attachment 7 request 4 - level 1 and 2 vibration

23
Attachment 7 Request 4 - Level 1 and 2 Vibration Acceptance Criteria Support Documents

Upload: others

Post on 06-Apr-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Attachment 7 Request 4 - Level 1 and 2 Vibration

Attachment 7

Request 4 - Level 1 and 2 Vibration Acceptance Criteria SupportDocuments

Page 2: Attachment 7 Request 4 - Level 1 and 2 Vibration

Attachment 7

Request 4 - Level 1 and 2 Vibration Acceptance Criteria SupportDocuments

Page 3: Attachment 7 Request 4 - Level 1 and 2 Vibration

Attachment 7

Documents Included

MPR Associates Inc., Letter 1101 -0009-HDG-01, "Vibration Acceptance Criteria forQuad Cities ASBs," dated April 13, 2006

MPR Associates Inc., Letter 1101 -0009-HDG-02, "Vibration Acceptance Criteria forERV Valve Actuators - Revision 1," dated April 13, 2006

Attachment to MPR Associates Inc., Letter 1101 -0009-HDG-02, "Vibration AcceptanceCriteria for ERV Valve Actuators - Revision 1"

MPR Associates Inc., Calculation 1101 -0009-HDG-01, "ASME Code Evaluation forVibration Testing of ASBs," Revision 0

Page 4: Attachment 7 Request 4 - Level 1 and 2 Vibration

*IMPRASSOCIATES mNcENGINEERS

April 13, 20061101-0009-HDG-01

Mr. Mohammad MolaeiExelon Nuclear4300 Winfiel4RoadWarrenville, IL 60555

Subject: Vibration Acceptance Criteria for Quad Cities ASBs

Reference: Exelon Contract No. 0084512, Release 00022

Dear Mr. Molaei:

This attachment to this letter provides the basis for a Vibration Acceptance Criteria for theAcoustic Side Branch (ASB) devices that are being considered for installation at Quad Cities.The ASBs are to be installed on the Safety Relief Valve (SRV) and Electromatic Relief Valve(ERV) branch lines on the main steam piping in the drywell. The ASBs are 6" diameter pipesthat are either 24" long or 30" long, closed off by a blind flange at the free end, and wouldbranch off the vertical branch lines that support the valves. The ASB contains a steel canisterthat is packed with circular stainless steel screens to provide resistance to steam flow. Thepurpose of the ASB is to mitigate the intensity of the acoustic modes that exist in the SRV andERV branch lines when steam flow rate is high.

The Vibration Acceptance Criteria described below are based on the results from three series ofvibration tests that were recently conducted on the ASBs at the Quanta Laboratories in SantaClara, California. The tests were conducted to determine the vibration levels that could beimposed on an ASB without damaging the internals. These tests included both transverse andinline excitation of the ASBs and utilized five separate internal canisters to evaluate differentcanister designs and vibratory loadings. The testing and the results of the testing are described in06Q4568-DR-004, "Quad Cities Acoustic Side Branch (ASB) Vibration Test Report", Rev 2dated April 9, 2006.

The vibration tests indicated that if the vibration becomes excessive, some debris could begenerated from the internals of the canisters. The debris appears to result from two differentmechanisms. One mechanism is the fatigue failure of some of the edges of the wire screens asthey rub or impact against the canister walls. The other mechanism is a wear mechanismprobably due to relative motion between the screens and canister wall that results in the creationof metallic dust or powder. There are indications that canisters are more susceptible togenerating debris if the screens are packed too tightly into the canister.

The tests also indicated that the most likely failure mechanism for the ASBs, that could cause aproblem, is the fatigue failure of the internal screens. This could generate debris of sufficient

320 KING STREET ALEXANDRIA, VA 22314-3230 703-519-0200 FAX: 703-519-0224 hftp://www.mpr.com

Page 5: Attachment 7 Request 4 - Level 1 and 2 Vibration

Mr. Mohammad Molaei - 2 - April 13, 2006

size to cause problems with some components in the main steam system. The attachment to thisletter provides a calculation for vibration acceptance criteria that are based on fatigue testing ofthe ASBs. The acceptance criteria can be summarized as follows:

* The vibration acceleration amplitude in the axial direction should be less than 1.6 g RMSif measured on the blind flange of the ASB and less than 1.5 g RMS if measured on thepipe end of the ASB. This level of vibration is significantly lower than that experiencedby canisters #1 and #5 during the testing and meets the guidance provided by the ASMEBoiler and Pressure Vessel Code, Appendix II, for cyclic testing of components based onthe testing of canister #5 in the third series of tests.

