Alarm Systems Control Panels Float Switches Leak Detection Systems Page 1 of 2 PO Box 827 Hawley, MN 56549 (218) 483-3034 Fax (218) 483-3034 www.alderonind.com Auto Dialer™ Operation, Maintenance and Installation Manual Figure 1 1. Disconnect Power. Make sure auto dialer is turned “off” prior to wiring and phone line hook-up. Before beginning the installation, read the entire contents of the Installation and Instruction manual for “United Security Products Model AVD-45b Automatic Voice Dialer.” 2. Determine mounting location for the auto dialer. Wire the “two” wire cable into a telephone outlet and snap the other end into the auto dialer labeled “TEL LINE”. Connect the “A” - four wire cable into the auto dialer labeled “12V and Alarm”. See Figure 1. 3. Remove the knock-out on the Versa’larm. Using a 1/2” romex connector, bring the “A” - four wire cable from the auto dialer and the “B” cable from the included auto dialer power supply. Note: Power supply is factory connected to cable “A”. See Figure 3. 4. Locate the white and red auxiliary contact wires located inside the Versa’larm. Strip installation off approximately 1/4” on each wire. Insert the white wire from cable “A” into the included “white” wire connector and then insert the “stripped white” wire from the Versa’larm and use a plier to squeeze the connector to make a secure connection. Do the same for the “yellow” wire from cable “A” and the “stripped red” wire from the Versa’larm. See Figure 2. 5. Plug the power supply into a standard 120 VAC, 50/60 HZ wall outlet. Place a standard 9 volt battery in the back of the auto dialer to provide 4 hours of continuous battery back up for the auto dialer. Use two screws spaced appropriately on the wall at the desired loca- tion and mount the auto dialer to the wall. The unit should be on - check the display for text to appear on the screen indicating power to the unit. 6. Program the auto dialer per the instruction manual entitled, “United Security Products Model AVD-45b Automatic Voice Dialer” IM- PORTANT! Select NC “Normally Closed” for the input when programming the Auto Dialer. 7. Test the system by pressing the “Test” switch located on the Versa’larm or by activating the “signaling device” on the Versa’larm. The auto dialer should begin to call out with an outgoing alarm message (if properly programmed). Note: the Versa’larm must remain in the alarm mode for the auto dialer to activate. Pressing the “Silence” switch on the Versa’larm will disable the auto dialer. When the Versa’larm is out of alarm condition, everything is reset and in normal monitoring mode. 8. Test product weekly to ensure system integrity and replace batteries as needed. NOTE: If installing the LOW TEMPERATURE FURNACE FAIL option, do not use these instructions. Instead, refer to instructions part number: 100314 AUTO DIALER 1 2 3 4 5 6 7 8 9 * 0 # p r m Auto Dialer Wire Connectors Versa‘larm Alarm Unit Base 1/2” Electrical Knockout 1/2” Strain Relief Figure 3 Unimax Control Float AC Adaptor AC Adaptor Typical Application Monitoring a Sump Basin Versa’larm Alarm Unit Typical Wall Mounted Phone Jack Part Number 7006 Auto Dialer Model AVD-45b 120 VAC Wallmount Receptacle Alderon Industries, LLC P.O. Box 827 Hawley, MN 56549 Page 1 of 2 P/N 10223 Rev A 9/24/01 Phone: 218.483.3034 Fax: 218.483.3036 Connections made with wire connectors inside the Versa’larm 120VAC Wallmount Receptacle Versa’larm Power Supply Figure 2 Insert wires into connec- tor and squeeze tightly witgh plier for secure connection. “A” Cable 4 Wire Flat Cord From Auto Dialer “B” Power Cord from Auto Dialer Power Supply Factory Installed Wire Connectors For Power Red Black Red Yellow White White Auxiliary Contacts From Versa’larm located inside the alarm panel “A” Cable 4 Wire Flat Cord From Auto Dialer “B” Power Cord from Auto Dialer Power Supply

Upload: others

Post on 12-Sep-2021

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Auto Dialerâ„¢ - Alderon Industries Hawley Minnesota

Alarm Systems Control Panels Float Switches Leak Detection Systems Page 1 of 2PO Box 827 Hawley, MN 56549 (218) 483-3034 Fax (218) 483-3034 www.alderonind.com

Auto Dialer™Operation, Maintenance and Installation Manual

Figure 1

1. Disconnect Power. Make sure auto dialer is turned “off” prior to wiring and phone line hook-up. Before beginning the installation, read the entire contents of the Installation and Instruction manual for “United Security Products Model AVD-45b Automatic Voice Dialer.”2. Determine mounting location for the auto dialer. Wire the “two” wire cable into a telephone outlet and snap the other end into the auto dialer labeled “TEL LINE”. Connect the “A” - four wire cable into the auto dialer labeled “12V and Alarm”. See Figure 1.3. Remove the knock-out on the Versa’larm. Using a 1/2” romex connector, bring the “A” - four wire cable from the auto dialer and the “B” cable from the included auto dialer power supply. Note: Power supply is factory connected to cable “A”. See Figure 3.4. Locate the white and red auxiliary contact wires located inside the Versa’larm. Strip installation off approximately 1/4” on each wire. Insert the white wire from cable “A” into the included “white” wire connector and then insert the “stripped white” wire from the Versa’larm and use a plier to squeeze the connector to make a secure connection. Do the same for the “yellow” wire from cable “A” and the “stripped red” wire from the Versa’larm. See Figure 2.5. Plug the power supply into a standard 120 VAC, 50/60 HZ wall outlet. Place a standard 9 volt battery in the back of the auto dialer to provide 4 hours of continuous battery back up for the auto dialer. Use two screws spaced appropriately on the wall at the desired loca-tion and mount the auto dialer to the wall. The unit should be on - check the display for text to appear on the screen indicating power to the unit.6. Program the auto dialer per the instruction manual entitled, “United Security Products Model AVD-45b Automatic Voice Dialer” IM-PORTANT! Select NC “Normally Closed” for the input when programming the Auto Dialer.7. Test the system by pressing the “Test” switch located on the Versa’larm or by activating the “signaling device” on the Versa’larm. The auto dialer should begin to call out with an outgoing alarm message (if properly programmed). Note: the Versa’larm must remain in the alarm mode for the auto dialer to activate. Pressing the “Silence” switch on the Versa’larm will disable the auto dialer. When the Versa’larm is out of alarm condition, everything is reset and in normal monitoring mode.8. Test product weekly to ensure system integrity and replace batteries as needed.

