automatic transfer switchesresources.kohler.com › power › kohler › industrial › pdf ›...

48
Models: KSS/KSP 40 to 1000 Amperes TP-6834 4/14 Operation and Installation Automatic Transfer Switches

Upload: others

Post on 27-Jun-2020

14 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

Models:

KSS/KSP40 to 1000 Amperes

TP-6834 4/14

Operation andInstallation

Automatic Transfer Switches

Page 2: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

Product Identification Information

Product identification numbers determine service parts.Record the product identification numbers in the spacesbelow immediately after unpacking the products so thatthe numbers are readily available for future reference.Record field-installed kit numbers after installing thekits.

Transfer Switch Identification Numbers

Record the product identification numbers from thetransfer switch nameplate.

Model Designation

Serial Number

Accessories

- Alarm Board

- Battery Module

- Controller Disconnect Switch

- Digital Meter

- Heater

- I/O Module, Standard (max. 4) qty:

- I/O Module, High Power (max. 4) qty:

- Load Shed

- Line-Neutral Monitoring

- Seismic Certification

- Supervised Transfer Switch

- Surge Protection Device (SPD)

-

-

-

-

-

-

Controller Identification

Record the controller description from the generator setoperation manual, spec sheet, or sales invoice.

Controller Description

Page 3: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

Table of Contents

TP-6834 4/14 Table of Contents 3

Safety Precautions and Instructions 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Introduction 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .List of Related Materials 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Service Assistance 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Section 1 Product Description 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.1 Purpose 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2 Nameplate 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.3 Model Designation 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Section 2 Installation 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.1 Introduction 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.2 Receipt of Unit 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2.1 Inspection 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.2.2 Lifting 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.2.3 Storage 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.2.4 Unpacking 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3 Installation 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.4 Seismic Certification 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.5 Manual Operation 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.1 Manual Operation, Model KSS Standard-Transition Switches 14. . . . . . . .2.5.2 Manual Operation, Model KSP Programmed-Transition Switches 16. . . .

2.6 Controller Connections 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.6.1 Controller Input and Output Connections 18. . . . . . . . . . . . . . . . . . . . . . . . . .2.6.2 Harness Connection 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.6.3 Controller Ground 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.7 Electrical Wiring 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.7.1 Source and Load Connections 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.7.2 Engine Start Connection 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.7.3 Auxiliary Contacts 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.8 Communication and Accessory Connections 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.9 Functional Tests 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Section 3 Communication and Accessory Connections 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.1 Introduction 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2 Communication Connections 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.2.1 USB Port SiteTech Connection 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2.2 Modbus Connection 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2.3 Ethernet Connection 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3 Accessory Modules (MPAC 1200 only) 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.3.1 Accessory Module Mounting 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.3.2 Input/Output (I/O) Modules 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.3.3 External Battery Supply Module (EBSM) 31. . . . . . . . . . . . . . . . . . . . . . . . . .3.3.4 Alarm Module 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4 Heater 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.5 Load Shed (Forced Transfer to OFF, KSP with MPAC 1200 only) 36. . . . . . . . . . . . .3.6 Programmable Exerciser 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.7 Other Accessories 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 4: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

Table of Contents, continued

TP-6834 4/14Table of Contents4

Section 4 Functional Tests and Setup 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.1 Introduction 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.2 Manual Operation Test 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.3 Voltage Check 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.4 Automatic Operation Test 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.5 System Setup 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.6 Exerciser Setup 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.7 User Interface Cover 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.8 Startup Notification 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Appendix A Abbreviations 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 5: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 5Safety Precautions and Instructions

Safety Precautions and Instructions

IMPORTANTSAFETY INSTRUCTIONS.Electromechanical equipment,including generator sets, transferswitches, switchgear, and accessories,can cause bodily harm and poselife-threatening danger whenimproperly installed, operated, ormaintained. To prevent accidents beaware of potential dangers and actsafely. Read and follow all safetyprecautions and instructions. SAVETHESE INSTRUCTIONS.

Thismanual has several types of safetyprecautions and instructions: Danger,Warning, Caution, and Notice.

DANGER

Danger indicates the presence of ahazard that will cause severepersonal injury, death, orsubstantialproperty damage.

WARNING

Warning indicates the presence of ahazard that can cause severepersonal injury, death, orsubstantialproperty damage.

CAUTION

Caution indicates the presence of ahazard that will or can cause minorpersonal injury or property damage.

NOTICENotice communicates installation,operation, or maintenance informationthat is safety related but not hazardrelated.

Safety decals affixed to the equipmentin prominent places alert the operatoror service technician to potentialhazards and explain how to act safely.The decals are shown throughout thispublication to improve operatorrecognition. Replace missing ordamaged decals.

Accidental Starting

Accidental starting.Can cause severe injury or death.

Disconnect the battery cables beforeworking on the generator set.Remove the negative (--) lead firstwhen disconnecting the battery.Reconnect the negative (--) lead lastwhen reconnecting the battery.

WARNING

Disabling the generator set.Accidental starting can causesevere injury or death. Beforeworking on the generator set orconnected equipment, disable thegenerator set as follows: (1) Move thegenerator set master switch to the OFFposition. (2) Disconnect the power tothe battery charger. (3) Remove thebattery cables, negative (--) lead first.Reconnect the negative (--) lead lastwhen reconnecting the battery. Followthese precautions to prevent starting ofthe generator set by an automatictransfer switch, remote start/stopswitch, or engine start command fromaremote computer.

(Decision-Makerr 3+ and 550Generator Set Controllers)

Disabling the generator set.Accidental starting can causesevere injury or death. Beforeworking on the generator set orequipment connected to the set,disable the generator set as follows:(1) Press the generator set off/resetbutton to shut down the generator set.(2) Disconnect the power to the batterycharger, if equipped. (3) Remove thebattery cables, negative (--) lead first.Reconnect the negative (--) lead lastwhen reconnecting the battery. Followthese precautions to prevent thestarting of the generator set by theremote start/stop switch.

(RDC, DC, RDC2, DC2,Decision-Makerr 3000, 3500 and6000 Generator Set Controllers)

Hazardous Voltage/Moving Parts

Hazardous voltage.Will cause severe injury or death.

Disconnect all power sources beforeopening the enclosure.

DANGER

Hazardous voltage.Will cause severe injury or death.

Only authorized personnel shouldopen the enclosure.

DANGER

Grounding electrical equipment.Hazardous voltage can causesevere injury or death. Electrocutionis possible whenever electricity ispresent. Ensure you comply with allapplicable codes and standards.Electrically ground the generator set,transfer switch, and related equipmentand electrical circuits. Turn off themaincircuit breakers of all power sourcesbefore servicing the equipment. Nevercontact electrical leads or applianceswhen standing in water or on wetground because these conditionsincrease the risk of electrocution.

Short circuits. Hazardousvoltage/current can cause severeinjury or death. Short circuits cancause bodily injury and/or equipmentdamage. Do not contact electricalconnections with tools or jewelry whilemaking adjustments or repairs.Remove all jewelry before servicing theequipment.

Making line or auxiliaryconnections. Hazardous voltagecan cause severe injury or death. Toprevent electrical shock deenergize thenormal power source before makingany line or auxiliary connections.

Page 6: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/146 Safety Precautions and Instructions

Servicing the transfer switch.Hazardous voltage can causesevere injuryor death. Deenergizeallpower sources before servicing. Turnoff the main circuit breakers of alltransfer switch power sources anddisable all generator sets as follows:(1) Move all generator set mastercontroller switches to theOFFposition.(2) Disconnect power to all batterychargers. (3) Disconnect all batterycables, negative (--) leads first.Reconnect negative (--) leads lastwhenreconnecting the battery cables afterservicing. Follow these precautions toprevent the starting of generator setsby an automatic transfer switch, remotestart/stop switch, or engine startcommand from a remote computer.Before servicing any componentsinside the enclosure: (1) Remove alljewelry. (2) Stand on a dry, approvedelectrically insulated mat. (3) Testcircuits with a voltmeter to verify thatthey are deenergized.

(Decision-Makerr 3+ and 550Generator Set Controllers)

Servicing the transfer switch.Hazardous voltage can causesevere injuryor death. Deenergizeallpower sources before servicing. Turnoff the main circuit breakers of alltransfer switch power sources anddisable all generator sets as follows:(1) Press the generator set off/resetbutton to shut down the generator set.(2) Disconnect power to all batterychargers. (3) Disconnect all batterycables, negative (--) leads first.Reconnect negative (--) leads lastwhenreconnecting the battery cables afterservicing. Follow these precautions toprevent the starting of generator setsby an automatic transfer switch, remotestart/stop switch, or engine startcommand from a remote computer.Before servicing any componentsinside the enclosure: (1) Remove alljewelry. (2) Stand on a dry, approvedelectrically insulated mat. (3) Testcircuits with a voltmeter to verify thatthey are deenergized.

(RDC, DC, RDC2, DC2,Decision-Makerr 3000, 3500 and6000 Generator Set Controllers)

Testing live electrical circuits.Hazardous voltage or current cancause severe injury or death. Havetrained and qualified personnel takediagnostic measurements of livecircuits. Use adequately rated testequipment with electrically insulatedprobes and follow the instructions of thetest equipment manufacturer whenperforming voltage tests. Observe thefollowing precautions when performingvoltage tests: (1) Remove all jewelry.(2) Standonadry, approvedelectricallyinsulated mat. (3) Do not touch theenclosure or components inside theenclosure. (4) Be prepared for thesystem to operate automatically.(600 volts and under)

Airborne particles.Can cause severe injury orblindness.

Wear protective goggles and clothingwhen using power tools, hand tools,or compressed air.

WARNING

Heavy Equipment

Unbalanced weight.Improper lifting can cause severeinjury or death and equipmentdamage.

Use adequate lifting capacity.Never leave the transfer switchstanding upright unless it is securelybolted in place or stabilized.

WARNING

NoticeNOTICE

Improper operator handle usage.Use the manual operator handle on thetransfer switch for maintenancepurposes only. Return the transferswitch to the normal position. Removethe manual operator handle, if used,and store it in the place provided on thetransfer switch when service iscompleted.

NOTICEForeign material contamination.Cover the transfer switch duringinstallation to keep dirt, grit, metal drillchips, and other debris out of thecomponents. Cover the solenoidmechanism during installation. Afterinstallation, use the manual operatinghandle to cycle the contactor to verifythat it operates freely. Do not use ascrewdriver to force the contactormechanism.

NOTICEElectrostatic discharge damage.Electrostatic discharge (ESD)damages electronic circuit boards.Prevent electrostatic dischargedamage by wearing an approvedgrounding wrist strap when handlingelectronic circuit boards or integratedcircuits. An approved grounding wriststrap provides a high resistance (about1 megohm), not a direct short, toground.

