assessment of the minimum vertical reinforcement limits ... · assessment of the minimum vertical...
TRANSCRIPT
Paper Number 135
Assessment of the minimum vertical reinforcement
limits for RC walls
2013 NZSEE Conference
R. S. Henry
The University of Auckland, Auckland, New Zealand.
ABSTRACT: During the 2010/2011 Canterbury earthquakes, several reinforced
concrete (RC) walls in multi-storey buildings formed a single crack in the plastic hinge
region as opposed to distributed cracking. In several cases the crack width that was
required to accommodate the inelastic displacement of the building resulted in fracture of
the vertical reinforcing steel. This type of failure is characteristic of RC members with
low reinforcement contents, where the area of reinforcing steel is insufficient to develop
the tension force required to form secondary cracks in the surrounding concrete. The
minimum vertical reinforcement in RC walls was increased in NZS 3101:2006 with the
equation for the minimum vertical reinforcement in beams also adopted for walls, despite
differences in reinforcement arrangement and loading. A series of moment-curvature
analyses were conducted for an example RC wall based on the Gallery Apartments
building in Christchurch. The analysis results indicated that even when the
NZS 3101:2006 minimum vertical reinforcement limit was satisfied for a known concrete
strength, the wall was still susceptible to sudden failure unless a significant axial load was
applied. Additionally, current equations for minimum reinforcement based on a sectional
analysis approach do not adequately address the issues related to crack control and
distribution of inelastic deformations in ductile walls.
1 INTRODUCTION
Assessments of buildings following the Canterbury earthquakes highlighted several examples of
reinforced concrete (RC) walls that had formed a single crack in the plastic hinge region as opposed to
the expected larger number of distributed cracks (Kam et al. 2011; Structural Engineering Society of
New Zealand (SESOC) 2011b; Bull 2012). After breaking out the surrounding concrete it was found
that the vertical reinforcing steel was often fractured due to the inelastic demand at the single crack
location. This type of failure is characteristic of RC members with low vertical reinforcement contents
and was also observed in buildings following the 1985 Chilean Earthquake (Wood 1989; Wood et al.
1991). As described by Paulay and Priestley (1992), if a section has insufficient reinforcement there is
a danger that the probable cracking moment may exceed the section flexural strength resulting in a
sudden non-ductile failure. If too little vertical reinforcement is used in walls, there is insufficient
tension generated to replace the tensile resistance provided by the surrounding concrete after a crack
forms, resulting in a reduced number of cracks in the critical moment region, large crack widths, and
possible fracture of the reinforcing steel.
As part of the Canterbury Earthquakes Royal Commission (CERC) a detailed investigation was
conducted into the performance of the Gallery Apartments building (Smith and England 2012). The
RC walls in the Gallery Apartment building contained less vertical reinforcement than is required by
current design standards and were observed to have formed a small number of cracks at the wall base.
As highlighted in volume 2 of the CERC final report, the quantity of vertical reinforcement in the
Gallery Apartment walls was insufficient to develop the tension force required to form secondary
cracks (Canterbury Earthquakes Royal Commission 2012). Additionally, samples extracted from the
Gallery Apartments building following the earthquakes indicated that the concrete strength was
significantly higher than the specified concrete strength (Holmes Solutions 2011). The higher
concrete strength further increased the likelihood of a single crack formation and fracture of vertical
reinforcing steel.
2
A summary of the development of minimum reinforcement limits for both RC beams and RC walls is
presented, followed by a series of moment-curvature analyses conducted to investigate the expected
behaviour of one of the RC walls in the Gallery Apartment building. Additional analyses are
presented that investigate the suitability of the minimum vertical reinforcement limits for walls
specified in the current version of the New Zealand Concrete Structures Standard, NZS 3101:2006.
Other factors that may have contributed to the observed behaviour of lightly reinforced concrete walls
during the Canterbury earthquakes, including higher than specified concrete strength, loading history,
and loading rate, were not considered within the scope of this investigation.
2 MINIMUM LONGITUDINAL/VERTICAL REINFORCEMENT LIMITS
Most design standards impose minimum and maximum limits on reinforcement for different types of
concrete members. In addition to minimum required reinforcement to mitigate shrinkage and
temperature effects, limits on reinforcement are also used to ensure that a ductile response is achieved.
To ensure a ductile flexural response, minimum longitudinal or vertical reinforcement is required in
concrete beams, columns, and walls.
