ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 Rendered to: ARCADIA INC. Vernon, California PRODUCT TYPE: Awning SERIES/MODEL: IPMT200 Test Date: 06/30/16 Report Date: 09/20/16 Revision Date: 10/11/16 Test Record Retention End Date: 06/30/20 25800 Commercenter Drive Lake Forest, CA 92630 www.intertek.com/building p. 949.448.4100 f. 717.764.4129

Upload: others

Post on 13-Aug-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

ASTM E1886 and ASTM E1996 TEST REPORT

Report No.: G0058.01-301-44

Rendered to:

ARCADIA INC. Vernon, California

PRODUCT TYPE: Awning

SERIES/MODEL: IPMT200

Test Date: 06/30/16 Report Date: 09/20/16 Revision Date: 10/11/16 Test Record Retention End Date: 06/30/20

25800 Commercenter DriveLake Forest, CA 92630

www.intertek.com/building p. 949.448.4100f. 717.764.4129

Page 2: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

Test Report No.: G0058.01-301-44 Report Date: 09/20/16

Revision 1 Date: 10/11/16 Page 1 of 8

1.0 Report Issued To: Arcadia Inc. 2301 East Vernon Avenue Vernon, California 90058 2.0 Test Laboratory: Architectural Testing, Inc., an Intertek company ("Intertek-ATI") 25800 Commercentre Dr. Lake Forest, California 92630 949-460-9600 3.0 Project Summary:

3.1 Product Type: Awning

3.2 Series/Model: IPMT200

3.3 Compliance Statement: Results obtained are tested values and were secured by using the designated test methods. The specimen tested met the performance requirements set forth in the referenced test procedures for a ±4597 Pa (±96.0 psf) Design Pressure with missile impacts corresponding to Missile Level D and Wind Zone 3.

3.4 Test Date: 06/30/16

3.5 Test Record Retention End Date: All test records for this report will be retained until June 30, 2020.

3.6 Test Location: Intertek-ATI test facility in Lake Forest, California.

3.7 Test Specimen Source: The test specimen was provided by the client. Representative samples of the test specimen will be retained by Intertek-ATI for a minimum of four years from the test completion date.

3.8 Drawing Reference: The test specimen drawings have been reviewed by Intertek-ATI

and are representative of the test specimen reported herein. Test specimen

construction was verified by Intertek-ATI per the drawings located in Appendix B. Any

deviations are documented herein or on the drawings.

3.9 List of Official Observers:

Name Company Greg Millward Arcadia Inc. Charles Presley Intertek-ATI Jarod Hardman Intertek-ATI

Page 3: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

Test Report No.: G0058.01-301-44 Report Date: 09/20/16

Revision 1 Date: 10/11/16 Page 2 of 8

4.0 Test Specifications:

ASTM E1886-13a, Standard Test Method for Performance of Exterior Windows, Curtain Walls, Doors, and Impact Protective Systems Impacted by Missile(s) and Exposed to Cyclic Pressure Differentials ASTM E1996-14a, Standard Specification for Performance of Exterior Windows, Curtain Walls, Doors, and Impact Protective Systems Impacted by Windborne Debris in Hurricanes

5.0 Test Specimen Description:

5.1 Product Sizes: Test Specimens #1:

Overall Area: 1.5 m² (15.95 ft2)

Width Height

millimeters inches millimeters inches

Overall size 1585 62-13/32 935 36-13/16

Vent 1531 60-1/4 879 34-19/32

5.2 Frame Construction:

Frame Member Material Description

Head, sill, and jambs

Aluminum Thermally broken extrusion, Part No. WTH-01, see attached drawing #D-1, D-2, and D-3.

Joinery Type Detail

All corners Mitered Corners were secured with aluminum corner keys, Part No. WWM-01.

5.3 Vent Construction:

Vent Member Material Description

Head, sill, and jambs

Aluminum Thermally broken extrusion, Part No. WTZ-02, see attached drawing #D-1, D-2, and D-3.

Head, sill, and jambs

Aluminum Glazing bead, Part No. WWB-14, snap fit into vent frame, see attached drawing #D-1, D-2, and D-3.

Joinery Type Detail

All corners Mitered Corners were secured with aluminum corner keys, Part No. WWM-01.

Page 4: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

Test Report No.: G0058.01-301-44 Report Date: 09/20/16

Revision 1 Date: 10/11/16 Page 3 of 8

5.0 Test Specimen Description: (Continued) 5.4 Reinforcement: No reinforcement was utilized. 5.5 Weatherstripping:

Description Quantity Location

Hollow bulb gasket, Part No. D#4-5169

1 row Full perimeter of interior leg of frame.

