atr 142 - apar.pl · • separate the control line from the power wires. • avoid proximity of...
TRANSCRIPT
ATR 142Controller / Regolatore
User manual / Manuale d’uso
Table of contents1 Safety standards ................................................................................ 62 Model Identification ......................................................................... 63 Technical Data ................................................................................... 7
3.1 General Features ...................................................................... 73.2 Hardware Features .................................................................. 73.3 Software Features ................................................................... 8
4 Dimensions and Installation .......................................................... 85 Electrical wirings ............................................................................... 9
5.1 Wiring diagram ........................................................................ 96 Configuration EASYUP ................................................................... 137 Display and keys functions ........................................................... 14
7.1 Numeric indicators (Display) .............................................. 147.2 Meaning of status lights (Led) ............................................ 147.3 Keys ............................................................................................ 15
8 Controller functions........................................................................ 158.1 Modifying main setpoint and alarm setpoint values .. 158.2 Auto-Tune ................................................................................168.3 Manual tuning........................................................................168.4 Automatic tuning ..................................................................168.5 Soft start ...................................................................................168.6 Automatic / manual regulation for % output control . 178.7 Pre-Programmed cycle ........................................................ 178.8 Memory card (optional) .......................................................188.9 Loading default values......................................................... 198.10 LATCH ON functions.............................................................. 198.11 Digital input functions .........................................................208.12 Dual action heating-cooling ..............................................22
9 Timer operation ...............................................................................249.1 Single timer .............................................................................249.2 Dual timer ................................................................................24
9.3 Dual sequential timer ...........................................................259.4 Dual timer loop ......................................................................269.5 Relating timers to alarms ....................................................26
10 Serial Communication ...................................................................2710.1 Slave ..........................................................................................2710.2 Master .......................................................................................32
10.2.1 Master mode in retransmission ............................3210.2.2 Master Mode Remote process ...............................34
11 Configuration ...................................................................................3411.1 Modify Configuration Parameter ......................................34
12 Table of configuration parameters ............................................3513 Alarm Intervention Modes ............................................................5014 Table of Anomaly Signals ..............................................................54
Sommario1 Norme di sicurezza .........................................................................582 Identificazione del modello ..........................................................583 Dati tecnici ........................................................................................59
3.1 Caratteristiche generali .......................................................593.2 Caratteristiche hardware ....................................................593.3 Caratteristiche software ......................................................60
4 Dimensioni e installazione ...........................................................605 Collegamenti elettrici .................................................................... 61
5.1 Schema di collegamento ..................................................... 616 Configurazione EASYUP ................................................................657 Funzione dei visualizzatori e tasti ...............................................66
7.1 Indicatori numerici (display) ...............................................667.2 Significato delle spie di stato (led) .....................................667.3 Tasti ...........................................................................................67
8 Funzioni del regolatore..................................................................678.1 Modifica valore setpoint principale e di allarme ..........678.2 Auto-tune.................................................................................68
8.3 Lancio del Tuning Manuale ................................................688.4 Tuning Automatico ...............................................................688.5 Soft Start ..................................................................................688.6 Regolazione automatico/manuale per controllo %
uscita .........................................................................................698.7 Ciclo pre-programmato .......................................................698.8 Memory Card (opzionale) ...................................................708.9 Caricamento valori di default ............................................718.10 Funzione LATCH ON ..............................................................728.11 Funzioni da ingresso digitale .............................................738.12 Funzionamento in doppia azione (caldo-freddo) ........ 74
9 Funzioni timer ..................................................................................779.1 Singolo timer ..........................................................................779.2 Doppio timer ...........................................................................789.3 Doppio timer sequenziale ...................................................789.4 Doppio timer loop .................................................................799.5 Associazione Timer - Allarmi ..............................................80
10 Comunicazione seriale ..................................................................8110.1 Slave ..........................................................................................8110.2 Master .......................................................................................85
10.2.1 Modalità master in ritrasmissione .......................8510.2.2 Modalità master processo remoto ......................87
11 Configurazione ................................................................................8811.1 Modifica parametro di configurazione ...........................88
12 Tabella parametri di configurazione .........................................8913 Modi d’intervento allarme ..........................................................10414 Tabella segnalazioni anomalie .................................................108
6 - ATR142 - User manual
IntroductionThank you for choosing a Pixsys controller.With the ATR142 model Pixsys makes available in a single device multiple options related to sensor input and actuators command in addition to the extended power range 24…230 Vac/Vdc. With 17 sensors to select and outputs configurable as relay or SSR command, the user or retailer can reduce stock by rationalising investment and device availability. The series includes a version equipped with serial communication RS485 Modbus. The configuration is further simplified by the Memory cards which are provided with internal battery and therefore do not require cabling to power the controller.
1 Safety standardsCarefully read the instructions and safety measures in this manual before using the device. Disconnect power before performing any interventions on the electrical connections or hardware settings. Only qualified personnel may use/perform maintenance in full respect of the technical data and declared environmental conditions.Do not dispose of electrical appliances together with household waste. In compliance with the European Directive 2002/96/EC, waste electrical equipment must be collected separately for eco-compatible reuse or recycling.
2 Model IdentificationRefer to the table below to easily select preferred model.All versions available with power 24…230 Vac/Vdc +/-15% 50/60Hz – 4,6VAATR142-ABC 2 relays (8A+5A) + 1 SSRATR142-ABC-T 1 relays 8A + 1 Ssr + RS485
User manual - ATR142- 7
3 Technical Data3.1 General FeaturesDisplay 4 0.40 inch displays + 4 0.30 displaysOperating temperature 1 relays 8A + 1 Ssr + RS485
Sealing IP65 front panel (with gasket)IP30 box, IP20 terminals
Material Polycarbonate UL94V2 self-extinguishingWeight 100 g
3.2 Hardware Features
Analogue input
AN1. Configurable via software. Thermocouple type: K, S, R, J. Automatic compensation of cold junction from 0°C to 50°C.Thermoresistance: PT100, PT500, PT1000, Ni100, PTC1K, NTC10K (β 3435K). Linear: 0-10V, 0-20 or 4-20mA, 0-40mVPotentiometers:6KΩ, 150KΩ,
Tolerance (25°C)+/-0.2 % ± 1 digit (full scale) for thermocouple input, thermo- resistance and V/mA.Cold junction accuracy 0.1°C/°CImpedance:0-10V: Ri>110KΩ0-20mA: Ri<5Ω4-20mA: Ri<5Ω0-40mV: Ri>1MΩ
Relay output
2 relays (ATR142-ABC)1 relay (ATR142-ABC-T)Configurable as command and/or alarm output
Contacts:Q1: 8A-250V~for resistive loadsQ2: 5A-250V~for resistive loads
SSR output
1 SSR Configurable as command output and/or alarm output.
12Vdc/30mA
8 - ATR142 - User manual
SupplyPower supply 24..230 Vac/Vdc +/-15% 50/60Hz
Power consumption 4.6VA
3.3 Software FeaturesRegulation algorithms
ON-OFF with hysteresis.P, PI, PID, PD with proportional time
Proportional band 0...9999°C or °F
Integral time 0,0...999,9 sec (0 excluded)Derivative time 0,0...999,9 sec (0 excluded)
Controller functions
Manual or automatic Tuning, confi gurable alarms, protection of command and alarm setpoints, activation of functions via digital input, preset cycle with Start/Stop.
4 Dimensions and Installation
U1
C1
CN1 16
1 2 3
Dima di foratura28.5 x 70.5 mm
Frontal panel cut-out
Spessore suggerito2 ÷ 8 mm
Suggested thickness
77 mm
35 m
m
53 mm7
42mminserimento
Memory Card
42mminsertMemory Card
PIXSYS
Memory Card (optional)with battery
Memory Card (optional)Cod. MEMORY 2100.30.005
Cod. MEMORY 2100.30.003
Guarnizione per 32x74Cod. 1600.00.082 (optional)Gasket for 32x74
User manual - ATR142- 9
5 Electrical wiringsAlthough this controller was designed to resist electro-magnetic interferences in industrial environments, please observe following safety guidelines:• Separate the control line from the power wires.• Avoid proximity of remote control switches, electroma-
gnetic contactors, powerful engines and in all instances use specific filters.
• Avoid proximity of power groups, especially those with phase control
5.1 Wiring diagramPIXSYS
10A 230VCosf 1
3A 230VCosf 0.8
Q1 PTC/NTC
- +Tc
+VDC
SSR
1 2 3 4 5 6 7 8 9 10 11 12- +
I
V/I+-PT/NI100/1K
2 wire 4/20mA
Power5A 230VCosf 1
1A 230VCosf 0.8
Q2
Memory1
ATRxxx-xx
- +
SUPPLY
PIXSYS
10A 23a0VCosf 1
3A 230VCosf 0.8
Q1 PTC/NTC
- +Tc
+VDC
SSR
1 2 3 4 5 6 7 8 9 10 11 12- +
I
V/I+-PT/NI100/1K
2 wire 4/20mA
Power
Memory1
- +ATRxxx-xxT
- +
RS485SUPPLY
ATR142-ABC ATR142-ABC-T
5.1.a Power Supply
12
24...230VAC/DC
Switching power supply with extended range 24..230 Vac/dc ±15% 50/60Hz – 5,5VA.
5.1.b AN1 Analogue Input
-
+Tc11
12
Shield/Schermo
For thermocouples K, S, R, J.• Comply with polarity• For possible extensions, use
compensated cable and terminals suitable for the thermocouples used(compensated)
• When shielded cable is used, it should be grounded at one side only
10 - ATR142 - User manual
1011
12
PT/NI100
Shield/Schermo For thermoresistances PT100, NI100• For the three-wire connection use
wires with the same section• For the two-wire connection short-
circuit terminals 10 and 12• When shielded cable is used, it should
be grounded at one side only10
11
12
RED
WHITE
RED
Shield/Schermo
PTC/NTC
1011
For thermoresistances NTC, PTC, PT500, PT1000 e potentiometers• When shielded cable is used, it should
be grounded at one side only to avoid ground loop currents
Shield/Schermo
+VDC
910
1112
V/I+
-
For linear signals V/mA• Comply with polarity• When shielded cable is used, it should
be grounded at one side only
5.1.c Examples of Connection for linear input
0...10V
1112
For signals 0..10V• Comply with polarity
PRESSURE TRANSMITTERSENSORE DI PRESSIONE
0/4...20mA
A
B
C
1112
9
For signals 0/4..20mA with three-wire sensor• Comply with polarityC = Sensor outputB = Sensor groundA = Sensor power supply (12V/30mA)
User manual - ATR142- 11
EXTERNAL SUPPLYALIMENTAZIONE ESTERNA
PRESSURE TRANSMITTERSENSORE DI PRESSIONE
0/4...20mA
B
C
1112
For signals 0/4..20mA with external power of sensor• Comply with polarityC = Sensor outputB = Sensor ground
PRESSURE TRANSMITTERSENSORE DI PRESSIONE
C
4...20mA
A
129
For signals 0/4..20mA with two-wire sensor• Comply with polarityC = Sensor outputA = Sensor power supply (12V/30mA)
5.1.d Serial input
117
6 -+
Shield/Schermo
RS485
RS485 Modbus RTU communicationDo not use LT (line termination) resistors• For networks with more than
five instruments supply in low voltage
12 - ATR142 - User manual
5.1.e Relay Q1 Output
76
54
Q1
Q2
3
Capacity:• Q1: 8A, 250Vac,resistive loads,105
operations. 30/3A, 250Vac, cosφ=0.3, 105 operations.
• Q2: 5A, 250Vac, resistive loads, 105 operations. 20/2A, 250Vac, cosφ=0.3, 105 operations.
5.1.f SSR output
SSR8
9 SSR command output 12V/30mA
5.1.g Digital Input
1011
Digital input according to parameter DGT.i.The use of digital input in this version is possible only with TC sensors or 0..10V, 0/4..20mA and 0...40mV signals
User manual - ATR142- 13
6 Configuration EASYUPTo simplify the setting of parameters and the integration of the different components involved in the control system, Pixsys introduces the EASY-UP coding which allows to set sensors and/or command outputs in a single step.By means of the code listed in the data sheet enclosed to the sensor or actuator (SSR, motorized valve etc..) the EASY-UP coding will set the relevant main parameters on the controllers (ex. selection of PT100 on parameter “Sensor” and the corresponding measuring range on parameters “Lower and Upper limits of setpoint”).Different codes may be entered on the controllers in sequence to configure inputs, control output or retransmission of signal.
14 - ATR142 - User manual
7 Display and keys functions
543 876 2
1M T R
2 3
9
10
12
11
ATR 142
1
7.1 Numeric indicators (Display)
1 1234
Normally displays the process. During the confi guration phase, it displays the parameter being inserted.
2 1234
Normally displays the setpoint. During the confi guration phase, it displays the parameter value being inserted.
7.2 Meaning of status lights (Led)
3 1ON when the output command is on. For motorised valve command, led is ON when valve is opening and blinks when closing.
4 2 ON when alarm 1 is on.
5 3 ON when alarm 2 is on.
6 M ON when the “Manual” function is on.
7 TON when the controller is running an “Autotuning” cycle.
8 RON when the controller communicates via serial port.
User manual - ATR142- 15
7.3 Keys
9 “m ”
• Allows to decrease main setpoint.• During configuration phase, allows to slide
through parameters. Together with SET key it modifies them.
• Pressed after SET key it allows to decrease alarm setpoint.
10 “n”
• Allows to increase main setpoint.• During configuration phase, allows to slide
through parameters. Together with SET key it modifies them.
• Pressed after SET key it allows to increase alarm setpoint.
11 SET• Allows to display alarm setpoint and runs the
autotuning function.• Allows to modify configuration parameters.
12 FNC• Allows to run the autotuning function and to
select Manual/automatic operation.• Allows to enter/exit for configurator procedure.
8 Controller functions8.1 Modifying main setpoint and alarm
setpoint valuesSetpoint value can be changed by keyboard as follows:
Press Effect Do
9 “n” or “m” Value on display 2 changes
Increase or decrease main setpoint
10 SET Visualize alarm setpoint on display 1
11 “n” or “m” Value on display 2 changes
Increase or decrease the alarm set point value
16 - ATR142 - User manual
8.2 Auto-TuneTuning procedure calculates the controller parameters and can be manual or automatic according to selection on parameter 46 tune.
8.3 Manual tuningManual procedure allows the user greater flexibility to decide when to update PID algorithm parameters. The procedure can be activated in two ways.• Running Tuning by keyboard: Press FNC key until display 1 shows the writing tune with
display 2 showing oFF, press “n”, display 2 shows on. The T led switches on and the procedure begins.
• Running Tuning by digital input: Select tune on parameter 50 dGt.i.. At first activation of
digital input (commutation on front panel) T led switches ON and at second activation switches off.
8.4 Automatic tuningAutomatic tuning activates whenever the controller is switched on or when the setpoint is modified to a value over 35%.To avoid an overshoot, the threshold where the controller calculates new PID parameters is determined by the setpoint value minus the “Set Deviation Tune” (Parameter 47 s.d.tu.).To exit Tuning and keep PID values unchanged, just press the FNC key until display 1 shows the writing tune with the display showing on, press “m”, display 2 shows off.The T led switches off and the procedure finishes.
8.5 Soft startTo reach the setpoint the controller can follow a gradient expressed in units (e.g. degree/hour).Enter this gradient on parameter 51 Grad. with the chosen units/hour; only on subsequent activation the controller uses soft start function.
User manual - ATR142- 17
Automatic/manual tuning cannot be enabled if the Soft start is active.
8.6 Automatic / manual regulation for % output control
This function allows to select automatic functioning or manual command of the output percentage.Parameter 49 Au.ma., can select two methods.• First selection en.: pressing the FNC key display 1 shows
p.---, while display 2 shows Auto. Press the “n” key to select man. mode; it is now possible,
to change the output percentage using the keys “n” and “m ”. To return to automatic mode, using the same procedure, select auto on display 2: M led switches off and functioning returns to automatic mode.
• Second selection en.st.: same functioning, but with two important variants:
- If there is a temporary power failure or after switch-off, manual functioning as well as the previous output percentage value will be maintained at restarting.
- If the sensor breaks during automatic functioning, controller moves to manual mode while maintaining the output percentage command unchanged as generated by the PID immediately before breakage.
8.7 Pre-Programmed cyclePre-programmed cycle function activates by setting pr.cY. on parameter 48 op.Mo.Controller reaches setpoint1 basing on the gradient set on parameter 51 Grad., then it reaches max. power up to setpoint2. When the process reaches max. power, this setpoint is maintained for the time set on parameter 52 ma.t.i.At expiry, process will reach ambient temperature according to gradient entered on parameter 64 fa.Gr., then command output will be disabled and display will visualize Stop.