Page 7: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 7Introduction

Introduction

This manual provides operation and installationinstructions for the followingKohlerrAutomaticTransferSwitches (ATS):

D Model KSS standard-transition specific breaker ATSequipped with the Decision-Makerr MPAC 750controller.

D Model KSS standard-transition specific breaker ATSequipped with the Decision-Makerr MPAC 1200controller.

D Model KSP programmed-transition specific breakerATS equipped with the Decision-MakerrMPAC 1200 controller.

A separate manual provided with the transfer switchcovers the transfer switch controller operation. See Listof Related Materials for the document part number.

Information in this publication represents data availableat the time of print. Kohler Co. reserves the right tochange this literature and the products representedwithout notice and without any obligation or liabilitywhatsoever.

Read this manual and carefully follow all proceduresand safety precautions to ensure proper equipmentoperation and to avoid bodily injury. Readand follow theSafety Precautions and Instructions section at thebeginning of this manual. Keep this manual with theequipment for future reference.

The equipment service requirements are very importantto safe and efficient operation. Inspect parts often andperform required service at the prescribed intervals.See the controller Operation manual for the serviceschedule. Obtain service from an authorized servicedistributor/ dealer to keep equipment in top condition.

List of Related Materials

A separate manual covers the transfer switch controllerand related accessories. Separate manuals containservice and parts information for transfer switch powerswitching devices and electrical controls.

The following table lists the part numbers for relatedliterature.

Literature Item Part Number

Specification Sheet, Decision-Makerr MPAC750 Controller G11-126

Specification Sheet, Decision-Makerr MPAC1200 Controller G11-127

Specification Sheet, Model KSS/KSP G11-130

Operation Manual, Decision-MakerrMPAC 750 Controller TP-6865

Operation Manual, Decision-MakerrMPAC 1200 Controller TP-6866

Parts Catalog, Transfer Switch and Controller TP-6433

Service Manual, Model KSS/KSP/KGS/KGP TP-6921

Page 8: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/148 Service Assistance

Service Assistance

For professional advice on generator powerrequirementsandconscientiousservice, pleasecontactyour nearest Kohler distributor or dealer.

D Consult the Yellow Pages under the headingGenerators—Electric.

D Visit the Kohler Power Systems website atKOHLERPower.com.

D Lookat the labels and stickers on yourKohler productor review the appropriate literature or documentsincluded with the product.

D Call toll free in the US and Canada 1-800-544-2444.

D Outside theUSandCanada, call the nearest regionaloffice.

Headquarters Europe, Middle East, Africa(EMEA)Kohler Power Systems Netherlands B.V.Kristallaan 14761 ZC ZevenbergenThe NetherlandsPhone: (31) 168 331630Fax: (31) 168 331631

Asia PacificPower Systems Asia Pacific Regional OfficeSingapore, Republic of SingaporePhone: (65) 6264-6422Fax: (65) 6264-6455

ChinaNorth China Regional Office, BeijingPhone: (86) 10 6518 7950

(86) 10 6518 7951(86) 10 6518 7952

Fax: (86) 10 6518 7955

East China Regional Office, ShanghaiPhone: (86) 21 6288 0500Fax: (86) 21 6288 0550

India, Bangladesh, Sri LankaIndia Regional OfficeBangalore, IndiaPhone: (91) 80 3366208

(91) 80 3366231Fax: (91) 80 3315972

Japan, KoreaNorth Asia Regional OfficeTokyo, JapanPhone: (813) 3440-4515Fax: (813) 3440-2727

Latin AmericaLatin America Regional OfficeLakeland, Florida, USAPhone: (863) 619-7568Fax: (863) 701-7131

Page 9: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 9Section 1 Product Description

Section 1 Product Description

1.1 Purpose

An automatic transfer switch (ATS) transfers electricalloads from a normal (preferred) source of electricalpower to an emergency (standby) source when thenormal source falls outside the acceptable electricalparameters.

When the normal (preferred) source fails, the ATSsignals the emergency (standby) source generator setto start. When theemergency (standby) source reachesacceptable levels and stabilizes, the ATS transfers theload from the normal (preferred) source to theemergency (standby) source. The ATS continuouslymonitors the normal (preferred) source and transfersthe load back when the normal (preferred) sourcereturnsandstabilizes. After transferring the loadback tothe normal (preferred) source, the ATS removes thegenerator start signal, allowing the generator set to shutdown.

Figure 1-2 shows a typical installation block diagram.

Figure 1-1 Automatic Transfer Switch

PowerSwitchingDevice

To Load

Automatic Transfer Switch

ElectricalControls

Normal(Utility)Power

Emergency(Generator)Power

Generator

Start Generator

TS-003

Figure 1-2 Typical ATS Block Diagram

1.2 Nameplate

A nameplate attached to the controller cover on theinside of the enclosure door includes a modeldesignation, a serial number, ratings, and otherinformation about the transfer switch. See Figure 1-3.The serial number is also shown on a label inside thetransfer switch enclosure.

Copy the model designation, serial number, andaccessory information from thenameplate to thespacesprovided in the Product Identification Informationsection inside the front cover of thismanual for usewhenrequesting service or parts.

GM21291

Figure 1-3 Typical Transfer Switch Nameplate

Page 10: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1410 Section 1 Product Description

1.3 Model Designation

Model Controls Voltage Poles Enclosure Current Rating ConnectionsMechanism Transition

Record the transfer switch model designation in the boxes. The transfer switch model designation definescharacteristics and ratings as explained below.

Sample Model Designation: KSS-JCNA-0100S

Model

K: Kohler

Mechanism

S: Standard (Specific-Breaker)

Transition

S: Standard

P: Programmed

Controller

A: Decision-Makerr MPAC 1200, Automatic

B: Decision-Makerr MPAC 1200, Non-Automatic

J: Decision-Makerr MPAC 750, Automatic

Voltage/Frequency

C: 208 Volts /60 Hz J: 416 Volts /50 Hz

D: 220 Volts /50 Hz K: 440 Volts /60 Hz

F: 240 Volts /60 Hz M: 480 Volts /60 Hz

G: 380 Volts /50 Hz P: 380 Volts /60 Hz

H: 400 Volts /50 Hz R: 220 Volts /60 Hz

Number of Poles/Wires

N: 2 Poles /3 Wires, Solid Neutral

T: 3 Poles /4 Wires, Solid Neutral

V: 4 Poles /4 Wires, Switched Neutral

Enclosure

A: NEMA 1 D: NEMA 4

B: NEMA 12 F: NEMA 4X

C: NEMA 3R G: Open Unit

Current, Amps

0040 0200 600

0080 0225 800

0100 0260 1000

0150 0400

Connections

S: Standard

Note: Some selections are not available for every model.Contact your Kohler distributor for availability.

Page 11: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 11Section 2 Installation

Section 2 Installation

2.1 Introduction

Kohlerr transfer switches are shipped factory-wired,factory-tested, and ready for installation. Have theequipment installed only by trained and qualifiedpersonnel. Verify that the installation complies withapplicable codes and standards. Installation includesthe following steps:

D Unpack and inspect the transfer switch upon receipt.

D Verify that the transfer switch voltage and frequencyratings match the voltages and frequencies of thesources.

D Install the transfer switch.

D Check the manual operation.

D Connect the controller harness and ground lead.

D Connect the generator set engine start leads.

D Connect the normal power source (utility),emergency power source (generator set), and loadcircuits.

D Connect accessories, if provided.

D Check voltages and operation.

Protect the switch against damage before and duringinstallation.

Note: An approved protective device such as amolded-case circuit breaker or fused disconnectswitch MUST be installed on both sources ofincoming power for circuit protection and used asa disconnect device.

The functional tests in Section 4 are a necessary part ofthe installation. Be sure to perform the functional tests,which include voltage checks and operation tests,before putting the transfer switch into service.

2.2 Receipt of Unit

2.2.1 Inspection

At the time of delivery, inspect the packaging and thetransfer switch for signs of shipping damage. Unpackthe transfer switch as soon as possible and inspect theexterior and interior for shipping damage. If damageand/or rough handling is evident, immediately file adamage claim with the transportation company.

2.2.2 Lifting

Unbalanced weight.Improper lifting can cause severeinjury or death and equipmentdamage.

Use adequate lifting capacity.Never leave the transfer switchstanding upright unless it is securelybolted in place or stabilized.

WARNING

See Figure 2-1 or the dimension drawing for theapproximate weight of the transfer switch. Use aspreader bar to lift the transfer switch. Attach the baronly to the enclosure’s mounting holes or liftingbrackets; do not lift the unit any other way. Close andlatch the enclosure door before moving the unit.

Model Amps

Weight kg (lb.)

2-Pole 3-Pole 4-Pole

KSS

40--225 28 (62) 30 (65) 31 (68)

260--400 52 (115) 56 (123) 59 (131)

600 179 (395) 183 (403) 186 ( 410)

800 N/A 226 (498) 236 (520)

1000 N/A 231 (509) 241 ( 531)

KSP

100--200 52 (115) 56 (123) 59 (131)

400 52 (115) 56 (123) 59 (131)

600 179 (395) 183 (403) 186 ( 410)

Figure 2-1 Approximate Transfer Switch Weights,NEMA Type 1 and 3R Enclosures

Page 12: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1412 Section 2 Installation

2.2.3 Storage

Store the transfer switch in its protective packing untilfinal installation. Protect the transfer switch at all timesfrommoisture, construction grit, andmetal chips. Avoidstorage in low-temperature and high-humidity areaswhere moisture could condense on the unit. SeeFigure 2-2 for acceptable storage temperatures.

Item Specification

Storage temperature --40C to 70C (--40F to 158F)

Operating temperature --20C to 85C (--4F to 185F)

Humidity 5% to 95% noncondensing

Figure 2-2 Environmental Specifications

2.2.4 Unpacking

Allow the equipment to warm to room temperature for atleast 24 hours before unpacking to preventcondensation on the electrical apparatus. Use carewhen unpacking to avoid damaging transfer switchcomponents. Remove dirt and packing material thatmayhaveaccumulated in the transfer switchor anyof itscomponents.

Note: Do not use compressed air to clean the switch.Cleaning with compressed air can cause debristo lodge in the components and damage theswitch.

2.3 Installation

NOTICEForeign material contamination. Cover the transfer switchduring installation to keep dirt, grit, metal drill chips, and otherdebris out of the components. Cover the solenoidmechanismduring installation. After installation, use themanual operatinghandle to cycle the contactor to verify that it operates freely.Do not use a screwdriver to force the contactor mechanism.

Hardware damage. The transfer switch may use bothAmericanStandard andmetric hardware. Use the correct sizetools to prevent rounding of the bolt heads and nuts.

Check the system voltage and frequency. Comparethe voltage and frequency shown on the transfer switchnameplate to the source voltage and frequency. Do notinstall the transfer switch if the system voltage andfrequency are different from the nominal normal (utility)source voltage and frequency or the nominalemergency source voltage and frequency shown on thegenerator set nameplate.

