COMMERCIALwww.braycommercialdivision.com ATT-E-1
Pressure Independent Control ValveModulating control valve, dynamic balancing valve and differential pressure control valve in one body. Field adjustable, self-balancing, dynamic flow control valves that are pressure independent, two-way and modulating to accept analog signal inputs. Each valve has an adjustable maximum flow rate setting to enable flow limitation and balancing to the coil or zone that the valve is controlling.
Advantages of Bray ATT Valves -
1. Installation costs - up to 60% fewer valves are required. Due to the automatic balancing of each heat exchanger, no other differential pressure control valves or balancing valves are required. This simplifies installation, reduces installed costs, and improves accuracy and reliability.
2. Operating costs - Minimizes pumping, heating and cooling costs by eliminating overflow through the coil and by reducing pressure drop.
3. The location of the Bray ATT automatic balancing valve does not require lengths of pipe before or after the valve.
Features and Benefits
• Field Adjustable, up to 41 different flow rates in one and the same cartridge
Flow rate can be changed on demand without removing the cartridge from the valve body
• 100% Authority Pressure Independent
The valve will always use full stroke of the control element offering the 100% authority for any of its 41 flow settings
• Up to 60 GPM of flow capacity for high volume applications
• NPT or BSP female by female threaded connection
Secure, leak free connection to most common applications
• Optional Pressure/Temperature Measurement Ports
Allows for verifying operating differential pressure across the valve
- System Types: - Media:
Fan Coil, Hot Water, Chilled Water,
Air Handling Units 50/50 Glycol Solutions.
COMMERCIAL ATT-E SeriesAdjustable PIC Valves
2 Way • 1-1/2”- 2” • ATT-E - AutoTouch Terminal
05/26/16
COMMERCIALwww.braycommercialdivision.comATT-E-2
ATT-E - Valve SpecificationsBody Style E 1-1/2” – 2”
Hot Water, Chilled Water, 50/50 Glycol Solutions
Valve Body Pressure Rating Water
Maximum
Technical SpecificationsService
Operational ∆P
Operational ∆P
Pressure rating: 360 psi / (25 Bar)
Close-Off Pressure Maximum
Minimum
87 psid / (6 Bar)
2.3 psid / (0.16 Bar)
58 psid / (4 Bar)
Ambient Valve & Actuator Temperature Rating 36˚ to 122˚ F (-2.2˚ to 50˚ C)
Leakage
(Body E) Fixed female NPT
Body
Materials
Forged Brass ASTM CuZn40Pb2
Cartridge
Diaphragm
Disclaimer - The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Bray office. Bray, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
POM (Polyoxymethylene) - with Stainless Steel trim
Hydrogenated Acrylonitrile-Butadiene-Rubber
O-Rings EPDM
8.36 to 60.0 GPM, (1900 to 13647 L/hr)Flow Rate Range
End Connections
Media Temperature Rating
Valve BodyOnly
Weights (lbs.) 1-1/2” (Body E) 10.1lb., 4.58kg
2“ (Body E) 9.3 lb., 4.22kg
ANSI / FCI 70-2 2006 (R1982) / IEC 60534-4 Class - Class IV- < 0.01%
-4°F to 248°F (-20°C to 120°C)
COMMERCIALwww.braycommercialdivision.com ATT-E-3
ATT-E - Valve Specifications ATT-E - Actuator Specifications
ATT-E Actuators FH.0.2 FH.0.4 FH.1.2
Supply voltage 24V AC/DC ±10%, 50/60 Hz
Motor Bi-directional synchronous
(2-position / 3-point floating)
Power consumption 7VA 7VA 9VA
Control signal Analog 0(2)-10V DCDigital
Analog 0(2)-10V DC
Position output 0(2)-10V DC No 0(2)-10V DC
Failsafe function No No Yes
Auto stroke Yes No Yes
Operation time 50 Hz: 28 Seconds/mm
Humidity rating <95% Non Condensing
Closing Point Adjustment During operation the actuator will self-adjust according to the closing point of the valve
Protection NEMA 3S/IP54, class II
Cable 4 wires 22 AWG halogenfree cable, 3.2 feet
3 wires 22 AWG halogenfree cable, 3.2 feet
4 wires 22 AWG halogenfree cable, 3.2 feet
Weight 0.55 lbs 0.55 lbs 0.66 lbs
FH.0.2 & FH.0.4 Series FH.1.2 Series
Auto Stroke OptionWith the auto stroke option activated, the actuator will make one full cycle every 24 hours, if the actuator constantly has been in fully open or fully closed position during the previous 24 hours.
This operation will clear up any possible impurities accumulated in the valve, and re-calculate the end positions.
COMMERCIALwww.braycommercialdivision.comATT-E-4
ATT-E - Piping Diagrams
ATT-E - Actuator Wiring
RETURN
SUPPLY
COIL
RETURN
SUPPLY
COIL
Blac
k
Power 24V AC/DC
Ground/common
Gre
en
Whi
te
Feedback signal0(2)-10V DCInput signal
0(2)-10V DC
Red
FH.0.4 Series Actuator
FH.0.2 & FH.1.2 Series Actuators
Default is “Normally Open” unless stated.
