avk generator
DESCRIPTION
3.3 KV generatorTRANSCRIPT
Date: 04/05/2012 Customer: Bitte Interessent eingeben! Project No.: P-2012-hf195-10000006/1DE AvK Reference: 1-416-0000006-1
Object data: Site: Prime Mover: Diesel engine
Application: Stationary Power Plant Manufacturer:
Generator data: Generator: DIG 120 k/4 Poles: 4 Standards: IEC 60034 Rated power: 2050 kVA 1640 kWe 1705 kWm Power factor: 0.80 Power at pf 1,0 1654 kVA 1654 kWe 1705 kWm Rated voltage: 3.3 kV Speed: 1500 1/min Frequency: 50 Hz Voltage range / frequency range: Rated current: 358.7 A Zone A according IEC 60034-1 (dU = +/-5%, df = +/-2%)
Winding pitch: ca. 5/6
Insulation class: Stator: Class F Rotor: Class F Temperature rise: F
Ambient temperature: 40 ° C Environment: Standard environment Site altitude: 1000 m Enclosure: IP23 Filter:
Cooling: IC 01 - Open-circuit ventilation Coolant: Ambient Air Temperature
Coolant: 40 ° C Temperature Air inlet
generator: 40 ° C
Cooling air vol.: 2.5 m³/s Cooling water quantity: n/a Moment of inertia (I): 66 kgm² Weight: 6000 Kg Losses (environment):
Losses (cooling): 65 KW n/a
Wires: 4 terminals, starpoint connected in terminal box Operation mode: Island mode with identical generators in parallel Regulators: Voltage regulator: DECS 100
Electrical data: (acc. IEC) Efficiencies: 110% 100% 75% 50% 25% Power factor 0.8 96,01 96,2 96,1 95,4 92,6 Power factor 0.9 96,43 96,6 96,4 95,7 92,8 Power factor 1.0 96,85 97 96,7 96 93
Reactances and time constants
unsaturated saturated unsaturated saturated
xd 2.30 2.07 p.u. xq 1.15 1.13 p.u. Td0' 3.2 s Td0'' 0.02382 s xd' 0.270 0.270 p.u. xq' 1.15 1.13 p.u. Td' 0.38 s Tq0' 0.3 s xd'' 0.187 0.170 p.u. xq'' 0.187 0.187 p.u. Td'' 0.015 s Tq0'' 0.18449 s x2 0.197 0.179 p.u. x0 0.056 0.051 p.u. Ta 0.05 s Tq' 0.3 s x1s n.a. 0.102 p.u. Tq'' 0.03 s
Short circuit ratio saturated: 0.48 Zn 5.312 Ohm
Short circuit data:
Initial short circuit current (3-phase): Ik'' 2110 A Max. peak current (3-phase): IS 5371 A Sustained short circuit current: Ik 1076 A 3 x rated current for max.10 s Initial short circuit torque: Mk2 99.8 kNm Mk3 59.9 kNm Max. faulty synchron moment: Mf 214.6 kNm Rated kVA torque: MSN 13.05 kNm Rated torque MN 10.44 kNm Shaft torque MSh 10.85 kNm
Load application:
max. load application: 1139 kVA(corresponds to 55,56 % von 2050 kVA) for Power factor 0.4 15% transient voltage drop
Power: 2050 kVA Power factor: 0.8 transient voltage drop: -21.3 %
Remarks:
FM 7.3-5
Technical Data Sheet for AvK-Alternators
Document: Revision: J dated 17.09.2004 7_2f04jE.xls Cummins Generator Technologies Germany GmbH 2 / 3
FM 7.2-4
Order specification for AvK-Alternators
-technical-
Issued by: Sales department
Created by: Jerry Yu (hf195)
Released by: QuotationTool
Date: 04/05/12
1
CGT Order No.: Spare parts order no.: Others: Customer: Revision no.: Revision date:
Bitte Interessent eingeben! 1 04/05/12
2
Application / Project:
Alternator type:
DIG 120 k/4
3 CGT quotation no.: 1-416-0000006-1 P-2012-hf195-10000006/1DE
Quantity: 1
4 Factory Project no.:
5 Customer Order no.: Mode of operation: Stationary Power Plant
6 Delivery Date:
7.1 Order Type:
7.2 Reference:
7.3 Valid drawing at order entry:
17
Rated data
Rules, Standards
18 Output: 2050 kVA Standards: IEC 60034
19 P.F. Cos Phi: 0.80 R.I.S. Degree: VDE 0875 N 20 Voltage: 3.3 kV Insulation class: Class F
21 Current: 358.7 A Temperature rise: F 22 Frequency: 50 Hz Ambient temperature: 40 ° C
23 Speed: 1500 1/min Altitude at site: 1000 m
24
Technical data
27 Efficiency: see technical data sheet attached
28 Rated load at cos phi = 0.8: 96.20
29 Rated load at cos phi = 1: 97.00
30 Efficiency tolerance: acc. to VDE 0530, EN 60034
31 Reactances, time constants: see technical data sheet attached
32 Overspeed: 1,2 x rated speed for 2 min
33
Operating voltage range:
Zone A according IEC 60034-1 (dU = +/-5%, df = +/-2%) +/- 10% at no load for synchronisation, short term operation only