Plan the installation. Use the dimensions given on theenclosure dimension (ADV) drawings. Select amounting site that complies with local electrical coderestrictions for the enclosure type. Mount the transferswitch as close to the load and power sources aspossible. Allow adequate space to fully open theenclosure and to service the switch. Provide cablebending space and clearance to live metal parts.

Outdoor installations. Transfer switches withNEMA 3R, 4, or 4X enclosures can be installedoutdoors. In locations with very high ambienttemperatures, installation in a shaded area or a locationwith the enclosure door facing away from direct sunlightis recommended.

Prepare the foundation. Ensure that the supportingfoundation for the enclosure is level and straight. Forbottom cable entry, if used, install conduit stubs in thefoundation. Refer to the enclosure dimension drawingfor the conduit stub locations. When pouring a concretefloor, use interlocking conduit spacer caps or a wood ormetal template to maintain proper conduit alignment.

Installation of seismically certified transferswitches. See Section 2.4 and the transfer switchdimension (ADV) drawings for additional installationrequirements.

Install the ATS. Mount 40- through 400-amp transferswitches to a wall or other rigid vertical supportingstructure. Clearance holes through the back of eachenclosure are provided for mounting. Level theenclosure and use shims if needed to plumb theenclosure. Verify that the door hinges are vertical toavoid distortion of the enclosure or door.

Bolt 600- through 1000-amp automatic transferswitches directly to floor mounting pads. Use shims ifneeded to plumb the enclosure. Verify that the doorhinges are vertical to avoid distortion of the enclosure ordoor.

Page 13: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 13Section 2 Installation

2.4 Seismic Certification

Automatic transfer switches with seismic certificationmust be installed according to the instructions in thissection. Also refer to the Certificate of Compliance andthe installation drawings for the transfer switch.

Abbreviations:

ACI: American Concrete Institute

IBC: International Building Coder

SDS: Design spectral response acceleration at shortperiod, as determined in Section 1615.1.3 ofthe IBC

Rp: Equipment response modification factor

Ip: Equipment importance factor

ap: In-structure equipment amplification factor

Refer to the International Building Coder for moreinformation.

General Seismic Installation Notes:

1. Anchors used for seismic installation must bedesigned in accordance with ACI 355.2--04.Suggested manufacturers include Simpson,Ramset, and Hilti.

2. Anchors must be installed to a minimumembedment of 8x the anchor diameter.

3. Anchors must be installed in minimum 4000 psicompressive strength normal weight concrete.Concrete aggregate must comply with ASTMC33.Installation in structural lightweight concrete is notpermitted unless otherwise approved by thestructural engineer of record.

4. Anchors must be installed to the required torquespecified by the anchor manufacturer to obtainmaximum loading.

5. Anchors must be installed with spacing and edgedistance required to obtain maximum load unlessotherwise approved by the structural engineer ofrecord.

6. Anchors used for seismic installation must bedesigned and rated to resist seismic loading inaccordancewith ACI 355.2--04 and documented in

a report by a reputable testing agency (ex. theEvaluation Service Report issued by theInternational Code Council).

7. Wide washers must be installed at each anchorlocation between the anchor head and equipmentfor tension load distribution. See applicable ADVdrawing for specificanchor informationandwasherdimensions.

8. Equipment installed on a housekeeping padrequires the housekeeping pad thickness to be atleast 1.5x the anchor embedment depth.

9. All housekeeping pads must be seismicallydesigned and dowelled or cast into the buildingstructure as approved by the structural engineer ofrecord.

10. Rebar reinforcing in the housekeeping pad isrequired for all installations.

11. Rebar reinforcement in concretemust be designedin accordance with ACI 318--05.

12. Wall mounted equipment must be installed to arebar reinforced structural concrete wall that isseismically designed and approved by theengineer of record to resist the added seismicloads fromcomponents being anchored to thewall.

13. Floor mounted equipment (with or without ahousekeeping pad) must be installed to a rebarreinforced structural concrete floor that isseismically designed and approved by theengineer of record to resist the added seismicloads from components being anchored to thefloor.

14. When installing to a floor or wall, rebar interferencemust be considered.

15. Equipment attached to any structural floor otherthan those constructed of structural concrete anddesigned to accept the seismic loads from themounted equipment are beyond the scope of thisspecification.

16. Installation to light-weight concrete over steeldecking is beyond the scope of this specification.

17. Installation to concrete block or cinder block wallsis beyond the scope of this specification.

Page 14: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1414 Section 2 Installation

2.5 Manual Operation

Hazardous voltage.Will cause severe injury or death.

Disconnect all power sources beforeopening the enclosure.

DANGER

Servicing the transfer switch. Hazardous voltage cancause severe injury or death. Deenergize all power sourcesbefore servicing. Turn off the main circuit breakers of alltransfer switch power sources and disable all generator setsas follows: (1) Press the generator set off/reset button to shutdown the generator set. (2) Disconnect power to all batterychargers. (3) Disconnect all battery cables, negative (--) leadsfirst. Reconnect negative (--) leads last when reconnecting thebattery cables after servicing. Follow these precautions toprevent the starting of generator sets by an automatic transferswitch, remote start/stop switch, or engine start commandfrom a remote computer. Before servicing any componentsinside the enclosure: (1) Remove all jewelry. (2) Stand on adry, approved electrically insulatedmat. (3) Test circuits with avoltmeter to verify that they are deenergized.

NOTICEImproper operator handle usage. Use the manual operatorhandle on the transfer switch for maintenance purposes only.Return the transfer switch to the normal position. Remove themanual operator handle, if used, and store it in the placeprovided on the transfer switch when service is completed.

A manual operation handle is provided with the transferswitch for maintenance purposes only. Use the manualoperation handle to check the manual operation beforeenergizing the transfer switch. Use the followingmanualoperation procedures to verify that the contactoroperates smoothly without binding.

Note: A contactor in normal and serviceable conditionoperates smoothly without binding. Do not placethe transfer switch into service if the contactordoes not operate smoothly; contact anauthorized distributor/dealer to service thecontactor.

2.5.1 Manual Operation, Model KSSStandard-Transition Switches

Note: Never use themaintenancehandle to transfer theload with the power connected. Disconnect bothpower sources before manually operating theswitch.

1. Disable the generator set to prevent starting anddisconnect all power sources before manuallyoperating the transfer switch.

2. Remove the maintenance handle from its storagelocation inside the enclosure. See Figure 2-3through Figure 2-5.

3. Attach the maintenance handle:

a. 40--600 Amp switches: Insert themaintenancehandle into the hole in the shaft on the left sideof the operator as shown in Figure 2-3 orFigure 2-4.

b. 800--1000 Amp switches: Slide themaintenance handle over the square shaft onthe left side of the operator as shown inFigure 2-5.

4. Move the maintenance handle up or down asshown in the corresponding figure to manuallyoperate the transfer switch. It should operatesmoothly without any binding. If it does not, checkfor shipping damage or construction debris.

5. Return the transfer switch to the Normal position.

6. Remove the maintenance handle and return it to thestorage location.

Page 15: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 15Section 2 Installation

1. Handle storage location2. Insert handle here for manual operation

1

tp6225

2

Figure 2-3 Manual Operation, 40--260 AmpStandard-Transition Switches

tp6225

1

2

1. Handle storage location2. Insert handle here for manual operation

Figure 2-4 Manual Operation, 400--600 AmpStandard-Transition Switches

2

tp6447

1. Handle storage location inside enclosure2. Shaft (attach handle here)3. Move maintenance handle down and release to manually operate

3

1

Figure 2-5 Manual Operation, 800--1000 Amp Standard-Transition Switches

Page 16: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1416 Section 2 Installation

2.5.2 Manual Operation, Model KSPProgrammed-Transition Switches

Note: Never use the manual operation handle totransfer the load with the power connected.Disconnect both power sources before manuallyoperating the switch.

1. Disable the generator set to prevent starting anddisconnect all power sources before manuallyoperating the transfer switch.

2. Check the contactor position, indicated by the Aand B position indicators. See Figure 2-6. Oneposition indicator will display ON to indicate thesource position. If both indicators display OFF, thetransfer switch is in the OFF position.

1

tp6225

1. Shaft (attach handle here)2. Trip button3. Select button4. Source 1 (A) position indicator (ON/OFF)5. Source 2 (B) position indicator (ON/OFF)

2

3

4

5

Figure 2-6 Manual Operation, Programmed-Transition Switches (handle not shown)

3. If the transfer switch is not in the OFF position, usea screwdriver or other tool to push the TRIP button.

See Figure 2-6. Check that both positionindicators display OFF.

4. Slide the manual operating handle (provided withthe switch) over the shaft on the left side of theswitch. See Figure 2-6.

5. Move the switch to theA (Source 1) or B (Source 2)position as follows:

a. To move the switch to position A (Source 1),move themanual operation handle up and thenrelease the handle. Verify that the A positionindicator displays ON.

b. To move the switch to position B (Source 2),use a screwdriver or other tool to push theSELECT button. Hold the SELECT button inand move the manual operation handle up andthen release the handle. Verify that the Bposition indicator displays ON.

Note: Always move the manual operation handleUP and then release it.

6. Remove the manual operation handle and store itin a convenient location.

6225

Move handle up andthen release.

Figure 2-7 Manual Operating Handle, Programmed-Transition Switches

Page 17: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 17Section 2 Installation

2.6 Controller Connections

Hazardous voltage.Will cause severe injury or death.

Disconnect all power sources beforeopening the enclosure.

DANGER

NOTICEElectrostatic discharge damage. Electrostatic discharge(ESD) damages electronic circuit boards. Preventelectrostatic discharge damage by wearing an approvedgrounding wrist strap when handling electronic circuit boardsor integrated circuits. An approved grounding wrist strapprovides a high resistance (about 1 megohm), not a directshort, to ground.

The controller is mounted in a plastic housing on theinside of the transfer switch enclosure door.

Figure 2-8 shows the locations of the connectors on thecontroller. It is not necessary to open the cover toaccess the Ethernet, Modbusr, and input/outputconnectors.

Opening the cover. If necessary, open the plastichousing by pushing up on the latch on the bottom of thecover and swinging the cover up and out. The cover ishinged at the top. Lift the cover off the hinges to removeit completely, if necessary.

Note: Always replace the cover before energizing thetransfer switch controls.

6

1. Standard input/output connection2. RS-485 connection TB23. Connection for optional current sensing kit4. Optional I/O board connection P16

5. Access openings to optional RJ-45 connector6. Latch7. Ground wire8. Contactor harness connection

5

GM85884

1

3

8

7

24

Figure 2-8 Controller

Modbus is a registered trademark of Schneider Electric.