Hollow bulb gasket, Part No. D#4-5169

1 row Full perimeter of exterior leg of vent top rail, bottom rail, and stiles with interruptions in gasket at weeps in sill.

5.6 Glazing: No conclusions of any kind regarding the adequacy or inadequacy of the glass

in any glazed test specimen(s) can be made.

Glass Type

Spacer Type Interior Lite Exterior Lite Glazing Method

1-5/16" IG

Aluminum – Dual Seal

spacer (A-D2)

1/4" clear heat strengthened –

0.090 Sentryglass –

1/4" clear heat strengthened

1/4" clear heat

strengthened

Wet sealed at interior side with structural silicone sealant and secured at exterior face with snap in glazing bead Part No. WWB-14 (see attached drawing #D-1, D-2, and D-3).

Location Quantity Daylight Opening

Glass Bite millimeters inches

Vent 1 1411 x 761 55-9/16 x 29-31/32 3/4"

5.7 Drainage:

Drainage Method Size Quantity Location

Weep hole 1" x 1/8" 2 Notch in the snap in legs of the glazing bead of the bottom rail to drain the glazing pocket.

Gasket interrupt 1" 2 Gasket was removed directly in front of weep holes to allow for drainage of the vent pocket.

Page 5: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

Test Report No.: G0058.01-301-44 Report Date: 09/20/16

Revision 1 Date: 10/11/16 Page 4 of 8

5.0 Test Specimen Description: (Continued)

5.8 Hardware:

Description Quantity Location

Cam lock 2 Secured to bottom rail of vent with two #8 x 1/2" Phillips flat head screws, 10" from each corner of vent.

Keeper 2 Secured directly opposite cam lock on sill of frame with two #8 x 1/2" Phillips flat head screws.

5.9 Screen Construction: No screen was utilized.

6.0 Installation: The specimen was installed into a Pine wood buck. The rough opening allowed for a 1/4" shim space. The exterior perimeter of the window was sealed with silicone sealant.

Location Anchor Description Anchor Location

Through frame full perimeter

1/4" x 3" Hex head wood screw 16" on center spacing

Page 6: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

Test Report No.: G0058.01-301-44 Report Date: 09/20/16

Revision 1 Date: 10/11/16 Page 5 of 8

7.0 Test Results: The results are tabulated as follows:

ASTM E1886, Large Missile Impact

Conditioning Temperature: 23.9°C (75°F) Missile Weight: 4082 g (9.0 lbs) Missile Length: 2.4 m (8'0") Muzzle Distance from Test Specimen: 4.3 m (14'0")

Test Unit #1: Orientation within ±5° of horizontal

Impact #1: Missile Velocity: 15.4 m/s (50.5 fps)

Impact Area: Bottom right corner of vent

Observations: Missile hit target area, broke glass, no penetration

Results: Pass

Impact #2: Missile Velocity: 15.4 m/s (50.4 fps)

Impact Area: Center of vent

Observations: Missile hit target area, broke glass, no penetration

Results: Pass

Note: See Intertek-ATI Sketch #1 for impact locations.

Page 7: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

Test Report No.: G0058.01-301-44 Report Date: 09/20/16

Revision 1 Date: 10/11/16 Page 6 of 8

7.0 Test Results: (Continued)

ASTM E1886, Air Pressure Cycling Test Unit #1 Design Pressure: ±4597 Pa (±96.0 psf)

POSITIVE PRESSURE

Pressure Range

Pa (psf)

Number of Cycles

Average Cycle Time

(seconds) Observations

919 to 2298 (19.2 to 48.0)

3500 1.86 Ok, no damage.

0 to 2758 (0.0 to 57.6)

300 2.02 Ok, no damage.

2298 to 3677 (48.0 to 76.8)

600 1.91 Ok, no damage.

1379 to 4597 (28.8 to 96.0)

100 2.43 Ok, no damage.

NEGATIVE PRESSURE

Pressure Range

Pa (psf)

Number of Cycles

Average Cycle Time

(seconds) Observations

1379 to 4597 (28.8 to 96.0)

50 2.89 Ok, no damage.

2298 to 3677 (48.0 to 76.8)

1050 2.13 Ok, no damage.

0 to 2758 (0.0 to 57.6)

50 2.47 Ok, no damage.

919 to 2298 (19.2 to 48.0)

3350 2.12 Ok, no damage.

