astm conductor spec sheets

Upload: javad4531

Post on 12-Apr-2018

242 views

Category:

Documents


1 download

TRANSCRIPT

  • 7/21/2019 ASTM Conductor Spec Sheets

    1/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 583.2 mm2 1151.0 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-007) 9.53 mm 0.375 in.

    ominal Cross-sectional Area of Core 71.3 mm2 0.110 in

    2

    verall Diameter of Conductor 29.90 mm 1.177 in.

    ominal Cross-sectional Area of the Conductor 654.2 mm2 1.014 in

    2

    ltimate Tensile Strength of Conductor1,2 186.4 kN 41.9 kips

    ated Strength of Core - 313 ksi (2158 MPa) 153.8 kN 34.6 kips

    ore Nominal Mass per unit length 132 kg/km 89 lb/kft

    onductor Nominal Mass per unit length 1745 kg/km 1172.8 lb/kft

    uminum Nominal Mass per unit length** 1612.6 kg/km 1083.8 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.87E-05 /oC 1.04E-05 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 60.5 GPa 8.8 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0480 ohm/km 0.0773 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0503 ohm/km 0.0809 ohm/mile

    C Nominal Resistance at 75C 0.0599 ohm/km 0.0964 ohm/mile

    C Nominal Resistance at 180C 0.0801 ohm/km 0.1290 ohm/mile

    1213 @ 100C & 60 Hz

    1830 @ 180C & 60 Hz

    MR (estimated) 0.012 m 0.040 ft

    ductive Reactance 0.243 ohm/km 0.391 ohm/mile

    apacitive Reactance 0.144 Mohm-km 0.089 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-124-D www.ctcglobal.com Date Produced: 4/24/2012

    Metric Imperial

    ACCC-Arlington

    NOT RELEASED

    For questions, please contact CTC Application Engineering Department: [email protected]

    Metric Imperial

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 600.4 sq. mm (1184.9 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

  • 7/21/2019 ASTM Conductor Spec Sheets

    2/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 723.9 mm2 1428.6 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-007) 9.53 mm 0.375 in.

    ominal Cross-sectional Area of Core 71.3 mm2 0.110 in

    2

    verall Diameter of Conductor 32.87 mm 1.294 in.

    ominal Cross-sectional Area of the Conductor 794.8 mm2 1.232 in

    2

    ltimate Tensile Strength of Conductor1,2 194.4 kN 43.7 kips

    ated Strength of Core - 313 ksi (2158 MPa) 153.8 kN 34.6 kips

    ore Nominal Mass per unit length 132 kg/km 89 lb/kft

    onductor Nominal Mass per unit length 2136 kg/km 1435.6 lb/kft

    uminum Nominal Mass per unit length** 2003.6 kg/km 1346.6 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.94E-05 /oC 1.08E-05 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 59.4 GPa 8.6 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0387 ohm/km 0.0623 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0411 ohm/km 0.0661 ohm/mile

    C Nominal Resistance at 75C 0.0488 ohm/km 0.0785 ohm/mile

    C Nominal Resistance at 180C 0.0650 ohm/km 0.1045 ohm/mile

    1381 @ 100C & 60 Hz

    2096 @ 180C & 60 Hz

    MR (estimated) 0.013 m 0.043 ft

    ductive Reactance 0.237 ohm/km 0.381 ohm/mile

    apacitive Reactance 0.139 Mohm-km 0.087 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-127-D www.ctcglobal.com Date Produced: 4/24/2012

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 745.2 sq. mm (1470.6 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

    Metric Imperial

    ACCC-Beaumont

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

  • 7/21/2019 ASTM Conductor Spec Sheets

    3/27

  • 7/21/2019 ASTM Conductor Spec Sheets

    4/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 1388.7 mm2 2740.6 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-011) 10.54 mm 0.415 in.

    ominal Cross-sectional Area of Core 87.3 mm2 0.135 in

    2

    verall Diameter of Conductor 44.75 mm 1.762 in.

    ominal Cross-sectional Area of the Conductor 1476.1 mm2 2.288 in

    2

    ltimate Tensile Strength of Conductor1,2 266.4 kN 59.9 kips

    ated Strength of Core - 313 ksi (2158 MPa) 188.3 kN 42.3 kips

    ore Nominal Mass per unit length 164 kg/km 110 lb/kft

    onductor Nominal Mass per unit length 4022 kg/km 2702.9 lb/kft

    uminum Nominal Mass per unit length** 3858.0 kg/km 2592.9 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 2.06E-05 /oC 1.14E-05 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 57.7 GPa 8.4 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0203 ohm/km 0.0326 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0240 ohm/km 0.0387 ohm/mile

    C Nominal Resistance at 75C 0.0278 ohm/km 0.0447 ohm/mile

    C Nominal Resistance at 180C 0.0356 ohm/km 0.0573 ohm/mile

    2010 @ 100C & 60 Hz

    3130 @ 180C & 60 Hz

    MR (estimated) 0.018 m 0.058 ft

    ductive Reactance 0.214 ohm/km 0.345 ohm/mile

    apacitive Reactance 0.125 Mohm-km 0.077 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-115-D www.ctcglobal.com Date Produced: 4/23/2012

    Metric Imperial

    ACCC-Bluebird

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1429.6 sq. mm (2821.2 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

  • 7/21/2019 ASTM Conductor Spec Sheets

    5/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 1135.8 mm2 2241.5 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-010) 10.03 mm 0.395 in.

    ominal Cross-sectional Area of Core 79.1 mm2 0.123 in

    2

    verall Diameter of Conductor 40.74 mm 1.604 in.

    ominal Cross-sectional Area of the Conductor 1215.5 mm2 1.884 in

    2

    ltimate Tensile Strength of Conductor1,2 234.4 kN 52.7 kips

    ated Strength of Core - 313 ksi (2158 MPa) 170.6 kN 38.4 kips

    ore Nominal Mass per unit length 147 kg/km 99 lb/kft

    onductor Nominal Mass per unit length 3303 kg/km 2219.6 lb/kft

    uminum Nominal Mass per unit length** 3155.3 kg/km 2120.6 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 2.03E-05 /oC 1.13E-05 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 58.0 GPa 8.4 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0247 ohm/km 0.0398 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0277 ohm/km 0.0445 ohm/mile