2.1 RC Beams
The current version of the New Zealand Concrete Structures Standard, NZS 3101:2006, states that the
area of longitudinal reinforcement in beams should satisfy Eq. 1 (clause 9.3.8.2.1).
(1)
where As is the area of flexural tension reinforcement, fc′ is the specified concrete compressive
strength, fy is the yield strength of the longitudinal reinforcement, bw is the width of the beam web, and
d is the effective beam depth.
The origins of Eq. 1 can be traced back through early concrete design codes. A previous version of
Eq. 1 that was intended to balance the cracking moment with a cracked flexural strength at a steel
stress of 2fy/3 was later modified to account for variable concrete strength with an assumed modulus of
rupture equal to 0.62√ fc′ (ACI 363R-84 1984). It has been suggested that Eq. 1 result in a nominal
flexural strength between 1.5 to 2 times greater than the probable cracking moment of a rectangular
beam (Paulay and Priestley 1992; Wang et al. 2007; Wight and MacGregor 2009).
The cracking moment (Mcrack) of an unreinforced rectangular beam with a width bw, height h, and a
modulus of rupture fr is shown in Eq. 2a. The nominal flexural strength (Mn) for a RC beam is
calculated using Eq. 2b, where jd is the lever arm between the tension and compression resultant
forces. For a beam with minimum longitudinal reinforcement the lever arm jd is likely to be
approximately 0.95d, and beam height h can be approximated as 1.1d. Using these assumptions,
Eq. 2a and Eq. 2b can be combined to form Eq. 2c., and then rearranged to give Eq. 2d.
(2a)
(2b)
(2c)
(2d)
By equating Eq. 1 and Eq. 2d, the ratio of nominal flexural strength to cracking moment (Mn/Mcrack)
for a rectangular beam with minimum longitudinal reinforcement would be equal to 1.90 when a
modulus of rupture of 0.62√ fc′ is applied, or equal to 1.18 when an upper characteristic modulus of
rupture of √ fc′ is applied.
3
2.2 RC Walls
Versions of NZS 3101 Concrete Structures Standard prior to 2006 specified a minimum ratio of wall
vertical reinforcement to gross section area, ρt, as shown in Eq. 3.
(3)
The origins of Eq. 3 are associated with requirements for shrinkage and temperature effects, and
resulted in a minimum content of vertical reinforcement between 0.14 - 0.24% depending on the
reinforcing steel grade. Interestingly, by analysing the results of 37 RC wall tests completed between
1950 and 1984, Wood (1989) concluded that walls with vertical reinforcement contents less than 1%
were susceptible to premature fracture of reinforcing steel. Perhaps in response to Wood’s analysis,
the ACI 318-95 concrete deign code introduced an additional requirement that special structural walls
designed for seismic applications should have a vertical reinforcement content greater than 0.25%.
In the NZS 3101:2006 revision, the minimum vertical reinforcement in walls was increased with the
adoption of Eq. 4 (clause 11.3.11.3).
(4)
where ρn is the ratio of vertical reinforcement area to the gross section area (At/Ag).
On the surface it appears as if the equation previously developed for RC beams (Eq. 1) has simply
been applied to walls. However, it should be noted that there are distinct differences between walls
and beams that could lead to inaccuracies when Eq. 4 is used, notably:
Eq. 4 refers to the total vertical reinforcement in walls, At, compared with the area of tension
reinforcement, As, in beams in Eq. 1;
Vertical reinforcement is typically distributed along the wall length compared to lumped
reinforcement at the top and bottom of beam sections;
Wall sections are typically more slender than beams;
Walls often have significant axial loads;
Scale effects influence the flexural tensile strength of concrete and typical wall lengths are
significantly larger than typical beam depths.
These listed differences between walls and beams would alter the assumptions used to derive Eq. 1
and may result in a reduced margin of safety between the flexural and cracking strength of a typical
wall section.
Following the observations of RC wall behaviour during the Christchurch earthquakes, the Structural
Engineering Society of New Zealand (SESOC) issued interim design guidelines that included Eq. 5 for
the minimum vertical reinforcement in RC walls (2011a).
(5)
Eq. 5 is modified from Eq. 4 based on the assumption that the actual concrete strength is 2.5 times
greater than the specific concrete strength. The intention was that the 2.5 factor would account for
mean concrete strengths, use of concrete strength greater than specified, additional strength gain over
time, and dynamic strength enhancement. This issue of higher concrete strength was further
highlighted in the CERC final report (2012) and is currently being investigated by the New Zealand
concrete industry.
