astm standards for pervious - virginia department of ... · astm c-1701 used to check infiltration...
TRANSCRIPT
![Page 1: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/1.jpg)
![Page 2: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/2.jpg)
![Page 3: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/3.jpg)
ASTM Standards for Pervious
C-1688 – Fresh Unit Weight
C-1701 – Hardened Infiltration
C-1747 – Raveling Potential
C-1754 - Hardened Density and Voids
![Page 4: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/4.jpg)
ASTM C 1688
Closest thing to a ‘slump test’ for pervious – used to check the ready mix producer’s consistency
Also provides important information to the installer and the testing lab or owner
Current range of +/- 5 pounds per cubic foot may be too broad (my opinion)
Voids and density will vary based on local materials, application requirements and installer’s method of placement.
![Page 5: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/5.jpg)
ASTM C-1701
Used to check infiltration rates of hardened pervious
May now be used for acceptance – specify as a minimum (400 inches/hour?)
Results for individual test vary – look at averages.
Useful for determining loss of infiltration rate over time – if test is run immediately after placement and before service to set a baseline
Use to determine when cleaning or other maintenance is needed
![Page 6: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/6.jpg)
![Page 7: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/7.jpg)
ASTM C-1747
More important than compressive strength for pervious (my opinion…)
Samples are molded per the standard and then tumbled (LA Abrasion) 500 cycles (no steel shot)
Mass loss is measured – lower loss should mean tougher, more durable pervious.
Results under 40% mass loss appear to represent good pervious mixes.
Not intended for use with cores
![Page 8: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/8.jpg)
ASTM C-1754
For HARDENED density and voids
Requires coring – tests are run on cores taken from field installation
Two drying methods are allowed in the standard – they will produce different results. Can’t compare results between the two drying methods.
![Page 9: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/9.jpg)
ACI 522.1-13
Reference Specification for Pervious Concrete
Specifiers may add additional requirements – suggest inclusion of the following:
Baseline infiltration testing using C-1701
Determination of hardened density to use C-1754
Consider use of C-1747 for mix design submittals
ENFORCE requirements for certified installers AND testing personnel
![Page 10: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/10.jpg)
Modern Pervious Placement
REQUIRE certified installers, per ACI 522.1-13
Most pervious today placed with single roller screeds and should produce good, consistent results.
Better techniques are being developed to increase compaction without sealing the pavement
BUT they require skilled installers and good mix designs!
![Page 11: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/11.jpg)
Contractor Certification
Pervious Concrete Installer Certification developed by the National Ready Mixed Concrete Association
Three levels of certification:
Technician – pass written exam. Required for field testing technicians. NOT sufficient for Installer personnel
Installer – pass written and performance exam, plus meet minimum experience qualifications. Three Installers required on every pervious placement to meet ACI 522.1-13
Craftsman – All of the above, plus 1500 hours of direct pervious experience. (Still very rare – about 45 in US)
![Page 12: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/12.jpg)
![Page 13: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/13.jpg)
![Page 14: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/14.jpg)
Modern Pervious Mixes
Easier to place and harder to mess up
CAUTION: Still a lot of “old” mix designs floating around
Cementitious contents are trending lower and w/c ratios are trending higher – both good things!
NEVER specify cement content or require minimum cement contents!