34 Operating frequency range: view line 33
35 Parallel operation: Island mode with identical generators in parallel
36 Overload capability: 10 % for 1 h every 12 hours or 50 % for 30 sec.
37 3-phas. sustained short circuit current: 3 x rated current for max. 10 sec.
53
Design details, general
54 Design form: IMB3 / IM 100x IM 1001
55 AvK project drawing:
57 Center height: 630 mm
59 Type of prime mover / Manufacturer and name of prime mover:
Diesel engine /
62 Shaft end / -flange (DE): cylindrical shaft end
63 Rotation facing DE: clockwise
64 Surface treatment: Standard primer
65 Dynamic balancing: with half key at shaft end
70
Enclosure, Cooler
71 Enclosure alternator: IP23
72 Enclosure terminal box: IP54
73 Cooling type: IC 01 - Open-circuit ventilation
Projekt checklist
Document: Revision: J dated 17.09.2004 7_2f04jE.xls Cummins Generator Technologies Germany GmbH 3 / 3
FM 7.2-4
Order specification for AvK-Alternators
-technical-
77 Coolant: Ambient Air
98
Bearing arrangement + Lubrication
99 Bearing Design: Anti-Friction bearing
100 Calculated Lifetime: about 30.000 operating hours
101 Protection against shaft currents: Not insulated,
116
Terminal box + Accessories, Current transformers
117 Location main terminal box (seen on DE): Standard terminal box top
119 Cable entry:
121 Cable gland plate: Undrilled gland plate aluminium
122 Details, quantity + diameter of cables: Each phase: Cable qty. unknown; Type unknown; ODM unknown N point: Cable qty. unknown; Type unknown; ODM unknown
123 Star point arrangement: 4 terminals, starpoint connected in terminal box
141
Voltage regulation system
142 Voltage regulator: DECS 100 Regulator function(s): VAR regulation Voltage matching Overexcitation limiter Underexcitation limiter Black Start Capability
148 Power supply of voltage regulator:: PMG
149 Regulator location:
154
Instrumentation
155 Temperature detection stator windings: 6 PT100
156 Bearing temperature detection NDE-side: Single PT100
157 Bearing temperature detection DE-side: Single PT100
159 PT 100 design / connection: Standard design in 2-wire connection
162 Anti-condensation heater built-in: Supply voltage 230 V, 1-phase, 50/60 Hz, AC/DC Power required 500 W
168
Works Tests
169 CGT Test: first generator: Repeat Test acc. to AvK Specification ING-PS-0005; all other generators (if applicable):
170 Additional tests: not applicable
171 Works test witnessed by client: not applicable
174
Documentation / Dates:
175 Dimensional drawing: ca. 4 weeks after placement of order
177 Shaft drawing with moment of inertia: ca. 4 weeks after placement of order
178 Connection/terminal plan: ca. 6 weeks after placement of order
179 Drawings as DXF-File No
180 Operating instructions, Spare part lists: 2 weeks after works test
171 Test reports and Certificates: 2 weeks after works test
183 Number copies and language of documentation: 3 x English
202
Additional details
203 Voltage matching: For Decs 100 and 200 the ratio of the sensing VTs for generator and busbar voltage can be different.