    C Nominal Resistance at 75C 0.0324 ohm/km 0.0521 ohm/mile

    C Nominal Resistance at 180C 0.0423 ohm/km 0.0681 ohm/mile

    1808 @ 100C & 60 Hz

    2785 @ 180C & 60 Hz

    MR (estimated) 0.016 m 0.053 ft

    ductive Reactance 0.221 ohm/km 0.356 ohm/mile

    apacitive Reactance 0.129 Mohm-km 0.080 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-114-D www.ctcglobal.com Date Produced: 4/24/2012

    Metric Imperial

    ACCC-Chukar

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1169.2 sq. mm (2307.5 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

  • 7/21/2019 ASTM Conductor Spec Sheets

    6/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 558.9 mm2 1103.0 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-008) 8.76 mm 0.345 in.

    ominal Cross-sectional Area of Core 60.3 mm2 0.093 in

    2

    verall Diameter of Conductor 29.11 mm 1.146 in.

    ominal Cross-sectional Area of the Conductor 618.9 mm2 0.959 in

    2

    ltimate Tensile Strength of Conductor1,2 161.5 kN 36.3 kips

    ated Strength of Core - 313 ksi (2158 MPa) 130.2 kN 29.3 kips

    ore Nominal Mass per unit length 113 kg/km 76 lb/kft

    onductor Nominal Mass per unit length 1656 kg/km 1113.2 lb/kft

    uminum Nominal Mass per unit length** 1543.3 kg/km 1037.2 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.45E-06 /oC 8.06E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.90E-05 /oC 1.06E-05 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 116.0 GPa 16.8 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 60.2 GPa 8.7 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0501 ohm/km 0.0806 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0524 ohm/km 0.0843 ohm/mile

    C Nominal Resistance at 75C 0.0624 ohm/km 0.1005 ohm/mile

    C Nominal Resistance at 180C 0.0836 ohm/km 0.1345 ohm/mile

    1179 @ 100C & 60 Hz

    1777 @ 180C & 60 Hz

    MR (estimated) 0.012 m 0.039 ft

    ductive Reactance 0.245 ohm/km 0.395 ohm/mile

    apacitive Reactance 0.145 Mohm-km 0.090 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-123-D www.ctcglobal.com Date Produced: 4/24/2012

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 575.4 sq. mm (1135.4 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

    Metric Imperial

    ACCC-Corpus Christi

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

  • 7/21/2019 ASTM Conductor Spec Sheets

    7/27

    DATA SHEET:

    Governing Units: ImperialMechanical Specifications

    Nominal Aluminum Cross-sectional Area* 523.4 mm2 1033.0 kcmil

    Nominal Diameter of Composite Core (CTC Part Number 200-011) 10.54 mm 0.415 in.

    Nominal Cross-sectional Area of Core 87.3 mm2 0.135 in

    2

    Overall Diameter of Conductor 28.96 mm 1.140 in.

    Nominal Cross-sectional Area of the Conductor 610.5 mm2 0.946 in

    2

    Ultimate Tensile Strength of Conductor1,2 218.0 kN 49.0 kips

    Rated Strength of Core - 313 ksi (2158 MPa) 188.3 kN 42.3 kips

    Core Nominal Mass per unit length 164 kg/km 110 lb/kft

    Conductor Nominal Mass per unit length 1610 kg/km 1082.0 lb/kft

    Aluminum Nominal Mass per unit length** 1446.2 kg/km 972.0 lb/kft

    Maximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.75E-05 /oC 9.75E-06 /

    oF

    Final Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    Final Modulus of Elasticity Below Thermal Kneepoint 62.5 GPa 9.1 Msi

    Electrical Specifications

    Nominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0536 ohm/km 0.0862 ohm/mile

    Temperature Coefficient of Resistance 0.00404 0.00404

    Frequency 60 Hz 60 Hz

    AC Nominal Resistance at 25C 0.0558 ohm/km 0.0898 ohm/mile

    AC Nominal Resistance at 75C 0.0664 ohm/km 0.1069 ohm/mile

    AC Nominal Resistance at 180C 0.0887 ohm/km 0.1428 ohm/mile

    1142 @ 100C & 60 Hz

    1722 @ 180C & 60 Hz

    GMR (estimated) 0.012 m 0.039 ft

    Inductive Reactance 0.245 ohm/km 0.394 ohm/mile

    Capacitive Reactance 0.145 Mohm-km 0.090 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-132-D www.ctcglobal.com Date Produced: 4/24/201

    AC Current Rating at Given Temperature3

    *ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 538.8 sq. mm (1063.4 kcmil)

    **ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    conductor).

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    result in slight variations in some of the indicated values.

    Metric Imperial

    ACCC-Curlew

    NOT RELEASED

    For questions , please con tact CTC App l ication Engineering Department : appl ication sup port@ct ccable.com

    Metric Imperial

  • 7/21/2019 ASTM Conductor Spec Sheets

    8/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 909.5 mm2 1794.9 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-009) 9.78 mm 0.385 in.

    ominal Cross-sectional Area of Core 75.1 mm2 0.116 in

    2

    verall Diameter of Conductor 36.88 mm 1.452 in.

    ominal Cross-sectional Area of the Conductor 984.3 mm2 1.526 in

    2

    ltimate Tensile Strength of Conductor1,2 213.1 kN 47.9 kips

    ated Strength of Core - 313 ksi (2158 MPa) 162.1 kN 36.4 kips

    ore Nominal Mass per unit length 143 kg/km 96 lb/kft

    onductor Nominal Mass per unit length 2670 kg/km 1794.5 lb/kft

    uminum Nominal Mass per unit length** 2527.2 kg/km 1698.5 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.99E-05 /oC 1.11E-05 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 58.6 GPa 8.5 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0309 ohm/km 0.0497 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0339 ohm/km 0.0546 ohm/mile

    C Nominal Resistance at 75C 0.0398 ohm/km 0.0640 ohm/mile

    C Nominal Resistance at 180C 0.0520 ohm/km 0.0837 ohm/mile

    1585 @ 100C & 60 Hz

    2430 @ 180C & 60 Hz

    MR (estimated) 0.015 m 0.048 ft

    ductive Reactance 0.228 ohm/km 0.367 ohm/mile

    apacitive Reactance 0.134 Mohm-km 0.083 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-129-D www.ctcglobal.com Date Produced: 4/24/2012