Page 18: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1418 Section 2 Installation

2.6.1 Controller Input and OutputConnections

The controller provides connections for twoprogrammable inputs and two programmable outputs.See Figure 2-8 for the connector location.

Each input has a signal and a return connection. Theoutputs are C form contacts with ratings of500 mA@ 120 VAC. See Figure 2-10 for connections.Use #12--24 AWG wire and tighten the connections to0.5 Nm (4.4 in. lbs.).

See the transfer switch controller operation manual forinstructions to assign inputs and outputs.

Transfer switches equipped with the MPAC 750controller may also include the optional programmableexerciser. This accessory uses one input connection,which must be assigned to Remote Test. Refer to theinstructions provided with the exerciser kit for moreinformation.

Transfer switches equipped with the MPAC 1200controller can use optional input/output modules foradditional input and output connections. See Section3.3 for instructions.

Main Board I/O Specifications

Output contact type Isolated form C (SPDT)

Output contact rating 1 amp @ 30 VDC,500 mA @120 VAC

I/O terminals wire size #12--24 AWG

Figure 2-9 Main Board I/O Specifications

6866

Input 1A

Input 1BInput 2A

Input 2B

Output 1 NC

Output 1 C

Output 1 NO

Output 2 NC

Output 2 C

Output 2 NO

TB1

NC = normally closedNO = normally openC = common

12

61

7

Figure 2-10 Input and Output Connections

2.6.2 Harness Connection

Verify that the contactor harness is connected at thecontroller base (or at the controller disconnect switch, ifequipped). See Figure 2-11.

Note: Verify that the power is disconnected beforeconnecting or disconnecting the contactorharness.

2.6.3 Controller Ground

Verify that the grounding wire is connected from thecontroller’s lower left mounting stud to the enclosure.This connection provides proper grounding that doesnot rely upon the door hinges.

2

1. Contactor Harness Connection2. Ground Connection

1

GM85844

Figure 2-11 Contactor Harness and ControllerGround Connections

Page 19: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 19Section 2 Installation

2.7 Electrical Wiring

The transfer switch is factory-wired and tested. Fieldinstallation includes connecting the sources, loads,generator start circuit(s), and auxiliary circuits, if used.

Note: An approved protective device such as amolded-case circuit breaker or fused disconnectswitch MUST be installed on both sources ofincoming power for circuit protection and used asa disconnect device.

Refer to the wiring diagrams provided with the transferswitch. Observeall applicable national, state, and localelectrical codes during installation.

Install DC, control, and communication system wiringin separate conduit from AC power wiring.

Accidental starting.Can cause severe injury or death.

Disconnect the battery cables beforeworking on the generator set.Remove the negative (--) lead firstwhen disconnecting the battery.Reconnect the negative (--) lead lastwhen reconnecting the battery.

WARNING

Servicing the transfer switch. Hazardous voltage cancause severe injury or death. Deenergize all power sourcesbefore servicing. Turn off the main circuit breakers of alltransfer switch power sources and disable all generator setsas follows: (1) Press the generator set off/reset button to shutdown the generator set. (2) Disconnect power to all batterychargers. (3) Disconnect all battery cables, negative (--) leadsfirst. Reconnect negative (--) leads last when reconnecting thebattery cables after servicing. Follow these precautions toprevent the starting of generator sets by an automatic transferswitch, remote start/stop switch, or engine start commandfrom a remote computer. Before servicing any componentsinside the enclosure: (1) Remove all jewelry. (2) Stand on adry, approved electrically insulatedmat. (3) Test circuits with avoltmeter to verify that they are deenergized.

Hazardous voltage.Will cause severe injury or death.

Disconnect all power sources beforeopening the enclosure.

DANGER

Making line or auxiliary connections. Hazardous voltagecan cause severe injury or death. To prevent electricalshock deenergize the normal power source beforemaking anyline or auxiliary connections.

Grounding electrical equipment. Hazardous voltage cancause severe injury or death. Electrocution is possiblewhenever electricity is present. Ensure you comply with allapplicable codes and standards. Electrically ground thegenerator set and related equipment and electrical circuits.Turn off the main circuit breakers of all power sources beforeservicing the equipment. Never contact electrical leads orappliances when standing in water or on wet ground becausethese conditions increase the risk of electrocution.

NOTICEForeign material contamination. Cover the transfer switchduring installation to keep dirt, grit, metal drill chips, and otherdebris out of the components. Cover the solenoidmechanismduring installation. After installation, use themanual operatinghandle to cycle the contactor to verify that it operates freely.Do not use a screwdriver to force the contactor mechanism.

2.7.1 Source and Load Connections

Determine the cable size. Refer to the transfer switchdimension drawing to determine the size and number ofconductors that can be used. Make sure that the cablesare suitable for use with the transfer switch lugs.Watertight conduit hubs may be required for outdooruse.

Drill the entry holes. Cover the internal components ofthe ATS to protect them from metal chips andconstruction grit. Then drill entry holes for theconductors at the locations shown on the enclosuredrawings. Remove debris from the enclosure with avacuum cleaner.

Note: Do not use compressed air to clean the switch.Cleaning with compressed air can cause debristo lodge in the components and damage theswitch.

Page 20: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1420 Section 2 Installation

Install and test the power cables. Leave sufficientslack in the power leads to reach all of the powerconnecting lugs on the power switching device. Test thepower conductors before connecting them to thetransfer switch. Installing power cables in conduit, cabletroughs and ceiling-suspended hangers often requiresconsiderable force. Pulling cables can damageinsulation and stretch or break the conductor’s strands.

Test the cables after pulling them into position andbefore they are connected to verify that they are notdefective and that they were not damaged duringinstallation.

Connect the cables. Be careful when strippinginsulation from the cables; avoid nicking or ringing theconductor. Clean cables with a wire brush to removesurface oxides before connecting them to the terminals.Apply joint compound to the connections of anyaluminum conductors.

Refer to the wiring diagram provided with the switch.The connection points on the contactor are labeledNormal, Emergency, and Load. Be sure to follow thephase markings (A, B, C, and N). For single-phasesystems, connect to A and C.

Note: Connect the source and load phases asindicated by the markings and drawings toprevent short circuits and to prevent phase-sensitive load devices from malfunctioning oroperating in reverse.

Tighten the lugs. Verify that all connections areconsistent with drawings before tightening the lugs.Tightenall lug connections to the torquevaluesshown inFigure 2-12. Carefully wipe off any excess jointcompound after tightening the terminal lugs.

Socket Size Across Flats, in.

Bolt Torque

Nm Ft. lb.

1/8 5 4

5/32 11 8

3/16 14 10

7/32 16 12

1/4 23 17

5/16 31 23

3/8 42 31

1/2 57 42

9/16 68 50

Figure 2-12 Tightening Torque for Lugs

2.7.2 Engine Start Connection

Accidental starting.Can cause severe injury or death.

Disconnect the battery cables beforeworking on the generator set.Remove the negative (--) lead firstwhen disconnecting the battery.Reconnect the negative (--) lead lastwhen reconnecting the battery.

WARNING

Disabling the generator set. Accidental starting cancause severe injury or death. Before working on thegenerator set or equipment connected to the set, disable thegenerator set as follows: (1) Press the generator set off/resetbutton to shut down the generator set. (2) Disconnect thepower to the battery charger, if equipped. (3) Remove thebattery cables, negative (--) lead first. Reconnect the negative(--) lead last when reconnecting the battery. Follow theseprecautions to prevent the starting of the generator set by theremote start/stop switch.

Prevent the generator set from starting by pressing theOFF button on the generator controller; disconnectingpower to the generator engine start battery charger, ifinstalled; and disconnecting all generator engine startbattery cables, negative (--) leads first.

Connect the generator set remote starting circuit to theengine start terminals located on the transfer switchcontactor assembly. See Figure 2-14 throughFigure 2-19 for the locations of the engine startterminals, which are labeled on the unit with a red decal.Refer to the generator set installation manual for wiresize specifications.

The engine start contact ratings are shown inFigure 2-13.

Page 21: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 21Section 2 Installation

2.7.3 Auxiliary Contacts

Connect the auxiliary contacts to customer-suppliedalarms, remote indicators, or other devices. Auxiliarycontacts provide contacts that close when the transferswitch is in the Normal position and contacts that closewhen the transfer switch is in the Emergency position.

Refer to the schematic diagram provided with thetransfer switch to identify which auxiliary contacts areclosed on Normal and which are closed on Emergency.

The auxiliary contact ratings are shown in Figure 2-13.Figure 2-14 through Figure 2-19 show the locations ofthe auxiliary contacts for different models.

Contacts Resistive Load Inductive Load

Motor Load

NC NO

Engine Start Contacts 2 A @ 30 VDC N/A N/A N/A

Auxiliary Contacts, KSS (40--600A) 15 A @ 250 VAC N/A N/A N/A

Auxiliary Contacts, KSS (800--1000A) 15 A @ 480 VAC 15 A @ 250 VAC;6 A @ 500 VAC

5 A @ 125 VAC;3 A @ 250 VAC;1.5 A @ 500 VAC

2.5 A @ 125 VAC;1.5 A @ 250 VAC;0.75 A @ 500 VAC

Auxiliary Contacts, KSP 15 A @ 480 VAC 15 A @ 250 VAC;6 A @ 500 VAC

5 A @ 125 VAC;3 A @ 250 VAC;1.5 A @ 500 VAC

2.5 A @ 125 VAC;1.5 A @ 250 VAC;0.75 A @ 500 VAC

Figure 2-13 Contact Ratings

tp6225

1. Engine start terminal location2. Auxiliary contacts

1

2

Figure 2-14 Engine Start and Auxiliary ContactLocations, 40--225 AmpStandard-Transition Switches

tp6225

1

1. Engine start terminal location2. Auxiliary contacts

2

Figure 2-15 Engine Start and Auxiliary ContactLocations, 400--600 AmpStandard-Transition Switches

Page 22: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1422 Section 2 Installation

tp6447

1. Engine start connection2. Auxiliary contacts

1

2

Figure 2-16 Engine Start and Auxiliary ContactLocations, 800--1000 AmpStandard-Transition Switches

1

adv6906

1. Engine start contacts2. Auxiliary contacts

2

2

Figure 2-17 Engine Start and Auxiliary ContactLocations, 100--200 AmpProgrammed-Transition Switches

1. Engine start contacts2. Auxiliary switches

1

adv6907

2

Figure 2-18 Engine Start and Auxiliary ContactLocations, 400 AmpProgrammed-Transition Switches

Page 23: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 23Section 2 Installation

1. Engine start contacts2. Auxiliary contacts

2

adv6908

1

Figure 2-19 Engine Start and Auxiliary ContactLocations, 600 AmpProgrammed-Transition Switches

2.8 Communication andAccessory Connections

See Section 3 for accessory and communicationconnection instructions.