18 - ATR142 - User manual
Setp
oint
Time
Setpoint 1
Setpoint 2
Maintenance timeMantenimento
CoolingRa�reddamentoMax Power
Max Potenza
Rising gradientGradiente di salita
Cycle starts at each activation of the controller, or via digital input if it is enabled for this type of functioning (parameter 50 dGt.i.).
8.8 Memory card (optional)Parameters and setpoint values can be duplicated from one controller to another using the Memory card. There are two methods:• With the controller connected to the power supply Insert the memory card when the controller is off. On activation display 1 shows memo and display 2 show
---- (Only if the correct values are saved in the memory card). By pressing the “n” key display 2 shows Load, then confirm using the FNC key. The controller loads the new data and starts again.
• With the controller not connected to power supply. The memory card is equipped with an internal battery with
an autonomy of about 1000 operations. Insert the memory card and press the programming
button.When writing the parameters, the led turns to red and on completing the procedure it turns to green. It is possible to repeat the procedure without any particular attention.
Updating Memory CardTo update the memory card values, follow the procedure described for the first method, setting display 2 to ---- so as not to load the parameters on controller1.Enter configuration level and change at least one parameter. Exit configuration. Changes are saved automatically.
1 If on activation the controller does not display memo it means no data have been saved on the memory card, but it is possible to update values.
User manual - ATR142- 19
8.9 Loading default valuesThis procedure allows to restore factory settings of the device
Press Effect Do
1 FNC for 3s.
Display 1 shows 0000 with the 1st digit flashing, while display 2 shows pass
2 “n” and “m”
Change the flashing digit and move to the next one using the SET key.
Enter password 9999
3 SET to confirm
Instrument loads default settings
Turn off and restart the instrument
8.10 LATCH ON functionsFor use with input Pot.1 (potentiometer 6KΩ) and Pot.2 (potentiometer 150KΩ) and with linear input (0…10V, 0...40mV, 0/4…20mA), it is possible to associate start value of the scale (parameter 6 Lo.L.i.) to the minimum position of the sensor and value of the scale end (parameter 7 up.L.i.) to the maximum position of the sensor (parameter 8 Latc. configured as std.). It is also possible to fix the point in which the controller will display 0 (however keeping the scale range between Lo.L.i. and up.L.i.) using the “virtual zero” option by setting u.0st. or u.0in. in parameter 8 Latc. If you set u.0in. the virtual zero will reset after each activation of the device; if you set u.0st. the virtual zero remains fixed once tuned.To use the LATCH ON function, configure according to required operation the parameter Latc.2
2 The tuning procedure starts by exiting the configuration after changing the parameter.
20 - ATR142 - User manual
For the calibration procedure refer to the following table:Press Eff ect Do
1 FNCExit parameters confi guration. Display 2 shows the writing Latc.
Place the sensor on the minimum operating position (associated with Lo.L.i.)
2 “m”Set the value to minimum.The display shows Low
Place the sensor on the maximum operating position (associated with up.L.i.)
3 “n”Set the value to maximum.The display shows HiGt
To exit standard procedure press FNC.For “virtual zero” settings place the sensor on zero point.
4 SET
Set the virtual zero value. The display shows uirt. NB: for selection of u.0in. the procedure on point 4 should be followed at each re-activation.
To exit the procedure press FNC.
MaxMin Zero
8.11 Digital input functionsOn ATR142 model, digital input can be enabled by using parameters 48 op.mo. and 50 dGt.i.• Parameter 48 op.mo. cont.: Operating as controller. NB: When using this settings, parameter 50 dGt.i. is
ignored.
User manual - ATR142- 21
2t.s.: Switch two thresholds setpoint: with open contact ATR142 regulates on SET1; with closed contact regulates on SET2;
2t.s.i.: Switch two thresholds setpoint: setpoint selection is done by an impulse on digital input;
3t.s.i.: Switch three thresholds setpoint by an impulse on digital input;
4t.s.i: Switch four thresholds setpoint by an impulse on digital input;
p.r.c.Y.: Pre-programmed cycle (parameter 7.7). Setpoints values can be modified any time pressing SET
key.
• Parameter 50 dGt.i. NB: Settings on this parameter are available only if cont. or
pr.cY. are selected on parameter 48 op.mo. st.st.: Start / Stop; operating on digital input the controller
switches alternatively from start to stop; rn.n.o.: Run N.O. Controller is in start only with closed
input; rn.n.c. : Run N.C. Controller is in start only with open input; L.c.n.o.: With closed input allows to lock the reading of
sensors; Lc.n.c.: With open input allows to lock the reading of
sensors; tune: Enables/disables Tuning function if parameter 46
tune is selected as man.; a.ma.i.: If parameter 49 au.ma. is selected as en. or en.st.
controller switch from automatic to manual functioning; a.ma.c.: If parameter 49 au.ma. is selected as en. or en.st.
ATR142 works in automatic mode if input is open or in manual mode if input is closed.
t.1.s.s.: timer 1 Start/Stop, (parameter 8.)
NB: digital input functions are not available with sensors PT100, NI100, NTC, PTC, PT500, PT1000 and potentiometers.
22 - ATR142 - User manual
8.12 Dual action heating-coolingATR142 is suitable also for systems requiring a combined heating-cooling action.Main command output must be configured foe hearting PID (act.t. = Heat and p.b. must be greater than 0), and one of the alarms (AL.1 or AL.2) must be configured as cooL. Command output must be connected to the actuator responsible for heat, while the alarm output will control cooling action.Parameters to configure for the Heating PID are:act.t. = Heat Command output type (Heating)p.b. : Heating proportional bandt.i. : Integral time of heating and coolingt.d. : Derivative time of heating and coolingt.c. : Heating time cycleThe parameters to configure for the Cooling PID are the following (example: action associated to alarm1):AL.1 = cooL Alarm1 selection (cooling)p.b.m. : Proportional band multiplier ou.d.b. : Overlapping/Dead bandco.t.c. : Cooling time cycleParameter p.b.m. (that ranges from 1.00 to 5.00) determines the proportional band of cooling basing on the formula:Cooling proportional band = p.b. * p.b.m.This gives a proportional band for cooling which will be the same as heating band if p.b.m. = 1.00, or 5 times greater if p.b.m. = 5.00. The integral time and derivative time are the same for both actions.Parameter ou.d.b. determines the overlapping percentage between the two actions. For systems in which the heating and cooling output must never be simultaneously active a dead band (ou.d.b. ≤ 0) can be configured, and viceversa an overlapping (ou.d.b. > 0).
The following diagram shows an example of dual PID action (heating-cooling) with t.i. = 0 and t.d. = 0.
User manual - ATR142- 23
ACTIVE
ACTIVE
SPV
PV
x = COOL
x = COOL
x = COOL
< 0
= 0
> 0
(HEAT)
(HEAT)
(HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
SPV
PV
ACTIVE
ACTIVE
SPV
PV
ACTIVE
ACTIVE
ACTIVE
ACTIVE
SPV
PV
x = COOL
x = COOL
x = COOL
< 0
= 0
> 0
(HEAT)
(HEAT)
(HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
SPV
PV
ACTIVE
ACTIVE
SPV
PV
ACTIVE
ACTIVE
ACTIVE
ACTIVE
SPV
PV
x = COOL
x = COOL
x = COOL
< 0
= 0
> 0
(HEAT)
(HEAT)
(HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
SPV
PV
ACTIVE
ACTIVE
SPV
PV
ACTIVE
ACTIVE
Parameter co.t.c. has the same meaning of the cycle time t.c. for heating.Parameter coo.F. (cooling fluid) pre-selects the proportional band multiplier P.b.m. and the cooling PID cycle time co.t.c. basing on the type of cooling fluid:
coo.f. Cooling fluid type P.b.m. co.t.c.Air Air 1.00 10oiL Oil 1.25 4H2o Water 2.50 2
24 - ATR142 - User manual
9 Timer operationTimer operation is enabled by parameter 63 tmr.f. To modify duration of counting time, follow the steps below:
Press Effect Do
1 SETPress until tim.1 or tim.2 visualized on display 1.
2 “n” and “m” Digits on display 2 changes.
Increase or decrease time value for the selected timer.
Below a description of available options for Timer operation.
9.1 Single timerThis option enables one single Timer and the time is selectable by the operator. To achieve this operation set parameter 63 tmr.f. as follows:• s.tm.s. (Single Timer Seconds) time-basis in seconds (mm.ss)• s.tm.m. (Single Timer Minutes) time-basis in minutes (hh.mm)To start/stop the Timer, press FNC for 1s.During the counting, Led R is On and display2 shows decrementing time. At elapsing of Timer, led R switches off and display 2 flashes, visualising the programmed time until any key is pressed.Start/Stop of Timer is possibile also by digital input, selecting t.1.s.s. on parameter 50 dGt.i..
9.2 Dual timerThis option enables two Timers and the time is selectable by the operator: timers cannot be started at same time.To achieve this operation set parameter 63 as follows:• d.tm.s. (Double Timer Seconds) time-basis in seconds (mm.ss)• d.tm.m. (Double Timer Minutes) time-basis in minutes (hh.mm)Check the table below for the Start procedure:
User manual - ATR142- 25
Press Effect Do
1 FNC Press until tim.1 or tim.2 visualized on display 1.
2 “n”
Start the Timer. Display 2 shows decrementing time and Led R switches on (fixed for timer 1, flashing for timer 2).
Back to point 1, after selection of running Timer press “n” to stop counting. Led R switches off.
At elapsing of Timer the led R switches off and display 2 flashes, showing the programmed time until any key is pressed. Start/Stop of Timer by digital input is NOT available for dual timer mode.
9.3 Dual sequential timerThis option enables two Timers and the time is selectable by the operator. At elapsing of Timer 1, counting of Timer 2 will automatically start . At elapsing of Timer 2, counting will stop. To achieve operation of dual sequential Timer set the parameter 63 tmr.f. as follows: • d.s.t.s. (Double Sequential Timer Seconds) time-basis in
seconds (mm.ss)• d.s.t.m. (Double Sequential Timer Minutes) time-basis in
minutes (hh.mm)To start/stop the Timer, press key FNC for 1s. During the counting, Led R is On (fixed for Timer 1, flashing for Timer 2) and display2 shows decrementing time. Start is always made on Timer 1. At elapsing of Timer, led R is switched off and display 2 shows setpoint value. Start/Stop of Timer is possibile also by digital input, selecting t.1.s.s. on parameter 50 dGt.i.
26 - ATR142 - User manual
9.4 Dual timer loopThis option enables 2 Timers and the time value is selectable by the operator. At elapsing of one Timer, the other one will automatically start and this sequence is repeated cycling.To achieve operation of dual timer loop set the parameter 63 tmr.f. as follows:• d.t.L.s. (Double Timer Loop Seconds) time-basis in seconds
(mm.ss)• d.t.L.M. (Double Timer Loop Minutes) time-basis in minutes
(hh.mm)To start/stop the Timer, press FNC for 1s.During the counting, Led R is On (fixed for Timer1, flashing for Timer 2) and display 2 shows decrementing time. Start is always made on Timer 1.Start/Stop of Timer is possibile also by digital input, selecting t.1.s.s. on parameter 50 dGt.i.
9.5 Relating timers to alarmsIt is possible to associate the alarms (relay or SSR outputs) to the timers by parameters 23 aL.1 and 31 aL.2. The table below is showing the combined operation of alarms and Timers.
Selectionpar. 23 or 31
Description
t.1.s.a.Timer 1 Start Alarm
Alarm active as long as Timer 1 is in Start mode (Timer active)
t.1.E.a.Timer 1 End Alarm
Alarm active at elapsing of Timer1 until any key is pressed. Option not available for Dual sequential Timer and Dual Timer Loop.
t.1.W.a.Timer 1 Warning Expiring
Alarm active for the last 5” of Timer1
t.2.s.a.Timer 2 Start Alarm
Alarm active as long as Timer 2 is in Start mode (Timer active)
User manual - ATR142- 27
t.2.e.a.Timer 2 End Alarm
Alarm active at elapsing of Timer2 until any key is pressed. Option not available for Dual sequential Timer and Dual Timer Loop.
t.2.w.e.Timer 2 Warning Expiring
Alarm active for the last 5” of Timer2
t.1.2.s.Timer 1-2 Start Alarm
Alarm active as long as Timers 1 and 2 are in Start mode (Timers active)
t.1.2.e.Timer 1-2 End Alarm
Alarm active at elapsing of Timers 1 and 2 until any key is pressed. Option not available for Dual sequential Timer and Dual Timer Loop.
t.1.2.w.Timer 1-2 Warning expiring
Alarm active for the last 5” of Timers 1 and 2.
10 Serial Communication10.1 SlaveATR142-ABC-T is equipped with RS485, it can receive and broadcast data via serial communication using MODBUS RTU protocol. The device operates as slave if parameter 59 mast. is set as dis. This function enables the control of multiple devices connected to a supervisory system (SCADA).Each controller will answer to a master query only if the query contains same address as on parameter sL.ad. The permitted addresses range from 1 to 254 and there should not be controllers with the same address on the same line.Address 255 can be used by the master to communicate with all the connected equipment (broadcast mode), while with 0 all the devices receive the command, but no answer is expected.ATR142 can introduce an answer delay (in milliseconds) to master request. This delay has to be set on parameter 58 se.de..
28 - ATR142 - User manual
At each parameter configuration, the device stores changed values in the EEPROM memory (100000 writing cycles), while setpoints are stored with a delay of 10 seconds after last modification. NB: modifications made to words different from those described in the following table can lead to instrument malfunction.
Modbus RTU protocol features
Baud-rate
Selectable on parameter 564.8k 4800bit/sec9.6k 9600bit/sec19.2k 19200bit/sec28.8k 28800bit/sec38.4k 38400bit/sec57.6k 57600bit/sec
Format 8, N, 1 (8bit, no parity, 1 stop)
Supported functions
WORD READING (max 20 word) (0x03, 0x04)SINGLE WORD WRITING (0x06)MULTIPLE WORDS WRITING (max 20 word) (0x10)
The list below includes all available addresses:
RO = Read Only R/W = Read/Write WO = Write Only
Modbus address
DescriptionRead Write
Reset value
0 Device type RO EEPROM1 Software version RO EEPROM5 Slave Address R/W EEPROM6 Boot version RO EEPROM50 Automatic addressing WO -51 System code comparison WO -
User manual - ATR142- 29
500
Loading default values:9999 restore all values9998 restore all values except for baud-rate and slave address 9997 restore all values except for slave address 9996 restore all values except for baud-rate
WO 0
1000Process (with tenths of degree for temperature sensors; digits for linear sensors)
RO -
1001 Setpoint1 R/W EEPROM1002 Setpoint2 R/W EEPROM1003 Setpoint3 R/W EEPROM1004 Setpoint4 R/W EEPROM1005 Alarm1 R/W EEPROM1006 Alarm2 R/W EEPROM1007 Setpoint gradient RO EEPROM
1008
Outputs status (0=off, 1=on) Bit 0 = Q1 relayBit 1 = Q2 relayBit 2 = SSR
RO 0
1009 Heating output percentage (0-10000) RO 0
1010 Cooling output percentage (0-10000) RO 0
1011Alarms status (0=none, 1=active)Bit0 = Alarm 1Bit1 = Alarm 2
RO 0
1012
Manual reset:write 0 to reset all the alarms.In reading(0=not resettable, 1=resettable):Bit0 = Alarm 1Bit1 = Alarm 2
WO 0
30 - ATR142 - User manual
1013
Error flags Bit0 = Eeprom writing errorBit1 = Eeprom reading errorBit2 = Cold junction errorBit3 = Process error (sensor)Bit4 = Generic errorBit5 = Hardware errorBit6 = Master off-lineBit7 = Missing calibration data
RO 0
1014 Cold junction temperature(tenths of degree) RO -
1015Start/Stop0=controller in STOP1=controller in START
R/W 0
1016Lock conversion ON/OFF0=Lock conversion off1=Lock conversion on
R/W 0
1017Tuning ON/OFF0=Tuning off1=Tuning on
R/W 0
1018Automatic/manual selection0=automatic1=manual
R/W 0
1019 OFF LINE* time (milliseconds) R/W 0
1100 Process visualized (decimal as display) RO -
1101 Visualized Setpoint 1 (decimal as display) R/W EEPROM
1102 Visualized Setpoint 2 (decimal as display) R/W EEPROM
1103 Visualized Setpoint 3 (decimal as display) R/W EEPROM
1104 Visualized Setpoint 4 (decimal as display) R/W EEPROM
1105 Visualized Alarm 1 (decimal as display) R/W EEPROM
User manual - ATR142- 31
1106 Visualized Alarm 2 (decimal as display) R/W EEPROM
1107 Setpoint gradient (decimal as display) RO EEPROM
1108 Heating output percentage (0-1000) RO 0
1109 Heating output percentage (0-100) RO 0
1110 Cooling output percentage (0-1000) RO 0
1111 Cooling output percentage (0-100) RO 0
2001 Parameter 1 R/W EEPROM... ... ... ...2064 Parameter 64 R/W EEPROM
3000 Disabling serial control of machine** WO 0
3001 First word display1 (ASCII) R/W 0... ….. R/W 03008 Eighth word display1 (ASCII) R/W 03009 First word display2 (ASCII) R/W 0... ….. R/W 03016 Eighth word display2 (ASCII) R/W 0
3017
Word LEDBit 0 = LED 1Bit 1 = LED 2Bit 2 = LED 3Bit 3 = LED MANBit 4 = LED TUNBit 5 = LED REM
R/W 0
3018
Word keys (write 1 to command keys)Bit 0 = “m”Bit 1 = “n”Bit 2 = SETBit 3 = FNC
R/W 0
32 - ATR142 - User manual
3019
Word serial outputsBit 0 = Q1 relayBit 1 = Q2 relayBit 2 = SSR
R/W 0
3020
Word serial outputs state if off-lineBit 0 = Q1 relayBit 1 = Q2 relayBit 2 = SSR
R/W 0
3021 Word serial process R/W 0* If value is 0, the control is disabled. If different from 0, it is the max.
time which can elapse between two pollings before the controller goes off-line. If it goes off-line, the controller returns to Stop mode, the control output is disabled but the alarms are active.