* The vibration acceleration amplitude in the transverse direction at the flange end of theASB should be less than 2.3 g RMS. This corresponds to the limit for no fatigue basedon the tested vibration magnitude and duration according to the ASME Code. It alsocorresponds to about 1/2 of the response levels that were measured in the transversedirection during the vibration testing of the production canister. Based on the test datafor canisters similar to the production canister design, we would not expect anysignificant debris to be generated at this vibration level. In addition, the acceptanceresponse level in the transverse direction at the flange assures that the ASB is not beingsignificantly excited at its natural frequency.

These acceptance levels for vibration are based on the following reasoning and observations:

* The ASBs were subjected to vibrations approximately twice these levels for aconsiderable period of time during the vibration tests at the Quanta Labs. The canistersthat were packed in a manner similar to the production model (canister #5) had nosignificant debris during testing at the higher levels. Using l/2 the levels at which theASBs responded without any observable damage based on external observations madeduring the testing, including inspections for debris from the FME end, provides marginwith respect to the testing without resulting in an unreasonable vibration level,particularly if the ASBs are effective in suppressing the acoustic modes.

* The acceptance criteria meets the fatigue testing requirements of the ASME Boiler andPressure Vessel code as outlined in Appendix II. This assures that fatigue of the screenswill not occur. Fatigue of the screens is the only mechanism identified during the testingthat can generate debris that may have the potential to affect components in the mainsteam system.

* The acceptance levels provided are sufficient, even if the ASBs have no affect on theacoustic response, to allow operation at current EPU vibration levels since the currentacoustic frequencies are well removed from the natural frequencies of the ASBs. Therewould be no amplification of the vibration at the flange end of the ASB.

Page 6: Attachment 7 Request 4 - Level 1 and 2 Vibration

Mr. Mohammad Molaei - 3 - April 13, 2006

* Despite the fact that the ASBs were aligned vertically with the FME at the bottom duringtesting, such that gravitational forces would tend to help debris to escape from the ASBduring the testing, there was no observation that any of the debris that could cause aproblem in the steam piping was able to work its way through the screens inside thecanister at vibratory loads equal to twice the acceptance level criteria for the productioncanister. Therefore, we conclude it would be very difficult for the debris to be dislodgedthrough the screens by vibration when the ASB is in the horizontal orientation andexperiencing only V2 the acceleration in the axial direction than it experienced during thetests.

* Although no wear would be expected at half the vibratory response that produced nowear during testing of the production canister, wear would likely only result in thegeneration of the fine metallic dust that was generated at higher vibration levels for thecanisters that were more tightly packed with screens. We do not consider that such finemetallic dust would pose a problem to the main steam system.

If you have any questions regarding this letter or the conclusions drawn from the test data, pleasegive me a call.

Sincerely,

Hans Giesecke

Attachment

Cc: Mr. David R. Melear Exelon NuclearMr. Robert Stakenborghs Exelon NuclearMr. Guy DeBoo Exelon NuclearMr. Steve Anagnostis Stevenson & AssociatesMr. Roy Hunicutt Exelon Nuclear

Page 7: Attachment 7 Request 4 - Level 1 and 2 Vibration

I*MPRASSOCIATES INCE N Q I N E E R S

April 13, 2006l 101-0009-HDG-02

Mr. Mohammad MolaeiExelon Nuclear4300 Winfield RoadWarrenville, IL 60555

Subject: Vibration Acceptance Criteria for ERV Valve Actuators - Revision I

Reference: Exelon Contract No. 0084512, Release 00022

Dear Mr. Molaei:

The attachment to this letter is Revision 1 of the report that provides the vibration acceptancecriteria for the Electromatic Relief Valve (ERV) pilot valve actuators at Quad Cities. The reportis based on our evaluation of the vibration testing that was performed on the actuators at theQuanta Laboratories in Santa Clara, California in February and March of 2006. Revision 1includes the effect of the March 2006 testing that was conducted to test improvements in theactuator design.

The test results demonstrate that, if the vibration levels in the plant remain below those definedby the acceptance criteria, there is high confidence that the actuators will be capable ofperforming their function for at least one fuel cycle (24 months) at those vibration levels.

If you have any questions regarding this report or the acceptance criteria, or if you needadditional information, please feel free to call.