    Metric Imperial

    ACCC-Dallas

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 936.3 sq. mm (1847.7 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

  • 7/21/2019 ASTM Conductor Spec Sheets

    9/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 361.6 mm2 713.5 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-005) 7.75 mm 0.305 in.

    ominal Cross-sectional Area of Core 47.1 mm2 0.073 in

    2

    verall Diameter of Conductor 23.55 mm 0.927 in.

    ominal Cross-sectional Area of the Conductor 408.6 mm2 0.633 in

    2

    ltimate Tensile Strength of Conductor1,2 122.3 kN 27.5 kips

    ated Strength of Core - 313 ksi (2158 MPa) 101.7 kN 22.9 kips

    ore Nominal Mass per unit length 86 kg/km 58 lb/kft

    onductor Nominal Mass per unit length 1083 kg/km 727.7 lb/kft

    uminum Nominal Mass per unit length** 996.5 kg/km 669.7 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.85E-05 /oC 1.03E-05 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 60.9 GPa 8.8 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0771 ohm/km 0.1240 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0792 ohm/km 0.1274 ohm/mile

    C Nominal Resistance at 75C 0.0947 ohm/km 0.1524 ohm/mile

    C Nominal Resistance at 180C 0.1273 ohm/km 0.2049 ohm/mile

    902 @ 100C & 60 Hz

    1346 @ 180C & 60 Hz

    MR (estimated) 0.010 m 0.031 ft

    ductive Reactance 0.261 ohm/km 0.420 ohm/mile

    apacitive Reactance 0.155 Mohm-km 0.097 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-090-D www.ctcglobal.com Date Produced: 4/24/2012

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 372.2 sq. mm (734.5 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

    Metric Imperial

    ACCC-Dove

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

  • 7/21/2019 ASTM Conductor Spec Sheets

    10/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 519.7 mm2 1025.6 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-007) 9.53 mm 0.375 in.

    ominal Cross-sectional Area of Core 71.3 mm2 0.110 in

    2

    verall Diameter of Conductor 28.14 mm 1.108 in.

    ominal Cross-sectional Area of the Conductor 590.6 mm2 0.916 in

    2

    ltimate Tensile Strength of Conductor1,2 183.3 kN 41.2 kips

    ated Strength of Core - 313 ksi (2158 MPa) 153.8 kN 34.6 kips

    ore Nominal Mass per unit length 132 kg/km 89 lb/kft

    onductor Nominal Mass per unit length 1565 kg/km 1051.8 lb/kft

    uminum Nominal Mass per unit length** 1432.6 kg/km 962.8 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.83E-05 /oC 1.02E-05 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 61.2 GPa 8.9 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0536 ohm/km 0.0863 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0554 ohm/km 0.0892 ohm/mile

    C Nominal Resistance at 75C 0.0662 ohm/km 0.1065 ohm/mile

    C Nominal Resistance at 180C 0.0888 ohm/km 0.1428 ohm/mile

    1134 @ 100C & 60 Hz

    1706 @ 180C & 60 Hz

    MR (estimated) 0.011 m 0.038 ft

    ductive Reactance 0.247 ohm/km 0.398 ohm/mile

    apacitive Reactance 0.147 Mohm-km 0.091 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-097-D www.ctcglobal.com Date Produced: 4/24/2012

    Metric Imperial

    ACCC-Drake

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 535 sq. mm (1055.8 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

  • 7/21/2019 ASTM Conductor Spec Sheets

    11/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    0.486*aerAlanoitces-ssorCmunimulAlanimo mm2 1349.9 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-008) 8.76 mm 0.345 in.

    3.06eroCfoaerAlanoitces-ssorClanimo mm2 0.093 in

    2

    .ni252.1mm08.13rotcudnoCforetemaiDllarev

    0.447rotcudnoCehtfoaerAlanoitces-ssorClanimo mm2 1.153 in

    2

    ltimate Tensile Strength of Conductor1,2 168.6 kN 37.9 kips

    spik3.92Nk2.031)aPM8512(isk313-eroCfohtgnertSdeta

    tfk/bl67mk/gk311htgneltinurepssaMlanimoNero

    tfk/bl0.5431mk/gk1002htgneltinurepssaMlanimoNrotcudno

    tfk/bl0.9621mk/gk2.8881**htgneltinurepssaMlanimoNmunimu

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.45E-06 /oC 8.06E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.96E-05 /oC 1.09E-05 /

    oF

    isM8.61aPG0.611tniopeenKlamrehTevobAyticitsalEfosuludoMlan

    isM6.8aPG2.95tniopeenKlamrehTwoleByticitsalEfosuludoMlan

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0409 ohm/km 0.0659 ohm/mile

    40400.040400.0ecnatsiseRfotneiciffeoCerutarepme

    zH06zH06ycneuqer

    elim/mho2760.0mk/mho8140.0C52taecnatsiseRlanimoNC

    elim/mho5080.0mk/mho0050.0C57taecnatsiseRlanimoNCelim/mho4801.0mk/mho4760.0C081taecnatsiseRlanimoNC

    1353 @ 100C & 60 Hz

    2038 @ 180C & 60 Hz

    tf240.0m310.0)detamitse(RM

    elim/mho583.0mk/mho932.0ecnatcaeRevitcud

    elim-mhoM880.0mk-mhoM141.0ecnatcaeReviticapa

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    3102/03/4:decudorPetaDmoc.labolgctc.wwwD-621-037

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 704.1 sq. mm (1389.6 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 92.9 W/sq. f t (1000 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result

    slight variations in some of the indicated values.