** By writing 1 on this word, the effects of the writing are cancelled on all the Modbus addresses from 3001 to 3022. Control therefore returns to the controller.
10.2 MasterThe device works as master if value selected on parameter 59 mast. is other than dis.
10.2.1 Master mode in retransmissionSelecting this mode, the device will write the value to be retransmitted to the address selected on parameter 60 ADD.R on the slave devices having same ID as value selected on parameter 57 SL.AD. Regarding retransmission of setpoint values, after writing the value on slaves, ATR142 starts reading the corresponding word, so that any modification of value on the slave will be automatically updated also on the Master. Two successive pollings will be delayed for the time selected on parameter 57 SE.DE.The following table includes the options allowing the Master mode in retransmission and the relevant retransmitted value.
User manual - ATR142- 33
mast. Descriptionw.pro.Write Process Write process value
r.w.co.Read/Write Command Setpoint
Write and read command setpoint value
w.ou.p.Write Output Percentage
Write output percentage rated by P.I.D. function (Range 0-10000)
r.w.a.1Read/Write Alarm 1 Write and read alarm 1 setpoint value
The read/written value might be rescaled according to the proportion described in the following table:
mast.Value limits input Limits of rescaled valueMin Max Min Max
w.pro.Write Process
Lo.L.i.Lower Limit Input
up.L.i.Upper Limit Input
Lo.L.r.Lower Limit Re-transmis-sion
up.L.r.Upper Limit Re-transmis-sion
r.w.co.Read/Write Command Setpoint
Lo.L.s.Lower Limit Setpoint
up.L.s.Upper Limit Setpoint
Lo.L.r.Lower Limit Re-transmis-sion
up.L.r.Upper Limit Re-transmis-sion
w.ou.p.Write Output Percentage
0 10000
Lo.L.r.Lower Limit Re-transmis-sion
up.L.r.Upper Limit Re-transmis-sion
r.w.a.1Read/Write Alarm 1
Lo.L.s.Lower Limit Setpoint
up.L.s.Upper Limit Setpoint
Lo.L.r.Lower Limit Re-transmis-sion
up.L.r.Upper Limit Re-transmis-sion
34 - ATR142 - User manual
The input value (included between minimum and max limit) is linearly converted into the retransmitted value which is included between min and max output value. Rescaling is not executed if parameters Lo.L.r. and up.L.r. have the same value.
10.2.2 Master Mode Remote processTo enable this function it is necessary to select r.pro. on parameter 59 mast. In this mode the process value on ATR142 is a value read via serial communication. The ID of the slave must be same as value selected on parameter 57 sL.ad. and the word to read is selected on parameter 60 add.r. Two successive pollings will be delayed for the time selected on parameter 57 se.de. The read value might be rescaled according to the proportion described in the following table:
mast.Limits of read value Limits of rescaled value
Min Max Min Max
r.pro.Read Process
Lo.L.r.Lower Limit Re-transmis-sion
up.L.r.Upper Limit Re-transmis-sion
Lo.L.i.Lower Limit Input
up.L.i.Upper Limit Input
11 Configuration11.1 Modify Configuration ParameterFor configuration parameters (parameter 11.)
Press Effect Do
1 FNC for 3s
Display 1 shows 0000 with the 1st digit flashing, while display 2 shows pass.
2 “n” and “m”
Change the flashing digit and move to the next one using the SET key.
Enter password 1234
User manual - ATR142- 35
3 SET to confirm
Display 1 shows the first parameter and display 2 shows the value.
4 “n” and “m” Slide up/down through parameters
5SET +“n” and “m”
Increase or decrease the value displayed by pressing firstly SET and then an arrow key.
Enter the new data which will be saved on releasing the keys. To change another parameter return to point 4.
6 FNC
End of configuration parameter change.The controller exits from programming.
12 Table of configuration parametersThe following table includes all parameters. Some of them will not be visible on the models which are not provided with relevant hardware features.
1 c.out Command Outputselect command output type.c.o2c.o1 > Default (Factory setting)c.ssrc.uaL.
36 - ATR142 - User manual
ATR142-ABCCommand Alarm 1 Alarm 2
c.o1 Q1 Q2 SSRc.o2 Q2 Q1 SSRc.ssr SSR Q1 Q2c.uaL. Q1(opens) Q2(closes) SSR -
ATR142-ABC-TCommand Alarm 1
c.o1 Q1 SSRc.ssr SSR Q1c.uaL. Q1(opens) SSR(closes) -
2 SEN. Sensoranalogue input configuration.Tc.k Tc-K -260…1360°C > DefaultTc.s Tc-S -40…1760°CTc.r Tc-R -40…1760°CTc.J Tc-J -200…1200°Cpt PT100 -200…600°Cpt1 PT100 -200…140°Cni NI100 -60…180°Cntc NTC10K -40…125°Cptc PTC1K -50…150°Cpts PT500 -100…600°Cpt1k PT1000 -100…600°C0.10 0…10Volt0.20 0…20mA4.20 4…20mA0.40 0…40mVoltpot.1 Potenz. Max 6KΩ F.S.pot.2 Potenz. Max 150KΩ F.S.
User manual - ATR142- 37
3 d.p. Decimal Pointselect number of displayed decimal points.0 > Default0.0 1 Decimal0.00 2 Decimals0.000 3 Decimals
4 Lo.L.s. Lower Limit Setpointlower limit setpoint.-999…+9999 [digit3] (degrees.tenths for temperature sensors) Default: 0.
5 UP.L.S. Upper Limit Setpointupper limit setpoint.-999…+9999 [digit3] (degrees.tenths for temperature sensors) Default: 1750.
6 Lo.L.i. Lower Linear Inputlower range limit AN1 only for linear input.-999…+9999 [digit3] Default: 0.
7 up.L.i. Upper Linear Inputupper range limit AN1 only for linear input.-999…+9999 [digit3] Default: 1000.
8 Latc. Latch On Functionautomatic setting of limits for Linear input.dis. Disabled > Defaultstd. Standardv.0.st. Virtual Zero Stored (parameter 8.10)v.0.in. Virtual Zero Initialized (parameter 8.10)
38 - ATR142 - User manual
9 o.caL. Offset Calibrationnumber added/subtracted to process value visualized on display (usually correcting the ambient temperature value).-999…+1000 [digit3] for linear sensors and potentiome-ters.-99.9…+100.0 (degrees.tenths for temperature sensors). > Default: 0.0.
10 G.caL. Gain Calibrationthis % is multiplied with displayed value to calibrate the process value. -99.9%…+100.0% > Default: 0.0
11 act.t. Action typeregulation typeheat Heating (N.A.) > DefaultcooL, Cooling (N.C.)H.o.o.s. If process is above setpoint, output is disabled
(Heating).
12 c.re. Command Resettype of reset for state of command contact (always automatic in PID functioning).a.re. Automatic Reset > Defaultm.re. Manual Resetm.re.s. Manual Reset Stored
13 c.s.e. Command State Errorstate of contact for command output in case of error.c.o. > Defaultc.c.
14 c.Ld. Command Ledstate of OUT1 led corresponding to the relevant contact.c.o. c.c. > Default
User manual - ATR142- 39
15 c.HY. Command Hysteresishysteresis in ON/OFF or dead band in P.I.D.-999…+999 [digit3], (degrees.tenths for temperature sensors) > Default: 0.0
16 c.de. Command Delay(only in ON/OFF functioning).(In case of servo valve it also functions in PID and represents the delay between the opening and closure of the two contacts).-180…+180 seconds, tenths of second in case of servo valve.Negative: delay in switching off phase.Positive: delay in activation phase.Default: 0.
17 c.s.p. Command Setpoint Protectionallow/deny modifications of command setpoint by frontal keyboard.free > DefaultLock. Locked
18 p.b. Proportional Bandprocess inertia in units (°C if temperature).0 on/off if t.i. equal to 0. > Default1-9999 [digit3], (degrees for temperature sensors).
19 t.i. Integral Timeprocess inertia in seconds0.0-999.9 sec. (0 excludes integral) > Default: 0.
20 t.d. Derivative Timenormally ¼ of integral time.0.0-999.9 sec. (0 excludes derivative) > Default: 0.
3 The display of decimal point depends on the setting of parameter sen.and the parameter d.p.
40 - ATR142 - User manual
21 t.c. Cycle TimeCycle time for time-proportioning output (10/15sec for PID contactors, 1 sec for PID on SSR or value declared by manufacturer for motorised valves) 0.1-300.0 sec. > Default: 10.0.For motorised valve min. time is 1.0 sec
22 o.po.L. Output Power Limitlimit of output power %.10-100 % > Default: 100
23 aL.1 Alarmoperating mode for Alarm 1. Intervention of the alarm is associated to AL1.dis. Disabled > Defaulta.aL. Absolute Alarm (parameter 12)b.aL. Band Alarm (parameter 12)H.d.aL. High Deviation Alarm (parameter 12)L.d.aL. Low Deviation Alarm (parameter 12)a.c.aL. Absolute Command setpoint Alarmst.aL. Start Alarm, Active in RuncooL. Coolingt.1.s.a. Timer 1 Start Alarmt.1.e.a. Timer 1 End Alarmt.1.w.e. Timer 1 Warning Expiringt.2.s.a. Timer 2 Start Alarmt.2.e.a. Timer 2 End Alarmt.2.w.e. Timer 2 Warning Expiringt.1.2.s. Timer 1-2 Start Alarmt.1.2.e. Timer 1-2 End Alarmt.1.2.w. Timer 1-2 Warning Expiring
User manual - ATR142- 41
24 a.1.s.o. Alarm 1 State Outputalarm 1 output contact and intervention typen.o.s. (n.o. start) Normally open, active at start >
Defaultn.c.s. (n.c. start) Normally closed, active at start.n.o.t. (n.o. threshold) Normally open, active on
reaching alarm4.n.c.t. (n.c. threshold) Normally closed on reaching
alarm4.
25 a.1.re. Alarm 1 Resettype of Reset for contact of alarm 1.a.re. Automatic Reset > Defaultm.re. Manual Resetm.re.s. Manual Reset Stored
26 a.1.s.e. Alarm 1 State Errorstate of contact for alarm 1 output in case of error.c.o. > Defaultc.c.
27 a.1.Ld. Alarm 1 Ledstate of OUT2 led corresponding to the relative contact.c.o.c.c. > Default
28 a.1.HY. Alarm 1 Hysteresis-999…+999 [digit5], (degrees.tenths for temperature sensors).
4 On activation the output is inhibited if the controller is in alarm mode. Activates only if alarm condition reappers after that it was restored.
5 The display of decimal point depends on the setting of parameter sen.and the parameter d.p.
42 - ATR142 - User manual
29 a.1.de. Alarm 1 Delay-180…+180 Sec. > Default: 0.Negative: delay at exit from alarmPositive: delay at starting of alarm
30 a.1.s.p. Alarm 1 Setpoint Protectiondoes not allow the user to modify setpoint.Free > DefaultLock. LockedHide Locked and hidden
31 aL.2 Alarm 2Alarm 2 selection. Alarm intervention is associated to AL2.dis. Disabled > Defaulta.aL. Absolute Alarmb.aL. Band AlarmH.d.aL. High Deviation AlarmL.d.aL. Low Deviation Alarma.c.aL. Absolute Command setpoint Alarmst.aL. Start Alarm, Attivo in RunCooL Coolingt.1.s.a. Timer 1 Start Alarmt.1.e.a. Timer 1 End Alarmt.1.w.e. Timer 1 Warning Expiringt.2.s.a. Timer 2 Start Alarmt.2.e.a. Timer 2 End Alarmt.2.w.e. Timer 2 Warning Expiringt.1.2.s. Timer 1-2 Start Alarmt.1.2.e. Timer 1-2 End Alarmt.1.2.w. Timer 1-2 Warning Expiring
User manual - ATR142- 43
32 a.2.s.o. Alarm 2 State Outputalarm 2 output contact and intervention type.n.o.s. (n.o. start) Normally open, active at start. >
Defaultn.c.s. (n.c. start) Normally closed, active at start.n.o.t. (n.o. threshold) Normally open, active on
reaching alarm6
n.c.t. (n.c. threshold) Normally closed, active on reaching alarm6
33 a.2.re. Alarm 2 Resettype of Reset for contact of alarm 2.a.re. Automatic Reset > Defaultm.re. Manual Resetm.re.s. Manual Reset Stored
34 a.2.s.e. Alarm 2 State Errorstate of contact for alarm 2 output in case of error.c.o. > Defaultc.c.
35 a.2.Ld. Alarm 2 Ledstate of OUT2 led corresponding to relative contact.n.o.n.c. > Default
36 a.2.HY. Alarm 2 Hysteresis-999…+999 [digit7], (degrees.tenths for temperature sensors). > Default: 0.
37 a.2.de. Alarm 2 Delay-180…+180 Sec. > Default: 0.Negative: delay in alarm output phase.Positive: delay in alarm entry phase.
6 On activation the output is inhibited if the controller is in alarm mode. Activates only if alarm condition reappers, after that it was restored.
44 - ATR142 - User manual
38 a.2.s.p. Alarm 2 Setpoint ProtectionAlarm 2 set protection.Does not allow operator to change setpoint value.free > DefaultLock. LockedHide Locked and hidden
39 coo.f. Cooling Fluidselect type of cooling fluid for Heating/Cooling PID (parameter 7.12)air Air > DefaultoiL OilH2o Water
40 p.b.m. Proportional Band Multiplier1.00-5.00 > Default: 1.00. (parameter 7.12)
41 ov.d.b. Overlap/Dead Bandoverlapping/Dead band (parameter 7.12)-20.0-50.0% > Default: 0.
42 co.t.c. Cooling Cycle Timecycle time for cooling output.1-300 sec. > Default: 10.
43 c.fLt. Conversion FilterADC filter, number of means on analogue-digital conversions.dis. Disabled2.s.m. 2 Samples Mean3.s.m. 3 Samples Mean4.s.m. 4 Samples Mean5.s.m. 5 Samples Mean6.s.m. 6 Samples Mean7.s.m. 7 Samples Mean8.s.m. 8 Samples Mean
User manual - ATR142- 45
9.s.m. 9 Samples Mean10.s.m. 10 Samples Mean > Default11.s.m. 11 Samples Mean12.s.m. 12 Samples Mean13.s.m. 13 Samples Mean14.s.m. 14 Samples Mean15.s.m. 15 Samples Mean
44 c.frn. Conversion FrequencyFrequency of sampling for analogue-digital converter.242H. 242 Hz Max ADC conversion frequency123H. 123 Hz62H. 62 Hz50H. 50 Hz39H. 39 Hz33.2H. 33.2 Hz19.6H. 19.6 Hz16.7H. 16.7 Hz > Default12.5H. 12.5 Hz10H. 10 Hz8.33H. 8.33 Hz6.25H. 6.25 Hz4.17H. 4.17 Hz Min. ADC conversion frequency
45 v.fLt. Visualization Filterslow down the refresh of display in order to simplify the reading (keeping unchanged the ADC conversion frequency)dis. DisabledptcH Pitchfork filter > Defaultfi.or. First Orderf.or.p. First Order with Pitchfork2.s.m. 2 Samples Mean3.s.m. 3 Samples Mean4.s.m. 4 Samples Mean5.s.m. 5 Samples Mean6.s.m. 6 Samples Mean
46 - ATR142 - User manual
7.s.m. 7 Samples Mean8.s.m. 8 Samples Mean9.s.m. 9 Samples Mean10.s.m. 10 Samples Mean
46 tune Tunetuning type selectiondis. Disabled > Defaultauto Automatic. PID parameters are calculated at
each activation and/or change of setpoint.man. Manual. Launch by keyboard or by digital input.once Once (P.I.D. parameters calculation only at first
start)
47 s.d.tu. Setpoint Deviation Tuneselect the deviation from the command setpoint as threshold used by Autotuning to calculate PID parameters.0-5000 [digit7], (degrees.tenths for temperature sensors) > Default: 10.