Sincerely,

Hans Giesecke

Attachment

Cc: Mr. Roy Hunnicutt Exelon NuclearMr. Steve Anagnostis Stevenson & Associates

320 KING STREET ALEXANDRIA, VA 22314-3230 703-519-0200 FAX: 703-51940224 hftp://Www.mpr.com

Page 8: Attachment 7 Request 4 - Level 1 and 2 Vibration

*MPRASSOCIA-TfS WO.ENGINEERS$

Attachment toMPR Letter datedApril 13, 2006

Vlbratfon Acceptance criteria @ hV ve Actuators

Revision 1

'Prepared"by:

Reviewed by:

Approved by:

'A".i ----- a., ;.Hans Giesecke

./6lb, .,-

Robert coward

Thi dcunnthasben pepr~4reiewda~n' a0Q, rit~ the attyAsumirm qIreet f!oT~Ajedi ,as 4*ified 6nte~~ it sua~ aui

Page 9: Attachment 7 Request 4 - Level 1 and 2 Vibration

-MPRA$SOCIATES INtE N G I NE E.R S

Contents

Background .......................................... 4

Simplified Acceptance Criteria for Modified Actuator ..................................... 5

V ibr ation Te st Basis .......................................... 6

Measured Vibrations at EPU Power Levels ............................................ 6

In-Plant Experience ............................................. 6

Enhancements Made to Actuator Design ............................................ 7

Description of Vibration Tests .......................................... 8

Development of Test Plan ............................................. 8

First Series of Tests ............................................ 8

Second Series of Tests ............................................ 10

Basis for Acceptance Criteria for Modified Actuator ..................................... 10

References......................................................................................................... 12

3

Page 10: Attachment 7 Request 4 - Level 1 and 2 Vibration

Background

The main steam piping near the reactor at both Quad Cities units has been experiencingsignificant vibration for some time. This vibration has resulted in damage to the actuators on theElectromatic Relief Valves (ERVs), among other components. The vibration increasedsignificantly (by about a factor of 2) when the plant power level was increased to ExtendedPower Uprate (EPU) conditions. Apparently, the dominant part of the vibration is beinggenerated by the response of the piping to several acoustic modes that exist inside the piping.These acoustic modes are most likely standing pressure waves that form in the standpipes thatattach the ERVs, Safety Relief Valves (SRVs), and Target Rock valve to the main steam piping.Most likely, the acoustic response is excited by turbulence in the main steam flow at theconnecting tees to the standpipes. Since the turbulence spectrum typically increases in bothamplitude and frequency with increasing steam flow, the increase in vibration at EPU powerlevels is significantly higher than at pre-EPU power levels.

Due to damage to the ERV actuators that was discovered at Quad Cities Unit 1 during Q 1 F51,Exelon decided to perform vibration testing of an ERV at the Wyle Laboratories in February2004. These tests are described in Reference I and Figure 3-5 in Reference 1 shows the initialtest configuration, which included an ERV with the attached pilot valve and the pilot valveactuator. The testing resulted in modifications to the actuators to "harden" them against wear byemploying better materials for parts where wear was observed. The modified actuators wereinstalled in both units at Quad Cities and after operating an extended period of time at pre-EPUlevels, they were inspected and no damage was observed. However, after several months ofoperation at EPU power levels, significant damage was discovered on some of the actuators andall actuators had some wear in the bushings and guide posts. Figure 1 is a picture of an actuatorsimilar to the modified actuators that were installed following the February 2004 Wyle testing.The damage to these actuators was concentrated in the guide post-spring-bushing interface due tothe hardened spring getting caught between the post and the bushing, causing considerable wearto all three components due to vibratory motion. Damage also occurred to the pivot plate thatopens the cutoff switch and limits the current to the solenoid when the pilot valve is open. If thisswitch fails to operate, the solenoid will fail in about 30 seconds due to excessive current,making the valve inoperable.

Based on the observed damage, in January 2006 a beveled washer was inserted below thebushings to protect the post and bushing from the spring (see Figure 2) and the plants wererestarted and operated at pre-EPU power levels while a permanent solution to the problem wasbeing investigated. This permanent solution concentrated on the installation of acoustic sidebranches (ASBs) on the standpipes that support the valves to mitigate the acoustic modes inconjunction with modifications to the ERV actuators to make them considerably more resistantto the damage mechanisms that were being observed.

4

Page 11: Attachment 7 Request 4 - Level 1 and 2 Vibration

Figure 3 shows a picture of the newly modified actuator. Vibration testing of the new actuatorwas conducted during February and March of 2006 to test modifications and improve confidencein the new actuator for installation in the plant. The test included testing of alternative designssuch as the design that was damaged during operation in the plant to provide a comparison ofrelative damage levels during the testing. This report evaluates the new design and provides anestimate of the vibration levels that are considered acceptable for operation in the plant.