3 MOMENT-CURVATURE ANALYSIS
A series of analyses were conducted to investigate the behaviour of RC walls with minimum vertical
reinforcement. Moment-curvature sectional analyses were performed using Respone-2000 software
(Bentz and Collins 2001). Response-2000 also incorporates Modified Compression Field Theory
4
(MCFT) to extend the moment-curvature results to a simple 2D member analysis. Analyses were first
performed based on one of the walls in the Gallery Apartment building, after which the reinforcing
contents were modified to investigate the current NZS 3101:2006 provisions.
3.1 Material properties
The concrete material properties entering into Response-2000 were based on either the specified or
measured concrete compressive strength, fc′, with default base curve, and compression and tension
stiffening. When confinement was provided in the wall ends through the use of transverse
reinforcement, the compressive stress-strain backbone response was defined using procedures
proposed by Mander et al. (1988). The flexural tensile strength (or modulus of rupture) assumed for
the concrete was selected to represent either a realistic average or alternatively an upper characteristic
estimate of the wall cracking strength rather than lower characteristic properties that are specified in
design standards. The mean concrete tensile strength, fct, can be estimated using Eq. 6 (Fédération
Internationale du Béton (fib) 2012), with the upper characteristic value obtain by multiplying the mean
by a factor of 1.3.
(6)
As mentioned earlier, there is a notable scale effect that influences the flexural tensile strength, fct, fl, of
concrete members (Bažant 1984; Fenwick and Dickinson 1987; Carpinter 1989). As the depth of the
member increases, the ratio of the flexural tensile strength to direct tensile strength decreases. This
scale effect can be accounted for by using Eq. 7 that are derived from principles of fracture mechanics
(Fédération Internationale du Béton (fib) 2012). It should be noted that the calculated αf values are in
agreement with the values listed in Table C5.1 of the NZS 3101:2006 commentary and for typical wall
lengths results in flexural tensile strengths only slightly greater than the direct tensile strength.
(7)
(7a)
The concrete flexural tensile strength used in the analyses to calculate the cracking moment was
calculated using Eqns. 6 and 7. For a concrete compressive strength of 30 MPa this resulted in a mean
flexural tensile strength of 3.03 MPa and an upper characteristic flexural tensile strength of 3.94 MPa.
The properties of the reinforcing steel were also varied for different analyses to represent the use of
either lower characteristic or average values. Grade 500 reinforcing steel was used throughout the
analyses, consistent with that used in the walls of the Gallery Apartments building. The lower
characteristic properties used included a yield strength, fy, of 500 MPa, a ratio of ultimate strength to
yield strength (fu/fy) of 1.15, and a maximum elongation of 10%. The average properties specified
were based on previous testing of G500 reinforcing steel, including yield strength, fy, of 560 MPa, an
ultimate strength, fu, of 690, and a maximum elongation of 12.9%.
3.2 Gallery Apartments building
As described earlier, several RC walls in the Gallery Apartments building were observed to have
formed a small number of cracks at the wall base that resulted in fracture of the vertical reinforcement.
The seismic performance of the Gallery Apartments building was analysed in detail as part of the
CERC (Canterbury Earthquakes Royal Commission 2012; Smith and England 2012). One of the
critically damaged RC walls on grid-F was analysed to investigate the expected behaviour using
moment-curvature analysis. The grid-F wall had a length of 4300 mm, a thickness of 325 mm, two
layers of DH12 vertical reinforcement at 460 mm centres, and DH12 closed stirrup transverse
reinforcement at 400 mm centres. Although the building was designed assuming a limited ductile
response, detailing of the RC walls was only consistent with requirements for a nominally ductile
response with no transverse confinement reinforcement in the wall ends (Smith and England 2012).
The specified 28-day concrete strength of the RC walls was 30 MPa, however, tests performed on two
concrete cores extracted from the building indicated compressive strengths of 46.5 MPa and 56.0 MPa
(Holmes Solutions 2011). The axial load on the grid-F wall was calculated by Smith and England
(2012) to be 2250 kN, just over half of which (1308 kN) is attributed to the self-weight of the wall.
5
The ratio of vertical reinforcement in the grid-F wall, ρn, is equal to 0.0016, slightly above the 0.0014
minimum required by NZS 3101:1995 (Eq. 3) but below the 0.00274 minimum required by
NZS 3101:2006 (Eq. 4).