48 op.mo. Operating Modeselect operating mode (parameter 7.11)cont. Controller > Defaultpr.cY. Programmed Cycle2t.s. 2 Thresholds Switch2t.s.i. 2 Thresholds Switch Impulsive3t.s.i. 3 Thresholds Switch Impulsive4t.s.i. 4 Thresholds Switch Impulsive
49 au.ma. Automatic/Manualenable automatic/manual selection. (parameter 7.6)dis. Disabled > Defaulten. Enableden.st. Enabled Stored
User manual - ATR142- 47
50 dGt.i. Digital InputDigital input functioning. (parameter 7.11)Parameter 48 selection must be cont. or Pr.cy.dis. Disabled > Defaultst.st. Start/Stoprn.n.o. Run n.o.rn.n.c. Run n.c.L.c.n.o. Lock Conversion n.o. (Lock visualisation on
display with N.O. contact)L.c.n.c. Lock Conversion n.c. (Lock visualisation on
display with N.C. contact)tune Tune > Manuala.ma.i. Automatic Manual impulsea.ma.c. Automatic Manual Contactt.1.s.s. Timer 1 Start Stop
51 Grad. GradientRising gradient for soft start or pre-programmed cycle0 Disabled > Default: 0.1-9999 Digit/time7 (degrees/hours with display of tenths if temperature)
52 ma.ti. Maintenance Timemaintenance time for pre-programmed cycle00.00-24.00 hh.mm > Default: 00.00
7 The display of decimal point depends on the setting of parameter sen.and the parameter d.p.
48 - ATR142 - User manual
53 u.m.c.p. User Menu Cycle ProgrammedAllows the rising/falling gradient and the maintenance time to be changed from the user menu in pre-program-med cycle functioning. (parameter 7.7)dis. Disabled > Defaultri.Gr. Rising Gradient (modify gradient)ma.t.i. Maintenance Time (modify time)r.G.m.t. Rising Gradient and Maintenance Time (modify
both)fa.Gr. Falling Gradient (modify cooling gradient)r.f.Gr. Rising and Falling Gradient (modify rising and
cooling gradient)f.G.m.t. Falling Gradient and Maintenance TimeaLL. All (modify all parameters for pre-programmed
cyle)
54 vi.tY. Visualization Typeselect visualization for display 1 and 21.p.2.s. 1 Process, 2 Setpoint > Default1.p.2.H. 1 Process, 2 Hide after 3 sec.1.s.2.p. 1 Setpoint, 2 Process.1.s.2.H. 1 Setpoint, 2 Hide after 3 sec.
55 deGr. Degreeselect degree typec Celsius > DefaultF Fahrenheit
56 bd.rt. Baud Rateselect baud rate for serial communication4.8k9.6k19.2k > Default28.8k38.4k 57.6k
User manual - ATR142- 49
57 sL.ad. Slave Addressselect slave address for serial communication0 – 255 > Default: 254.
58 se.de. Serial Delayselect serial delay0 – 100 milliseconds > Default: 20.
59 mast. Masterselect master mode. (parameter 9.2)dis. Disable > Defaultw.pro Write Processr.w.co. Read Write Command Setpointw.ou.p. Write Output Percentager.w.a.1 Read Write Alarm 1 Setpointr.pro. Read Process
60 add.r. Address Retransmissionselect address for retransmission.0x0000 – 0xFFFF hexadecimal > Default: 0x03E9.
61 Lo.L.r. Lower Limit Retransmissionlower limit retransmission range.-999 - 9999 [digit8], (degrees for temperature sensors) > Default: 0.
62 up.L.r. Upper Limit Retransmissionupper limit retransmission range9.-999 – 9999 [digit8], (degrees for temperature sensors) > Default: 0.
8 The display of decimal point depends on the setting of parameter sen.and the parameter d.p.
9 If parameter 61 Lo.L.r. and 62 up.L.r. have the same value, retransmit-ted value is not rescaled.
50 - ATR142 - User manual
63 tmr.f. Timer Functionenable 1 or 2 Timers which may be set from user menu and which can be related to alarms. (parameter 8)dis. Disable > Defaults.tm.s. Single Timer Secondsd.tm.s. Double Timer Secondsd.s.t.s. Double Sequential Timer Secondsd.t.L.s. Double Timer Loop Secondss.tm.m. Single Timer Minutesd.tm.m. Double Timer Minutesd.s.t.m. Double Sequential Timer Minutesd.t.L.m. Double Timer Loop Minutes
64 Fa.Gr. Falling Gradientcooling gradient for pre-programmed cycle0 desabled (uncontrolled cooling) > Default: 0.1-9999 degrees/hour, with display of tenths
13 Alarm Intervention Modes13.a Absolute Alarm or Threshold Alarm (a.aL.
selection)
Alarm Spv
Pv.
O�On On
O�
Hysteresisparameter > 0
Time
Alarm output
Absolute alarm with controller in heating functioning (Parameter 11 act.t. selected Heat) and hysteresis value greater than “0” (Parameter 28 a.1.Hy. > 0). *
User manual - ATR142- 51
O�On On
O�
Hysteresisparameter < 0
Alarm Spv.
Pv
Time
Alarm output
Absolute alarm with controller in heating functioning (Parameter 11 act.t. selected Heat) and hysteresis value less than “0” (Parameter 28 a.1.Hy. < 0). *
O�On On
O�
Hysteresisparameter > 0
Alarm Spv
PvTime
Alarm output
Absolute alarm with controller in cooling functioning (Parameter 11 act.t. selected cooL) and hysteresis value greater than “0” (Parameter 28 a.1.Hy. > 0). *
On On
Hysteresisparameter
< 0
Alarm Spv
PvTime
Alarm output
Absolute alarm with controller in cooling functioning (Parameter 11 act.t. selected cooL) and hysteresis value less than “0” (Parameter 28 a.1.Hy. > 0). *
52 - ATR142 - User manual
13.b Absolute alarm or threshold alarm referring to setpoint command (a.c.aL. selection)
O�On
Hysteresisparameter > 0
O�
Alarm Spv
Command Spv
Time
Alarm output
Absolute alarm refers to the command set, with the controller in heating functioning (Parameter 11 act.t. selected Heat) and hysteresis value greater than “0” (Parameter 28 a.1.Hy. > 0).The command set can be changed by pressing the arrow keys on front panel or using serial port RS485 commands. *
13.c Band Alarm (b.aL. selection)
O�
Hysteresisparameter > 0
Alarm Spv
Alarm Spv
Command Spv
Time
Alarm output
Band alarm hysteresis value greater than “0” (Parameter 28 a.1.Hy. > 0). *
O� O� O�
Hysteresisparameter < 0
Hysteresis
Pv
Alarm SpvCommand Spv
Time
Alarm output
Band alarm hysteresis value less than “0” (Parameter 28 a.1.Hy. < 0). *
User manual - ATR142- 53
13.d Upper Deviation Alarm (H.d.aL. selection)
O� O�On On
Hysteresisparameter > 0
Pv
Alarm Spv
Command Spv
Time
Alarm output
Upper deviation alarm value of alarm setpoint greater than “0” and hysteresis value greater than “0” (Parameter 28 a.1.Hy. > 0). **
O� O�On On
Hysteresisparameter > 0
Pv
Alarm SpvCommand Spv
Time
Alarm output
Upper deviation alarm value of alarm setpoint less than “0” and hysteresis value greater than “0” (Parameter 28 a.1.Hy. > 0). **
13.e Lower Deviation Alarm (L.d.aL. selection)
O� O�On On
Hysteresisparameter > 0
Pv
Alarm Spv
Command Spv
Time
Alarm output
Lower deviation alarm value of alarm setpoint greater than “0” and hysteresis value greater than “0” (Parameter 28 a.1.Hy. > 0). **
54 - ATR142 - User manual
O�On On
Hysteresisparameter > 0
Pv.
Alarm Spv
Command Spv
Time
Alarm output
Lower deviation alarm value of alarm setpoint less than “0” and hysteresis value greater than “0” (Parameter 28 a.1.Hy. > 0). **
* The example refers to alarm 1; the function can also be enabled for alarm 2 on model that include it.
** a) The example refers to alarm 1; the function can also be enabled for alarm 2 on model that include it. b) With hysteresis less than “0” (a.1.Hy. < 0) the segmented line moves above the alarm setpoint.
14 Table of Anomaly SignalsIf installation malfunctions, controller will switch off regulation output and will report the anomaly. For example, controller will report failure of a connected thermocouple visualizing e-05 fl ashing on display for other signals, see table below.
Cause What to doE-01sYs.e.
Error in E²PROM cell programming Call Assistance
E-02sYs.e.
Cold junction sensor fault or room temperature outside of allowed limits.
Call Assistance
E-04sYs.e.
Incorrect confi guration data. Possible loss of calibration values.
Check if the confi gu-ration parameters are correct.
E-05prb.
Thermocouple open or temperature outside of limits.
Check the connection with the sensors and their integrity.
User manual - ATR142- 55
E-06ser.e.
Off-line in master mode remote process
Check the serial connection, baud-rate and device ID.
E-08sYs.e.
Missing calibration data Call Assistance
Notes
56 - ATR142 - User manual
Table of configuration parameters1 c.out Command Output 352 SEN. Sensor 363 d.p. Decimal Point 374 Lo.L.s. Lower Limit Setpoint 375 UP.L.S. Upper Limit Setpoint 376 Lo.L.i. Lower Linear Input 377 up.L.i. Upper Linear Input 378 Latc. Latch On Function 379 o.caL. Offset Calibration 3810 G.caL. Gain Calibration 3811 act.t. Action type 3812 c.re. Command Reset 3813 c.s.e. Command State Error 3814 c.Ld. Command Led 3815 c.HY. Command Hysteresis 3916 c.de. Command Delay 3917 c.s.p. Command Setpoint Protection 3918 p.b. Proportional Band 3919 t.i. Integral Time 3920 t.d. Derivative Time 3921 t.c. Cycle Time 4022 o.po.L. Output Power Limit 4023 aL.1 Alarm 4024 a.1.s.o. Alarm 1 State Output 4125 a.1.re. Alarm 1 Reset 4126 a.1.s.e. Alarm 1 State Error 4127 a.1.Ld. Alarm 1 Led 4128 a.1.HY. Alarm 1 Hysteresis 4129 a.1.de. Alarm 1 Delay 4230 a.1.s.p. Alarm 1 Setpoint Protection 4231 aL.2 Alarm 2 4232 a.2.s.o. Alarm 2 State Output 43
User manual - ATR142- 57
33 a.2.re. Alarm 2 Reset 4334 a.2.s.e. Alarm 2 State Error 4335 a.2.Ld. Alarm 2 Led 4336 a.2.HY. Alarm 2 Hysteresis 4337 a.2.de. Alarm 2 Delay 4338 a.2.s.p. Alarm 2 Setpoint Protection 4439 coo.f. Cooling Fluid 4440 p.b.m. Proportional Band Multiplier 4441 ov.d.b. Overlap/Dead Band 4442 co.t.c. Cooling Cycle Time 4443 c.fLt. Conversion Filter 4444 c.frn. Conversion Frequency 4545 v.fLt. Visualization Filter 4546 tune Tune 4647 s.d.tu. Setpoint Deviation Tune 4648 op.mo. Operating Mode 4649 au.ma. Automatic/Manual 4650 dGt.i. Digital Input 4751 Grad. Gradient 4752 ma.ti. Maintenance Time 4753 u.m.c.p. User Menu Cycle Programmed 4854 vi.tY. Visualization Type 4855 deGr. Degree 4856 bd.rt. Baud Rate 4857 sL.ad. Slave Address 4958 se.de. Serial Delay 4959 mast. Master 4960 add.r. Address Retransmission 4961 Lo.L.r. Lower Limit Retransmission 4962 up.L.r. Upper Limit Retransmission 4963 tmr.f. Timer Function 5064 Fa.Gr. Falling Gradient 50
58 - ATR142 - Manuale d’uso
IntroduzioneGrazie per aver scelto un regolatore Pixsys.Con il modello ATR142 Pixsys rende disponibile in un singolo strumento tutte le opzioni relative alla connessione dei sensori e al comando di attuatori, in aggiunta all’a-limentazione a range esteso 24..230 Vac/Vdc. Con le 17 sonde selezionabili e l’uscita configurabile come relè o SSR l’utilizzatore o il rivenditore può gestire al meglio le scorte di magazzino, razionalizzando investimento e disponibilità dei dispositivi. La serie si completa con il modello dotato di comunicazione seriale RS485 Modbus Rtu. La ripetibilità in serie delle operazioni di parametrizzazione è ulteriormente semplificata dalle Memory Card, dotate di batteria interna che non richiedono cablaggio per alimentare il regolatore.
1 Norme di sicurezzaPrima di utilizzare il dispositivo, leggere con attenzione le istruzioni e le misure di sicurezza contenute in questo manuale. Disconnettere l’alimentazione prima di qualsiasi intervento sulle connessioni elettriche o settaggi hardware.L’utilizzo/manutenzione è riservato a personale qualificato ed è da intendersi esclusivamente nel rispetto dei dati tecnici e delle condizioni ambientali dichiarate.Non gettare le apparecchiature elettriche tra i rifiuti domestici.Secondo la Direttiva Europea 2002/96/CE, le apparecchiature elettriche esauste devono essere raccolte separatamente al fine di essere reimpiegate o riciclate in modo eco-compatibile.
2 Identificazione del modelloLa serie di regolatori ATR142 prevede due versioni riassunte dalla tabella seguenteAlimentazione 24..230 Vac/Vdc ±15% 50/60Hz - 4,6VAATR142-ABC 2 Relè (8A+5A) + 1 SSRATR142-ABC-T 1 Relè 8A + 1 SSR + RS485
Manuale d’uso - ATR142- 59
3 Dati tecnici3.1 Caratteristiche generaliVisualizzatori 4 display 0,40 pollici + 4 da 0,30 polliciTemperatura di esercizio
temperatura funzionamento 0-45°C, umidità 35..95uR%
Protezione IP65 (con guarnizione) su Frontale, contenitore IP30 e morsettiere IP20
Materiale Policarbonato UL94V2 autoestinguentePeso 100 g
3.2 Caratteristiche hardware
Ingressoanalogico
AN1 Configurabile via software Termocoppie tipo:K, S, R, J Compen-sazione automatica del giunto freddo da 0..50°C.Termoresistenze: PT100, PT500, PT100 0, Ni100, PTC1K, NTC10K (β 3435K). Ingresso V/I: 0-10V, 0-20 o 4-20mA, 0-40mV. Ingresso Pot: 6KΩ, 150KΩ
Tolleranza (25°C)+/-0.2 % ± 1 digit su fondoscala per ingresso termocoppia, termoresistenza e V/mA.Precisione giunto freddo 0.1°C/°CImpedenza:0-10V: Ri>110KΩ0-20mA: Ri<5Ω4-20mA: Ri<5Ω0-40mV:Ri>1MΩ
Uscite relè
2 relè (ATR142-ABC)1 relè (ATR142-ABC-T)Configurabili come uscita comando e allarme.
Contatti:Q1: 8A-250V~per carichi resistiviQ2: 5A-250V~per carichi resistivi
Uscita SSR1 SSR Configurabile come uscita comando e allarme.
12Vdc/30mA
AlimentazioneAlimentazione a range esteso 24..230Vac/Vdc ±15% 50/60Hz
Consumo: 4.6VA
60 - ATR142 - Manuale d’uso
3.3 Caratteristiche softwareAlgoritmi regolazione
ON-OFF con isteresi.P, PI, PID, PD a tempo proporzionale
Banda proporzionale 0..9999°C or °F
Tempo integrale 0,0..999,9 sec (0 esclude)Tempo derivativo 0,0..999,9 sec (0 esclude)
Funzioni del regolatore
Tuning manuale o automatico allarme selezionabile, protezione set comando e allarme, selezione funzioni da ingresso digitale, ciclo preprogrammato con Start/Stop.
4 Dimensioni e installazione
U1
C1
CN1 16
1 2 3
Dima di foratura28.5 x 70.5 mm
Frontal panel cut-out
Spessore suggerito2 ÷ 8 mm
Suggested thickness
77 mm
35 m
m
53 mm7
42mminserimento
Memory Card
42mminsertMemory Card
PIXSYS
Memory Card (optional)with battery
Memory Card (optional)Cod. MEMORY 2100.30.005
Cod. MEMORY 2100.30.003
Guarnizione per 32x74Cod. 1600.00.082 (optional)Gasket for 32x74
Manuale d’uso - ATR142- 61
5 Collegamenti elettrici Benché questo regolatore sia stato progettato per resistere ai più gravosi disturbi presenti in ambienti industriali è buona norma seguire la seguenti precauzioni:• Distinguere la linea di alimentazioni da quelle di potenza.• Evitare la vicinanza di gruppi di teleruttori, contattori
elettromagnetici, motori di grossa potenza e comunque usare gli appositi filtri.