Simplified Acceptance Criteria for Modified Actuator

The vibration limits specified by the Vibration Acceptance Criteria described below are based onthe testing that was conducted during February and March of 2006. The acceptance criteriaconsiders a broad band random vibration base with a single frequency sine dwell from anacoustic mode such as was measured in the plant during EPU operating conditions. TheVibration Acceptance Criteria is sufficiently high to envelop the vibration levels experienced byERV 3D from Quad Cities Unit 2, the actuator with the highest vibration as measured duringoperation at EPU. Since there is some uncertainty associated with the effect that the ASBs mayhave on the acoustic mode, the testing included excitation of the actuator at various frequencies,including excitation close to resonance, so that a Vibration Acceptance Criteria could beestablished that considered all reasonable possibilities for the frequency of the acoustic mode.However, at lower frequencies a strong acoustic mode could damage the actuator due to thehigher displacements associated with lower frequency at the same acceleration magnitude.Therefore, the acceptable acceleration levels had to be reduced at lower frequencies. In effect, atfrequencies below 100 Hz, the Acceptance Criteria must be limited by displacement amplitudewhereas at high frequencies, the Acceptance Criteria must be limited by acceleration amplitude.

To account for both these phenomena, an acceptance criteria was devised that limits the vibrationat the base of the actuator where it attaches to the yoke of the pilot valve to about /2 the levelstested based on the integrated spectrum RMS values as follows:

* The integrated RMS value for the spectrum of the measured displacement shouldbe less than 2.2 mils RMS. Due to the difficulty of obtaining accurateacceleration values at low frequency, the displacement RMS value should bebased on the frequency interval between 30 and 200 Hz.

* The integrated RMS value for the spectrum of the measured acceleration shouldbe less than 2 g RMS. To be consistent with the displacement value, thefrequency range of integration should also be between 30 Hz and 200 Hz.

* A horizontal value that is the square root of the sum of the squares (SRSS) of thetwo orthogonal horizontal components should be obtained and compared to theacceptance criteria value. The vertical component should be compared directly tothe acceptance criteria value.

Based on the test data, the actuator will be able to withstand vibration levels up to the acceptancecriteria limits for at least one full operating cycle (24 months) without incurring an unacceptableamount of damage that would prevent its operation. The vibration levels should be limited by

5

Page 12: Attachment 7 Request 4 - Level 1 and 2 Vibration

both the acceleration and displacement values. The acceleration value of 2 g RMS will limit theamplitude of the acoustic mode at frequencies above 100 Hz whereas the displacement value of2.2 mils RMS will ensure that the acoustic mode, if its frequency is less than 100 Hz, will not bestrong enough to damage the actuator. The basis for the acceptance criteria is discussed in therest of this report.

Vibration Test Basis

Vibration testing for the ERV actuator was performed at the Quanta Laboratories in Santa Clara,California in two phases during February and March of 2006. The tests are described inReference 2.

Measured Vibrations at EPU Power Levels

The acoustic modes generate single frequency responses that are tuned to each specific standpipeand they exist over a frequency range of about 130 to 160 Hertz, depending on the particularstandpipe involved. Vibration measurements obtained at Quad Cities during operation at EPUindicate that, in general, the vibration levels on Unit 2 are high~r then those on Unit 1. Inparticular, the valve with the highest vibration is ERV 3D on Unit 2 and its vibration isdominated by an acoustic mode with a frequency of about 151 Hz. Figure 4 provides a plot of allthe power spectral densities of the measured locations on the Unit 2 ERVs. The plot is providedin a linear scale to accentuate the dominance of the acoustic modes. The acceleration vibrationspectra for ERV 3D on Unit 2 are plotted separately in Figure 5 and the ones for all the othervalves on Unit 2 are plotted in Figure 6 to demonstrate that the 3D valve is subjected to thehighest vibration levels. In fact, when the spectra from Unit 2 ERV 3E is removed from Figure6, the remaining responses for valves 3B and 3C are much smaller. Consequently, the vibrationspectrum levels from ERV 3D on Quad Cities Unit 2 were used to develop the "base testspectrum". However, the frequency inputs for the base spectrum were expanded to account forthe different frequencies of the various acoustic modes as well as for any impact that the ASBsmay have if they are installed on the standpipes of the valves.

As is seen in Figures 4 through 6, the measured vibration is essentially composed ofmonochromatic accelerations at about 138 Hz, 151 Hz, and 161 Hz with the dominant responseat 151 Hz at an amplitude of about 2 g RMS. The amplitude of the associated displacement isless than one mil.

In-Plant Experience -

The modified actuators that were installed in Unit 1 operated at EPU vibration levels for over 5months and those that were installed in Unit 2 operated at EPU vibration levels for over 6months. Prior to operation at EPU power levels, the Unit 2 actuators operated for over a year atpre-EPU vibration levels, after which they were inspected. No significant damage was identifiedat that time.