2.9 Functional Tests

After completion of the mechanical installation and allelectrical connections, perform the functional testsdescribed in Section 4. The procedures in Section 4 arerequired to complete the installation and startup of thetransfer switch.

Page 24: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1424 Section 2 Installation

Notes

Page 25: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 25Section 3 Communication and Accessory Connections

Section 3 Communication and Accessory Connections

3.1 Introduction

This section explains the connection of communicationcables and factory-installed accessories.

Also refer to the followingdocumentation for instructionsto install, connect, and operate optional accessories.

D Transfer switch wiring diagrams.

D Installation instructions or diagrams provided withloose accessory kits.

3.2 Communication Connections

The Decision-Makerr MPAC 750 and MPAC 1200controllers are equipped with a USB port and aModbusport with an RS-485 connector. An Ethernetcommunication board is optional.

3.2.1 USB Port SiteTech Connection

A personal computer and Kohlerr SiteTecht softwarecanbeused for changing controller settings. UseaUSBcable to connect the controller to a personal computer.

See Figure 3-1 for the USB port location on the front ofthe controller assembly. Remove the small port coverand use aUSBcable with amini-B connector to connectthe controller’s USB port to the computer.

See TP-6701, SiteTech Software OperationManual, forinstructions to use the software. Disconnect the USBcable from the controller and replace the port coverwhen finished.

1

GM85888

1. USB connection (below port cover)

Figure 3-1 USB Connection for SiteTech(MPAC 1200 controller shown)

3.2.2 Modbus Connection

Hazardous voltage.Will cause severe injury or death.

Disconnect all power sources beforeopening the enclosure.

DANGER

Servicing the transfer switch. Hazardous voltage cancause severe injury or death. Deenergize all power sourcesbefore servicing. Turn off the main circuit breakers of alltransfer switch power sources and disable all generator setsas follows: (1) Press the generator set off/reset button to shutdown the generator set. (2) Disconnect power to all batterychargers. (3) Disconnect all battery cables, negative (--) leadsfirst. Reconnect negative (--) leads last when reconnecting thebattery cables after servicing. Follow these precautions toprevent the starting of generator sets by an automatic transferswitch, remote start/stop switch, or engine start commandfrom a remote computer. Before servicing any componentsinside the enclosure: (1) Remove all jewelry. (2) Stand on adry, approved electrically insulatedmat. (3) Test circuits with avoltmeter to verify that they are deenergized.

See Figure 3-2 for the RS-485 Modbus connectorlocation.

Use serial connections to TB2 on the controller toconnect the transfer switch to a personal computer forsystem monitoring, the optional remote annunciator, ora Modbus network. See Figure 3-4.

Notice that a 121 ohm terminating resistor isrecommended on the last device in a network. If there isonly one device, a terminating resistor may be requireddepending on the cable distance and communicationspeed. Long cables and high speeds will increase theneed for a terminating resistor.

The serial port is an isolated RS-485 port withconnection speeds of 9.6, 19.2, and 57.6 kbps. Useshielded twisted-pair cable to connect to the RS-485connectors on the controller’s terminal strip TB2 forserial connections. For connection to a PC, use a USBto RS-485 converter.

Connect the Modbus input and output to the terminalsshown in Figure 3-3. Use #12-24 AWG shielded,twisted-pair wire. Belden cable #9841 or equivalent isrecommended. Connect one end of the shield toground. Leave the other end of the shield disconnected.Tighten the connections to 0.5 Nm (4.4 in. lb.).

Page 26: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1426 Section 3 Communication and Accessory Connections

Use Modbus RTU (remote terminal unit) protocol forcommunication through the serial port. A map of theModbus codes for this controller is available. Contactyour local distributor/dealer.

Note: Modbusr applications require a Modbussoftware driver written by a trained and qualifiedsystems programmer.

1. RS-485 Modbus connections2. Access opening for RS-485 cables

GM85884

1

2

Figure 3-2 Modbus Connections (controller coverremoved for illustration only)

TB2

A1(--)

B1(+)

GND1

3

6

1

4

A1(--)

B1(+)

GND1

Customer connections

Input

Output

Cable shield

Cable shield

Figure 3-3 Modbus RS-485 Connections

USB to RS-485 portconverter

RS-485 *USB port

Device

USB port

Device

LastDevice

RS-485

*

RS-485 *

Device

Terminating resistor [,(121 Ohms)

USB to RS-485port converter

Terminating resistormay be required [

(121 Ohms)

In

Out

In

In

In

Out

Out

Out

PCPC

PC

* Use Belden #9841 or equivalent shielded, twisted-paircommunication cable for RS-485 connections. Groundone end of the cable shield. Leave the other end of thecable shield disconnected.

[ Long cables and high communication speeds will requirea terminating resistor. Use 121 ohm resistor X-6058-27.

RS-485

*Figure 3-4 Serial Connections

Page 27: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 27Section 3 Communication and Accessory Connections

3.2.3 Ethernet Connection

Hazardous voltage.Will cause severe injury or death.

Disconnect all power sources beforeopening the enclosure.

DANGER

Servicing the transfer switch. Hazardous voltage cancause severe injury or death. Deenergize all power sourcesbefore servicing. Turn off the main circuit breakers of alltransfer switch power sources and disable all generator setsas follows: (1) Press the generator set off/reset button to shutdown the generator set. (2) Disconnect power to all batterychargers. (3) Disconnect all battery cables, negative (--) leadsfirst. Reconnect negative (--) leads last when reconnecting thebattery cables after servicing. Follow these precautions toprevent the starting of generator sets by an automatic transferswitch, remote start/stop switch, or engine start commandfrom a remote computer. Before servicing any componentsinside the enclosure: (1) Remove all jewelry. (2) Stand on adry, approved electrically insulatedmat. (3) Test circuits with avoltmeter to verify that they are deenergized.

The Ethernet communication accessory board isrequired for connection to the Ethernet. The Ethernetcommunication board is an optional accessory for theMPAC 750 and MPAC 1200 controllers. Thecommunication board connects to the controller boardas shown in Figure 3-5.

1. Ethernet communication board with RJ-45 connector2. Access opening for Ethernet cable

GM85884

1

12

Figure 3-5 Ethernet Board (controller coverremoved for illustration only)

The Ethernet communication accessory board allowsthe transfer switch to be connected to a building’sEthernet network to communicate with personalcomputers connected to the same subnet.

Note: For an ethernet connection, obtain an IP addressand subnet mask number from the local systemadministrator.

Ethernet Port. The ethernet port is a standard RJ-45jack. SeeFigure 3-5 for the locationof theEthernet port.UseCategory5eorbetter cable toconnect thecontrollerto the building’s network.

Use the controller’s Setup menus or a personalcomputer connected to the controller’s USB port andKohler SiteTech software to set the communicationparameters. The Ethernet communication board mayhave a default IP address assigned at the factory for testpurposes. See Figure 3-6. Change the IP address toan address owned by the user. See the controlleroperation manual for instructions to set thecommunication parameters.

The transfer switch controller does not operate as aModbus-to-Ethernet converter for other devices in anetwork. Formultiple device networks connected to thepersonal computer through the Ethernet, use aModbus-to-Ethernet converter for the other devices inthe network. See Figure 3-7 and instruction sheetTT-1405, provided with the converter, for connectioninstructions.

The controller can communicate with up to five (5)simultaneous TCP/IP (ethernet) connections. Thesefive connections do not include the RS-485 serial port.In the extreme case, five users may be communicatingwith the controller via TCP/IP network connections andanother may be communicating through the serial port,for a total of six (6) communication channels. As thecontroller is asked to communicate with more andmoreoutside devices, the communication will slow down.

Page 28: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1428 Section 3 Communication and Accessory Connections

PCIP xx.xx.xx.02

EthernetNetwork

Modbusr TCP/IPCategory 5e

Modbusr TCP/IPCategory 5e

Note: ThePCand theATSmust be on the samesubnet.

Note: A crossover cable can be used to connect the PCto the ATS controller through the Ethernet port.

MPACController withEthernet comm.

boardIP xx.xx.xx.03

Figure 3-6 Remote Network (Ethernet) Connection

MPACController withEthernet comm.

boardIP xx.xx.xx.03

PCIP xx.xx.xx.02

Device

Last device

RS-485

Converter,Modbusr/EthernetIP xx.xx.xx.05 RS-485

ModbusrTCP/IP

ModbusrTCP/IP

EthernetNetwork

PCIP xx.xx.xx.01

Terminating resistor(121 Ohms)

Device

Device

RS-485

Device

ModbusrRTU

RS-485

Modbusr TCP/IPCategory 5e

Modbusr TCP/IPCategory 5e

Figure 3-7 Ethernet Connections to Multiple-Device Network

Page 29: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 29Section 3 Communication and Accessory Connections

3.3 Accessory Modules(MPAC 1200 only)

Hazardous voltage.Will cause severe injury or death.

Disconnect all power sources beforeopening the enclosure.

DANGER

Servicing the transfer switch. Hazardous voltage cancause severe injury or death. Deenergize all power sourcesbefore servicing. Turn off the main circuit breakers of alltransfer switch power sources and disable all generator setsas follows: (1) Press the generator set off/reset button to shutdown the generator set. (2) Disconnect power to all batterychargers. (3) Disconnect all battery cables, negative (--) leadsfirst. Reconnect negative (--) leads last when reconnecting thebattery cables after servicing. Follow these precautions toprevent the starting of generator sets by an automatic transferswitch, remote start/stop switch, or engine start commandfrom a remote computer. Before servicing any componentsinside the enclosure: (1) Remove all jewelry. (2) Stand on adry, approved electrically insulatedmat. (3) Test circuits with avoltmeter to verify that they are deenergized.

Accessory modules are available with the MPAC 1200controller. This section provides specifications and fieldconnection information for factory-installed accessorymodules. If themodules are not factory-installed, followthe instructions provided with the kits to install themounting assembly and modules.

The transfer switch uses a standard bus system forconnecting accessory modules to the controller. Thisbus incorporates a standard serial communicationinterface for passing data back and forth between themain logic board and the assemblies on the expansionbus.

The module mounting kit holds up to five optionalmodules. Add the current draw for all modules installedto determine the total current draw. SeeFigure 3-8. Thetotal current drawn by all modules must not exceed 300mA. If an External Battery Module is installed andconnected to a battery, there is no current restriction.The External Battery Module, if used, must be the lastboard on the bus.

Module Current Draw Specifications, mA

Alarm Module 75

Standard I/O Module 75

High Power I/O Module 100

Note: EBSM required if total current is higher than 300 mA.

Figure 3-8 Module Current Requirements

3.3.1 Accessory Module Mounting

Mount the accessory modules on the module mountingplate. Starting at the end of the module mountingassembly nearest the cable connection, install any I/Omodules first, then install the alarm board, if used. Theexternal battery module, if used, must be the lastmodule. See Figure 3-9. The alarm board has a fixedModbus address = 5.