The results from the moment-curvature analysis performed on the grid-F wall from the Gallery
Apartments building are summarised in Table 1, where Mcrack is the cracking moment, Myield is flexural
strength when the vertical reinforcement steel yields, and Mmax is the maximum flexural strength
immediately prior to failure. The analysis was completed for combinations of concrete compressive
strength, concrete tensile strength, reinforcing steel properties, and axial load. The moment-curvature
results in Table 1 highlight the vulnerability of the grid-F wall to sudden failure and loss of strength,
confirming the inadequacy of minimum vertical reinforcement provisions based solely on temperature
and shrinkage effects. Of the 10 different analysis options considered, half resulted in a section yield
moment less than the cracking moment, indicating that the wall cannot retain its lateral resistance after
the formation of a crack at the wall base. This drop in strength following the crack formation can be
seen in the moment-curvature analysis results for wall G2, which are plotted in Figure 1.
Table 1 – Summary of moment-curvature results for the Gallery Apartments grid-F wall
Ref.
Concrete
properties Reo.
properties
Axial
load
(kN)
Myield
(kNm)
Mmax
(kNm)
Mcrack
(kNm)
Myield/
Mcrack
Mmax/
Mcrack fc′
(MPa)
fct, fl
(MPa)
G1 30.0 3.03
[Mean] LC 0 2221.4 2638.7 3039.3 0.73 0.87
G2 30.0 3.94
[UC] LC 0 2241.5 2623.5 3951.1 0.57 0.66
G3 30.0 3.03
[Mean] LC 2250
[5.4%] 6130.1 6786.6 4651.8 1.32 1.46
G4 30.0 3.94
[UC] LC 2250
[5.4%] 6152.4 6786.8 5563.6 1.11 1.22
G5 30.0 3.03
[Mean] Average 2250
[5.4%] 6405.8 7059.4 4651.8 1.38 1.52
G6 30.0 3.94
[UC] Average 2250
[5.4%] 6435.1 7059.6 5563.6 1.16 1.27
G7 51.3*
4.34
[Mean] Average 2250
[3.1%] 6528.2 7449.6 5958.6 1.10 1.25
G8 51.3*
5.64
[UC] Average 2250
[3.1%] 6554.3 7452.4 7262.4 0.90 1.03
G9 51.3*
4.34
[Mean] Average 0 2506.7 3145.3 4346.1 0.58 0.72
G10 51.3*
5.64
[UC] Average 0 2527.3 3134.6 5649.9 0.45 0.55
*51.3 MPa is the mean concrete strength of the two extracted core samples.
LC = lower-characteristic; UC = upper-characteristic.
When considering the measured concrete strength and the average reinforcing steel properties, the
moment-curvature results vary from Myield/Mcrack ratios of 0.45-1.10 depending on the assumed
concrete tensile strength and whether the axial load can be relied on. These results confirm the
observed behaviour of the grid-F wall with a single crack formation and ruptured reinforcing steel and
the increased vulnerability of walls when the actual concrete strength is considerably greater than
specified strength.
6
Figure 1 – Moment-curvature response for the Gallery Apartments grid-F wall G2 analysis
3.3 NZS 3101:2006 standard
Moment-curvature analysis was also conducted on a modified wall design using the dimensions of the
Gallery Apartments grid-F wall with vertical reinforcing consistent with the current minimum vertical
reinforcement requirements in NZS 31010:2006 (Eq. 4) and the specified concrete compressive
strength of 30 MPa. For these analyses conservative material properties were used, including the
upper-characteristic concrete tensile strength (fct, fl = 3.94 MPa) and the lower characteristic grade 500
reinforcing steel properties (fy, = 500 MPa, fu/fy = 1.15, and εsu = 10%). In order to satisfy the
NZS3101:2006 minimum vertical reinforcement limits the DH-12 bars in the as-built grid-F walls
were replaced with DH-16 bars. The larger bar diameter resulted in a vertical reinforcement content of
0.288%, slightly greater that the 0.274% minimum calculated from Eq. 4.
