availability based tariff meter
DESCRIPTION
Availability Based Tariff Meter. ER300P. LARSEN & TOUBRO LIMITED. Features of ABT Meter. The Meter measures Active/Reactive energy on 3 phase, 4 wire principle, - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: Availability Based Tariff Meter](https://reader036.vdocuments.us/reader036/viewer/2022062409/56814758550346895db494ef/html5/thumbnails/1.jpg)
LARSEN & TOUBRO LIMITEDLARSEN & TOUBRO LIMITED
Availability Based Availability Based Tariff MeterTariff Meter
![Page 2: Availability Based Tariff Meter](https://reader036.vdocuments.us/reader036/viewer/2022062409/56814758550346895db494ef/html5/thumbnails/2.jpg)
Features of ABT MeterFeatures of ABT Meter• The Meter measures Active/Reactive energy on 3
phase, 4 wire principle,• Computes the active energy import /export from the
substation bus bars during each successive 15 minutes block and stores it in its Memory.
• Integrates the reactive energy algebraically into two separate registers,
A) One for the period for which the average RMS
voltage is 103% or higher (High VARh), B) The other for the period for which the average RMS voltage is below 97.0% or lower (Low VARH).
![Page 3: Availability Based Tariff Meter](https://reader036.vdocuments.us/reader036/viewer/2022062409/56814758550346895db494ef/html5/thumbnails/3.jpg)
Features of ABT MeterFeatures of ABT Meter• Average frequency for each successive 15-min
block, as a 2-digit code Original Frequency = 49 + 0.02*2-digit code.
• Net Wh transmitted during each successive 15-minute block, upto second decimal, with plus/minus sign
• Cumulative Wh transmitted at each midnight, in six digits including one decimal
• Cumulative VARh transmitted for voltage high condition, at each midnight in six digits including one decimal
![Page 4: Availability Based Tariff Meter](https://reader036.vdocuments.us/reader036/viewer/2022062409/56814758550346895db494ef/html5/thumbnails/4.jpg)
Features of ABT MeterFeatures of ABT Meter
• Cumulative VARh transmittal for voltage low condition, at each midnight, in six digits including one decimal
• Date and time blocks of failure of VT supply on any phase, as a star (*) mark
• The meters shall store all the listed data in their memories for a period of ten days
• Battery back-up for data viewing display.Battery back-up for data viewing display.
![Page 5: Availability Based Tariff Meter](https://reader036.vdocuments.us/reader036/viewer/2022062409/56814758550346895db494ef/html5/thumbnails/5.jpg)
Basic Technical SpecificationsBasic Technical Specifications
• . Accuracy Class : 0.2• INTERFACE : WITH RS485
• Reference Voltage(Vref) : 110V.(P-P) • Rated Current ( Ib) : 5A or 1A.• Operating Voltage :+20% to -30% of
Vref.• Operating Current : 0.2% to 200% of Ib
![Page 6: Availability Based Tariff Meter](https://reader036.vdocuments.us/reader036/viewer/2022062409/56814758550346895db494ef/html5/thumbnails/6.jpg)
Display ListDisplay List i) Meter Serial No :NP5001A
ii) Date (year month day) :081112 d iii) Time ( hour min. sec. ) :151030 t iv) Cumulative Wh reading :12345.6 C v) Average frequency of the last block :49.89 F vi) Net Wh transmitted in last block :28.75 E vii) Average % voltage :99.2 U viii) Reactive power (VAR) :106.5 r ix) Voltage - high VARh register reading :01234.5 H x) Voltage - low VARh register reading :00123.4 L xi) Low battery indication
![Page 7: Availability Based Tariff Meter](https://reader036.vdocuments.us/reader036/viewer/2022062409/56814758550346895db494ef/html5/thumbnails/7.jpg)
LARSEN & TOUBRO LIMITEDLARSEN & TOUBRO LIMITED
Data Collecting Data Collecting DeviceDevice
![Page 8: Availability Based Tariff Meter](https://reader036.vdocuments.us/reader036/viewer/2022062409/56814758550346895db494ef/html5/thumbnails/8.jpg)
DCD Main WindowDCD Main Window
(D) COLL. SELECTED DATA
(U) PC COMMUNICATION
(P) PROGRAMMING MODE
(O) MEMORY STATUS CHECK
(R) ACCURACY
![Page 9: Availability Based Tariff Meter](https://reader036.vdocuments.us/reader036/viewer/2022062409/56814758550346895db494ef/html5/thumbnails/9.jpg)
Data Collecting DeviceData Collecting Device
1. Press (D) for Collecting of Meter Dada
2. Press (U) for damping the data from DCD to PC
3. Press (P) for enter into Programming Mode i.e only for time adjustment for 1 minute
4. Press (O) for Memory status check
![Page 10: Availability Based Tariff Meter](https://reader036.vdocuments.us/reader036/viewer/2022062409/56814758550346895db494ef/html5/thumbnails/10.jpg)
Time adjustment through DCDTime adjustment through DCD
After connecting the Optical Port to the meter and DCD following step to be done for Time adjustment.