NOTE: If installing the LOW TEMPERATURE FURNACE FAIL option, do not use these instructions. Instead, refer to instructions partnumber: 100314

AUTO DIALER

1 2 3

4 5 6

7 8 9

* 0 #

p r m

Auto Dialer

Wire Connectors

Versa‘larm Alarm Unit

Base

1/2” Electrical Knockout

1/2” StrainRelief

Figure 3

Uni

max

Co

ntro

l Fl

oat

AC Adaptor

AC Adaptor

Typical ApplicationMonitoring a SumpBasin

Versa’larm Alarm Unit

Typical WallMounted Phone Jack

Part Number 7006 Auto DialerModel AVD-45b

120 VAC Wallmount Receptacle

Alderon Industries, LLCP.O. Box 827Hawley, MN 56549Page 1 of 2

P/N 10223 Rev A9/24/01Phone: 218.483.3034Fax: 218.483.3036

Connections made with wire connectors inside the Versa’larm

120VAC WallmountReceptacle

Versa’larmPower Supply

Figure 2Insert wires into connec-tor and squeeze tightly witgh plier for secure connection.

“A” Cable4 Wire Flat CordFrom Auto Dialer

“B” PowerCord fromAuto DialerPower Supply

Factory InstalledWire ConnectorsFor Power

Red

Black

Red

Yellow

White

White Auxiliary ContactsFrom Versa’larmlocated inside the alarm panel

“A” Cable4 Wire Flat CordFrom Auto Dialer

“B” PowerCord fromAuto Dialer Power Supply

Page 2: Auto Dialerâ„¢ - Alderon Industries Hawley Minnesota

Auto Dialer ProgrammingOperation, Maintenance and Installation Manual

Quick Start Programming

1. Make sure the unit is powered up. Press the “M” key twice (if the word “OPERATE” is displayed, or once if “OFF” is displayed). to place the unit in the programming mode. Display should read: Program: Numbers. Press “1” for (Yes).

2. Enter Number will be displayed. Use the digits on the keypad to enter all the digits of the first number to be dialed. Check the LCD while programming to make sure the correct numbers are pressed. If programming long distance, re-member to enter 1+area code. Example: If a long distance number, the LCD might look like, 12184731234 and if not long distance the LCD might look like 4731234. Do not use spaces or hyphens.

3. After the digits are entered for the first number, press “P” and the LCD will display “ENTER MEMORY LOCATION 1-4” Press “1” for first location. Display will then read “PROGRAM: NUMBERS” Press “1” if you want to program a second number. If you do not wish to program any other numbers press “2” for (NO). Up to 4 separate numbers may be pro-grammed.

4. After you have programmed all the numbers and have pressed “2” for (No) at the “Program: Numbers” prompt, the display will read “Program: T-Line”. Press “2” for (NO)

5. The LCD will now read “Program: OGM”. This is your 16 second message that will be played by the auto dialer. Press “1” for (YES). Press and hold “*” to record your message remembering that you have 16 seconds. Locate the micro-phone on the front lower left corner. For best results while recording, speak about 12 inches from the microphone in a clear and normal voice. Press and hold the key for the duration of the message and begin speaking your message (the word “recording” will be displayed). When the “*” key is released the message will be stored into memory. If your mes-sage goes beyond 16 seconds the display will read “DONE”. If you wish to change your message, repeat the preceding steps. The new message will automatically replace the previous message.

6. When you are finished recording your message and you release the “*” key the display will read “Program: Channel”, press “1” for (YES). The display will read “EXIT DELAY”, press “2” (OFF). The display will read “ENTRY DELAY”, press “2” (OFF). The display will read “N.O./N.C.”, press “2” (N.C.) The display will read “N.O./N.C.”, press “2” (CONT). Dis-play will read “PROGRAM: NUMBERS”, if you are done press “M” key twice so the display reads “OPERATE”. The unit has now been programmed and is ready for testing.

7. Test the system by pressing the “TEST” button on the Versa’larm or by activating any of the sensors. The unit should trigger and will show calling of number if the phone line is connected otherwise the system tries to dial and will go back to “OPERATE”.

If a mistake is made while programming, you may always exit and re-enter the program mode and re-enter the correct values. To exit anywhere within theprogram press “M” key twice. The display will read “OPERATE”. To getback into the programming mode press the “M” key twice. You will now beready to re-program.

For those application not requiring a pager connection or PBX (Dialing a digit to access an outgoing phone line), you may use the Quick Start Programming Instructions. If testing does not pass after programming the unit, read the entire installation and instruction man-ual for “United Security Products Model AVD-45b Automatic Voice Dialer.” Before program-ming, read pages 2,3,6,15 and 16 of the manual.