However, after the operation at EPU power levels, some actuators had significant damage. Inparticular, the actuator on ERV 3D had significant damage to the posts, the springs, and the

6

Page 13: Attachment 7 Request 4 - Level 1 and 2 Vibration

cutoff switch and was not considered capable of operating. The actuator on ERV 3E also hadsignificant damage to the rods but was still operational. The actuators on ERV 3B and ERV 3Chad some damage to the posts but were still functional. The damage level was comparable to themeasured vibration level since 3D had the highest measured vibration, 3E had the secondhighest, and 3B and 3C had relatively low levels of vibration.

Enhancements Made to Actuator Design

The new actuator design (see Figure 3) incorporated a significant number of improvements,many of which were implemented as a result of lessons learned during the testing. The newactuator provides substantially more support for the guide posts. This was accomplished bymounting the posts to a thicker support plate at the bottom in place of the angle brackets on theoriginal and including a frame that is tied to that plate and supports the tops of the guide posts.In addition, the springs are of a larger diameter and are split into two parts. The ends of thespring were mounted on the outside of both the bushings and a spacer that was added betweenthe two spring parts on each post so the springs would remain separated from the posts. Thisprevents the springs from getting caught between the post and the bushing and limits the wearthat will occur to the springs, the bushings, and the posts. Clearance between the top bushingand the post must be loose enough to prevent binding due to clearances between the plunger andthe frame that allow the plunger to displace at the bottom but must be small enough to limitimpact or fretting wear when the posts vibrate. The new actuator design also includes a siliconeisolation pad that prevents much of the high frequency vibration from reaching the posts. Inaddition, the pivot plate that actuates the cutoff switch to limit current through the solenoidswhen the pilot valve is open was improved by tightening clearances to avoid rattling, addingbushings for the pivot pins, and modifying the material for the pivot pins and bushings toimprove wear characteristics. Finally, the brackets used to attach the actuator components to itsbase were reinforced by gussets to help redistribute stresses over a larger region and procedureswere implemented to ensure there is even loading on the heads of the bolts that secure thesolenoid frame to the base plate of the actuator. The gussets were added halfway through thefirst series of testing due to cracking in the brackets and indicated, by no additional damagethrough the most severe testing period, that they were effective in eliminating the crackingproblem. The modifications to the pivot plate were implemented due to knowledge gainedduring the first series of testing.

During the second series of tests, it was discovered that the clearance for the upper bushings onthe guide rods was too tight, resulting in binding of the bushing on the guide post. The clearancewas increased from 2.5 mils to 15 mils and the leading edge of the bushing was chamfered toreduce the susceptibility for binding. In addition, it was discovered that the bolts that hold theframe on the base plate were not making full contact around their circumference, resulting insignificant bending moment on the head of the bolt and the failure of several bolts early in thesecond round of testing. This oversight was corrected by modifying the production procedure toensure good contact between the head of the bolt and the bearing surface by counter-boring thecontact surface to obtain a good fit. Since the prototype actuator had experienced a significantamount of testing at higher vibration levels without any baseplate bolt failures, and since the newactuator on which the contact was modified completed the testing without any additional boltfailures, it was apparent that the cause of the bolt failures was correctly identified.

7

Page 14: Attachment 7 Request 4 - Level 1 and 2 Vibration

Description of Vibration Tests

The purpose of the vibration testing Was to demonstrate a high confidence level that the modifiedERV actuator could operate for a full fuel cycle without being damaged such that it would nolonger function to operate the ERV. An alternate purpose was to obtain a vibration spectrumenvelope below which only limited damage would be expected so that the envelope could beused for comparison to measured plant vibration spectra. If the plant vibration spectra are belowthis envelope, the actuator would be expected to perform adequately in response to the appliedvibratory loading.

In order to provide confidence in the results of the tests, it was decided to test the originalactuator in conjunction to the others, thereby providing a reference point for comparison. Allactuators were mounted on the same shaker table simultaneously to ensure they all saw the samevibration input.

The results of the testing are covered in Reference 2 and are only described in general here.

Development of Test Plan

The test plan for these tests utilized a conservative "base test spectrum" that envelops themeasured spectra from all the ERV and pilot valve spectra that were obtained from actual plantmeasurements while the plants were operating at EPU power levels. Including the spectra fromthe pilot valves in the base spectrum allowed the actuators to be vibration tested independently ofthe ERV since the applied spectrum was representative of what was applied directly to theactuator in the plant. In order to account for changes in the natural frequency of the acousticmodes that may result from installation of the ASBs, the frequency spectrum was broadened toinclude any possible actuator resonance between the range of 90 Hz and 160 Hz.