1. Press “P” in DCD to enter in Programming mode.
2. Enter the Password: XMISSION
![Page 11: Availability Based Tariff Meter](https://reader036.vdocuments.us/reader036/viewer/2022062409/56814758550346895db494ef/html5/thumbnails/11.jpg)
Time adjustment through DCDTime adjustment through DCD
3. Press Enter after typing the “XMISSION” in DCD
4. Following Manu will come after pressing enter in DCD :
(A) Advance
(R) Retard
(X) back to Manu
![Page 12: Availability Based Tariff Meter](https://reader036.vdocuments.us/reader036/viewer/2022062409/56814758550346895db494ef/html5/thumbnails/12.jpg)
Time adjustment through DCDTime adjustment through DCD
5. i) Press “A” if the meter time is slow
ii) Press “R” if the meter time is fast
N.B :
i) Program/ time adjustment (only for 1 minute) can be done one in a week.
ii) Time taken to adjustment one min. 1 hrs. 30 min i.e. 6 Blocks
iii) Time adjustment can be done only on power On conditions
![Page 13: Availability Based Tariff Meter](https://reader036.vdocuments.us/reader036/viewer/2022062409/56814758550346895db494ef/html5/thumbnails/13.jpg)
Do’s & Don'ts with DCDDo’s & Don'ts with DCD
1. Don’t keep the DCD in Suspended mode
2. To save the battery life switch off the DCD properly
3. DCD battery should be charged at least twice in a week
4. Charging time is 3 hours
![Page 14: Availability Based Tariff Meter](https://reader036.vdocuments.us/reader036/viewer/2022062409/56814758550346895db494ef/html5/thumbnails/14.jpg)
RS485 Network
• Serial Port, Local Area Communication
– Two-wire, multidropping– Uncomplicated hardware– No distance limitation within a premises
![Page 15: Availability Based Tariff Meter](https://reader036.vdocuments.us/reader036/viewer/2022062409/56814758550346895db494ef/html5/thumbnails/15.jpg)
Hardware Required• We have used IEC 1107 protocol for RS 485 communication. • Recommended hardware is mentioned below :
1. Twisted pair with foil shielding and a drain wireMake : Belden ( Product Code 9841/8162/9501) cost Rs. 49,000 per 305m or equivalent local cable cost Rs. 2,000 per 100m.Characteristic Impedance : 120 OhmsTwist/Feet : 10
2. RS 485 to RS 232 Converter Make : Moxa Model No : Transio A53
3. PSTN Modem : Used for data transfer on PSTN Line from S/S to LDC
Make : Multitech 33.6 Kbps Model No : MT2834ZDXB
![Page 16: Availability Based Tariff Meter](https://reader036.vdocuments.us/reader036/viewer/2022062409/56814758550346895db494ef/html5/thumbnails/16.jpg)
The System
Collection PointCollection Point
RS232RS232
RS232 to RS232 to RS485 RS485 ConverterConverter
MeterMeter
D+D+
D-D-