Blac
k
Power 24V AC/DC
Ground/common
Whi
te
Red
OpenClose
FH.0.4 Actuator FH.0.4 Actuator
FH.0.4 ActuatorFH.0.4 Actuator
FH.0.2 / FH.1.2 Actuator
2-Position, Normally Closed
Blac
k
Power 24V AC/DC
Ground/common
Whi
te
Red
Open Close
2-Position, Normally Open
Blac
k
Power 24V AC/DC
Ground/common
Whi
te
Red
OpenStop
Close
3-Point-Floating, Normally Closed
Blac
k
Power 24V AC/DC
Ground/common
Whi
te
Red
OpenStop
Close
3-Point-Floating, Normally Open
COMMERCIALwww.braycommercialdivision.com ATT-E-5
Note * Add end connection length to body length.Note ** Weight for valve body only.Note *** For complete unit based on minimum DP.
ModelNumber
ValveModel
ValveSize
BodyTappings
A BFC
(FH.0.4 & FH.0.2)
D(FH.1.2)
** ***Weight(lbs.)
Cv(GPM)
ATT-E-150-E-X-X/Act.
ATT-E-200-E-X-X/Act.1/4”
10.1
9.3E
1 1/2”7.52 3.95 7.57 8.16 174.4
2”
Valve model: EShown with
FH.1.2 Actuator
Valve model: EShown with
FH.0.X Actuator
D
B
A
CF F
B
A
ATT-E - Valve/Actuator Dimensions
ATT-E - Strainer Dimensions
ATT-E - Piping Diagrams
ATT-E - Actuator Wiring
A
C
B
2”
7.5 1.9 3.71 1/2” 40
50 9.5 1.6 4.3
A B CConnection
in. mm
Dimensions are shown in inches and are approximate.
COMMERCIALwww.braycommercialdivision.com ATT-E-6
ATT-E - Flow Rate Table
ATT-ESetting
16-400 kPad · 2.3-58 psid
l/sec l/hr GPM0.528 1900 8.36 1.00.633 2278 10.0 1.10.738 2655 11.7 1.20.843 3033 13.3 1.30.947 3410 15.0 1.41.05 3787 16.7 1.51.16 4163 18.3 1.61.26 4537 20.0 1.71.36 4909 21.6 1.81.47 5279 23.2 1.91.57 5646 24.8 2.01.67 6011 26.4 2.11.77 6372 28.0 2.21.87 6730 29.6 2.31.97 7083 31.2 2.42.06 7432 32.7 2.52.16 7776 34.2 2.62.25 8115 35.7 2.72.35 8449 37.2 2.82.44 8777 38.6 2.92.53 9098 40.0 3.02.61 9413 41.4 3.12.70 9721 42.8 3.22.78 10021 44.1 3.32.86 10314 45.4 3.42.94 10599 46.6 3.53.02 10875 47.8 3.63.10 11142 49.0 3.73.17 11400 50.2 3.83.24 11649 51.3 3.93.30 11888 52.3 4.03.37 12116 53.3 4.13.43 12334 54.3 4.23.48 12540 55.2 4.33.54 12735 56.0 4.43.59 12919 56.8 4.53.64 13090 57.6 4.63.68 13249 58.3 4.73.72 13395 58.9 4.83.76 13527 59.5 4.93.79 13647 60.0 5.0
A micrometer setting of 3.4 as illustrated abovecorresponds to a maximum flow rate of: 45.4 GPM
Use the special designed key for micrometer setting.
Accuracy: Greatest of either ±10% of controlled flow rate or ±5% of maximum flow rate.
COMMERCIALwww.braycommercialdivision.comATT-E-7
ATT-E - Flow Rate Table ATT-E - Model Number
FH.0.2NFP21.6E150EATT-ESample Part NumberSizes (in/(mm)) Cartridge
E 1-1/2(40),2 (50)
E
in.SIZE
CODE
STYLE
CODE
mm
150 1-1/2 40
200 2 50Pressure range, ∆P(psi) Flow rate(GPM)
E Extra Flow 8.36 - 602.3 to 58 psid.
Description NF NPT female threads
NFP NPT female threads with pressure/temperature ports
BF BSP female threads
BFP BSP female threads with pressure/temperature ports
Body Style(see body style configurationchart below)
Valve Size
Flow Rate
Cartridge
Connection/Port Code
Actuator
8.39to 60
FH.0.2 24V Modulating (with feedback signal)FH.0.4 24V 3-Point Floating
FH.1.2 24V Modulating (with feedback signal and fail-safe)
Reference the previously listed Flow Rate Table and select the desiredflow rate GPM that is listed for the cartridge that you are using.
BodyType
NPT Female
Sizes(in. mm)
Pressure/Temp PortsCartridgeBody Style
Config-urations
BSP Female
E E 1-1/2 (40)2 (50)
*Example: Extra Flow Cartridge, 1-1/2", Body Style E, 21.6 GPM, Female NPT with PT ports with FH.0.2 actuator ATT-E-150-E-21.6-NFP/FH.02