Note: Some models may have the I/O moduleassembly installed with the cable connection endpointing to the side or the bottom. Regardless ofthe actual orientation of the assembly, the I/Omodules must be installed closest to the cableconnection, followed by the alarm module andthen the external battery module, if used.

1. Cable connection (defined as the TOP regardless oforientation)

2. I/O modules (if equipped)3. Alarm module (if equipped)4. External battery module (must be last, if equipped)5. Mounting plate

1

GM46258

3

5

2

2

2

4

Figure 3-9 Module Mounting

Page 30: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1430 Section 3 Communication and Accessory Connections

3.3.2 Input/Output (I/O) Modules

Two types of input/output modules are available. Thestandard I/O Module has two inputs and six outputs.The high-power I/O module has two inputs and threeoutputs. See Figure 3-10 through Figure 3-13 for I/Omodule illustrations and specifications.

1. Input LEDs 7 and 8 for inputs 1 and 22. Input connector (see Figure 3-14)3. Output connector4. Output LEDs 1--6

1

GM41093

2

3

4

Figure 3-10 Standard Input/Output Module

Inputs

Available Inputs 2

Input Definition Contact Closure

Current 5 mA Max

Connection Type Terminal Strip

Wire Size #14-24 AWG

Max Distance 700 feet

Outputs

Outputs Available 6

Contact Type Form C (SPDT)

Contact Voltage Rating2 A @ 30 VDC500 mA @ 125 VAC

Connection Type Terminal Strip

Wire Size #14-24 AWG

Figure 3-11 Standard I/O Module Specifications

1. Input LEDs 1 and 22. Input connector (see Figure 3-14)3. Output connector4. Output LEDs 3--5 for outputs 1, 2, and 3

2

GM42186

1

3

4

Figure 3-12 High-Power Input/Output Module

Inputs

Available Inputs 2

Input Definition Contact Closure

Current 5 mA Max

Connection Type Terminal Strip

Wire Size #14-24 AWG

Max Distance 700 feet

Outputs

Outputs Available 3

Contact Type Form C (SPDT)

Contact Voltage Rating

12 A @ 24 VDC12 A @ 250 VAC10 A @ 277 VAC2 A @ 480 VAC

Connection Type Terminal Strip

Wire Size #14-24 AWG

Environmental Specifications

Temperature --40C to 85C (--40F to 185F)

Humidity 35% to 85% noncondensing

Figure 3-13 High-Power I/O Module Specifications

Page 31: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 31Section 3 Communication and Accessory Connections

Use 14-24 AWG cable to connect to inputs and outputs.See Figure 3-14.

LEDs on the module circuit board light to indicate thateach input or output is active.

Note: Each I/O module must have unique address.

Use the address DIP switches on the I/O module toassign a unique (different) address to each module asshown in Figure 3-15. Assign addresses in order from1to 4. An LED for each DIP switch lights to indicate thatthe switch is closed.

The alarm module’s fixed address is 5. The batterymodule’s fixed address is 6.

See the controller operation manual for instructions toassign functions to each input and output. Inputs andoutputs can also be assigned using a personalcomputer with Kohlerr SiteTecht software or overModbus. See TP-6701, SiteTech Operation Manual, orTP-6113, Modbus Protocol Manual.

refGM41093

INPUT 1INPUT 2

Figure 3-14 I/O Module Input Connections(TB1 or TB10)

Both switches OFF

Address=1 shown

DIP Switch

Address1 2

Off Off 1

On Off 2

Off On 3

On On 4

Figure 3-15 Address DIP Switch Settings

3.3.3 External Battery Supply Module(EBSM)

The external battery supply module kit allowsconnection to the generator set engine start battery(ies)or other batteries to provide 12 VDC power to the ATScontroller. The external battery supply module kit isrequired for the following applications:

D Systems using extended engine start timedelays. The EBSM provides power to the ATScontroller during extended time delays longer than 15seconds, when neither the Normal nor theEmergency source is available.

D Installations with frequent utility power outages.TheEBSMprovidespower to theATScontrollerwhenneither source is available, preserving thecontroller’sbackup battery.

D Transfer switches equipped with multipleaccessory modules that require a total of morethan 300 mA current. See Figure 3-8.

The EBSMproduces 2 amps at 12 VDCwith 9--36 VDCinput. The EBSM input is reverse-polarity protected.TheEBSMoutputsa lowbattery voltagesignalwhen theexternal battery voltage falls below 11 VDC for a 12-voltsystem or 22 VDC for a 24-volt system. The module isshown in Figure 3-16.

GM42227-A1. Connector P202. LED indicators3. Battery input connection terminal block TB134. 12/24 volt DIP switch SW11-1. OFF=12 VDC, ON = 24 VDC

1

3

2

4

Figure 3-16 External Battery Supply Module

Page 32: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1432 Section 3 Communication and Accessory Connections

The external battery supply module kit includes oneexternal battery supply circuit board and the circuitboard mounting components. A module mounting kit isrequired for installation of the external battery supplymodule. See Section 3.3.1. Obtain a module mountingkit if one is not already installed and follow theinstructions providedwith the kits to install themountingassembly and modules.

The battery voltage selectionDIP switch SW11-1 allowsselection between 12-volt and 24-volt systems for lowbattery voltage sensing and indication. Connect one ortwobatteries to the external battery supplymodule. Usea battery charger tomaintain the battery(ies) connectedto the EBSM.

DIP Switch SW11-1 Setting Battery Voltage

OFF 12 VDC

ON 24 VDC

Figure 3-17 Battery Voltage Selection

EBSM Connection and Voltage Setting

1. Use #14-28 AWG wire to connect one or twobatteries to terminal blockTB13. (A secondbatterycan be connected but is not required.) Follow themarking on the board for the positive (+) andnegative (--) connections. See Figure 3-16 andFigure 3-17.

Note: If the battery connections are reversed, redLED1 or LED2 will light. See Figure 3-16.

2. Set voltage selector switch SW11-1 to 12 or24VDC. See Figure 3-16 and Figure 3-17. SwitchSW11-2 is not used.

Note: The EBSM has no address switches butmust be the last board on the bus.

3.3.4 Alarm Module

See Figure 3-18 for the optional alarm module. Amodule mounting kit is required for installation of thealarm module. See Section 3.3.1.

The functions provided by this board are:

D 90 dB Audible alarm (any alarm function can beprogrammed to trigger the audible alarm)

D Chicago alarm operation

D Preferred source selection

D Supervised transfer control (supervised transfercontrol switch required)

D Connection for external alarm

The alarm board has a fixed address = 5.

1. Supervised Transfer Switch Connection, P222. External Alarm Connection, TB 143. Alarm Indicator, LED14. DIP Switches

1

GM40764

2

34

Figure 3-18 Alarm Module

Page 33: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 33Section 3 Communication and Accessory Connections

Alarm Board DIP Switches

There are fourDIP switches on the alarmmodule board.Someof the switchesare not used. SeeFigure 3-19. Toenable the preferred source selection, set DIP switch 1to ON. If the supervised transfer switch is installed onthe ATS, set DIP switch 2 to ON.

DIP Switch Function

1 Preferred source selection

2 Supervised transfer enable

3 Not used

4 Not used

Figure 3-19 Alarm Board DIP Switches

Preferred Source Selection

The alarm module is required for preferred sourceselection. To enable the preferred source selection, setDIP switch 1 to ON. Then see the controller operationmanual for instructions to select Source N or Source Eas the preferred source.

External Alarm

A customer-supplied external alarm horn can beconnected to the alarm module at terminal block TB14.Connect to thenormally openor normally closedcontactas recommended by the alarm manufacturer’sinstructions. See Figure 3-20.

Item Specification

Wire Size #12-22 AWG Cu

Contact Voltage Rating500 mA @ 120 VAC

250 mA @ 240 VAC

Figure 3-20 External Alarm ConnectionSpecifications

Audible Alarm Setup

Thealarmboard is equippedwith a 90dBaudible alarm.The audible alarm can be set to sound under selectedfault conditions. Use the Common Alarms Setup menuto assign functions to the audible alarm. See thecontroller operation manual for instructions to setAudibleAlarm:Y for each function that should trigger thealarm.

Alarm Operation, Normal Mode

In Normal Mode, the horn sounds anytime a fault eventhappens in the system. The horn continues to soundunless the alarm silence button is pressed. When thefault is cleared, the alarm silence is ended and reset forthe next alarm.

Alarm Operation, Chicago Alarm Mode

Chicago Alarm mode requires the horn to sound and alampor LED to lightwhen the switch is in the emergency(non-preferred) position. The horn continues to soundunless the alarm silence button is pressed. When thefault is cleared, the alarm silence is ended and reset forthe next alarm.

For Chicago Alarm Mode, use the Common AlarmSetup menu to assign the necessary faults andconditions to the audible alarm. See the controlleroperation manual for instructions to assign commonfaults. Be sure to assign the Contactor in Standbycondition to trigger the audible alarm.

A remote alarm or indicator light can also be connectedto the alarm board to indicate the alarm condition, asdescribed previously. See External Alarm.

Page 34: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1434 Section 3 Communication and Accessory Connections

Alarm Silence Mode

In Alarm Silence Mode, the horn is disabled. AlarmSilenced appears on the display and the system alertLED lights.

The Alarm Silenced condition can be assigned to aprogrammable output. See the controller operationmanual for instructions to assign outputs.

Instructions to Silence the Alarm in Normal andChicago Alarm Modes

When the alarm is activated, thewordAlarmappears onthe main display menu above the first button. SeeFigure 3-21. Press the Alarm button to open the Resetmenu. Then press the button labeled Reset to silencethe alarm.

ResetTo Silence Alarm

B Y Reset Main

System ReadyLD Exer 12/14 @ 16:00Norm 480V Emer 480V

Alarm View Set Test

Reset

Status or Fault DescriptionAlarm Silenced

B Y Reset Main

Figure 3-21 Alarm Silence

3.4 Heater

Hazardous voltage.Will cause severe injury or death.

Disconnect all power sources beforeopening the enclosure.

DANGER

Servicing the transfer switch. Hazardous voltage cancause severe injury or death. Deenergize all power sourcesbefore servicing. Turn off the main circuit breakers of alltransfer switch power sources and disable all generator setsas follows: (1) Press the generator set off/reset button to shutdown the generator set. (2) Disconnect power to all batterychargers. (3) Disconnect all battery cables, negative (--) leadsfirst. Reconnect negative (--) leads last when reconnecting thebattery cables after servicing. Follow these precautions toprevent the starting of generator sets by an automatic transferswitch, remote start/stop switch, or engine start commandfrom a remote computer. Before servicing any componentsinside the enclosure: (1) Remove all jewelry. (2) Stand on adry, approved electrically insulatedmat. (3) Test circuits with avoltmeter to verify that they are deenergized.