    Metric Imperial

    ACCCElPaso

    NOT RELEASED

    For questions, please contact CTC Application Engineering Department: [email protected]

    Metric Imperial

  • 7/21/2019 ASTM Conductor Spec Sheets

    12/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 1036.3 mm2 2045.1 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-011) 10.54 mm 0.415 in.

    ominal Cross-sectional Area of Core 87.3 mm2 0.135 in

    2

    verall Diameter of Conductor 39.24 mm 1.545 in.

    ominal Cross-sectional Area of the Conductor 1123.2 mm2 1.741 in

    2

    ltimate Tensile Strength of Conductor1,2 246.4 kN 55.4 kips

    ated Strength of Core - 313 ksi (2158 MPa) 188.3 kN 42.3 kips

    ore Nominal Mass per unit length 164 kg/km 110 lb/kft

    onductor Nominal Mass per unit length 3043 kg/km 2045.3 lb/kft

    uminum Nominal Mass per unit length** 2879.6 kg/km 1935.3 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.99E-05 /oC 1.10E-05 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 58.7 GPa 8.5 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0271 ohm/km 0.0436 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0298 ohm/km 0.0479 ohm/mile

    C Nominal Resistance at 75C 0.0350 ohm/km 0.0563 ohm/mile

    C Nominal Resistance at 180C 0.0459 ohm/km 0.0739 ohm/mile

    1719 @ 100C & 60 Hz

    2639 @ 180C & 60 Hz

    MR (estimated) 0.016 m 0.052 ft

    ductive Reactance 0.224 ohm/km 0.360 ohm/mile

    apacitive Reactance 0.131 Mohm-km 0.081 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-131-D www.ctcglobal.com Date Produced: 4/24/2012

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1066.8 sq. mm (2105.2 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

    Metric Imperial

    ACCC-Falcon

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

  • 7/21/2019 ASTM Conductor Spec Sheets

    13/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 658.9 mm2 1300.4 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-007) 9.53 mm 0.375 in.

    ominal Cross-sectional Area of Core 71.3 mm2 0.110 in

    2

    verall Diameter of Conductor 31.50 mm 1.240 in.

    ominal Cross-sectional Area of the Conductor 729.9 mm2 1.131 in

    2

    ltimate Tensile Strength of Conductor1,2 190.8 kN 42.9 kips

    ated Strength of Core - 313 ksi (2158 MPa) 153.8 kN 34.6 kips

    ore Nominal Mass per unit length 132 kg/km 89 lb/kft

    onductor Nominal Mass per unit length 1952 kg/km 1311.9 lb/kft

    uminum Nominal Mass per unit length** 1819.6 kg/km 1222.9 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.91E-05 /oC 1.06E-05 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 59.9 GPa 8.7 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0425 ohm/km 0.0684 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0448 ohm/km 0.0721 ohm/mile

    C Nominal Resistance at 75C 0.0533 ohm/km 0.0858 ohm/mile

    C Nominal Resistance at 180C 0.0712 ohm/km 0.1146 ohm/mile

    1305 @ 100C & 60 Hz

    1975 @ 180C & 60 Hz

    MR (estimated) 0.013 m 0.042 ft

    ductive Reactance 0.240 ohm/km 0.385 ohm/mile

    apacitive Reactance 0.141 Mohm-km 0.088 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-125-D www.ctcglobal.com Date Produced: 4/24/2012

    Metric Imperial

    ACCC-Fort Worth

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 678.3 sq. mm (1338.6 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

  • 7/21/2019 ASTM Conductor Spec Sheets

    14/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 512.5 mm2 1011.3 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-008) 8.76 mm 0.345 in.

    ominal Cross-sectional Area of Core 60.3 mm2 0.093 in

    2

    verall Diameter of Conductor 27.69 mm 1.090 in.

    ominal Cross-sectional Area of the Conductor 572.5 mm2 0.887 in

    2

    ltimate Tensile Strength of Conductor1,2 158.8 kN 35.7 kips

    ated Strength of Core - 313 ksi (2158 MPa) 130.2 kN 29.3 kips

    ore Nominal Mass per unit length 113 kg/km 76 lb/kft

    onductor Nominal Mass per unit length 1525 kg/km 1025.1 lb/kft

    uminum Nominal Mass per unit length** 1412.2 kg/km 949.1 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.45E-06 /oC 8.06E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.87E-05 /oC 1.04E-05 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 116.0 GPa 16.8 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 60.7 GPa 8.8 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0544 ohm/km 0.0875 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0564 ohm/km 0.0907 ohm/mile

    C Nominal Resistance at 75C 0.0674 ohm/km 0.1084 ohm/mile

    C Nominal Resistance at 180C 0.0905 ohm/km 0.1456 ohm/mile

    1119 @ 100C & 60 Hz

    1681 @ 180C & 60 Hz

    MR (estimated) 0.011 m 0.037 ft

    ductive Reactance 0.249 ohm/km 0.401 ohm/mile

    apacitive Reactance 0.148 Mohm-km 0.092 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-121-D www.ctcglobal.com Date Produced: 4/23/2012

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 527.5 sq. mm (1041.1 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

    Metric Imperial

    ACCC-Galveston

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

  • 7/21/2019 ASTM Conductor Spec Sheets

    15/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 416.2 mm2 821.4 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-006) 8.13 mm 0.320 in.

    ominal Cross-sectional Area of Core 51.9 mm2 0.080 in

    2

    verall Diameter of Conductor 25.15 mm 0.990 in.

    ominal Cross-sectional Area of the Conductor 467.8 mm2 0.725 in

    2

    ltimate Tensile Strength of Conductor1,2 135.2 kN 30.4 kips

    ated Strength of Core - 313 ksi (2158 MPa) 112.0 kN 25.2 kips

    ore Nominal Mass per unit length 98 kg/km 66 lb/kft

    onductor Nominal Mass per unit length 1245 kg/km 836.9 lb/kft

    uminum Nominal Mass per unit length** 1147.0 kg/km 770.9 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.87E-05 /oC 1.04E-05 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 60.6 GPa 8.8 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0672 ohm/km 0.1081 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0692 ohm/km 0.1114 ohm/mile

    C Nominal Resistance at 75C 0.0829 ohm/km 0.1334 ohm/mile

    C Nominal Resistance at 180C 0.1116 ohm/km 0.1796 ohm/mile

    981 @ 100C & 60 Hz

    1468 @ 180C & 60 Hz

    MR (estimated) 0.010 m 0.033 ft

    ductive Reactance 0.256 ohm/km 0.412 ohm/mile

    apacitive Reactance 0.152 Mohm-km 0.095 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-092-D www.ctcglobal.com Date Produced: 4/23/2012