• Evitare la vicinanza di gruppi di potenza, in particolare se a controllo di fase.
5.1 Schema di collegamentoDi seguito sono riportati i collegamenti dei due modelli disponibili.
PIXSYS
10A 230VCosf 1
3A 230VCosf 0.8
Q1 PTC/NTC
- +Tc
+VDC
SSR
1 2 3 4 5 6 7 8 9 10 11 12- +
I
V/I+-PT/NI100/1K
2 wire 4/20mA
Power5A 230VCosf 1
1A 230VCosf 0.8
Q2
Memory1
ATRxxx-xx
- +
SUPPLY
PIXSYS
10A 23a0VCosf 1
3A 230VCosf 0.8
Q1 PTC/NTC
- +Tc
+VDC
SSR
1 2 3 4 5 6 7 8 9 10 11 12- +
I
V/I+-PT/NI100/1K
2 wire 4/20mA
Power
Memory1
- +
ATRxxx-xxT
- +
RS485SUPPLY
ATR142-ABC ATR142-ABC-T
5.1.a Alimentazione1
2
24...230VAC/DC
Alimentazione switching a range esteso24..230 Vac/dc ±15% 50/60Hz – 3,5VA
62 - ATR142 - Manuale d’uso
5.1.b AN1 Analogue Input
-
+Tc11
12
Shield/Schermo
Per termocoppie K, S, R, J.• Rispettare la polarità• Per eventuali prolunghe utilizzare
cavo compensato e morsetti adatti alla termocoppia utilizzata (compensati)
• Quando si usa cavo schermato lo schermo deve essere collegato a terra ad una sola estremità
1011
12
PT/NI100
Shield/SchermoPer termoresistenze PT100, Ni100• Per il collegamento a tre fili usare cavi
della stessa sezione.• Per il collegamento a due fili
cortocircuitare i morsetti 10 e 12.• Quando si usa cavo schermato, lo
schermo deve essere collegato a terra ad una sola estremità
10
11
12
RED
WHITE
RED
Shield/Schermo
PTC/NTC
1011
Per termoresistenze NTC, PTC, PT500, PT1000 e potenziometri lineari.• Quando si usa cavo schermato lo
schermo deve essere collegato a terra ad una sola estremità
Shield/Schermo
+VDC
910
1112
V/I+
-
Per segnali normalizzati in corrente e tensione• Rispettare la polarità• Quando si usa cavo schermato lo
schermo deve essere collegato a terra ad una sola estremità
Manuale d’uso - ATR142- 63
5.1.c Esempi di collegamento per ingressi normalizzati
0...10V
1112 Per segnali normalizzati in tensione
0..10V• Rispettare le polarità
PRESSURE TRANSMITTERSENSORE DI PRESSIONE
0/4...20mA
A
B
C
1112
9
Per segnali normalizzati in corrente 0/4..20mA con sensore a tre fili Rispettare le polaritàC = Uscita sensoreB = Massa sensoreA = Alimentazione sensore (12V/30mA)
EXTERNAL SUPPLYALIMENTAZIONE ESTERNA
PRESSURE TRANSMITTERSENSORE DI PRESSIONE
0/4...20mA
B
C
1112 Per segnali normalizzati in corrente
0/4..20mA con sensore ad alimentazione esterna Rispettare le polaritàC = Uscita sensoreB = Massa sensore
PRESSURE TRANSMITTERSENSORE DI PRESSIONE
C
4...20mA
A
129
Per segnali normalizzati in corrente 0/4..20mA con sensore a due fili Rispettare le polaritàC = Uscita sensoreA = Alimentazione sensore (12V/30mA)
5.1.d Ingresso Seriale
117
6 -+
Shield/Schermo
RS485
RS485, protocollo MODBUS-RTU Non usare resistenze di terminazione• Per reti con più di cinque
strumenti alimentare in bassa tensione
64 - ATR142 - Manuale d’uso
5.1.e Uscite relè
76
54
Q1
Q2
3
Portata contatti:Q1: 8A, 250Vac,carico resistivo,105
operazioni. 30/3A, 250Vac, cosφ=0.3, 105 operazioni.
Q2: 5A, 250Vac,carico resistivo,105 operazioni. 20/2A, 250Vac, cosφ=0.3, 105 operazioni.
5.1.f Uscita SSR
SSR
89 Uscita comando SSR portata 12V/30mA
5.1.g Ingresso digitale
1011
Ingresso digitale (parametro DGT.i.)L’utilizzo dell’ingresso digitale è possibile solo con sonde tipo Tc o 0..10V, 0/4..20mA e 0..40mV.
Manuale d’uso - ATR142- 65
6 Configurazione EASYUPPer semplificare il più possibile il lavoro di parametrizzazione della catena di controllo, Pixsys presenta una nuova modalità a codici che consente di configurare con un unico e semplice passaggio ingressi sonda e/o uscite di comando.La modalità EASYUP tramite il codice presente sulla do-cumentazione tecnica allegata al sensore o all’attuatore (SSR, valvola-motorizzata, ecc..) configura sullo strumento i relativi parametri caratteristici (esempio per una PT100 il parametro SEN, e la scala di utilizzo “Valore minimo di set” e “Valore massimo”).I codici possono essere utilizzati in sequenza per settare sia ingressi che uscite comando o modalità di ritrasmissione del segnale.
66 - ATR142 - Manuale d’uso
7 Funzione dei visualizzatori e tasti
543 876 2
1M T R
2 3
9
10
12
11
ATR 142
1
7.1 Indicatori numerici (display)
1 1234
Normalmente visualizza il processo.In fase di confi gurazione visualizza il parametro in inserimento.
2 1234
Normalmente visualizza i setpoint. In fase di confi gurazione visualizza il valore del parametro in inserimento.
7.2 Signifi cato delle spie di stato (led)
3 1Si accendono quando l’uscita comando è attiva. Nel caso di comando valvola motorizzata è acceso nel caso di apertura valvola e lampeggia in chiusura.
4 2 Si accende quando l’allarme 1 è attivo.
5 3 Si accende quando l’allarme 2 è attivo.
6 M Si accende all’attivazione della funzione “Manuale”.
7 TSi accende quando il regolatore sta eseguendo un ciclo di Tuning.
8 RSi accende quando il regolatore comunica via seriale.
Manuale d’uso - ATR142- 67
7.3 Tasti
9 “m”
• Decrementa il setpoint principale• In fase di configurazione consente di scorrere i
parametri. Insieme al tasto SET li modifica.• Premuto dopo il tasto SET decrementa i
setpoint di allarme.
10 “n”
• Incrementa il setpoint principale• In fase di configurazione consente di scorrere i
parametri. Insieme al tasto SET li modifica.• Premuto dopo il tasto SET Incrementa i
setpoint di allarme.
11 SET • Permette di visualizzare i setpoint di allarme.• Permette di variare i parametri di configurazione.
12 FNC
• Permette di entrare nella funzione di lancio del Tuning, selezione automatico/manuale.
• Permette di entrare/uscire dalla procedura di configurazione.
8 Funzioni del regolatore8.1 Modifica valore setpoint principale e di
allarmeIl valore dei setpoint può essere modificato da tastiera come segue:
Premere Effetto Eseguire
9 “n” o “m” La cifra sul display 2 varia
Incrementare o diminuire il valore del setpoint principale
10 SET Visualizza setpoint di allarme sul display 1
11 “n” o “m” La cifra sul display 2 varia
Incrementare o diminuire il valore del setpoint di allarme
68 - ATR142 - Manuale d’uso
8.2 Auto-tuneLa procedura di Tuning per il calcolo dei parametri di regolazione può essere manuale o automatica e viene selezionata da parametro 46 tune.
8.3 Lancio del Tuning ManualeLa procedura manuale permette all’utente maggiore flessibilità nel decidere quando aggiornare i parametri di regolazione dell’argoritmo PID. La procedura può essere attivata in due modi.• Lancio del Tuning da tastiera: Premere il tasto FNC finché il display 1 non visualizza la
scritta tune con il display 2 su oFF, premere “n”, il display 2 visualizza on. Il led T si accende e la procedura ha inizio.
• Lancio del Tune da ingresso digitale: Selezionare tune su parametro 50 dGt.i. Alla prima
attivazione dell’ingresso digitale (commutazione su fronte) il led T si accende, alla seconda si spegne.
8.4 Tuning AutomaticoIl Tuning automatico si attiva all’accensione dello strumento o quando viene modificato il setpoint di un valore superiore al 35%. Per evitare overshoot il punto dove il regolatore calcola i nuovi parametri PID è determinato dal valore di setpoint meno il valore “Set Deviation Tune” (vedere Parametro 47 s.d.tu.)Per interrompere il Tuning lasciando invariati i valori PID, premere il tasto FNC finché il display 1 non visualizza la scritta tune e il display 2 visualizza on. Premendo “m”, il display 2 visualizza off, il led T si spegne e la procedura termina.
8.5 Soft StartIl regolatore all’accensione per raggiungere il setpoint segue un gradiente di salita impostato in Unità (es. Grado / ora).Impostare sul parametro 51 Grad. il valore di incremento in Unità/Ora desiderato; alla successiva accensione lo strumento eseguirà la funzione Soft Start.
Manuale d’uso - ATR142- 69
Non può essere abilitata la funzione Tuning automatico e manuale se la funzione Soft Start è attiva.
8.6 Regolazione automatico/manuale per controllo % uscita
Questa funzione permette di passare dal funzionamento automatico al comando manuale della percentuale dell’uscita.Con il parametro 49 Au.ma. è possibile selezionare due modalità.• Selezione en. (Enable). Premendo il tasto FNC visualizza
la p.--- scritta sul display 1, mentre sul display 2 appare Auto. Premere il tasto “n” per selezionare la modalità manuale man. Con i tasti “n” e “m ” variare la percentuale di uscita.
Per tornare in automatico, con la stessa procedura, selezionare auto sul display 2: subito si spegne il led M e il funzionamento torna in automatico.
• Selezione en.st. (enable stored). Abilita lo stesso funzionamento, ma con due importanti varianti:
- Nel caso di temporanea mancanza di tensione o comunque dopo uno spegnimento, accendendo il regolatore verrà mantenuto sia il funzionamento in manuale, sia il valore di percentuale dell’uscita precedentemente impostato.
- Nel caso di rottura del sensore durante il funzionamento automatico, il regolatore si porterà in manuale mantenendo invariata la percentuale di uscita comando generata dal PID subito prima della rottura.
8.7 Ciclo pre-programmatoQuesta funzione permette di programmare un semplice ciclo di lavoro temporizzato, e si abilita impostando pr.cY. nel parametro 48 op.Mo.: il processo raggiunge il setpoint1 in base al gradiente impostato nel parametro 51 Grad., poi sale alla massima potenza verso il setpoint 2. Quando il processo raggiunge il setpoint 2 resta in mantenimento per il tempo impostato nel parametro 52 ma.t.i. Allo scadere, il processo
70 - ATR142 - Manuale d’uso
raggiunge la temperatura ambiente in base al gradiente impostato nel parametro 64 fa.Gr. e poi l’uscita di comando viene disabilitata e lo strumento visualizza Stop.
Setp
oint
Time
Setpoint 1
Setpoint 2
Maintenance timeMantenimento
CoolingRa�reddamentoMax Power
Max Potenza
Rising gradientGradiente di salita
Lo Start del ciclo avviene al ogni accensione dello strumento, oppure da ingresso digitale se risulta abilitato per questo tipo di funzionamento (parametro 50 dGt.i.).
8.8 Memory Card (opzionale)È possibile duplicare parametri e setpoint da un regolatore ad un altro mediante l’uso della Memory Card. Sono previste due modalità:• Con regolatore connesso all’alimentazione: Inserire la Memory Card con regolatore spento.
All’accensione il display 1 visualizza memo e il display 2 visualizza ---- (solo se nella Memory sono salvati valori corretti). Premendo il tasto “n” il display 2 visualizza Load. Confermare con il tasto FNC. Il regolatore carica i nuovi valori e riparte.
• Con regolatore non connesso all’alimentazione: La memory card è dotata di batteria interna con
autonomia per circa 1000 utilizzi. Inserire la memory card e premere il tasto di programmazione. Durante la scrittura dei parametri il led si accende rosso, al termine della procedura si accende verde. è possibile ripetere la procedura senza particolari attenzioni.
Manuale d’uso - ATR142- 71
Aggiornamento Memory Card.Per aggiornare i valori della Memory seguire il procedimento descritto nella prima modalità, impostando ---- sul display 2 in modo da non caricare i parametri sul regolatore1. Entrare in configurazione e variare almeno un parametro. Uscendo dalla configurazione il salvataggio sarà automatico.
8.9 Caricamento valori di defaultQuesta procedura permette di ripristinare le impostazioni di fabbrica dello strumento.
Premere Effetto Eseguire
1 FNC per 3s.
Su display 1 compare 0000 con la 1^ cifra lampeggiante, mentre sul display 2 compare pass
2 “n” or “m”
Si modifica la cifra lampeggiante si passa alla successiva con il tasto SET
Inserire la password 9999
3 SET per conferma
Lo strumento carica le impostazioni di fabbrica
Spegnere e riaccendere lo strumento
1 Nel caso in cui all’accensione il regolatore non visualizzi memo significa che non ci sono dati salvati nella Memory Card, ma è possibile ugualmente aggiornarne i valori.
72 - ATR142 - Manuale d’uso
8.10 Funzione LATCH ONPer l’utilizzo con ingresso Pot.1 (pot. 6KΩ) e Pot.2 (pot.150KΩ) e con ingressi normalizzati (0..10V, 0..40mV, 0/4..20mA), è possibile associare il valore di inizio scala (parametro 6 Lo.L.i.) alla posizione di minimo del sensore e quello di fine scala (parametro 7 up.L.i.) alla posizione di massimo del sensore (parametro 8 Latc. configurato come std.). è inoltre possibile fissare il punto in cui lo strumento visualizzerà 0 (mantenendo comunque il campo scala compreso tra Lo.L.i. e up.L.i. ) tramite l’opzione di “zero virtuale” impostando u.0st. oppure u.0in. nel parametro 8 Latc. Se si imposta u.0in., lo zero virtuale andrà reimpostato dopo ogni accensione dello strumento; se si imposta u.0st. lo zero virtuale resterà fisso una volta tarato.Per utilizzare la funzione LATCH ON configurare come desiderato il parametro Latc.2 Per la procedura di taratura fare riferimento alla seguente tabella:
Premere Effetto Eseguire
1 FNC
Esce dalla configurazio-ne parametri. Il display 2 visualizza la scritta Latc..
Posizionare il sensore sul valore minimo di funzionamento (associato a Lo.L.i.)
2 “m”Fissa il valore sul minimo. Il display visualizza Low
Posizionare il sensore sul valore massimo di funzionamento (associato a up.L.i.)
3 “n”Fissa il valore sul massimo. Il display visualizza HiGt
Per uscire dalla procedura standard premere FNC. Nel caso di impostazione con “zero virtuale” posizionare il sensore nel punto di zero.
2 La procedura di taratura parte uscendo dalla configurazione dopo aver variato il parametro.
Manuale d’uso - ATR142- 73
4 SET
Fissa il valore di zero virtuale. Il display visualizza uirt. NB: nel caso di selezione u.0in. la procedura al punto 4 va eseguita ad ogni ri-accensione.
Per uscire dalla procedura tenere premuto FNC.
MaxMin Zero
8.11 Funzioni da ingresso digitaleL’ATR142 integra alcune funzionalità relative all’ingresso digitale, che può essere abilitato utilizzando i parametri 48 op.mo. e 50 dGt.i.• Parametro 48 op.mo. cont.: Funzionamento come regolatore semplice. NB: Utilizzando le seguenti impostazioni, il parametro 50
dGt.i. viene ignorato. 2t.s.: Cambio setpoint a due soglie: con contatto aperto
l’ATR142 regola su SET1; con contatto chiuso regola su SET2;
2t.s.i.: Cambio setpoint a due soglie: la selezione del punto di lavoro viene fatta agendo con un impulso sull’ingresso digitale;
3t.s.i.: Cambio setpoint a tre soglie con impulso sull’ingresso digitale;
4t.s.i.: Cambio setpoint a quattro soglie con impulso sull’ingresso digitale;
p.r.c.Y.: Ciclo pre-programmato (parametro 7.7). I vari setpoint possono essere impostati durante il
funzionamento premendo il tasto SET.