An anti-condensation heater kit is available. The stripheater is controlled by a hygrostat to raise thetemperature inside theenclosureabove thedewpoint toprevent condensation. Figure 3-22 shows a typicallocation of the heater kit components inside theenclosure.

The installer must connect 120 VAC power to theterminal block near the hygrostat. See Figure 3-23 andFigure 3-24. Theheater and hygrostat are connected topower through a 15-amp circuit breaker.

The relative humidity setting on the hygrostat isadjustable from 35% to 95%. A setting of 65% isrecommended.

Because of space limitations in the smaller enclosures,30--225 AmpModel KSS switches can include either anenclosure heater or a surge protection device (SPD),but not both.

Page 35: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 35Section 3 Communication and Accessory Connections

1. Hygrostat assembly, see Figure 3-232. Strip heater with guard

1

GM69824

2

Right Side View

Figure 3-22 Heater Location, Typical

1. 120 VAC power connection terminal block2. Circuit breaker3. Relative humidity adjustment control

GM71056

3

2

1

Figure 3-23 Hygrostat Assembly, Typical

GM71278

HYGROSTAT

HEATER

CIRCUITBREAKER

TERMINALBLOCK

120 VAC ONLYCUSTOMER SUPPLIED

Figure 3-24 Heater Connections

Page 36: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1436 Section 3 Communication and Accessory Connections

3.5 Load Shed (Forced Transferto OFF, KSP with MPAC 1200only)

Hazardous voltage.Will cause severe injury or death.

Disconnect all power sources beforeopening the enclosure.

DANGER

Servicing the transfer switch. Hazardous voltage cancause severe injury or death. Deenergize all power sourcesbefore servicing. Turn off the main circuit breakers of alltransfer switch power sources and disable all generator setsas follows: (1) Press the generator set off/reset button to shutdown the generator set. (2) Disconnect power to all batterychargers. (3) Disconnect all battery cables, negative (--) leadsfirst. Reconnect negative (--) leads last when reconnecting thebattery cables after servicing. Follow these precautions toprevent the starting of generator sets by an automatic transferswitch, remote start/stop switch, or engine start commandfrom a remote computer. Before servicing any componentsinside the enclosure: (1) Remove all jewelry. (2) Stand on adry, approved electrically insulatedmat. (3) Test circuits with avoltmeter to verify that they are deenergized.

The load shed (forced transfer to OFF) accessory mustbe factory-installed. The load shed accessory isavailable only on programmed-transition transferswitches with the MPAC 1200 controller. SeeFigure 3-25 for an illustration of the load shed acessory.

The load shed function requires an external signal(contact closure) to initiate transfer to the OFF position.

Connect the external contact to input #1 (if available) orinput #2 on connector TB1 on themain logic board. SeeFigure 3-26. Use #12--24 AWG wire and tighten to0.5 Nm (4.4 in. lb.).

Use the Input/Output setup menu or Kohler SiteTechsoftware to assign the connected input (Main BoardInput #1 or #2) to the forced transfer to off function. If theexternal contact is connected to a different inputconnection on an optional I/Omodule, assign the forcedtransfer to off function to that input.

GM23469

Figure 3-25 Load Shed Accessory (foridentification)

Page 37: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 37Section 3 Communication and Accessory Connections

GM89713

1. Input/output terminal strip TB1

1

TB1

12

61

7MLB Input 2(alternateconnection)

#12--24 AWG wire0.5 Nm (4.4 in. lb.)

MLBInput 1

MPAC Controller Circuit Board

Figure 3-26 Forced Transfer to Off Input Connection (for factory-installed load shed kits)

Page 38: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1438 Section 3 Communication and Accessory Connections

3.6 Programmable Exerciser

An optional programmable exerciser is available fortransfer switches equipped with the Decision-MakerrMPAC 750 controller.

The optional programmable exerciser is a 7-day timerthat allowsprogrammingof up to 8 on/off events per day.See Figure 3-27. Use the exercise timer to scheduleweekly loaded or unloaded exercise runs in addition tothe exercise time set through the ATS controller. Thetimer is installed inside the ATS enclosure.

The programmable exerciser uses the Remote Testinput to the transfer switch controller. Refer to theinstruction sheet provided with the exerciser forinstallation, connection, loaded/unloaded test selection,and programming instructions. See Section 2.6.1 forinput connection information.

A personal computer and Kohlerr SiteTecht softwareare required to set up the remote exerciser. SiteTechsoftware is available to Kohler-authorized distributorsand dealers.

Figure 3-27 Programmable Exerciser

3.7 Other Accessories

Refer to the following documentation for instructions toinstall, connect, and operate optional accessories.

D Transfer switch wiring diagrams.

D Installation instructions provided with looseaccessory kits.

D Controller Operation Manual. See List of Relatedmaterials in the Introduction section of thismanual fordocument numbers.

Page 39: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 39Section 4 Functional Tests and Setup

Section 4 Functional Tests and Setup

4.1 Introduction

Be sure to performall of the functional tests described inthis section before putting the transfer switch intooperation.

The functional tests include the following checks:

D Manual Operation TestD Voltage ChecksD Automatic Operation Test

Note: Perform these checks in the order presented toavoid damaging the ATS.

Read all instructions on the labels affixed to theautomatic transfer switch before proceeding.

To complete the installation, follow the instructions inthis section to:

D Set the time, date, and exercise schedule on thecontroller.

D Perform the system startup procedures listed on thestartup form.

D Register the unit using the Kohlerr online WarrantyProcessing System.

4.2 Manual Operation Test

If you have not already done so, test the contactormanual operation before proceeding to the voltagecheck and electrical operation test.

Note: Disable the generator set and disconnect thepower byopening the circuit breakersor switchesfor both sources before manually operating thetransfer switch.

Follow the instructions in the Installation Section tocheck the transfer switch manual operation.

A contactor in normal and serviceable conditiontransfers smoothly without binding when operatedmanually. Do not place the transfer switch into service ifthe contactor does not operate smoothly withoutbinding; contact an authorized distributor/dealer toservice the contactor.

4.3 Voltage CheckThe voltage, frequency, and phasing of the transferswitchand thepower sourcesmust be thesame toavoiddamage to loads and the transfer switch. Compare thevoltage and frequency ratings of the utility source,transfer switch, and generator set, and verify that theratings are all the same.

Use the voltage check procedure explained in thissection to verify that the voltages and phasing of allpower sources are compatible with the transfer switchbefore connecting the power switching device andcontroller wire harnesses together.

Follow the instructions provided with the generator setto prepare the generator set for operation.

Read and understand all instructions on installationdrawings and labels on the switch. Note any optionalaccessories that have been furnished with the switchand review their operation.

Note: Source N is the source connected to the normalside of the contactor. Source E is the sourceconnected to the emergency side of thecontactor. Verify that the source leads areconnected to the correct lugs before proceeding.

The voltage check procedure requires the followingequipment:

D A digital voltmeter (DVM) with electrically insulatedprobes capable of measuring the rated voltage andfrequency

D A phase rotation meter

Page 40: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1440 Section 4 Functional Tests and Setup

Hazardous voltage.Will cause severe injury or death.

Only authorized personnel shouldopen the enclosure.

DANGER

Testing live electrical circuits. Hazardous voltage orcurrent can cause severe injury or death. Have trained andqualified personnel take diagnostic measurements of livecircuits. Use adequately rated test equipment with electricallyinsulated probes and follow the instructions of the testequipment manufacturer when performing voltage tests.Observe the following precautions when performing voltagetests: (1) Remove all jewelry. (2) Stand on a dry, approvedelectrically insulated mat. (3) Do not touch the enclosure orcomponents inside the enclosure. (4) Be prepared for thesystem to operate automatically.(600 volts and under)

Voltage Check Procedure

1. If Source N is a generator set, move the generatorset master switch to the RUN position. Thegenerator set should start.

2. Close the Source N circuit breaker or switch.

3. Use a voltmeter to check the Source N (normal)phase-to-phase and phase-to-neutral (ifapplicable) terminal voltages and frequency.

a. If Source N is the utility and themeasured inputdoes not match the voltage and frequencyshown on the transfer switch nameplate,STOP! Do not proceed further in installationbecause the transfer switch is not designed forthe application—call your distributor/dealer toorder the correct transfer switch.

b. If SourceN is a generator set and the generatorset output voltage and frequency do not matchthe nominal system voltage and frequencyshown on the transfer switch nameplate, followthe manufacturer’s instructions to adjust thegenerator set. The automatic transfer switchwill only function with the rated system voltageand frequency specified on the nameplate.

4. Use a phase rotation meter to check the phaserotationat theSourceN (normal) terminals. Rewirethe transfer switchSourceN terminals to obtain thecorrect phase sequence if necessary.

Note: The default setting for the phase rotation onthe controller is ABC. If the application usesa phase rotation of BAC, refer to thecontroller Operation Manual for instructionsto change the phase rotation setting on thecontroller.

5. If the source is a generator set, stop the generatorset by moving the master switch to the OFFposition.

6. Disconnect Source N by opening upstream circuitbreakers or switches.

7. Repeat steps 1 through 5 for Source E. Thenproceed to step 8.

8. Disconnect both sources to the transfer switch byopening the circuit breakers or switches.

9. Close and lock the transfer switch enclosure door.

10. Reconnect both power sources by closing thecircuit breakers or switches.

11. Move the generator setmaster switch to the AUTOposition.

Note: If the engine cooldown time delay setting isnot set to zero (default setting), thegenerator set may start and run until theEngine Cooldown Time Delay ends.

12. Perform the lamp test and then proceed to theautomatic operation test.

4.4 Automatic Operation TestCheck the transfer switch’s automatic control systemimmediately after the voltage check. Refer to thecontroller Operation Manual for instructions to run theautomatic operation test.

Note: Close and lock the enclosure door before startingthe test procedure.

Page 41: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 41Section 4 Functional Tests and Setup

4.5 System Setup

Set the controller’s current time and date. See thecontroller Operation Manual for instructions.

The transfer switch is factory-setwith default settings fortime delays and other parameters. See the controllerOperation Manual for instructions to view and changesettings, if necessary.

Note: Use caution when changing transfer switchsettings. The source voltage and frequencysettings must match the values shown on thetransfer switch nameplate.

4.6 Exerciser Setup

Set the exerciser to start and run the generator set atleast once aweek. See the controller OperationManualfor instructions.

Transfer switches equipped with the Decision-MakerrMPAC 750 controller may also use the optionalprogrammable exerciser. Refer to the instructionsprovided with the exerciser to schedule additionalloaded or unloaded exercise runs.

4.7 User Interface Cover

The gasket-sealed, hinged user interface coverprevents unauthorized access to the transfer switchcontrols and protects the user interface from harshenvironmental conditions. The cover is available as anoptional accessory for NEMA 1 enclosures. NEMA 3Renclosures include the cover as standard equipment.