    Metric Imperial

    ACCC-Grosbeak

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 428.4 sq. mm (845.5 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

  • 7/21/2019 ASTM Conductor Spec Sheets

    16/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 309.8 mm2 611.3 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-004) 7.11 mm 0.280 in.

    ominal Cross-sectional Area of Core 39.7 mm2 0.062 in

    2

    verall Diameter of Conductor 21.79 mm 0.858 in.

    ominal Cross-sectional Area of the Conductor 349.7 mm2 0.542 in

    2

    ltimate Tensile Strength of Conductor1,2 103.2 kN 23.2 kips

    ated Strength of Core - 313 ksi (2158 MPa) 85.7 kN 19.3 kips

    ore Nominal Mass per unit length 76 kg/km 51 lb/kft

    onductor Nominal Mass per unit length 930 kg/km 624.8 lb/kft

    uminum Nominal Mass per unit length** 853.8 kg/km 573.8 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.85E-05 /oC 1.03E-05 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 60.9 GPa 8.8 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0900 ohm/km 0.1448 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0923 ohm/km 0.1485 ohm/mile

    C Nominal Resistance at 75C 0.1094 ohm/km 0.1760 ohm/mile

    C Nominal Resistance at 180C 0.1452 ohm/km 0.2338 ohm/mile

    823 @ 100C & 60 Hz

    1231 @ 180C & 60 Hz

    MR (estimated) 0.009 m 0.029 ft

    ductive Reactance 0.267 ohm/km 0.429 ohm/mile

    apacitive Reactance 0.159 Mohm-km 0.099 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-088-D www.ctcglobal.com Date Produced: 4/23/2012

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 318.9 sq. mm (629.3 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

    Metric Imperial

    ACCC-Hawk

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

  • 7/21/2019 ASTM Conductor Spec Sheets

    17/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 976.7 mm2 1927.4 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-011) 10.54 mm 0.415 in.

    ominal Cross-sectional Area of Core 87.3 mm2 0.135 in

    2

    verall Diameter of Conductor 38.25 mm 1.506 in.

    ominal Cross-sectional Area of the Conductor 1063.7 mm2 1.649 in

    2

    ltimate Tensile Strength of Conductor1,2 243.3 kN 54.7 kips

    ated Strength of Core - 313 ksi (2158 MPa) 188.3 kN 42.3 kips

    ore Nominal Mass per unit length 164 kg/km 110 lb/kft

    onductor Nominal Mass per unit length 2878 kg/km 1934.1 lb/kft

    uminum Nominal Mass per unit length** 2714.1 kg/km 1824.1 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.97E-05 /oC 1.09E-05 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 59.0 GPa 8.6 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0285 ohm/km 0.0459 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0317 ohm/km 0.0510 ohm/mile

    C Nominal Resistance at 75C 0.0370 ohm/km 0.0596 ohm/mile

    C Nominal Resistance at 180C 0.0483 ohm/km 0.0777 ohm/mile

    1660 @ 100C & 60 Hz

    2554 @ 180C & 60 Hz

    MR (estimated) 0.015 m 0.050 ft

    ductive Reactance 0.225 ohm/km 0.363 ohm/mile

    apacitive Reactance 0.132 Mohm-km 0.082 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-130-D www.ctcglobal.com Date Produced: 4/23/2012

    Metric Imperial

    ACCC-Houston

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1005.4 sq. mm (1984.1 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

  • 7/21/2019 ASTM Conductor Spec Sheets

    18/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 308.8 mm2 609.5 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-008) 8.76 mm 0.345 in.

    ominal Cross-sectional Area of Core 60.3 mm2 0.093 in

    2

    verall Diameter of Conductor 22.40 mm 0.882 in.

    ominal Cross-sectional Area of the Conductor 368.8 mm2 0.572 in

    2

    ltimate Tensile Strength of Conductor1,2 147.7 kN 33.2 kips

    ated Strength of Core - 313 ksi (2158 MPa) 130.2 kN 29.3 kips

    ore Nominal Mass per unit length 113 kg/km 76 lb/kft

    onductor Nominal Mass per unit length 965 kg/km 648.5 lb/kft

    uminum Nominal Mass per unit length** 851.8 kg/km 572.5 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.45E-06 /oC 8.06E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.67E-05 /oC 9.28E-06 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 116.0 GPa 16.8 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 64.3 GPa 9.3 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0903 ohm/km 0.1454 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0926 ohm/km 0.1491 ohm/mile

    C Nominal Resistance at 75C 0.1111 ohm/km 0.1788 ohm/mile

    C Nominal Resistance at 180C 0.1499 ohm/km 0.2412 ohm/mile

    820 @ 100C & 60 Hz

    1222 @ 180C & 60 Hz

    MR (estimated) 0.009 m 0.030 ft

    ductive Reactance 0.264 ohm/km 0.424 ohm/mile

    apacitive Reactance 0.158 Mohm-km 0.098 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-119-D www.ctcglobal.com Date Produced: 4/23/2012

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 317.9 sq. mm (627.4 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

    Metric Imperial

    ACCC-Irving

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

  • 7/21/2019 ASTM Conductor Spec Sheets

    19/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 987.6 mm2 1948.9 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-009) 9.78 mm 0.385 in.

    ominal Cross-sectional Area of Core 75.1 mm2 0.116 in

    2

    verall Diameter of Conductor 38.20 mm 1.504 in.

    ominal Cross-sectional Area of the Conductor 1062.6 mm2 1.647 in

    2

    ltimate Tensile Strength of Conductor1,2 217.5 kN 48.9 kips

    ated Strength of Core - 313 ksi (2158 MPa) 162.1 kN 36.4 kips

    ore Nominal Mass per unit length 143 kg/km 96 lb/kft

    onductor Nominal Mass per unit length 2887 kg/km 1940.0 lb/kft

    uminum Nominal Mass per unit length** 2743.7 kg/km 1844.0 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 2.01E-05 /oC 1.12E-05 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 58.3 GPa 8.5 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0285 ohm/km 0.0458 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0315 ohm/km 0.0507 ohm/mile

    C Nominal Resistance at 75C 0.0370 ohm/km 0.0595 ohm/mile

    C Nominal Resistance at 180C 0.0485 ohm/km 0.0780 ohm/mile

    1660 @ 100C & 60 Hz

    2547 @ 180C & 60 Hz

    MR (estimated) 0.015 m 0.050 ft

    ductive Reactance 0.226 ohm/km 0.363 ohm/mile

    apacitive Reactance 0.132 Mohm-km 0.082 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-111-D www.ctcglobal.com Date Produced: 4/23/2012

    Metric Imperial

    ACCC-Lapwing

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1016.6 sq. mm (2006.3 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

  • 7/21/2019 ASTM Conductor Spec Sheets

    20/27

    DATA SHEET:

    Governing Units: ImperialMechanical Specifications

    Nominal Aluminum Cross-sectional Area* 268.5 mm2 529.8 kcmil

    Nominal Diameter of Composite Core (CTC Part Number 200-004) 7.11 mm 0.280 in.