74 - ATR142 - Manuale d’uso
• Parametro 50 dGt.i. NB: Le impostazioni su questo parametro sono considerate
solo impostando cont. oppure pr.cY. sul parametro 48 op.mo.
st.st.: Start/Stop; agendo sull’ingresso digitale il regolatore passa alternativamente da start a stop;
rn.n.o.: Run N.O. Il regolatore è in start solamente con ingresso chiuso;
rn.n.c. : Run N.C. Il regolatore è in start solamente con ingresso aperto;
L.c.n.o.: Con ingresso chiuso blocca la lettura delle sonde; Lc.n.c.: Con ingresso aperto blocca la lettura delle sonde; tune: Abilita/disabilita il Tuning se il parametro 46 tune è
impostato su man.; a.ma.i.: Se parametro 49 au.ma. è impostato su en. o en.st.
agendo sull’ingresso il regolatore passa alternativamente da regolazione automatica a regolazione manuale;
a.ma.c.: Se parametro 49 au.ma. è impostato su en. o en.st. l’ATR142 regola in automatico con ingresso aperto e in manuale con ingresso chiuso.
t.1.s.s.: Start/Stop del timer 1 (parametro 8.)
NB: le funzioni da ingresso digitale non sono disponibili con sonde PT100, NI100, NTC, PTC, PT500, PT1000 e potenziometri lineari.
8.12 Funzionamento in doppia azione (caldo-freddo)
L’ATR142 è adatto alla regolazione anche su impianti che prevedano un’azione combinata caldo-freddo.L’uscita di comando deve essere configurata in PID caldo (act.t. = Heat e p.b. maggiore di 0), e uno degli allarmi (AL.1 o AL. 2) deve essere configurato come cooL. L’uscita di comando va collegata all’attuatore responsabile dell’azione caldo, l’allarme comanderà invece l’azione refrigerante.I parametri da configurare per il PID caldo sono:act.t. = Heat Tipo azione uscita di comando (Caldo)
Manuale d’uso - ATR142- 75
p.b.: Banda proporzionale azione caldot.i. : Tempo integrale azione caldo ed azione freddot.d.: Tempo derivativo azione caldo ed azione freddot.c.: Tempo di ciclo azione caldoI parametri da configurare per il PID freddo sono (azione associata, per esempio, all’allarme1):AL. 1 = cooL Selezione Allarme1 (Cooling)p.b.m. : Moltiplicatore di banda proporzionaleou.d.b.: Sovrapposizione / Banda mortaco.t.c.: Tempo di ciclo azione freddoIl parametro p.b.m. (che varia da 1.00 a 5.00) determina la banda proporzionale dell’azione refrigerante secondo la formula:Banda proporzionale azione refrigerante = p.b. * p.b.m.Si avrà così una banda proporzionale per l’azione refrigerante che sarà uguale a quella dell’azione caldo se p.b.m. = 1.00, o 5 volte più grande se p.b.m. = 5.00.Tempo integrale e Tempo derivativo sono gli stessi per entrambe le azioni.Il parametro ou.d.b. determina la sovrapposizione in percentuale tra le due azioni. Per gli impianti in cui l’uscita riscaldante e l’uscita refrigerante non devono mai essere attive contemporaneamente si configurerà una Banda morta (ou.d.b. ≤ 0), viceversa si potrà configurare una sovrapposi-zione (ou.d.b. > 0).La figura seguente riporta un esempio di PID doppia azione (caldo-freddo) con t.i. = 0 e t.d. = 0.
ACTIVE
ACTIVE
SPV
PV
x = COOL
x = COOL
x = COOL
< 0
= 0
> 0
(HEAT)
(HEAT)
(HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
SPV
PV
ACTIVE
ACTIVE
SPV
PV
ACTIVE
ACTIVE
76 - ATR142 - Manuale d’uso
ACTIVE
ACTIVE
SPV
PV
x = COOL
x = COOL
x = COOL
< 0
= 0
> 0
(HEAT)
(HEAT)
(HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
SPV
PV
ACTIVE
ACTIVE
SPV
PV
ACTIVE
ACTIVE
ACTIVE
ACTIVE
SPV
PV
x = COOL
x = COOL
x = COOL
< 0
= 0
> 0
(HEAT)
(HEAT)
(HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
SPV
PV
ACTIVE
ACTIVE
SPV
PV
ACTIVE
ACTIVE
Il parametro co.t.c. ha lo stesso significato del tempo di ciclo per l’azione caldo t.c. Il parametro coo.F. (Cooling Fluid) pre-seleziona il moltiplicatore di banda proporzionale P.b.m. ed il tempo di ciclo co.t.c. del PID freddo in base al tipo di fluido refrigerante:
coo.f. Tipo di fluido refrigerante P.b.m. co.t.c.
Air Air 1.00 10oiL Oil 1.25 4H2o Water 2.50 2
Una volta selezionato il parametro coo.F., i parametri P.b.m., ou.d.b. e co.t.c. possono essere comunque modificati.
Manuale d’uso - ATR142- 77
9 Funzioni timerLe funzionalità legate al timer vengono abilitate sul parametro 63 tmr.f. Per variare la durata del tempo di conteggio seguire i punti elencati nella seguente tabella:
Premere Effetto Eseguire
1 SET
Premere fino alla visualizzazione di tim.1 o tim. 2 sul display1.
2 “n” o “m” La cifra sul display 2 varia
Incrementare o diminuire il tempo del timer selezionato
Di seguito la descrizione delle varie modalità di funzionamento dei timer.
9.1 Singolo timerQuesta modalità abilita un timer con tempo impostabile dall’utente. Per il funzionamento del singolo timer impostare il parametro 63 tmr.f. come segue:• s.tm.s. (Single Timer Seconds) base tempi in secondi (mm.ss)• s.tm.m. (Single Timer Minutes) base tempi in minuti (hh.mm)Per far partire o fermare il timer tenere premuto il tasto FNC per 1s. Durante il conteggio si accende il led R e il display 2 visualizza il tempo in decremento. Allo scadere del timer il led R si spegne e il display 2 lampeggia mostrando il tempo impostato, fino alla pressione di un tasto. È possibile fare lo start/stop del timer anche da ingresso digitale impostando t.1.s.s. sul parametro 50 dGt.i.
78 - ATR142 - Manuale d’uso
9.2 Doppio timerQuesta modalità abilita due timer con tempo impostabile dall’utente: i timer non possono essere messi in start con-temporaneamente. Per il funzionamento del doppio timer impostare il parametro 63 t.mr.f. come segue:• d.tm.s. (Double Timer Seconds) base tempi in secondi (mm.ss)• d.tm.m . (Double Timer Minutes) base tempi in minuti (hh.mm)
Per la procedura di start dei timer far riferimento alla tabella seguente:
Premere Effetto Eseguire
1 FNCPremere fino alla visualizzazione di tim. 1 o tim. 2 sul display1.
2 “n”
Start del timer. Il display 2 visualizza il tempo in decremento e si accende il led
R (fisso per timer 1 e lampeggiante per timer2)
Tornare al punto 1 e una volta selezionato il timer in start premere “n” per Wfermare il conteggio. Il led R si spegne
Allo scadere del timer il led R si spegne e il display 2 lampeggia mostrando il tempo impostato, fino alla pressione di un tasto. Nella modalità doppio timer non è possibile abilitare lo start/stop da ingresso digitale.
9.3 Doppio timer sequenzialeQuesta modalità abilita due timer con tempo impostabile dall’utente. Allo scadere del timer 1 parte automaticamente il conteggio del timer2: una volta scaduto anche il timer 2 il conteggio si ferma. Per il funzionamento del doppio timer sequenziale impostare il parametro 63 tmr.f. come segue:• d.s.t.s. (Double Sequential Timer Seconds) base tempi in
secondi (mm.ss)• d.s.t.m. (Double Sequential Timer Minutes) base tempi in
minuti (hh.mm)
Manuale d’uso - ATR142- 79
Per far partire o fermare il timer tenere premuto il tasto FNC per 1s.Durante il conteggio si accende il led R (fisso per timer 1 e lampeggiante per timer 2) e il display 2 visualizza il tempo in decremento. Lo start avviene sempre sul timer 1. Allo scadere del timer il led R si spegne e il display 2 torna alla visualiz-zazione del setpoint. È possibile fare lo start/stop del timer anche da ingresso digitale impostando t.1.s.s. sul parametro 50 dGt.i.
9.4 Doppio timer loopQuesta modalità abilita due timer con tempo impostabile dall’utente. Allo scadere di un timer parte automaticamente l’altro: la sequenza si ripete ciclicamente.Per il funzionamento del doppio timer loop impostare il parametro 63 tmr.f. come segue:• d.t.L.s. (Double Timer Loop Seconds) base tempi in
secondi (mm.ss)• d.t.L.M. (Double Timer Loop Minutes) base tempi in minuti
(hh.mm)Per far partire o fermare il timer tenere premuto il tasto FNC per 1s.Durante il conteggio si accende il led R (fisso per timer 1 e lampeggiante per timer 2) e il display 2 visualizza il tempo in decremento. Lo start avviene sempre sul timer 1.È possibile fare lo start/stop del timer anche da ingresso digitale impostando t.1.s.s. sul parametro 50 dGt.i.
80 - ATR142 - Manuale d’uso
9.5 Associazione Timer - AllarmiÈ possibile associare gli allarmi (uscite relè o SSR) ai timer mediante i parametri 23 aL. 1 e 31 aL. 2. Per la logica di funzionamento degli allarmi correlati ai timer fare riferimento alla seguente tabella:
Selezionepar. 23 o 31 Descrizione
t.1.s.a. Timer 1 Start Alarm
Allarme attivo durante lo start del timer 1
t.1.E.a. Timer 1 End Alarm
Allarme attivo allo scadere del timer 1: resta attivo fino alla pressione di un tasto. Non funziona in modalità doppio timer sequenziale e loop.
t.1.W.E. Timer 1 Warning Expiring
Allarme attivo gli ultimi 5“ del timer 1.
t.2.s.a. Timer 2 Start Alarm
Allarme attivo durante lo start del timer 2
t.2.e.a. Timer 2 End Alarm
Allarme attivo allo scadere del timer 2: resta attivo fino alla pressione di un tasto. Non funziona in modalità doppio timer sequenziale e loop.
t.2.w.e. Timer 2 Warning Expiring
Allarme attivo gli ultimi 5“ del timer 2.
t.1.2.s. Timer 1-2 Start Alarm
Allarme attivo durante lo start del timer 1 e 2
t.1.2.e. Timer 1-2 End Alarm
Allarme attivo allo scadere del timer 1 e 2: resta attivo fino alla pressione di un tasto. Non funziona in modalità doppio timer sequenziale e loop.
t.1.2.w. Timer 1-2 Warning expiring
Allarme attivo gli ultimi 5“ del timer 1 e 2.
Manuale d’uso - ATR142- 81
10 Comunicazione seriale10.1 SlaveL’ATR142-ABC-T con RS485 può ricevere e trasmettere dati via seriale tramite protocollo MODBUS RTU. Il dispositivo funziona come slave se il parametro 59 mast. è impostato su dis. Questa funzione permette il controllo di più regolatori collegati ad un sistema di supervisione. Ciascuno strumento risponderà ad un’interrogazione del Master solo se questa contiene l’indirizzo uguale a quello contenuto nel parametro sL.ad. Gli indirizzi permessi vanno da 1 a 254 e non devono esserci regolatori con lo stesso indirizzo sulla stessa linea. L’indirizzo 255 può essere usato dal Master per comunicare con tutte le apparecchiature collegate (modalità broadcast), mentre con 0 tutti i dispositivi ricevono il comando, ma non è prevista alcuna risposta. L’ATR142 può introdurre un ritardo (in millisecondi) della risposta alla richiesta del Master. Tale ritardo deve essere impostato sul parametro 58 se.de. Ad ogni variazione dei parametri lo strumento salva il valore in memoria EEPROM (100000 cicli di scrittura), mentre il salvataggio dei setpoint avviene con un ritardo di 10 secondi dall’ultima modifica.NB: Modifiche apportate a Word diverse da quelle riportate nella tabella seguente possono causare mal funzionamenti dello strumento.
Caratteristiche protocollo Modbus RTU
Baud-rate
Selezionabile da parametro 564.8 k 4800bit/sec9.6 k 9600bit/sec19.2k 19200bit/sec28.8k 28800bit/sec38.4k 38400bit/sec57.6k 57600bit/sec
Formato 8, N, 1 (8bit, no parità, 1 stop)
Funzioni supportate
WORD READING (max 20 word) (0x03, 0x04)SINGLE WORD WRITING (0x06)MULTIPLE WORDS WRITING (max 20 word) (0x10)
82 - ATR142 - Manuale d’uso
Si riporta di seguito l’elenco di tutti gli indirizzi disponibili, dove:
RO = Read Only R/W = Read/Write WO = Write Only
Modbus address Descrizione Read
WriteReset value
0 Tipo dispositivo RO EEPROM1 Versione software RO EEPROM5 Address slave R/W EEPROM6 Versione boot RO EEPROM50 Indirizzamento automatico WO -51 Confronto codice impianto WO -
500
Caricamento valori di default:9999 ripristina tutti i valori9998 ripristina tutti i valori escluso baud-rate e address slave9997 ripristina tutti i valori escluso address slave9996 ripristina tutti i valori escluso baud-rate
WO 0
1000Processo (gradi con decimo per sensori di temperatura; digit per sensori normalizzati)
RO -
1001 Setpoint1 R/W EEPROM1002 Setpoint2 R/W EEPROM1003 Setpoint3 R/W EEPROM1004 Setpoint4 R/W EEPROM1005 Allarme1 R/W EEPROM1006 Allarme2 R/W EEPROM1007 Setpoint gradiente RO EEPROM
1008
Stato uscite (0=off, 1=on) Bit 0 = relè Q1Bit 1 = relè Q2Bit 2 = SSR
RO 0
1009 Percentuale uscita caldo (0-10000) RO 01010 Percentuale uscita freddo (0-10000) RO 0
Manuale d’uso - ATR142- 83
1011 Stato allarmi (0=assente, 1=presente)Bit0 = Allarme 1 Bit1 = Allarme 2 RO 0
1012
Riarmo manuale: scrivere 0 per riarmare tutti gli allarmi.In lettura (0=non riarmabile, 1=riarmabile):Bit0 = Allarme 1
WO 0
1013
Flags erroriBit0 = Errore scrittura eepromBit1 = Errore lettura eepromBit2 = Errore giunto freddoBit3 = Errore processo (sonda)Bit4 = Errore genericoBit5 = Errore hardwareBit6 = Master off-lineBit7 = Taratura mancante
RO 0
1014 Temperatura giunto freddo(gradi con decimo) RO -
1015Start/Stop0= regolatore in STOP1= regolatore in START
R/W 0
1016Blocco conversione ON/OFF0= Blocco conversione off1= Blocco conversione on
R/W 0
1017 Tuning ON/OFF0= Tuning off 1= Tuning on R/W 0
1018 Selezione automatico/manuale0=automatico 1=manuale R/W 0
1019 Tempo OFF LINE* (millisecondi) R/W 0
1100 Processo visualizzato (decimale come sul display) RO -
1101 Setpoint1 visualizzato (decimale come sul display) R/W EEPROM
1102 Setpoint2 visualizzato (decimale come sul display) R/W EEPROM
84 - ATR142 - Manuale d’uso
1103 Setpoint3 visualizzato (decimale come sul display) R/W EEPROM
1104 Setpoint4 visualizzato (decimale come sul display) R/W EEPROM
1105 Allarme1 visualizzato (decimale come sul display) R/W EEPROM
1106 Allarme2 visualizzato (decimale come sul display) R/W EEPROM
1107 Setpoint gradiente (decimale come sul display) RO EEPROM
1108 Percentuale uscita caldo (0-1000) RO 01109 Percentuale uscita caldo (0-100) RO 01110 Percentuale uscita freddo (0-1000) RO 01111 Percentuale uscita freddo (0-100) RO 02001 Parametro 1 R/W EEPROM.. .. ... ...2064 Parametro 64 R/W EEPROM
3000 Disabilitazione controllo macchina da seriale** WO 0
3001 Prima word display1 (ascii) R/W 0.. .. R/W 03008 Ottava word display1 (ascii) R/W 03009 Prima word display2 (ascii) R/W 0.. .. R/W 03016 Ottava word display2 (ascii) R/W 0
3017
Word LEDBit 0 = LED 1 Bit 3 = LED MANBit 1 = LED 2 Bit 4 = LED TUNBit 2 = LED 3 Bit 5 = LED REM
R/W 0
3018
Word tasti (scrivere 1 per assumere il controllo dei tasti)Bit 0 = “m” Bit 2 = SETBit 1 = “n” Bit 3 = FNC
R/W 0
Manuale d’uso - ATR142- 85
3019
Word uscite serialeBit 0 = relè Q1Bit 1 = relè Q2Bit 2 = uscita SSR
R/W 0
3020
Word stato uscite seriale in caso di off-lineBit 0 = relè Q1Bit 1 = relè Q2Bit 2 = uscita SSR
R/W 0
3021 Word processo seriale R/W 0* Se vale 0 il controllo è disabilitato. Se diverso da 0, è “Il tempo massimo
che può trascorrere tra due interrogazioni senza che il regolatore si porti in Off-Line”. In Off-Line il regolatore va in stato di Stop, disabilita l’uscita di comando, ma mantiene gli allarmi attivi.