The resulting moment-curvature response for the modified grid-F wall with DH-16 bars is shown in
Figure 2 for analyses with both no axial load applied to the wall (D1) and an axial load ratio (N/Ag fc′)
equal to 5% (D2). When no axial load is applied the wall exhibits a borderline non-ductile response
losing some strength immediately after cracking and rupture of the vertical reinforcement initiating at
a flexural strength only 15% greater than the cracking strength. This analysis with no axial load
highlights the differences between beam and walls. As described earlier a beam with minimum
reinforcing and no axial load would be expected to have a significant margin of safety, with the
nominal flexural strength between 1.5-2 times greater than the probable cracking moment. The
moment-curvature analysis with an axial load ratio of 5% indicates a more desirable behaviour with no
sudden loss of strength following cracking and significant strain hardening prior to rupture of the
vertical reinforcement. The axial load creates an initial pre-compression to the wall that increased the
moment required to cause cracking. However, the increase in the cracking moment is overshadowed
by the increase in ultimate flexural strength provided by the axial load. Interestingly, the positive
effect of the axial load compensates for the reduced margin of safety that was observed in the
moment-curvature analysis of the wall with no axial load.
Than moment-curvature analysis for the modified grid-F wall with distributed DH16 bars was
conducted for axial load ratios of 0, 5, 10, 15, and 20%. The results of these 5 analyses with different
axial loads are summarised in Table 2 and the margin of safety between the cracking moment and
flexural strength is also plotted in Figure 3. The trend that was observed in the first two analyses
plotted in Figure 2 continues with the larger increase in axial load. When an axial load ratio in excess
of 10% is applied, the margin of safety between the cracking moment and ultimate flexural strength is
similar to that of an RC beam. The trend indicated in Figure 3 highlights the importance of accounting
for the axial load when considering the flexural response of walls. However, axial load ratios of less
than 5% are common for walls with minimum vertical reinforcement and so walls constructed to
NZS 3101:2006 standards could still be vulnerable to non-ductile failure.
0
500
1000
1500
2000
2500
3000
3500
4000
0 5 10 15 20
Mo
me
nt (
kNm
)
Curvature (rad/km)
Mcrack
Myield
Mmax
7
(a) D1: No axial load
(b) D2: 5% axial load
Figure 2 – Moment-curvature responses for the NZS 3101:2006 walls with distributed vertical reinforcement
Table 2 – Summary of moment-curvature results for the walls with distributed vertical reinforcement conforming to NZS 3101:2006
Ref.
Axial
load
ratio
Myield
(kNm)
Mmax
(kNm)
Mcrack
(kNm)
Myield/
Mcrack
Mmax/
Mcrack
D1 0 3801 4546 3946 0.96 1.15
D2 5% 7256 8613 5448 1.33 1.58
D3 10% 10394 12391 6951 1.50 1.78
D4 15% 13335 15992 8453 1.58 1.89
D5 20% 16252 19585 9955 1.63 1.97
Figure 3 – Safety factors for different axial load ratios
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
0 5 10 15 20
Mo
me
nt (
kNm
)
Curvature (rad/km)
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
0 5 10 15 20
Mo
me
nt (
kNm
)
Curvature (rad/km)
0
0.5
1
1.5
2
2.5
0 5 10 15 20
Axial load ratio (%)
Mmax/Mcrack
Myield/Mcrack
8
3.4 Plastic hinge length
Assessment of the margin of safety between the cracking moment and ultimate flexural strength of a
wall section may prevent a sudden undesirable failure, but it does not explicitly address the
distribution of inelastic deformations within the wall. An RC wall must form a plastic hinge with
sufficient ductility to provide a suitable seismic load resisting system for a multi-storey building. The
ductility of the plastic hinge is severely compromised when deformations are concentrated at a few
large cracks as opposed to a large number of distributed cracks.
The member analysis function of Response-2000 was utilised to investigate the crack distribution and
spread of inelastic deformations in the modified grid-F wall that satisfied the current NZS 3101:2006
vertical reinforcement limits. The seismic load was represented by a concentrated lateral force applied
at an effective wall height of 15 m with a fixed constraint at the wall base. The crack pattern and
curvature distribution up the height of the wall that were calculated for the analysis of wall D1 (no
axial load ratio) are shown in Figure 4. The crack pattern does indicate some secondary crack
formation, but the deformation is predominantly concentrated at the initial crack at the wall base
which opened up to a 35 mm width before the vertical reinforcing steel ruptured. The curvature
distribution up the wall height confirms the concentration of inelastic deformation in a few cracks at
the wall base, with all but the lower 3 m height of the wall predicted to remain elastic (uncracked).