    Nominal Cross-sectional Area of Core 39.7 mm2 0.062 in

    2

    Overall Diameter of Conductor 20.50 mm 0.807 in.

    Nominal Cross-sectional Area of the Conductor 308.5 mm2 0.478 in

    2

    Ultimate Tensile Strength of Conductor1,2 101.0 kN 22.7 kips

    Rated Strength of Core - 313 ksi (2158 MPa) 85.7 kN 19.3 kips

    Core Nominal Mass per unit length 76 kg/km 51 lb/kft

    Conductor Nominal Mass per unit length 816 kg/km 548.4 lb/kft

    Aluminum Nominal Mass per unit length** 740.1 kg/km 497.4 lb/kft

    Maximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.80E-05 /oC 9.99E-06 /

    oF

    Final Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    Final Modulus of Elasticity Below Thermal Kneepoint 61.8 GPa 9.0 Msi

    Electrical Specifications

    Nominal Resistivity of Aluminum at 20C, DC 63% IACS 0.1038 ohm/km 0.1671 ohm/mile

    Temperature Coefficient of Resistance 0.00404 0.00404

    Frequency 60 Hz 60 Hz

    AC Nominal Resistance at 25C 0.1064 ohm/km 0.1712 ohm/mile

    AC Nominal Resistance at 75C 0.1276 ohm/km 0.2053 ohm/mile

    AC Nominal Resistance at 180C 0.1721 ohm/km 0.2769 ohm/mile

    747 @ 100C & 60 Hz

    1109 @ 180C & 60 Hz

    GMR (estimated) 0.008 m 0.027 ft

    Inductive Reactance 0.271 ohm/km 0.436 ohm/mile

    Capacitive Reactance 0.162 Mohm-km 0.101 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-118-D www.ctcglobal.com Date Produced: 4/24/201

    AC Current Rating at Given Temperature3

    *ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 276.4 sq. mm (545.4 kcmil)

    **ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    conductor).

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    result in slight variations in some of the indicated values.

    Metric Imperial

    ACCC-Laredo

    NOT RELEASED

    For questions , please con tact CTC App l ication Engineering Department : appl ication sup port@ct ccable.com

    Metric Imperial

  • 7/21/2019 ASTM Conductor Spec Sheets

    21/27

    DATA SHEET:

    Governing Units: ImperialMechanical Specifications

    Nominal Aluminum Cross-sectional Area* 218.1 mm2 430.5 kcmil

    Nominal Diameter of Composite Core (CTC Part Number 200-003) 5.97 mm 0.235 in.

    Nominal Cross-sectional Area of Core 28.0 mm2 0.043 in

    2

    Overall Diameter of Conductor 18.29 mm 0.720 in.

    Nominal Cross-sectional Area of the Conductor 245.9 mm2 0.381 in

    2

    Ultimate Tensile Strength of Conductor1,2 72.5 kN 16.3 kips

    Rated Strength of Core - 313 ksi (2158 MPa) 60.4 kN 13.6 kips

    Core Nominal Mass per unit length 54 kg/km 36 lb/kft

    Conductor Nominal Mass per unit length 655 kg/km 440.1 lb/kft

    Aluminum Nominal Mass per unit length** 601.3 kg/km 404.1 lb/kft

    Maximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.86E-05 /oC 1.03E-05 /

    oF

    Final Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    Final Modulus of Elasticity Below Thermal Kneepoint 60.8 GPa 8.8 Msi

    Electrical Specifications

    Nominal Resistivity of Aluminum at 20C, DC 63% IACS 0.1277 ohm/km 0.2055 ohm/mile

    Temperature Coefficient of Resistance 0.00404 0.00404

    Frequency 60 Hz 60 Hz

    AC Nominal Resistance at 25C 0.1307 ohm/km 0.2103 ohm/mile

    AC Nominal Resistance at 75C 0.1564 ohm/km 0.2517 ohm/mile

    AC Nominal Resistance at 180C 0.2104 ohm/km 0.3386 ohm/mile

    654 @ 100C & 60 Hz

    968 @ 180C & 60 Hz

    GMR (estimated) 0.007 m 0.024 ft

    Inductive Reactance 0.280 ohm/km 0.451 ohm/mile

    Capacitive Reactance 0.167 Mohm-km 0.104 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-082-D www.ctcglobal.com Date Produced: 4/24/201

    Metric Imperial

    ACCC-Linnet

    NOT RELEASED

    For questions , please con tact CTC App l ication Engineering Department : appl ication sup port@ct ccable.com

    Metric Imperial

    AC Current Rating at Given Temperature3

    *ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 224.6 sq. mm (443.1 kcmil)

    **ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    conductor).

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    result in slight variations in some of the indicated values.

  • 7/21/2019 ASTM Conductor Spec Sheets

    22/27

    DATA SHEET:

    Governing Units: ImperialMechanical Specifications

    Nominal Aluminum Cross-sectional Area* 458.0 mm2 903.9 kcmil

    Nominal Diameter of Composite Core (CTC Part Number 200-008) 8.76 mm 0.345 in.

    Nominal Cross-sectional Area of Core 60.3 mm2 0.093 in

    2

    Overall Diameter of Conductor 26.42 mm 1.040 in.