ALWAYS require ready mix producer to submit C 1688 information (density and voids) and consider C 1747 test results
![Page 15: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/15.jpg)
Pervious Wet Voids
![Page 16: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/16.jpg)
Modern Pervious Mix
![Page 17: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/17.jpg)
![Page 18: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/18.jpg)
It’s NOT 1-size Fits All…
![Page 19: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/19.jpg)
Results From the Field
Murfreesboro Ready Mix Plant Installation Preliminary Results Infiltration Results
![Page 20: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/20.jpg)
Murfreesboro (TN) 2016 Field Study
49 Test Loads UW Hard Hard Void C1688 NONE! C1747 C1701
C1754 C1754 Unit Weight PSI Mass R Infiltration
min 115.16 1155.50 58.00 469.82
max 134.37 3314.50 86.00 2839.64
range 19.21 2159.00 28.00 2369.82
(7 Tests) 113.7953541 27.49 mean 124.53 2056.69 72.28 1583.95
median 123.39 1959.25 71.50 1594.25
std. dev. 4.24 479.27 5.75 578.01
%std. dev. 3.4% 23.3% 8.0% 36.5%
![Page 21: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/21.jpg)
Adding 20# of OPC
Formula comp. strength 28d abrasion mass kept infiltration
A2 2724 86
C10 (+20 OPC) 2712.5 76 1573
C11 (+20 OPC) 2302 72 2258
C12 (+20 OPC) 2256.5 70 1697
C13 (+20 OPC) 2680.5 67 N/T
C17 (+20 OPC) 2966.5 74 N/T
Averages 2584 72 1843
![Page 22: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/22.jpg)
Adding 125# Sand
Formula comp. strength 28d abrasion mass kept infiltration
A2 2724 86
C14 (+125 sand) 2551.5 80 2116
C15 (+125 sand) 2902 72 2840
C16 (+125 sand) 2376.5 81 N/T
C18 (+125 sand) 2261 67 N/T
Averages 2523 75 2478
![Page 23: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/23.jpg)
Does it Need Maintenance?
![Page 24: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/24.jpg)
Absolutely!
![Page 25: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/25.jpg)
Can it be Cleaned?
![Page 26: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/26.jpg)
Absolutely!
![Page 27: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/27.jpg)
![Page 28: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/28.jpg)
NRMCA Maintenance & Operations Guide
![Page 29: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/29.jpg)
First Steps Designs should be checked to see if they are maintenance-
friendly
Assure/Verify a quality installation, including soil characteristics, gravel layer, and pervious
Require certified installers and REQUIRE initial infiltration testing (C1701)
Provide owner with Maintenance/Operations Guide
![Page 30: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/30.jpg)
Next (Three) Steps
Step One: Routine Maintenance
Periodic Visual Inspection
Leaf blower or similar as needed
Sweeping (for entire lot) as needed
Spot maintenance – more intensive as needed to prevent more severe clogging
![Page 31: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/31.jpg)
![Page 32: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/32.jpg)
Next (Three) Steps
Step Two: Periodic Maintenance
Often PRIOR to onset of winter, always when routine maintenance isn’t enough
Should start with sweeping or dry vacuum process – get all loose material off. Measure (weigh) if possible.
May require pressure wash and vacuum at same time
![Page 33: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/33.jpg)
Next (Three) Steps
Step Three: Deep Cleaning
When infiltration rate drops by more than 25%, or under 100 inches per hour.
Will require simultaneous application of pressurized water and significant vacuum – specialized equipment.
![Page 34: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/34.jpg)
![Page 35: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/35.jpg)
![Page 36: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/36.jpg)
Results From the Field
0 Franklin Eastern Flank Infiltration Testing
0 Pervious Field Inspection Report
![Page 37: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/37.jpg)
Franklin (TN) Parking Lot
Estimated Pounds Removed: 843
Primary Filter Bag 169
Dry Vacuum Removal: 280
Total Pounds Removed: 1292
Over ¼# of sediment per SF
![Page 38: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/38.jpg)
Franklin (TN) Parking Lot
Average Infiltration Before: 18 Inches/HR
Average Infiltration After: 196 Inches/HR
![Page 39: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/39.jpg)
Winter Time Notes
1st winter is more critical – same as for conventional concrete
De-icing chemicals NOT recommended. Research ongoing for admixtures to impart better chemical resistance
Calcium treated sand (after 1st winter) or plain COARSE sand may be used – pavement must be vacuumed at end of winter
Plow with caution
![Page 40: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/40.jpg)
Questions?
![Page 41: ASTM Standards for Pervious - Virginia Department of ... · ASTM C-1701 Used to check infiltration rates of hardened pervious May now be used for acceptance – specify as a minimum](https://reader033.vdocuments.us/reader033/viewer/2022042214/5eb9595a5342667ccd4162fa/html5/thumbnails/41.jpg)
Contact Information
Tennessee Concrete Association
705 Fort Negley Court
Nashville, TN 37203
615-360-7393
www.tnconcrete.org
Alan Sparkman, Executive Director