(a) Member crack pattern (b) Curvature distribution
Figure 4 – Member analysis results for wall D1 (no axial load ratio)
Member analysis was conducted for all of the walls with distributed vertical reinforcement conforming
to NZS 3101:2006 (D1-D5). An equivalent plastic hinge length was calculated for each wall by
equating the area under the plastic curvature distribution to an equivalent rectangle with the same peak
curvature. This procedure is the same as that used to derive the equivalent plastic hinge length and
curvature limits in NZS 3101:2006, as discussed by Fenwick and Dhakal (2007). The ultimate lateral
drift calculated from the failure displacement at the top of the wall and the equivalent plastic hinge
lengths calculated from the wall analyses are given in Table 3. The ultimate lateral drift increased
from 1.70% to 2.10% as the axial load ratio was increased from 0-20%. These drift capacities are less
than the allowable drift limits for ductile buildings, highlighting the possibility of premature failure of
the lightly reinforced walls in limited-ductile or ductile structures. The calculated equivalent plastic
hinge lengths assumed by NZS 3101:2006 would be lw/2, or 2.15 m, approximately twice the actual
equivalent plastic hinge length calculated from the member analysis.
0
2
4
6
8
10
12
14
0 5 10
He
igh
t fro
m w
all b
ase
(m)
Curvature (rad/km)
Mem
ber C
rack D
iag
ram
35.4
1
28.1
8
24.0
2
14.7
8
6.3
9
9
Table 3 – Equivalent plastic hinge lengths for the walls with distributed vertical reinforcement conforming to NZS 3101:2006
Ref.
Axial
load
ratio
Ultimate
lateral drift
(%)
Equivalent plastic hinge length
Calculated (mm) % of NZS 3101
D1 0 1.70 1127 52
D2 5% 1.72 1132 53
D3 10% 1.84 1177 55
D4 15% 1.87 1207 56
D5 20% 2.10 1224 57
3.5 Discussion and Recommendations
3.5.1 Minimum vertical reinforcement limits
The moment-curvature analysis of the as-built Gallery Apartment grid-F wall highlighted the
vulnerability of walls constructed with minimum vertical reinforcement prior to the adoption of
NZS 3101:2006. If yielding is expected in a wall with minimum vertical reinforcement based on
shrinkage and temperature requirements there is a strong possibility that a sudden failure could occur
due to the probable cracking moment being greater than the flexural strength of the cracked section.
Furthermore the equation adopted by NZS 3101:2006 for minimum vertical reinforcement in walls
may not be suitable for all applications. To achieve the equivalent margin of safety between the
nominal flexural strength and cracking moment of a beam, a wall would need to be subjected to an
axial load of approximately 10% of the section capacity. However, the reinforcement arrangement
and loading of walls are a significant deviation for the assumptions that were originally used to derive
Eq. 1 and it is not desirable to rely on axial load to achieve a ductile response.
3.5.2 Spread of plasticity
Although the current equations for minimum longitudinal and vertical reinforcement may prevent a
sudden failure caused by an abrupt drop in section flexural strength, the ductility of the member is not
specifically addressed. Even when the sectional analysis indicated a significant margin of safety
between the cracking moment and ultimate flexural strength, the member analysis still showed a
concentration of inelastic deformations over a relatively short height of the wall. For all analyses a
large crack was predicted to open up at the wall base which eventually led to fracture of the vertical
reinforcement. This concentration of inelastic deformations in a single crack has significant
consequences with regard to the procedures used in NZS 3101:2006 to estimate allowable curvature
limits. Alternative requirements for minimum vertical reinforcement may be required if a wall is
intended to provide the lateral resistance in a multi-story building designed to exhibit a limited ductile
or ductile seismic response. It should be noted that the member analysis conducted in Response has
not yet been verified against experimental data and a series of tests and more sophisticated analyses
are required to confirm these requirements.
The approach recommended by CERC (2012) is to investigate the reinforcement required to initiate
secondary flexural cracks in walls. The minimum vertical reinforcement calculated from Eq. 4 can be
rearranged to investigate the direct tensile stress induced in the surrounding concrete, as shown below
in Eq. 8. When considering the direct tension force required to initiate a secondary crack, Eq. 8
implies that a maximum direct tensile stress of 0.25√ fc′ can be overcome in the surrounding concrete.
This tensile stress is approximately half of the estimated direct tensile strength of concrete which
implies that secondary cracks would be unlikely to form when minimum vertical reinforcement is used
(Mindess et al. 2003; Fédération Internationale du Béton (fib) 2012). Additionally, the effective area
10
of concrete in tension that should be used to determine the criteria for secondary cracks needs to be
considered along with the stress concentrations that may initial a crack.
