynas Naphthenics Ltd

    UK

  • Three Important oil related IEC standards

    IEC60296, Specification for supply of unused MIO

    IEC60422, Maintenance guide for in-service MIO

    IEC60599, Interpretation of DGA

    Although these standards have maintenance cycle but, if required, they can be revised if and when require

  • Reason for revision

    During 2005 there was report of some transformer failure due to copper sulphide formation

    IEC, TC10 meeting in Cape Town decision was to revise these two standard to address this issue,

    Also to develop a method for detection of potentially corrosive sulphur

  • Nynas- 2012 5 2013-05-

    23

    Revised IEC60296, 2012 ed

    Introduction of corrosive sulphur test methods:

    IEC62535

    ASTM D1275B

    Introduction of IEC60666 test method for:

    passivator content

    Test method for antioxidant content to 0.01%

    Lower level of Furfural in oil (

  • Nynas- 2012 6 2013-05-

    23

  • Table 2 General specification

    Nynas- 2012 7 2013-05-

    23

    No changes to 2003 ed

  • Nynas- 2012 8 2013-05-

    23

  • Nynas- 2012 9 2013-05-

    23

  • Nynas- 2012 1

    0 2013-05-

    23

  • Special requirement for special application

    (high grade oil)

    Nynas- 2012 1

    1 2013-05-

    23

  • IEC 60422 Oil maintenance guide

    A tool for keeping the oil in good condition

    Oil tests divided into 3 groups

    Routine

    Complementary

    Special investigative

    Different recommended property limits depending on voltage class (also type of equipment)

    < 72.5 kV

    72.5-170 kV

    < 170 kV

    For each measured property 3 levels of assessment

    Good No action

    Fair More frequent sampling

    Poor Action required

  • Revision of IEC60422

    Originally was to address potentially corrosive sulphur in oil

    First meeting January 2007

    Report to TC10 Test the oil for presence of corrosive sulphur,

    corrective actions recommended (i.e change the oil, passivate the

    oil)

    MT22 members take the opportunity to revise IEC60422 and IEC

    central office agreed with this proposal.

    To bring it in line with current practice in industry, and address

    industries need.

  • Main changes

    Moisture content

    Inhibitor content

    Passsivator content

    DBDS content

    Potentially Corrosive Sulphur

  • Water content

    2005 ed. corrected to 20 C then limit for each category of

    equipment

    FDIS, at transformer operating temperature together with breakdown voltage .

    Consequently higher limits are used

    Correction to 20 C is transferred to annex (informative).

  • Water content

    (mg/kg at

    transformer

    operating

    temperature)

    O, A 20

    B, D 30

    C, E 40

    F Action

    necessit

    y >40

    G Not a routine test.

    2005 ed

    2013 ed

  • Inhibitor content

    Category Recommended Action Limits

    Good Fair Poor

    All >60 % of

    original

    value

    40 % to 60

    % of

    original

    value

  • Passivator content (new)

    O, A, B, C,

    D, E, F

    >70 and stable,

    (rate of decrease

  • Interfacial tension

    O, A, B, C, D

    Inhibited

    Uninhibited

    >28

    >25

    22 to 28

    20 to 25

  • Corrosive sulphur Three corrosive sulphur test are recommended

    Introducing new test IEC62535

    ASTM D1275B

    DIN51353

    Category Recommended Action Limits Recommended Action (1) (2)

    Good Fair Poor

    O, A, B, C, D,

    E, F

    Non corrosive Corrosive For corrosive oil:

    - conduct risk assessment

    - reduce the corrosivity of the oil by

    adding a copper passivator (e.g. triazole

    derivates)

    or

    - remove the source of corrosivity by

    changing the oil [see 12] or by removing

    corrosive compounds by mean of

    suitable oil treatments.

    See NOTE 3.

  • Passivator content, test method IEC60666, annex B

    O, A,

    B, C,

    D, E, F

    >70 and

    stable,

    (rate of

    decrease

  • DBDS content

    IEC62697-1 is introduce as test method.

    No limit for in-service oil as good, fair, bad

    Reference to CIGRE Brochure 378 is made

  • IEC60422, 205 ed.

  • Table of 2013 ed.

    Property Highest voltage for equipment (kV)

    170

    Appearance Clear, free from sediment and suspended matter

    Colour (on scale given in ISO 2049) Max. 2,0 Max 2,0 Max. 2,0

    Breakdown voltage (kV) >55 >60 >60

    Water content (mg/kg)a 20b

  • Compatibility

    The following functional tests are recommended for each individual oil

    and for the mixture:

    Foaming

    Oxidation stability according to IEC 61125 C, including acidity, sludge

    and DDF after ageing. Test time should be according to the oil group as

    stated in IEC 60296

    Corrosive sulphur and/or potential corrosivity after ageing according to

    IEC 61125C