    Nominal Cross-sectional Area of the Conductor 518.0 mm2 0.803 in

    2

    Ultimate Tensile Strength of Conductor1,2 156.1 kN 35.1 kips

    Rated Strength of Core - 313 ksi (2158 MPa) 130.2 kN 29.3 kips

    Core Nominal Mass per unit length 113 kg/km 76 lb/kft

    Conductor Nominal Mass per unit length 1375 kg/km 924.3 lb/kft

    Aluminum Nominal Mass per unit length** 1262.2 kg/km 848.3 lb/kft

    Maximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.45E-06 /oC 8.06E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.83E-05 /oC 1.02E-05 /

    oF

    Final Modulus of Elasticity Above Thermal Kneepoint 116.0 GPa 16.8 Msi

    Final Modulus of Elasticity Below Thermal Kneepoint 61.4 GPa 8.9 Msi

    Electrical Specifications

    Nominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0608 ohm/km 0.0979 ohm/mile

    Temperature Coefficient of Resistance 0.00404 0.00404

    Frequency 60 Hz 60 Hz

    AC Nominal Resistance at 25C 0.0628 ohm/km 0.1011 ohm/mile

    AC Nominal Resistance at 75C 0.0752 ohm/km 0.1210 ohm/mile

    AC Nominal Resistance at 180C 0.1012 ohm/km 0.1628 ohm/mile

    1045 @ 100C & 60 Hz

    1566 @ 180C & 60 Hz

    GMR (estimated) 0.011 m 0.035 ft

    Inductive Reactance 0.252 ohm/km 0.406 ohm/mile

    Capacitive Reactance 0.150 Mohm-km 0.093 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-120-D www.ctcglobal.com Date Produced: 4/24/201

    Metric Imperial

    ACCC-Lubbock

    NOT RELEASED

    For questions , please con tact CTC App l ication Engineering Department : appl ication sup port@ct ccable.com

    Metric Imperial

    AC Current Rating at Given Temperature3

    *ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 471.5 sq. mm (930.5 kcmil)

    **ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    conductor).

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    result in slight variations in some of the indicated values.

  • 7/21/2019 ASTM Conductor Spec Sheets

    23/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 222.3 mm2 438.6 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-004) 7.11 mm 0.280 in.

    ominal Cross-sectional Area of Core 39.7 mm2 0.062 in

    2

    verall Diameter of Conductor 18.82 mm 0.741 in.

    ominal Cross-sectional Area of the Conductor 262.3 mm2 0.407 in

    2

    ltimate Tensile Strength of Conductor1,2 98.3 kN 22.1 kips

    ated Strength of Core - 313 ksi (2158 MPa) 85.7 kN 19.3 kips

    ore Nominal Mass per unit length 76 kg/km 51 lb/kft

    onductor Nominal Mass per unit length 689 kg/km 463.0 lb/kft

    uminum Nominal Mass per unit length** 613.0 kg/km 412.0 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.72E-05 /oC 9.57E-06 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 63.1 GPa 9.1 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.1255 ohm/km 0.2019 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.1283 ohm/km 0.2065 ohm/mile

    C Nominal Resistance at 75C 0.1535 ohm/km 0.2471 ohm/mile

    C Nominal Resistance at 180C 0.2065 ohm/km 0.3324 ohm/mile

    665 @ 100C & 60 Hz

    986 @ 180C & 60 Hz

    MR (estimated) 0.008 m 0.025 ft

    ductive Reactance 0.277 ohm/km 0.446 ohm/mile

    apacitive Reactance 0.166 Mohm-km 0.103 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-086-D www.ctcglobal.com Date Produced: 4/23/2012

    Metric Imperial

    ACCC-Oriole

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 228.8 sq. mm (451.5 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

  • 7/21/2019 ASTM Conductor Spec Sheets

    24/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 154.4 mm2 304.7 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-003) 5.97 mm 0.235 in.

    ominal Cross-sectional Area of Core 28.0 mm2 0.043 in

    2

    verall Diameter of Conductor 15.65 mm 0.616 in.

    ominal Cross-sectional Area of the Conductor 182.1 mm2 0.282 in

    2

    ltimate Tensile Strength of Conductor1,2 68.9 kN 15.5 kips

    ated Strength of Core - 313 ksi (2158 MPa) 60.4 kN 13.6 kips

    ore Nominal Mass per unit length 54 kg/km 36 lb/kft

    onductor Nominal Mass per unit length 478 kg/km 321.3 lb/kft

    uminum Nominal Mass per unit length** 424.5 kg/km 285.3 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.72E-05 /oC 9.57E-06 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 63.1 GPa 9.1 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.1793 ohm/km 0.2885 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.1829 ohm/km 0.2944 ohm/mile

    C Nominal Resistance at 75C 0.2197 ohm/km 0.3535 ohm/mile

    C Nominal Resistance at 180C 0.2968 ohm/km 0.4776 ohm/mile

    528 @ 100C & 60 Hz

    778 @ 180C & 60 Hz

    MR (estimated) 0.006 m 0.021 ft

    ductive Reactance 0.291 ohm/km 0.468 ohm/mile

    apacitive Reactance 0.175 Mohm-km 0.109 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-116-D www.ctcglobal.com Date Produced: 4/23/2012

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 158.9 sq. mm (313.6 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

    Metric Imperial

    ACCC-Pasadena

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

  • 7/21/2019 ASTM Conductor Spec Sheets

    25/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 536.9 mm2 1059.5 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-008) 8.76 mm 0.345 in.

    ominal Cross-sectional Area of Core 60.3 mm2 0.093 in

    2

    verall Diameter of Conductor 28.63 mm 1.127 in.

    ominal Cross-sectional Area of the Conductor 596.8 mm2 0.925 in

    2

    ltimate Tensile Strength of Conductor1,2 160.1 kN 36.0 kips

    ated Strength of Core - 313 ksi (2158 MPa) 130.2 kN 29.3 kips

    ore Nominal Mass per unit length 113 kg/km 76 lb/kft

    onductor Nominal Mass per unit length 1597 kg/km 1073.4 lb/kft

    uminum Nominal Mass per unit length** 1484.0 kg/km 997.4 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.45E-06 /oC 8.06E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.89E-05 /oC 1.05E-05 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 116.0 GPa 16.8 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 60.4 GPa 8.8 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0522 ohm/km 0.0840 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.0544 ohm/km 0.0876 ohm/mile