Result: Pass

Page 8: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

Test Report No.: G0058.01-301-44 Report Date: 09/20/16

Revision 1 Date: 10/11/16 Page 7 of 8

General Note: Upon completion of testing, the specimens met the requirements of Section 7 of ASTM E1996. 8.0 Test Equipment:

Cannon: Constructed from steel piping utilizing compressed air to propel the missile

Missile: 2x4 Southern Pine

Timing Device: Electronic Beam Type

Cycling Mechanism: Computer controlled centrifugal blower with electronic pressure measuring device

Tape and film were used to seal against air leakage during structural testing. In our opinion, the tape and film did not influence the results of the test. Intertek-ATI will service this report for the entire test record retention period. Test records such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation, will be retained by Intertek-ATI for the entire test record retention period. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Intertek-ATI. For ARCHITECTURAL TESTING, INC.: ____________________________________ ____________________________________ Charles Presley Jarod S. Hardman Technician Laboratory Manager JSH:ss Attachments (pages): This report is complete only when all attachments listed are included. Appendix A: Sketch (1) Appendix B: Drawings (7)

Page 9: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

Test Report No.: G0058.01-301-44 Report Date: 09/20/16

Revision 1 Date: 10/11/16 Page 8 of 8

Revision Log

Rev. # Date Page(s) Revision(s)

0 09/20/16 N/A Original report issue.

1 10/11/16 Drawing cover page Update drawing cover page.

This report produced from controlled document template ATI 00498, revised 06/19/15.

Page 10: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

Appendix A

Sketch

Page 11: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

Sketch #1 Specimen #1 impact locations

Page 12: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

Appendix B

Drawings

Page 13: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

IPMT200 HURRICANE IMPACT WINDOW

MOCK UP

SYSTEM: SERIES IPT200 HURRICANE IMPACT WINDOW FOR 1 5/16" GLAZING

TEST PROCEDURES: TEST SPECIMENS TO BE EVALUATED PER THE FOLLOWING:

ASTM E 1886-13a, STANDARD TEST FOR PERFORMANCE OF EXTERIOR WINDOWS, CURTAIN

WALLS, DOORS AND STORM SHUTTERS IMPACTED BY MISSLE(S) AND EXPOSED TO CYCLIC

PRESSURE DIFFERENTIALS.

ASTM E 1996-14a, STANDARD SPECIFICATION FOR PERFORMANCE OF EXTERIOR WINDOWS,

GLAZED CURTAIN WALLS, DOORS, AND STORM SHUTTERS BY WIND BORNE DEBRIS IN

HURRICANES.

MOCK UP GENERAL RULES

X AWNING FOR 1 5/16" GLAZING

C-1

jhardman
g0058-r1
Page 14: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

X AWNING FOR 1 5/16" GLAZING

E-1

jhardman
G0058-r0
Page 15: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

EXTERIOR INTERIOR

X AWNING FOR 1 5/16" GLAZING

D-1

jhardman
G0058-r0
Page 16: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

EXTERIOR INTERIOR

X AWNING FOR 1 5/16" GLAZING

D-2

jhardman
G0058-r0
Page 17: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

EXTERIOR

INTERIOR

X AWNING FOR 1 5/16" GLAZING

D-3

jhardman
G0058-r0
Page 18: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

WTH01 WWB14WTZ02

X AWNING FOR 1 5/16" GLAZING

P-1

jhardman
G0058-r0
Page 19: ASTM E1886 and ASTM E1996 TEST REPORT Report No.: G0058.01-301-44 - Arcadia … · 2019-02-14 · Test Report No.: G0058.01-301-44 Report Date: 09/20/16 Revision 1 Date: 10/11/16

IPT200 X AWNING STORM IMPACT WINDOW MOCK UP BILL OF MATERIALS (OUTSIDE GLAZED)

ITEM DESCRIPTION

1. WTH01 (THERMALLY BROKEN WINDOW SECTION) 2. WWB14 (GLAZING BEAD) 3. WTZ02 (THERMALLY BROKEN WINDOW SECTION) 4. D4-5169 (BULB GASKET) 5. E260L (GLAZING GASKET) 6. 1/4” X 3/8” GLAZING SPACER TAPE 7. DOW CORNING 983 STRUCTURAL SILICONE SEALANT FOR STRUCTURAL SEALS 8. WWM01 (ALUM. CORNER KEY) 9. 1/4” X 2” WOOD SCREWS (PERIMETER FASTENERS) 10. THERMOPLASTIC SHIMS 11. GLASS SETTING BLOCKS/SPACERS 12. DOW CORNING 1199 SEALANT (INTERNAL & PERIMETER SEALS) 13. 1 5/16” OVERALL THICKNESS INSULATING GLASS

MAKE-UP: 6mm CLEAR HEAT STRENGTHENED – ½” LPX CLEAR ANO. SPACER – 6mm CLEAR HEAT STRENGTHENED/.090 SENTRYGLAS PLUS INTERLAYER/6mm CLEAR HEAT STRENGTHENED (LAMINATED)

jhardman