Use a customer-supplied padlock to lock the cover.

4.8 Startup NotificationPerform the system startup procedure explained on theStartup Notification Form. The Startup NotificationForm covers all equipment in the power system.Complete the Startup Notification Form and register thepower system using the Kohlerr online WarrantyProcessing System.

Page 42: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1442 Section 4 Functional Tests and Setup

Notes

Page 43: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 Appendix 43

Appendix A Abbreviations

The following list contains abbreviations that may appear in this publication.

A, amp ampereABDC after bottom dead centerAC alternating currentA/D analog to digitalADC advanced digital control;

analog to digital converteradj. adjust, adjustmentADV advertising dimensional

drawingAh amp-hourAHWT anticipatory high water

temperatureAISI American Iron and Steel

InstituteALOP anticipatory low oil pressurealt. alternatorAl aluminumANSI American National Standards

Institute (formerly AmericanStandards Association, ASA)

AO anticipatory onlyAPDC Air Pollution Control DistrictAPI American Petroleum Instituteapprox. approximate, approximatelyAPU Auxiliary Power UnitAQMD Air Quality Management DistrictAR as required, as requestedAS as supplied, as stated, as

suggestedASE American Society of EngineersASME American Society of

Mechanical Engineersassy. assemblyASTM American Society for Testing

MaterialsATDC after top dead centerATS automatic transfer switchauto. automaticaux. auxiliaryavg. averageAVR automatic voltage regulatorAWG American Wire GaugeAWM appliance wiring materialbat. batteryBBDC before bottom dead centerBC battery charger, battery

chargingBCA battery charging alternatorBCI Battery Council InternationalBDC before dead centerBHP brake horsepowerblk. black (paint color), block

(engine)blk. htr. block heaterBMEP brake mean effective pressurebps bits per secondbr. brassBTDC before top dead centerBtu British thermal unitBtu/min. British thermal units per minuteC Celsius, centigradecal. calorieCAN controller area networkCARB California Air Resources BoardCAT5 Category 5 (network cable)CB circuit breakerCC crank cyclecc cubic centimeterCCA cold cranking ampsccw. counterclockwiseCEC Canadian Electrical Codecert. certificate, certification, certifiedcfh cubic feet per hour

cfm cubic feet per minuteCG center of gravityCID cubic inch displacementCL centerlinecm centimeterCMOS complementary metal oxide

substrate (semiconductor)com communications (port)coml commercialComl/Rec Commercial/Recreationalconn. connectioncont. continuedCPVC chlorinated polyvinyl chloridecrit. criticalCSA Canadian Standards

AssociationCT current transformerCu coppercUL Canadian Underwriter’s

LaboratoriesCUL Canadian Underwriter’s

Laboratoriescu. in. cubic inchcw. clockwiseCWC city water-cooledcyl. cylinderD/A digital to analogDAC digital to analog converterdB decibeldB(A) decibel (A weighted)DC direct currentDCR direct current resistancedeg., degreedept. departmentdia. diameterDI/EO dual inlet/end outletDIN Deutsches Institut fur Normung

e. V. (also Deutsche IndustrieNormenausschuss)

DIP dual inline packageDPDT double-pole, double-throwDPST double-pole, single-throwDS disconnect switchDVR digital voltage regulatorE2PROM, EEPROM

electrically-erasableprogrammable read-onlymemory

E, emer. emergency (power source)ECM electronic control module,

engine control moduleEDI electronic data interchangeEFR emergency frequency relaye.g. for example (exempli gratia)EG electronic governorEGSA Electrical Generating Systems

AssociationEIA Electronic Industries

AssociationEI/EO end inlet/end outletEMI electromagnetic interferenceemiss. emissioneng. engineEPA Environmental Protection

AgencyEPS emergency power systemER emergency relayES engineering special,

engineered specialESD electrostatic dischargeest. estimatedE-Stop emergency stopetc. et cetera (and so forth)

exh. exhaustext. externalF Fahrenheit, femaleFHM flat head machine (screw)fl. oz. fluid ounceflex. flexiblefreq. frequencyFS full scaleft. foot, feetft. lb. foot pounds (torque)ft./min. feet per minuteftp file transfer protocolg gramga. gauge (meters, wire size)gal. gallongen. generatorgenset generator setGFI ground fault interrupter

GND, groundgov. governorgph gallons per hourgpm gallons per minutegr. grade, grossGRD equipment groundgr. wt. gross weightH x W x D height by width by depthHC hex capHCHT high cylinder head temperatureHD heavy dutyHET high exhaust temp., high

engine temp.hex hexagonHg mercury (element)HH hex headHHC hex head capHP horsepowerhr. hourHS heat shrinkhsg. housingHVAC heating, ventilation, and air

conditioningHWT high water temperatureHz hertz (cycles per second)IBC International Building CodeIC integrated circuitID inside diameter, identificationIEC International Electrotechnical

CommissionIEEE Institute of Electrical and

Electronics EngineersIMS improved motor startingin. inchin. H2O inches of waterin. Hg inches of mercuryin. lb. inch poundsInc. incorporatedind. industrialint. internalint./ext. internal/externalI/O input/outputIP internet protocolISO International Organization for

StandardizationJ jouleJIS Japanese Industry Standardk kilo (1000)K kelvinkA kiloampereKB kilobyte (210 bytes)KBus Kohler communication protocolkg kilogram

Page 44: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1444 Appendix

kg/cm2 kilograms per squarecentimeter

kgm kilogram-meterkg/m3 kilograms per cubic meterkHz kilohertzkJ kilojoulekm kilometerkOhm, k kilo-ohmkPa kilopascalkph kilometers per hourkV kilovoltkVA kilovolt amperekVAR kilovolt ampere reactivekW kilowattkWh kilowatt-hourkWm kilowatt mechanicalkWth kilowatt-thermalL literLAN local area networkL x W x H length by width by heightlb. pound, poundslbm/ft3 pounds mass per cubic feetLCB line circuit breakerLCD liquid crystal displayLED light emitting diodeLph liters per hourLpm liters per minuteLOP low oil pressureLP liquefied petroleumLPG liquefied petroleum gasLS left sideLwa sound power level, A weightedLWL low water levelLWT low water temperaturem meter, milli (1/1000)M mega (106 when used with SI

units), malem3 cubic meterm3/hr. cubic meters per hourm3/min. cubic meters per minutemA milliampereman. manualmax. maximumMB megabyte (220 bytes)MCCB molded-case circuit breakerMCM one thousand circular milsmeggar megohmmeterMHz megahertzmi. milemil one one-thousandth of an inchmin. minimum, minutemisc. miscellaneousMJ megajoulemJ millijoulemm millimetermOhm, mmilliohmMOhm, MmegohmMOV metal oxide varistorMPa megapascalmpg miles per gallonmph miles per hourMS military standardms millisecondm/sec. meters per secondmtg. mountingMTU Motoren-und Turbinen-UnionMW megawattmW milliwattF microfaradN, norm. normal (power source)NA not available, not applicablenat. gas natural gas

NBS National Bureau of StandardsNC normally closedNEC National Electrical CodeNEMA National Electrical

Manufacturers AssociationNFPA National Fire Protection

AssociationNm newton meterNO normally openno., nos. number, numbersNPS National Pipe, StraightNPSC National Pipe, Straight-couplingNPT National Standard taper pipe

thread per general useNPTF National Pipe, Taper-FineNR not required, normal relayns nanosecondOC overcrankOD outside diameterOEM original equipment

manufacturerOF overfrequencyopt. option, optionalOS oversize, overspeedOSHA Occupational Safety and Health

AdministrationOV overvoltageoz. ouncep., pp. page, pagesPC personal computerPCB printed circuit boardpF picofaradPF power factorph., phasePHC Phillipsr head Crimptiter

(screw)PHH Phillipsr hex head (screw)PHM pan head machine (screw)PLC programmable logic controlPMG permanent magnet generatorpot potentiometer, potentialppm parts per millionPROM programmable read-only

memorypsi pounds per square inchpsig pounds per square inch gaugept. pintPTC positive temperature coefficientPTO power takeoffPVC polyvinyl chlorideqt. quart, quartsqty. quantityR replacement (emergency)

power sourcerad. radiator, radiusRAM random access memoryRDO relay driver outputref. referencerem. remoteRes/Coml Residential/CommercialRFI radio frequency interferenceRH round headRHM round head machine (screw)rly. relayrms root mean squarernd. roundRO read onlyROM read only memoryrot. rotate, rotatingrpm revolutions per minuteRS right sideRTDs Resistance Temperature

Detectors

RTU remote terminal unitRTV room temperature vulcanizationRW read/writeSAE Society of Automotive

Engineersscfm standard cubic feet per minuteSCR silicon controlled rectifiers, sec. secondSI Systeme international d’unites,

International System of UnitsSI/EO side in/end outsil. silencerSMTP simple mail transfer protocolSN serial numberSNMP simple network management

protocolSPDT single-pole, double-throwSPST single-pole, single-throwspec specificationspecs specification(s)sq. squaresq. cm square centimetersq. in. square inchSMS short message serviceSS stainless steelstd. standardstl. steeltach. tachometerTB terminal blockTCP transmission control protocolTD time delayTDC top dead centerTDEC time delay engine cooldownTDEN time delay emergency to

normalTDES time delay engine startTDNE time delay normal to

emergencyTDOE time delay off to emergencyTDON time delay off to normaltemp. temperatureterm. terminalTHD total harmonic distortionTIF telephone influence factortol. toleranceturbo. turbochargertyp. typical (same in multiple

locations)UF underfrequencyUHF ultrahigh frequencyUIF user interfaceUL Underwriter’s Laboratories, Inc.UNC unified coarse thread (was NC)UNF unified fine thread (was NF)univ. universalURL uniform resource locator

(web address)US undersize, underspeedUV ultraviolet, undervoltageV voltVAC volts alternating currentVAR voltampere reactiveVDC volts direct currentVFD vacuum fluorescent displayVGA video graphics adapterVHF very high frequencyW wattWCR withstand and closing ratingw/ withWO write onlyw/o withoutwt. weightxfmr transformer

Page 45: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/14 45

Notes

Page 46: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

TP-6834 4/1446

Notes

Page 47: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr
Page 48: Automatic Transfer Switchesresources.kohler.com › power › kohler › industrial › pdf › tp6834.pdfSpecification Sheet, Model KSS/KSP G11-130 Operation Manual, Decision-Makerr

KOHLER CO. Kohler, Wisconsin 53044Phone 920-457-4441, Fax 920-459-1646For the nearest sales/service outlet in theUS and Canada, phone 1-800-544-2444KOHLERPower.com

Kohler Power SystemsAsia Pacific Headquarters7 Jurong Pier RoadSingapore 619159Phone (65) 6264-6422, Fax (65) 6264-6455E 2014 by Kohler Co. All rights reserved.

TP-6834 4/14