Once the "base test spectrum" was defined, the base spectrum was multiplied by a scale factor toprovide a means for adjusting the level of vibration in a controlled manner. The multiplier tothat base spectrum could be used to slowly increase the overall vibration levels and ultimately toaccelerate the wear mechanism so that an equivalent amount of wear could be generated in ashort term test as would be expected to occur in the plant over a full fuel cycle. The inclusion ofthe original actuators on the table was used to demonstrate that sufficient excitation levels werebeing applied to the actuators to represent long term plant conditions. If the original actuatordisplayed damage similar to what occurred in the plant, it would indicate that the alternativeactuators were subjected to realistic accelerated vibration levels during the testing.

First Series of Tests

A test spectrum was designed to envelop any spectrum that would be experienced in the plant.This spectrum included a broadband component of 0.3 g RMS and a series of swept sine inputsthat ensured any resonant frequencies of the actuators were being excited. There were 4 sweptsine inputs, at 2 g RMS each, distributed above 100 Hertz and three additional swept sine inputsbelow 100 Hz scaled in amplitude to maintain the average vibration displacement amplitude tothe same level that would result for a 100 Hz sine component. The low frequency swept sineshave the ability to damage the actuators due to their increased vibration displacement amplitude.

8

Page 15: Attachment 7 Request 4 - Level 1 and 2 Vibration

Since there was very little low frequency input in the plant spectra, it was considered possiblethat too much low frequency input would result in unrealistic damage to the actuators andinvalidate the test results. Details are provided in Reference 2.

The test spectrum was multiplied by a scale factor so that different levels of excitation could beapplied to the actuators in a controlled manner. The testing utilized a gradually increasingmultiplier with detailed inspections conducted prior to each time the multiplier was increased sothat the level and characteristics of the vibration that would cause damage to occur could bedefined. In this manner, the damage that was being incurred by each actuator on the test tablecould be quantified with respect to the severity of the load.

Prior to age-testing of the actuators, the actuators were subjected to sine sweeps to identify theirnatural frequencies and modes. Each actuator was tested individually with tri-axialaccelerometers attached at various locations such as on the top of the guide posts, the plunger,and the support plate. The sine sweeps were conducted at two levels of input and the resultsindicated that the natural frequencies were quite sensitive to input level. In order to account forchanges in the natural frequencies due to input level or changes in the frequency of the acousticmodes that may result from installation of the ASBs, the frequency spectrum was broadened toinclude any possible actuator resonance between the range of 90 Hz and 160 Hz.In the first series of tests, the applied spectra were increased slowly, starting at levels that were1/8 of the base spectrum and finishing at levels that were more than twice the base spectrum..

Damage assessments indicated that the low frequency vibration may have been causing excessdamage to the actuator covers relative to the damage to the posts that was observed in the plant.Since the plant spectra did not have very much low frequency input and the broadbandcomponent of the test spectrum enveloped the plant spectrum at those frequencies, it was decidedto limit the sine wave part of the spectrum to a single frequency sine dwell in conjunction withthe random broadband input to better represent the measured plant conditions. After 20 hours oftesting with this new spectrum with a multiplier of 2.0, significant damage occurred to theoriginal actuator that was similar, though less severe, than that experienced by the most highlydamaged actuator in the plant. The spring on one side of the original actuator broke and becametrapped between the bushing and the guide rod, doing significant damage to the guide rod andresulting in the plunger not being operable. On the other hand, the other two actuators had muchless damage with the Modified GE actuator only experiencing a slight amount of wear, more likepolishing, between the guide posts and the bushings.

Additional vibration testing resulted in the spring on the original actuator wearing all the waythrough the bushing and coming out the top of the actuator cover. Since there were observationholes in the cover above the guide post, the spring became free and no additional damage due tothe spring-guidepost-bushing interaction occurred on this post. However, the spring would haveremained trapped inside the cover during operation in the plant and might have caused additionalwear. Also, every inspection of the original actuator freed up the spring from inside the bushing,interrupting the accelerated damage rate that would have resulted in the plant. The new actuatoragain had only slight wear.

After it had been demonstrated that a spectrum similar to the one measured in the plant wouldresult in damage to the original actuator that was similar to that observed in the plant, the

9

Page 16: Attachment 7 Request 4 - Level 1 and 2 Vibration

frequency of the sine dwell was moved to excite the natural frequency of the new actuator. Amultiplier of 2.0 was still being applied. Despite significant testing with a spectrum that wasspecifically designed to test the new actuator, only about 2 mils of wear was measured on theguide posts of the new actuator. However, a weak spot associated with the cut-off switch thatlimits the current to the solenoid after the valve has opened was identified. The tests indicatedthat wear around the pins about which the plate rotates would likely be the failure mode of thisactuator if the vibration becomes too large.