(8)
3.5.3 Distribution of reinforcement
The analyses presented were conducted with evenly distributed bars to satisfy the minimum
NZS 3101:2006 minimum vertical reinforcement requirements (Eq. 4). Distributed vertical
reinforcement in RC walls is common practice in New Zealand and was previously recommended to
avoid undesirable shear failure modes (Park and Paulay 1975; Paulay and Priestley 1992). In the
published interim design guidelines, SESOC recommended that vertical reinforcing steel should
instead be lumped at the ends of the wall with minimum reinforcement along the wall web (Structural
Engineering Society of New Zealand (SESOC) 2011a). It was suggested that increasing the
reinforcement in the ends of the wall would increase the tension force and thus increase the chances of
forming secondary cracks. However, research by Dai (2012) found that concentrating too much
vertical reinforcement in the boundary regions can leave the web region vulnerable to undesirable
failures that reduce the wall ductility. Additionally, sufficient distributed reinforcement is required in
the web region to encourage the propagation of secondary cracks within the section (Fenwick 1988).
Further research is required to clarify the impact of reinforcement distribution on RC wall behaviour
with consideration to different wall typologies. For example, recommendations suitable for multi-
story ductile RC walls may be different to that suitable for low-rise nominally ductile RC walls.
Additionally, recommendations for distribution of reinforcement may need to consider the magnitude
of shear stresses on the wall and vertical reinforcing contents.
3.5.4 Other issues
The moment-curvature analysis indicated that increasing the axial load improved the margin of safety
between the nominal flexural strength and the probable cracking moment. However, reliance on axial
load is not sufficient to ensure a ductile response is achieved in RC walls. The analysis results
indicate that even for walls with modest axial loads, a significant portion of the flexural capacity in
walls with minimum vertical reinforcement is attributed to the axial load. This reliance on axial load
may result in low hysteretic energy dissipation for some walls. Additionally, the analysis indicated
that the spread of plasticity was not significantly affected by the magnitude of axial load, with only a
small increase in the equivalent plastic hinge length. This is because the axial load does not influence
the criteria for the formation of secondary cracks.
The crack distribution in RC walls with minimum vertical reinforcement also has an influence on the
section properties used to conduct analysis. The concentration of deformations in only a small number
of cracks at the wall base means that the upper stories of the wall remain uncracked. The use of
typical cracked section properties to analyse lightly reinforced concrete walls will overestimate the
fundamental period and could result in an inaccurate calculation of seismic design forces. Further
investigation is required to determine appropriate section properties for use in analysing RC walls with
minimum vertical reinforcement.
4 CONCLUSIONS
An investigation was conducted to examine the current minimum vertical reinforcement limits set out
in the New Zealand Concrete Structures Standard NZS 3101:2006. The development of the current
equations was presented in addition to a series of moment-curvature and member analyses of an
example multi-storey RC wall. The following conclusions were drawn from the results of this
investigation:
1. Current limits for minimum longitudinal and vertical reinforcement are intended to prevent a
sudden failure by ensuring that the nominal flexural capacity of a section exceeds the probable
cracking moment.
11
2. The required minimum vertical reinforcement in walls increased significantly in the
NZS 3101:2006 standard with the adoption of a similar equation to that used for RC beams.
3. The vertical reinforcement content in the RC walls of the Gallery Apartments building was
insufficient to ensure a ductile seismic response with distributed cracking at the wall base.
4. Walls designed with minimum vertical reinforcement in accordance with NZS 3101:2006 are
reliant on a significant axial load acting to avoid the possibility of a sudden loss in strength
after cracking.
5. A sectional analysis approach and the current minimum vertical reinforcement limits in
NZS 3101:2006 do not ensure that inelastic deformations are well distributed with a large
number of cracks at the base of the wall.
6. Further research, and in particular experimental testing, is required to investigate the
performance of lightly reinforced RC walls and to determine suitable vertical reinforcement
contents and distribution in multi-story RC walls.
5 ACKNOWLEDGEMENTS
The assistance of Muhunthen Ishwaran in conducting the Response-2000 analysis and advice on the
critical issues related to RC walls from Prof. Richard Fenwick are greatly appreciated. Financial
support for this research was provided by the Natural Hazards Research Platform through contract
C05X0907, in addition to the University of Auckland, Golden Bay Cement, and Pacific Steel Group.
6 REFERENCES
ACI 363R-84. 1984. State of the art report on high-strength concrete. Farmington Hills, MI, American Concrete
Institute.