    C Nominal Resistance at 75C 0.0649 ohm/km 0.1045 ohm/mile

    C Nominal Resistance at 180C 0.0870 ohm/km 0.1400 ohm/mile

    1150 @ 100C & 60 Hz

    1733 @ 180C & 60 Hz

    MR (estimated) 0.012 m 0.038 ft

    ductive Reactance 0.247 ohm/km 0.397 ohm/mile

    apacitive Reactance 0.146 Mohm-km 0.091 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    730-122-D www.ctcglobal.com Date Produced: 4/23/2012

    Metric Imperial

    ACCC-Plano

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 552.6 sq. mm (1090.6 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

  • 7/21/2019 ASTM Conductor Spec Sheets

    26/27

    DATA SHEET:

    Governing Units: ImperialMechanical Specifications

    Nominal Aluminum Cross-sectional Area* 747.4 mm2 1474.9 kcmil

    Nominal Diameter of Composite Core (CTC Part Number 200-009) 9.78 mm 0.385 in.

    Nominal Cross-sectional Area of Core 75.1 mm2 0.116 in

    2

    Overall Diameter of Conductor 33.40 mm 1.315 in.

    Nominal Cross-sectional Area of the Conductor 822.2 mm2 1.274 in

    2

    Ultimate Tensile Strength of Conductor1,2 204.2 kN 45.9 kips

    Rated Strength of Core - 313 ksi (2158 MPa) 162.1 kN 36.4 kips

    Core Nominal Mass per unit length 143 kg/km 96 lb/kft

    Conductor Nominal Mass per unit length 2211 kg/km 1486.3 lb/kft

    Aluminum Nominal Mass per unit length** 2068.6 kg/km 1390.3 lb/kft

    Maximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    Coefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    Coefficient of Linear Expansion Below Thermal Kneepoint 1.94E-05 /oC 1.08E-05 /

    oF

    Final Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    Final Modulus of Elasticity Below Thermal Kneepoint 59.5 GPa 8.6 Msi

    Electrical Specifications

    Nominal Resistivity of Aluminum at 20C, DC 63% IACS 0.0375 ohm/km 0.0603 ohm/mile

    Temperature Coefficient of Resistance 0.00404 0.00404

    Frequency 60 Hz 60 Hz

    AC Nominal Resistance at 25C 0.0387 ohm/km 0.0623 ohm/mile

    AC Nominal Resistance at 75C 0.0459 ohm/km 0.0738 ohm/mile

    AC Nominal Resistance at 180C 0.0609 ohm/km 0.0980 ohm/mile

    1432 @ 100C & 60 Hz

    2176 @ 180C & 60 Hz

    GMR (estimated) 0.013 m 0.044 ft

    Inductive Reactance 0.235 ohm/km 0.379 ohm/mile

    Capacitive Reactance 0.139 Mohm-km 0.086 Mohm-mile

    1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    2) Strength at ambient temperature

    F-730-128-D www.ctcglobal.com Date Produced: 4/23/201

    Metric Imperial

    ACCC-San Antonio

    NOT RELEASED

    For questions , please con tact CTC App l ication Engineering Department : appl ication sup port@ct ccable.com

    Metric Imperial

    AC Current Rating at Given Temperature3

    *ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 769.4 sq. mm (1518.3 kcmil)

    **ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    4) Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    conductor).

    The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    result in slight variations in some of the indicated values.

  • 7/21/2019 ASTM Conductor Spec Sheets

    27/27

    ATA SHEET:

    overning Units: Imperialechanical Specifications

    ominal Aluminum Cross-sectional Area* 230.1 mm2 454.0 kcmil

    ominal Diameter of Composite Core (CTC Part Number 200-005) 7.75 mm 0.305 in.

    ominal Cross-sectional Area of Core 47.1 mm2 0.073 in

    2

    verall Diameter of Conductor 19.56 mm 0.770 in.

    ominal Cross-sectional Area of the Conductor 277.2 mm2 0.430 in

    2

    ltimate Tensile Strength of Conductor1,2 114.8 kN 25.8 kips

    ated Strength of Core - 313 ksi (2158 MPa) 101.7 kN 22.9 kips

    ore Nominal Mass per unit length 86 kg/km 58 lb/kft

    onductor Nominal Mass per unit length 721 kg/km 484.6 lb/kft

    uminum Nominal Mass per unit length** 634.7 kg/km 426.6 lb/kft

    aximum Allowable Operating Temperature at Surface4 180 oC 356 oF

    oefficient of Linear Expansion Above Thermal Kneepoint 1.61E-06 /oC 8.94E-07 /

    oF

    oefficient of Linear Expansion Below Thermal Kneepoint 1.67E-05 /oC 9.26E-06 /

    oF

    nal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.3 Msi

    nal Modulus of Elasticity Below Thermal Kneepoint 64.1 GPa 9.3 Msi

    lectrical Specifications

    ominal Resistivity of Aluminum at 20C, DC 63% IACS 0.1212 ohm/km 0.1951 ohm/mile

    emperature Coefficient of Resistance 0.00404 0.00404

    requency 60 Hz 60 Hz

    C Nominal Resistance at 25C 0.1240 ohm/km 0.1996 ohm/mile

    C Nominal Resistance at 75C 0.1488 ohm/km 0.2395 ohm/mile

    C Nominal Resistance at 180C 0.2009 ohm/km 0.3233 ohm/mile

    683 @ 100C & 60 Hz

    1012 @ 180C & 60 Hz

    MR (estimated) 0.008 m 0.027 ft

    ductive Reactance 0.274 ohm/km 0.440 ohm/mile

    apacitive Reactance 0.164 Mohm-km 0.102 Mohm-mile

    Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.

    Strength at ambient temperature

    C Current Rating at Given Temperature3

    CCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 236.8 sq. mm (467.4 kcmil)

    ACCCConductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

    Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

    Maximum continuous operating temperature of ACCCis 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the

    nductor).

    he information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may

    sult in slight variations in some of the indicated values.

    Metric Imperial

    ACCC-Waco

    NOT RELEASED

    For questions , please con tact CTC Ap pl ication Engineering Departm ent: appl ication sup port@ct ccable.com

    Metric Imperial