Second Series of Tests

Due to excessive wear in the pins that secure the pivot plate for the cutout switch, the pins werereplaced with a harder material and a bushing was embedded into the frame to provide betterwear resistance for this part of the actuator. As a result of this modification, a second series oftests were conducted at the Quanta Labs in Santa Clara. This second series included threeactuators; the original design, the prototype that was tested previously, and a production actuatorthat met the criteria necessary for installation in the plant. The second series of testing identifiedseveral additional problems that were resolved as a result of the testing. In addition, the broadband component of the base spectrum was increased from 0.3 g RMS to 0.4 g RMS to providemore margin for the acceptance criteria.

Basis for Acceptance Criteria for Modified Actuator

The testing demonstrated that the design improvements of the modified actuator worked well.

* Support to the posts was effective in reducing post vibration, eliminating distortion of theposts, and maintaining a uniform configuration that allowed the plunger to operate.

* The new bushing and spring design was very effective in eliminating the spring as a sourceof the damage by preventing the springs from becoming trapped between the bushing and thesupport rods where they would induce significant wear of the posts.

* The isolation damper at the base of the actuator was effective in isolating the internals of theactuator from high frequency vibration. However, the angle brackets that tie the actuator toits base developed cracks and had to be reinforced by gussets during the test. The gussetsexperienced enough high level vibration during the latter part of the testing to demonstratethey would not crack during normal operation.

* The pivot plate set screw for the cut-off switch that limits current to the solenoid had notbeen modified at the time the first series of testing was conducted and remained the weakpart of the newly modified actuator design. This deficiency led to the last three actuationtests to be inconclusive during the first series of tests since sparks were generated at the cut-off switch when the plunger hit the pivot plate. The pivot pins continued to experiencesignificant wear. If the clearance around these pins becomes too large, the plate will nolonger rotate to open the switch. The design was modified for the second series of tests toharden the pins and their mating surface in order to reduce wear in this region. The resultsindicated the modification was very successful.

10

Page 17: Attachment 7 Request 4 - Level 1 and 2 Vibration

Since the spectrum the actuators were subjected to had a broadband component and specific sinedwells that were tuned to excite at the actuators natural frequencies, the frequency content of theexcitation was significantly more severe than that which is anticipated in the plant. Based on thetest data, a multiplier of 2.0 resulted in damage to the old actuator that was similar to that seen inthe plant. Therefore, the multiplier of 2.0 for the test period was comparable to extendedoperations in the plant with an effective multiplier of 1.0. Since the new actuator experiencedlittle damage during the second series of testing, it should be acceptable for vibration levelsequivalent to the "base test spectrum" with a multiplier of 1.0. The equivalence of short termtesting with a multiplier of 2.0 to an extended operating cycle at a multiplier of 1.0 is alsoindicated by the relative damage that occurred to the actuators after operating in the plant at pre-EPU levels compared to operating at EPU levels, particularly when the impact of the springbeing caught inside the bushing is removed from consideration.

As a result of the above analysis, we consider a reasonable limit for the vibration spectrum of thenew Quad Cities ERV actuators consists of the following:

* Broadband acceleration input at the base of the actuator must be less than 0.4 g RMSwhich is equivalent to an average amplitude of 0.00089 g2/Hz. The integrated vibrationinput should be less than the 0.4 g RMS value. Individual responses slightly in excess ofthe 0.00089 g2/Hz value are considered acceptable as long as the integrated value of thebroadband component remains below 0.4 g RMS.

* In addition to the broadband excitation, a monochromatic frequency due to the acousticmode can be tolerated if the amplitude of that frequency is less than 2.0 g RMS at 100 Hzto 200 Hz. Below 100 Hz, the displacement amplitude of the monochromatic vibrationmust remain below the 100 Hz 2 g RMS value. Figure 7 provides a plot of the vibrationlimit as a function of frequency for the monochromatic input at the base of the actuatorresulting from excitation by the acoustic mode. This graph provides the maximumacceleration of a single sine wave at a specific frequency as a function of that frequency.The graph does not represent a spectrum with multiple frequency inputs. Numeric valuesof the acceptable limit are listed as a function of frequency in Table 1. The broadbandbackground spectrum of 0.4 g RMS can be tolerated in addition to this monochromaticfrequency excitation.