Bažant, Z. P. 1984. Size Effect in Blunt Fracture: Concrete, Rock, Metal, Journal of Engineering Mechanics,
Vol 110(4) 518-535.
Bentz, E. and Collins, M. P. 2001. Response-2000, University of Toronto.
Bull, D. 2012. The performance of concrete structures in the Canterbury earthquakes: Lessons for concrete
buildings, Structural Engineers Association of California (SEAOC) Convention, Santa Fe, NM.
Canterbury Earthquakes Royal Commission. 2012. Final report: Volume 2: The performance of Christchurch
CBD buildings. http://canterbury.royalcommission.govt.nz/Commission-Reports, Wellington, New Zealand.
Carpinter, A. 1989. Size Effects on Strength, Toughness, and Ductility, Journal of Engineering Mechanics, Vol
115(7) 1375-1392.
Dai, H. 2012. An investigation of ductile design of slender concrete structural walls, ME thesis, Iowa State
University, Ames, IA.
Fédération Internationale du Béton (fib). 2012. Model Code 2010 - Final draft, Volume 2. fib Bulletin No. 66,
Lausanne, Switzerland.
Fenwick, R. and Dhakal, R. P. 2007. Material strain limits for seismic design of concrete structures, Journal of
the Structural Engineering Society New Zealand (SESOC), Vol 20(1) 14-28.
Fenwick, R. C. 1988. The behaviour of soffit slabs in concrete box girder bridges. Report no. 445, Dept. of Civil
Engineering, University of Auckland, Auckland, New Zealand.
Fenwick, R. C. and Dickinson, A. R. 1987. The flexural behaviour of lightly reinforced concrete beams and
slabs. Report no. 435, Dept. of Civil Engineering, University of Auckland, Auckland, New Zealand.
Holmes Solutions. 2011. Material testing in buildings of interest: Gallery Apartments, Westpac Centre and IRD
building. http://canterbury.royalcommission.govt.nz/documents-by-key/20111129.1351, Report prepared for
the Canturbury Earthquakes Royal Commission.
Kam, W. Y., Pampanin, S. and Elwood, K. J. 2011. Seismic performance of reinforced concrete buildings in the
22 Feburary Christchurch (Lyttelton) earthquake, Bulletin of the New Zealand Society for Earthquake
Engineering, Vol 44(4) 239-278.
12
Mander, J. B., Priestley, M. J. N. and Park, R. 1988. Theoretical stress-strain model for confined concrete,
Journal of Structural Engineering, Vol 114(8) 1804-1826.
Mindess, S., Young, J. F. and Darwin, D. 2003. Concrete. Prentice Hall, Upper Saddle River, NJ.
NZS 3101:2006. Concrete Structures Standard. Wellington, New Zealand, Standards New Zealand: 646.
Park, R. and Paulay, T. 1975. Reinforced concrete structures. John Wiley and Sons, New York.
Paulay, T. and Priestley, M. J. N. 1992. Seismic design of reinforced concrete and masonry buildings. John
Wiley and Sons Inc., New York.
Smith, P. and England, V. 2012. Independent assessment on earthquake performance of Gallery Apartments - 62
Gloucester Street. http://canterbury.royalcommission.govt.nz/documents-by-key/20120217.3188, Report
prepared for the Canturbury Earthquakes Royal Commission.
Structural Engineering Society of New Zealand (SESOC). 2011a. Practice note - Design of conventional
structural systems following Canterbury earthquakes. http://canterbury.royalcommission.govt.nz/documents-
by-key/20111221.1908, Report prepared for the Canterbury Earthquakes Royal Commission
Structural Engineering Society of New Zealand (SESOC). 2011b. Preliminary observations from Christchurch
earthquakes. http://canterbury.royalcommission.govt.nz/documents-by-key/20111205.1533, Report prepared
for the Canturbury Earthquakes Royal Commission
Wang, C.-K., Salmon, C. G. and Pincheira, J. A. 2007. Reinforced concrete design. John Wiley & Sons,
Hoboken, NJ.
Wight, J. K. and MacGregor, J. G. 2009. Reinforced concrete: mechanics and design. Prentice Hall, Upper
Saddle River, N.J.
Wood, S. L. 1989. Minimum tensile reinforcement requirements in walls, ACI Structural Journal, Vol 86(5)
582-591.
Wood, S. L., Stark, R. and Greer, S. A. 1991. Collapse of eight-story RC building during 1985 Chile earthquake,
Journal of Structural Engineering, Vol 117(2) 600-619.