** Scrivendo 1 su questa word, si annullano gli effetti della scrittura su tutti gli indirizzi Modbus da 3001 a 3019. Il controllo ritorna così al regolatore.
10.2 MasterIl dispositivo funziona come master se il valore impostato sul parametro 59 mast. è diverso da dis.
10.2.1 Modalità master in ritrasmissioneIn questa modalità lo strumento scrive il valore da ritrasmettere all’indirizzo impostato sul parametro 60 ADD.R, su altri slave che hanno ID uguale al valore impostato sul parametro 57 SL.AD. Per la ritrasmissione dei setpoint dopo l’avvenuta scrittura sullo slave, l’ATR142 inizia a leggere la word selezionata: in questo modo un’eventuale variazione del valore sullo slave viene appreso anche dal master. Due interrogazioni successive vengono ritardate del tempo impostato su parametro 57 SE.DE.Nella seguente tabella sono riportate le selezioni che permettono il funzionamento master in ritrasmissione e la relativa grandezza ritrasmessa.
86 - ATR142 - Manuale d’uso
mast. Descrizionew.pro. Write Process Scrive il valore del processo
r.w.co.Read/Write Command Setpoint
Scrive e legge il valore del setpoint di comando
w.ou.p. Write Output Percentage
Scrive la percentuale di uscita calcolata dal P.I.D. (Range 0-10000)
r.w.a.1Read/Write Alarm 1
Scrive e legge il valore del setpoint dell’allarme 1
Il valore letto/scritto può essere riscalato seguendo la proporzione proposta nella seguente tabella:
mast.limiti valore ingresso limiti valore riscalato
Min Max Min Max
w.pro. Write Process
Lo.L.i. Lower Limit Input
up.L.i. Upper Limit Input
Lo.L.r. Lower Limit Re-transmis-sion
up.L.r. Upper Limit Re-transmis-sion
r.w.co.Read/Write Command Setpoint
Lo.L.s. Lower Limit Setpoint
up.L.s. Upper Limit Setpoint
Lo.L.r. Lower Limit Re-transmis-sion
up.L.r. Upper Limit Re-transmis-sion
w.ou.p. Write Output Percentage
0 10000
Lo.L.r. Lower Limit Re-transmis-sion
up.L.r. Upper Limit Re-transmis-sion
r.w.a.1Read/Write Alarm 1
Lo.L.s. Lower Limit Setpoint
up.L.s.Upper Limit Setpoint
Lo.L.r. Lower Limit Re-transmis-sion
up.L.r. Upper Limit Re-transmis-sion
Manuale d’uso - ATR142- 87
Il valore in ingresso (compreso tra i limiti minimo e massimo) viene trasformato in maniera lineare nel valore in ritrasmissione compreso tra i valori minimo e massimo in uscita. La riscalatura non viene eseguita se i parametri Lo.L.r. e up.L.r. hanno lo stesso valore.
10.2.2 Modalità master processo remotoPer abilitare questo funzionamento bisogna impostare r.pro. sul parametro 59 mast. In questa modalità l’ATR142 legge un valore da remoto e lo imposta come processo. Lo slave deve avere un ID uguale a quello impostato sul parametro 57 sL.ad. e la word da leggere è selezionata sul parametro 60 add.r. Due interrogazioni successive vengono ritardate del tempo impostato su parametro 57 se.de. Il valore letto può essere riscalato seguendo la proporzione proposta nella seguente tabella:
mast.Limiti valore letto Limiti valore riscalatoMin Max Min Max
r.pro. Read Process
Lo.L.r. Lower Limit Re-transmis-sion
up.L.r. Upper Limit Re-transmis-sion
Lo.L.i. Lower Limit Input
up.L.i. Upper Limit Input
88 - ATR142 - Manuale d’uso
11 Configurazione11.1 Modifica parametro di configurazionePer parametri di configurazione vedi il parametro 11.
Premere Effetto Eseguire
1 FNC per 3s.
Su display 1 compare 0000 con la 1^ cifra lampeggiante, mentre sul display 2 compare pass.
2 “n” o “m”
Si modifica la cifra lampeggiante si passa alla successiva con il tasto SET
Inserire la password 1234
3 SET per conferma
Su display 1 compare il primo parametro e sul secondo il valore.
4 “n” o “m” Scorre i parametri
5SET +“n” o “m”
Si incrementa o decrementa il valore visualizzato premendo prima SET e poi un tasto freccia.
Inserire il nuovo dato che verrà salvato al rilascio dei tasti. Per variare un altro parametro tornare al punto 4
6 FNC
Fine variazione parametri di configurazione.Il regolatore esce dalla programma-zione.
Manuale d’uso - ATR142- 89
12 Tabella parametri di configurazioneL’elenco dei parametri sotto riportato è completo; alcuni di questi non appariranno sui modelli che non dispongono delle relative risorse hardware.
1 c.out Command Outputselezione tipo uscita di comando.c.o2c.o1 > Default (Parametro di fabbrica)c.ssrc.uaL.
ATR142-ABCCommand Alarm 1 Alarm 2
c.o1 Q1 Q2 SSRc.o2 Q2 Q1 SSRc.ssr SSR Q1 Q2c.uaL. Q1(apri) Q2(chiudi) SSR -
ATR142-ABC-TCommand Alarm 1
c.o1 Q1 SSRc.ssr SSR Q1c.uaL. Q1(apri) SSR(chiudi) -
2 SEN. Sensorconfigurazione ingresso analogico.Tc. k Tc-K -260..1360°C > DefaultTc. s Tc-S -40..1760°CTc. r Tc-R -40..1760°CTc. J Tc-J -200..1200°Cpt PT100 -200..600°Cpt 1 PT100 -200..140°Cni NI100 -60..180°Cntc NTC10K -40..125°Cptc PTC1K -50..150°Cpts PT500 -100..600°C
90 - ATR142 - Manuale d’uso
pt1k PT1000 - 100..600°C0.10 0..10Volt0.20 0..20mA4.20 4..20mA0.40 0..40mVoltpot.1 Potenz. Max 6KΩ F.S.pot.2 Potenz. Max 150KΩ F.S.
3 d.p. Decimal Pointseleziona il tipo di decimale visualizzato.0 > Default0.0 1 Decimale0.00 2 Decimali0.000 3 Decimali
4 Lo.L.s. Lower Limit Setpointlimite inferiore setpoint.-999..+9999 [digit3] (gradi.decimi per sensori di temperatura) Default: 0.
5 UP.L.S. Upper Limit Setpointlimite superiore setpoint.-999..+9999 [digit3] (gradi.decimi per sensori di temperatura) Default: 1750.
6 Lo.L.i. Lower Linear Inputlimite inferiore range AN1 solo normalizzati.-999..+9999 [digit3] Default: 0.
7 up.L.i. Upper Linear Inputlimite superiore range AN1 solo normalizzati.-999..+9999 [digit3] Default: 1000.
Manuale d’uso - ATR142- 91
8 Latc. Latch On Functionimpostazione automatica dei limiti per ingressi lineari.dis. Disabilitato > Defaultstd. Standardv.0.st. Zero virtuale memorizzato (parametro 8.10)v.0.in. Zero virtuale allo Start (parametro 8.10)
9 o.caL. Offset Calibrationcalibrazione offset. Numero che si somma/sottrae al processo visualizzato (normalmente corregge il valore di temperatura ambiente).-999..+1000 [digit3] per sensori normalizzati e potenziometri.-99.9..+100.0 (gradi.decimi per sensori di temperatura). > Default: 0.0.
10 G.caL. Gain Calibrationcalibrazione guadagno. Valore % che si moltiplica al processo per eseguire calibrazioni sul punto di lavoro.-99.9%..+100.0% > Default: 0.0
11 act.t. Action typetipo di regolazioneheat Caldo (N.A.) > DefaultcooL, Freddo (N.C.)H.o.o.s. Blocca comando sopra SPV.
12 c. re. Command Resettipo di riarmo del contatto di comando (sempre automatico in funzionamento PID).a.re. Riarmo/reset automatico > Defaultm.re. Riarmo/reset manualem.re.s. Riarmo/reset manuale memorizzato
92 - ATR142 - Manuale d’uso
13 c. s.e. Command State Errorstato del contatto per l’uscita di comando in caso di errore.c.o. > Defaultc.c.
14 c. Ld. Command Leddefinisce lo stato del led OUT1 in corrispondenza del relativo contatto.c.o. c.c. > Default
15 c. HY. Command Hysteresisisteresi in ON/OFF o banda morta in P.I.D.-999..+999 [digit3], (gradi.decimi per sensori di temperatura) > Default: 0.0
16 c. de. Command Delayritardo comando (solo in funzionamento ON/OFF).(In caso di servo valvola funziona anche in PID e rappresenta il ritardo tra l’apertura e la chiusura dei due contatti).-180..+180 secondi, decimi di secondo in caso di servo valvola.Negativo: ritardo in fase di spegnimento.Positivo: ritardo in fase di accensione.Default: 0.
17 c. s.p. Command Setpoint Protectionconsente o meno di variare il valore del setpoint di comando.free > Modificabile > DefaultLock. Bloccato
Manuale d’uso - ATR142- 93
18 p.b. Proportional BandBanda proporzionale.Inerzia del processo in unità (Es.: se temperatura in °C).0 on/off se t.i. uguali a 0. > Default1-9999 [digit3], (gradi per sensori di temperatura).
19 t.i. Integral TimeTempo integrale. Inerzia del processo in secondi.0.0-999.9 sec. (0 integrale disabilitato) > Default: 0.
20 t.d. Derivative TimeTempo derivativo. Normalmente ¼ del tempo integrale.0.0-999.9 sec. (0 integrale disabilitato) > Default: 0.
21 t.c. Cycle TimeTempo di ciclo (per PID su teleruttore 10/15 sec, per PID su SSR 1 sec) o tempo servo (valore dichiarato da produttore del servomotore).0.1-300.0 sec. > Default: 10.0.Per servo-valvole il tempo minimo impostabile è 1.0 sec.
22 o.po.L. Output Power Limitlimite del segnale di comando.10-100 % > Default: 100
23 aL. 1 AlarmAllarme 1. L’intervento dell’allarme è associato a AL1.dis. Disabilitato> Defaulta. aL. Allarme assoluto/ riferito a processo (param. 12)b. aL. Allarme di banda (param. 12)H.d.aL. Allarme deviazione superiore(param. 12)L.d.aL. Allarme deviazione inferiore (param. 12)a.c.aL. Allarme assoluto / riferito a setpoint di comandost.aL. Allarme di stato (attivo in Run/Start)
3 La visualizzazione del punto decimale dipende dall’impostazione del parametro sen. e del parametro d.p.
94 - ATR142 - Manuale d’uso
cooL. Allarme freddo (Cooling)t.1.s.a. Attivo dallo Start di Timer 1t.1.e.a. Attivo allo scadere di Timer 1t.1.w.e. Attivo 5” prima della scadenza di Timer 1t.2.s.a. Attivo dallo Start di Timer 2t.2.e.a. Attivo allo scadere di Timer 2t.2.w.e. Attivo 5” prima della scadenza di Timer 2t.1.2.s. Attivo dallo start di Timer 1-2t.1.2.e. Attivo allo scadere di Timer 1 - 2t.1.2.w. Attivo 5” prima della scadenza di Timer 1 - 2
24 a.1.s.o. Alarm 1 State Outputcontatto uscita allarme 1 e tipo interventon.o. s. (n.o. start) Normalmente aperto attivo allo start
> Defaultn.c. s. (n.c. start) Normalmente chiuso attivo allo start.n.o. t. (n.o. threshold) Normalmente aperto attivo al
raggiungimento dell’allarme4.n.c. t. (n.c. threshold) Normalmente chiuso attivo al
raggiungimento dell’allarme4.25 a.1.re. Alarm 1 Reset
tipo di riarmo del contatto dell’allarme 1.a.re. Riarmo/reset automatico > Defaultm.re. Riarmo/reset manualem.re.s. Riarmo/reset manuale memorizzato
26 a.1.s.e. Alarm 1 State Errorstato del contatto per l’uscita di allarme 1 in caso di errore.c.o. > Defaultc.c.
4 All’accensione l’uscita è inibita se lo strumento è in condizione di allarme. Si attiva solo quando rientrato dalla condizione d’allarme, questa si ripresenta.
Manuale d’uso - ATR142- 95
27 a.1.Ld. Alarm 1 Leddefinisce lo stato del led OUT2 in corrispondenza del relativo contatto.c.o.c.c. > Default
28 a.1.HY. Alarm 1 Hysteresis-999..+999 [digit5], (gradi.decimi per sensori di temperatura).
29 a.1.de. Alarm 1 Delay-180..+180 Sec. > Default: 0.Negativo: ritardo in fase di uscita dall’allarme.Positivo: ritardo in fase di entrata dell’allarme.
30 a.1.s.p. Alarm 1 Setpoint Protectionprotezione set allarme 1. Non consente all’utente di variare il setpoint.Free Modificabile > DefaultLock. BloccatoHide Bloccato e non visualizzato
31 aL. 2 Alarm 2Allarme 2. L’intervento dell’allarme è associato a AL2.dis. Disabilitato > Defaulta. aL. Allarme assoluto/ riferito a processob. aL. Allarme di bandaH.d.aL. Allarme deviazione superioreL.d.aL. Allarme deviazione inferiorea.c.aL. Allarme assoluto / riferito a setpoint di comandost.aL. Allarme di stato (attivo in Run/Start)CooL Allarme freddo (Cooling)t.1.s.a. Attivo dallo Start di Timer 1 t.1.e.a. Attivo allo scadere di Timer 1 t.1.w.e. Attivo 5” prima della scadenza di Timer 1
5 La visualizzazione del punto decimale dipende dall’impostazione del parametro sen. e del parametro d.p.
96 - ATR142 - Manuale d’uso
t.2.s.a. Attivo dallo Start di Timer 2t.2.e.a. Attivo allo scadere di Timer 2t.2.w.e. Attivo 5” prima della scadenza di Timer 2t.1.2.s. Attivo dallo start di Timer 1-2 t.1.2.e. Attivo allo scadere di Timer 1 - 2t.1.2.w. Attivo 5” prima della scadenza di Timer 1 - 2
32 a.2.s.o. Alarm 2 State Outputcontatto uscita allarme 2 e tipo interventon.o. s. (n.o. start) Normalmente aperto attivo allo start
> Defaultn.c. s. (n.c. start) Normalmente chiuso attivo allo start.n.o. t. (n.o. threshold) Normalmente aperto attivo al
raggiungimento dell’allarme6
n.c. t. (n.c. threshold) Normalmente chiuso attivo al raggiungimento dell’allarme6
33 a.2.re. Alarm 2 ResetTipo di riarmo del contatto dell’allarme 2.a.re. Riarmo/Reset automatico> Defaultm.re. Riarmo/Reset manualem.re.s. Riarmo/Reset manuale memorizzato
34 a.2.s.e. Alarm 2 State Errorstato del contatto per l’uscita di allarme 2 in caso di errore.c.o. > Defaultc.c.
35 a.2.Ld. Alarm 2 Leddefinisce lo stato del led OUT2 in corrispondenza del relativo contatto.c.o.c.c. > Default
6 All’accensione l’uscita è inibita se lo strumento è in condizione di allarme. Si attiva solo quando rientrato dalla condizione d’allarme, questa si ripresenta.
Manuale d’uso - ATR142- 97
36 a.2.HY. Alarm 2 Hysteresis-999..+999 [digit7], (gradi.decimi per sensori di temperatura). > Default: 0.
37 a.2.de. Alarm 2 Delay-180..+180 Sec. > Default: 0.Negativo: ritardo in fase di uscita dall’allarme.Positivo: ritardo in fase di entrata dell’allarme.
38 a.2.s.p. Alarm 2 Setpoint Protectionprotezione set allarme 2. Non consente all’operatore di variare il valore impostato.free Modificabile > DefaultLock. BloccatoHide Bloccato e non visualizzato
39 coo.f. Cooling Fluidtipo di fluido refrigerante (parametro 7.12)air Aria> DefaultoiL OlioH2o Acqua
40 p.b.m. Proportional Band MultiplierMoltiplicatore banda proporzionale (parametro 7.12)1.00-5.00 > Default: 1.00.
41 ov.d.b. Overlap/Dead Bandsovrapposizione/Banda Morta -20.0-50.0% > Default: 0.
42 co.t.c. Cooling Cycle Timetempo ciclo per uscita refrigerante1-300 sec. > Default: 10.