The vibration limits specified consider a broad band random vibration base with a singlefrequency sine dwell from the acoustic mode. The frequency of the acoustic mode is notspecified but its amplitude must be contained by the envelope provided in column 2 of Table 1and shown in Figure 7. Table 1 also provides the RMS value of the complete spectrum for boththe acceleration and the displacement. For simplicity in application, a conservative criteria basedon the full spectrum can be implemented by limiting the RMS value of the acceleration to lessthan 2 g RMS while simultaneously limiting the RMS value of the displacement to less than 2.2mils RMS. In this manner, the vibration amplitude is limited by the displacement for frequenciesbelow 100 Hz while limiting the acceleration for frequencies above 100 Hz.

These vibration limits are based on the measured vibration of the table on which the actuatorswere tested. Therefore, the acceptance criteria must be compared to measured values from the

11

Page 18: Attachment 7 Request 4 - Level 1 and 2 Vibration

plant that are located on the pilot valve yoke or the actuator base plate where it attaches to theyoke.

References

1. SIA Report SIR-04-023, Rev. 0, "Quad Cities ERV Vibration Testing Assessment", datedFebruary, 2004

2. 06Q4568-DR-005, "Quad Cities ERV Pilot Valve Actuator Vibration Test Report", Rev. 1,dated April 11, 2006.

Table 1. Acceptable Response Magnitude at Base of Actuator

Frequency Acoustic Mode Broadband Total Total RMSHertz g RMS g RMS g RMS Displacement

20 0.08 0.4 0.4079 0.002230 0.18 0.4 0.4386 0.002240 0.32 0.4 0.5123 0.002250 0.50 0.4 0.6403 0.002260 0.72 0.4 0.8236 0.002270 0.98 0.4 1.0585 0.002280 1.28 0.4 1.3410 0.002290 1.62 0.4 1.6687 0.0022

100 2.00 0.4 2.0396 0.0022110 2.00 0.4 2.0396 0.0019120 2.00 0.4 2.0396 0.0017130 2.00 0.4 2.0396 0.0016140 2.00 0.4 2.0396 0.0015150 2.00 0.4 2.0396 0.0014160 2.00 0.4 2.0396 0.0014170 2.00 0.4 2.0396 0.0013180 2.00 0.4 2.0396 0.0012190 2.00 0.4 2.0396 0.0012200 2.00 0.4 2.0396 0.0012

12

Page 19: Attachment 7 Request 4 - Level 1 and 2 Vibration

Figure 1. ERV Actuator Similar to the One that was Damaged in the Plant (No Cover)

13

U

Page 20: Attachment 7 Request 4 - Level 1 and 2 Vibration

Figure 2. Modification to Post-Spring-Bushing Interface Using a Beveled Washer

14

Page 21: Attachment 7 Request 4 - Level 1 and 2 Vibration

Figure 3. New Actuator Design for Testing

15

Page 22: Attachment 7 Request 4 - Level 1 and 2 Vibration

Unit 2 EPU test TC41, 5122105, 930 Mwe - Power Spectrum for All Valvei

2.50

2.00

Nz< 1.500c0

1.00

0.50

0.00

- EEX

EEY

- BEY

BEZBEPX

B PZsEY

-- -- -sEZ

0 PX

-PY

CEX11----' CEY

-- CEZ

,-DEY

__ DEZ

200 DPX

_ DPY

0 20 40 60 80 100 120 140 160 180

Frequency (Hz)

Figure 4. EPU Vibration Spectra for all Unit 2 ERVs

Unit 2 EPU test TC41, 5122/05, 930 Mwe - Power Spectrum for ERV 3D Only

2.50

2.00

,0

1.00

0.50

0.00

DEX

-DEY

-DEZ

- DPX

-DPY

-DPZ

0 20 40 60 80 100 120 140 160 180 200

Frequency (Hz)

Figure 5. EPU Vibration Spectra for ERV 3D Only

16

U

Page 23: Attachment 7 Request 4 - Level 1 and 2 Vibration

Unit 2 EPU test TC41, 5122/05,930 Mwe - Power Spectrum Al Valves Except 3D - E

2.50 - -EEY2.50 EEZ

EX2.00 PY

YEFZ

, 1.50 -BDE

.- BEY0a BEZ

~i1.00

BPY

0.50 BPZ

CEX(

0.00 Ad CEY0 20 40 60 80 100 120 140 160 180 200 CEZ

Frequency (Hz)

Figure 6. EPU Vibration Spectra for all Unit 2 ERVs Except 3D

Limits on Vibration Amplitude3.0

2.5

2.0

1.5

0.5

0.00 20 40 60 80 100 120 140 160 180 200

Frequency (Hertz)

Figure 7. Acceptable Vibration Magnitude at the base of the New Actuator due to theAcoustic Mode as a Function of the Acoustic Mode Frequency

17