98 - ATR142 - Manuale d’uso
43 c.fLt. Conversion Filterfiltro adc: n° medie effettuate su conversioni analogico-digitali.dis. Disabilitato2. s.m. Media su 2 campionamenti3. s.m. Media su 3 campionamenti4. s.m. Media su 4 campionamenti5. s.m. Media su 5 campionamenti6. s.m. Media su 6 campionamenti7. s.m. Media su 7 campionamenti8. s.m. Media su 8 campionamenti9. s.m. Media su 9 campionamenti10.s.m. Media su 10 campionamenti> Default11.s.m. Media su 11 campionamenti12.s.m. Media su 12 campionamenti13.s.m. Media su 13 campionamenti14.s.m. Media su 14 campionamenti15.s.m. Media su 15 campionamenti
44 c.frn. Conversion Frequencyfrequenza di camp. del convertitore analogico-digitale242H. 242 Hz Max velocità di conversione ADC123H. 123 Hz62 H. 62 Hz50 H. 50 Hz39 H. 39 Hz33.2H. 33.2 Hz19.6H. 19.6 Hz16.7H. 16.7 Hz > Default12.5H. 12.5 Hz10 H. 10 Hz8.33H. 8.33 Hz6.25H. 6.25 Hz4.17H. 4.17 Hz Min. velocità di conversione ADC
Manuale d’uso - ATR142- 99
45 v.fLt. Visualization Filterfiltro in visualizzazione. Rallenta l’aggiornamento del display mantenendo invariata la velocità di conversione ADC.dis. DisabilitatoptcH Filtro “forchetta” > Defaultfi.or. Primo ordine f.or.p. Primo ordine con filtro “forchetta”2. s.m. Media su 2 campionamenti3. s.m. Media su 3 campionamenti4. s.m. Media su 4 campionamenti5. s.m. Media su 5 campionamenti6. s.m. Media su 6 campionamenti7. s.m. Media su 7 campionamenti8. s.m. Media su 8 campionamenti9. s.m. Media su 9 campionamenti10.s.m. Media su 10 campionamenti
46 tune Tuneselezione tipo Autotuningdis. Disabilitato > Defaultauto Automatico. Calcolo parametri PID all’accensio-
ne e al variare del setpointman. Manuale. Autotuning lanciato da tastira o da
ingresso digitaleonce Once (Calcolo dei parametri P.I.D. solamente alla
prima accensione)
47 s.d.tu. Setpoint Deviation Tuneseleziona la deviazione dal setpoint di comando per la soglia usata dall’ autotuning per il calcolo dei parametri PID.0-5000 [digit7], (gradi.decimi per sensori di temperatura) > Default: 10.
100 - ATR142 - Manuale d’uso
48 op.mo. Operating Modeselezione funzionamento (param. 7.11)cont. Regolatore > Defaultpr.cY. Ciclo pre-programmato2t.s. Cambio setpoint (2 setpoint impostati) 2t.s.i. Cambio setpoint a impulso (2 setpoint impostati)3t.s.i. Cambio setpoint a impulso (3 setpoint impostati)4t.s.i. Cambio setpoint a impulso (4 setpoint impostati)
49 au.ma. Automatic/Manualabilita la selezione automatico/manuale (param. 7.6)dis. Disabilitato > Defaulten. Abilitatoen.st. Abilitato e memorizzato in caso di spegnimento
50 dGt.i. Digital Inputfunzionamento ingresso digitale (param. 7.11)Selezione parametro 48 deve essere cont. oppure Pr.cy.dis. Disabilitato (Default: 0)st.st. Ciclo pre-programmato con Start / Stoprn.no. Run N.O. (abilita regolazione con ingresso
chiuso)rn.nc. Run N.C. (abilita regolazione con ingresso
aperto)L.c.n.o. Lock conversion N.O. (blocca la lettura delle
sonde con ingresso chiuso)L.c.n.c. Lock conversion N.C. (blocca la lettura delle
sonde con ingresso aperto)tune Tune (abilita l’auto-tuning manualmente)a.ma.i. Auto manual impulsive (regolazione
automatica/manuale ad impulso, param. 7.11)a.ma.c Automatic manual contact (regolazione
automatica/manuale a seconda dello stato dell’ingresso, param. 7.11)
t.1.s.s. Timer 1 Start Stop
Manuale d’uso - ATR142- 101
51 Grad. Gradientgradiente di salita per Soft Start o ciclo preprogrammato.0 Disabilitato > Default: 0.1-9999 Digit/ora7 (gradi/ora con visualizzazione del decimo se temperatura)
52 ma.ti. Maintenance Timetempo mantenimento per ciclo preprogrammato.00.00-24.00 hh.mm > Default: 00.00
53 u.m.c.p. User Menu Cycle Programmedpermette di modificare gradiente di salita e tempo di mantenimento dal menù utente in funzionamento ciclo preprogrammato (parametro 7.7)dis. Disabilitato > Defaultri.Gr. Rising Gradient (modifica gradiente salita)ma.t.i. Maintenance Time (modifica tempo
mantenimento)r.G.m.t. Rising Gradient and Maintenance Time (mod.
entrambi)fa.Gr. Falling Gradient (modifica gradiente in discesa)r.f.Gr. Rising and Falling Gradient (modifica gradiente
in salita e discesa)f.G.m.t. Falling Gradient and Maintenance Time
(modifica gradiente discesa e tempo mantenimento)
aLL. All (modifica tutti i parametri)
54 vi.tY. Visualization Typeimposta la visualizzazione sul display 1 e 21.p.2.s. 1 Processo, 2 Setpoint > Default1.p.2.H. 1 Processo, 2 Non visualizzato dopo 3 sec.1.s.2.p. 1 Setpoint, 2 Processo1.s.2.H. 1 Setpoint, 2 Non visualizzato dopo 3 sec.
7 La visualizzazione del punto decimale dipende dall’impostazione del parametro sen. e del parametro d.p.
102 - ATR142 - Manuale d’uso
55 deGr. Degreeselezione tipo gradic Gradi Celsius > DefaultF Gradi Fahrenheit
56 bd.rt. Baud Rateseleziona il baud rate per la comunicazione seriale4.8 k9.6 k19.2k > Default28.8k38.4k 57.6k
57 sL.ad. Slave Addressseleziona l’ID dello slave per la comunicazione seriale.0 – 255 > Default: 254.
58 se.de. Serial Delayseleziona il ritardo seriale0 - 100 millisecondi > Default: 20.
59 mast. Masterseleziona la modalità Master (parametro 9.2)dis. Disabilitato > Defaultw.pro Write Process (scrive valore processo)r.w.co. Read Write Command Setpoint (scrive/legge
setpoint di comando)w.ou.p. Write Output Percentage (scrive % uscita
comando)r.w.a.1 Read Write Alarm 1 Setpoint (scrive/legge
setpoint allarme1)r.pro. Read Process (legge valore processo)
60 add.r. Address Retransmissionseleziona l’indirizzo per la ritrasmissione0x0000 – 0xFFFF esadecimale > Default: 0x03E9.
Manuale d’uso - ATR142- 103
61 Lo.L.r. Lower Limit Retransmissionlimite inferiore range ritrasmissione-999 - 9999 [digit8], (gradi per sensori di temperatura) > Default: 0.
62 up.L.r. Upper Limit Retransmissionlimite superiore range ritrasmissione9
-999 – 9999 [digit8], (gradi per sensori di temperatura) > Default: 0.
63 tmr.f. Timer Functionabilita 1 o 2 timer impostabili da menù utente e collegabili agli allarmi.dis. Disabilitato > Defaults.tm.s. Timer singolo/ base tempi in secondid.tm.s. Timer doppio/ base tempi in secondid.s.t.s. Doppio Timer sequenziale/ base tempi in
secondid.t.L.s. Doppio Timer Loop/base tempi in secondis.tm.m. Timer singolo/ base tempi in minutid.tm.m. Timer doppio/ base tempi in minutid.s.t.m. Doppio Timer sequenziale/ base tempi in minutid.t.L.m. Doppio Timer Loop/base tempi in minuti
64 Fa.Gr. Falling Gradientgradiente di discesa controllato per ciclo preprogrammato0 disabilitato (raffreddamento naturale) > Default: 0.1-9999 gradi/ora con visualizzazione del decimo.
8 La visualizzazione del punto decimale dipende dall’impostazione del parametro sen. e del parametro d.p.
9 Se i parametri 61 Lo.L.r. e 62 up.L.r. hanno lo stesso valore, il valore ritrasmesso non viene scalato.
104 - ATR142 - Manuale d’uso
13 Modi d’intervento allarme13.a Allarme assoluto o allarme di soglia (selezione
a. aL.)
Alarm Spv
Pv.
O�On On
O�
Hysteresisparameter > 0
Time
Alarm output
Allarme assoluto con regolatore in funzionamento caldo (Parametro 11 act.t. selezionato Heat) e valore di isteresi maggiore di “0” (Parametro 28 a.1.Hy. > 0). *
O�On On
O�
Hysteresisparameter < 0
Alarm Spv.
Pv
Time
Alarm output
Allarme assoluto con regolatore in funziona-mento caldo (Parametro 11 act.t. selezionato Heat) e valore di isteresi minore di “0” (Parametro 28 a.1.Hy. < 0). *
On On
Hysteresisparameter > 0
Alarm Spv
PvTime
Alarm output
Allarme assoluto con regolatore in funzionamento freddo (Parametro 11 act.t. selezionato cooL) e valore di isteresi maggiore di “0” (Parametro 28 a.1.Hy. > 0). *
Manuale d’uso - ATR142- 105
On On
Hysteresisparameter < 0
Alarm Spv
PvTime
Alarm output
Allarme assoluto con regolatore in funzionamento freddo (Parametro 11 act.t. selezionato cooL) e valore di isteresi maggiore di “0” (Parametro 28 a.1.Hy. > 0). *
13.b Allarme assoluto o allarme di soglia riferito al setpoint di comando (selezione a.c.aL.)
O�On
Hysteresisparameter > 0
O�
Alarm Spv
Command Spv
Time
Alarm output
Allarme assoluto riferito al set di comando, con regolatore in funzionamento caldo (Parametro 11 act.t. selezionato Heat) e valore di isteresi maggiore di “0” (Parametro 28 a.1.Hy. > 0).Il set di comando può essere variato con la pressione dei tasti freccia da frontale o con comandi su porta seriale RS485. *
106 - ATR142 - Manuale d’uso
13.c Allarme di Banda (selezione b. aL.)
Pv
O� O�On On On
Hysteresisparameter > 0
Alarm Spv
Alarm Spv
Command Spv
Time
Alarm output
Allarme di banda valore di isteresi maggiore di “0” (Parametro 28 a.1.Hy. > 0). *
O� O� O�On On On
Hysteresisparameter < 0
Hysteresis
< 0
Pv
Alarm SpvCommand Spv
Time
Alarm output
Allarme di banda valore di isteresi minore di “0” (Parametro 28 a.1.Hy. < 0). *
13.e Allarme deviazione superiore (selezione H.d.aL.)
O� O�On On
Hysteresisparameter > 0
Pv
Alarm Spv
Command Spv
Time
Alarm output
Allarme di deviazione superiore valore di setpoint allarme maggiore di “0” e valore di isteresi maggiore di “0” (Parametro28 a.1.Hy. > 0). **
Manuale d’uso - ATR142- 107
O� O�
Hysteresisparameter > 0
Pv
Alarm SpvCommand Spv
Time
Alarm output
Allarme di deviazione superiore valore di setpoint allarme minore di “0” e valore di isteresi maggiore di “0” (Parametro 28 a.1.Hy. > 0). **
13.f Allarme deviazione inferiore (selezione L.d.aL.)
O� O�On On
Hysteresisparameter
Pv
Alarm Spv
Command Spv
Time
Alarm output
Allarme di deviazione inferiore valore di setpoint allarme maggiore di “0” e valore di isteresi maggiore di “0” (Parametro 28 a.1.Hy. > 0). **
On On
Hysteresisparameter > 0
Pv.
Alarm Spv
Command Spv
Time
Alarm output
Allarme di deviazione inferiore valore di setpoint allarme minore di “0” e valore di isteresi maggiore di “0” (Parametro 28 a.1.Hy. > 0). **
* l’esempio è riferito all’allarme 1; la funzione è abilitabile anche per l’allarme 2 sui modelli che lo prevedono.
** a) L’esempio è riferito all’allarme 1; la funzione è abilitabile anche per l’allarme 2 sui modelli che lo prevedono. b) Con isteresi minore di “0” (a.1.Hy. < 0) la linea tratteggiata si sposta sopra il Setpoint di allarme.
108 - ATR142 - Manuale d’uso
14 Tabella segnalazioni anomalieIn caso di mal funzionamento dell’impianto il controllore spegne l’uscita di regolazione e segnala il tipo di anomalia riscontrata. Per esempio il regolatore segnalerà la rottura di un’eventuale termocoppia collegata visualizzando e-05 (lampeggiante) sul display. Per le altre segnalazioni vedi la tabella sottostante.
Cause What to doE-01sYs.e.
Errore in programmazio-ne cella E²PROM. Chiamare Assistenza
E-02sYs.e.
Guasto sensore temperatura giunto freddo o temperatura ambiente al di fuori dei limiti ammessi.
Chiamare Assistenza
E-04sYs.e.
Dati di configurazione errati. Possibile perdita della tarature dello strumento.
Verificare che i parametri di configurazione siano corretti.
E-05prb.
Termocoppia aperta o temperatura fuori limite.
Controllare il collega-mento con le sonde e la loro integrità.
E-06ser.e.
Fuori linea in caso di funzionamento master con processo remoto
Controllare il collegamento seriale, il baud-rate e l’ID dei moduli
E-08sYs.e.
Taratura mancante Chiamare Assistenza
Note / Aggiornamenti
Manuale d’uso - ATR142- 109
Tabella delle configurazioni dei parametri1 c.out Command Output 892 SEN. Sensor 893 d.p. Decimal Point 904 Lo.L.s. Lower Limit Setpoint 905 UP.L.S. Upper Limit Setpoint 906 Lo.L.i. Lower Linear Input 907 up.L.i. Upper Linear Input 908 Latc. Latch On Function 919 o.caL. Offset Calibration 9110 G.caL. Gain Calibration 9111 act.t. Action type 9112 c. re. Command Reset 9113 c. s.e. Command State Error 9214 c. Ld. Command Led 9215 c. HY. Command Hysteresis 9216 c. de. Command Delay 9217 c. s.p. Command Setpoint Protection 9218 p.b. Proportional Band 9319 t.i. Integral Time 9320 t.d. Derivative Time 9321 t.c. Cycle Time 9322 o.po.L. Output Power Limit 9323 aL. 1 Alarm 9324 a.1.s.o. Alarm 1 State Output 9425 a.1.re. Alarm 1 Reset 9426 a.1.s.e. Alarm 1 State Error 9427 a.1.Ld. Alarm 1 Led 9528 a.1.HY. Alarm 1 Hysteresis 9529 a.1.de. Alarm 1 Delay 9530 a.1.s.p. Alarm 1 Setpoint Protection 9531 aL. 2 Alarm 2 9532 a.2.s.o. Alarm 2 State Output 96
110 - ATR142 - Manuale d’uso
33 a.2.re. Alarm 2 Reset 9634 a.2.s.e. Alarm 2 State Error 9635 a.2.Ld. Alarm 2 Led 9636 a.2.HY. Alarm 2 Hysteresis 9737 a.2.de. Alarm 2 Delay 9738 a.2.s.p. Alarm 2 Setpoint Protection 9739 coo.f. Cooling Fluid 9740 p.b.m. Proportional Band Multiplier 9741 ov.d.b. Overlap/Dead Band 9742 co.t.c. Cooling Cycle Time 9743 c.fLt. Conversion Filter 9844 c.frn. Conversion Frequency 9845 v.fLt. Visualization Filter 9946 tune Tune 9947 s.d.tu. Setpoint Deviation Tune 9948 op.mo. Operating Mode 10049 au.ma. Automatic/Manual 10050 dGt.i. Digital Input 10051 Grad. Gradient 10152 ma.ti. Maintenance Time 10153 u.m.c.p. User Menu Cycle Programmed 10154 vi.tY. Visualization Type 10155 deGr. Degree 10256 bd.rt. Baud Rate 10257 sL.ad. Slave Address 10258 se.de. Serial Delay 10259 mast. Master 10260 add.r. Address Retransmission 10261 Lo.L.r. Lower Limit Retransmission 10362 up.L.r. Upper Limit Retransmission 10363 tmr.f. Timer Function 10364 Fa.Gr. Falling Gradient 103
PIXSYS s.r.l.www.pixsys.net
[email protected] - [email protected]
online assistance: http://forum.pixsys.net
2300.10.092-RevLSoftware Rev. 1.21
110117
Read carefully the safety guidelines and programming instructions contained in this manual before using/connecting the device.
Prima di utilizzare il dispositivo leggere con attenzione le informazioni di sicurezza e settaggio contenute in questo manuale.