Technical University of Denmark
Application of Radiant Cooling Systems
Professor Bjarne W. Olesen, Ph.D
Department of Civil Engineering.
Seminar outline• Basics for Radiant systems
– System types, Comfort
• Standards for Radiant Heating and CoolingSystems– Determination of Heating and Cooling Capacity
• Control of radiant cooling systems• Construction and Installation Technologies
– Examples
• Q&A
![Page 2: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/2.jpg)
HISTORYFrank Lloyd Wright's UsonianHouses 1930’s
A lightweight floor slab was used and the traditional basement was dispensed with. By using steam or hot water piping, it became possible to heat the floor, therefore eliminating the need for radiators. The overall result was heat without a draft or temperature variation of the most comfort - cool head and warm feet.
c. 10,000 B.C., China, the word “kang,” can be traced back to the 11th century B.C. and originally meant, “to dry” before it became known as a heated bed. c. 5,000 B.C., evidence of baked floors are found foreshadowing early forms of “kang” and “dikang” (heated floor) later “ondol” (warm stone) in China and Korea, respectively.
c. 10,000 B.C., China
HISTORY
Hypocausts were used from thethird century B.C. in ancientEurope.
c. 1904, Liverpool Cathedral heated with system based on the hypocaust principles.
![Page 3: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/3.jpg)
1. Screed 2. Pipes3. Plastic foil 4. Insulation5. Levelling 6. Concrete
No cooling – decreased performance
Low energy costs
Low operation costs
Full Air-Conditioning
Constant temperature
Draught, Noise, SBS
High energy costs
High operation costs
Thermo-Active-Building-Systems
Temperature ramps
Reasonable energy costs
Low operation costs
COMFORT-PERFORMANCE
![Page 4: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/4.jpg)
What is Low Temperatur Heating/ High Temperature Cooling?
• Heat exchange through large surfaces (floor, ceiling, walls)
• Supply water temperatures:– Heating: 25 – 40 °C (77 – 104 F)
– Cooling: 16 – 23 °C (61 – 74 F) • temperature limited by dew-point to avoid
condensation)
• Wide range of systems, solutions both for residential and non-residential buildings 7
COMBINATION WITH LOW ENERGY SOURCES
Heating supply temp. : 25 - 40°C
heat pumps
condensing boiler
ground coupling
waste heat
solar energy
Cooling supply temp. : 16 - 23°C
reversible heat pump
ground coupling
free cooling
air cooled chillers8
Day
Night
Cooling method
Ground water
Geothermal heat/coolth
Night air
Cooling unit
![Page 5: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/5.jpg)
CONCEPTS OF RADIANT HEATING AND COOLING SYSTEMS
• Heating - Cooling panels
• Surface systems
• Embedded systems
Suspended cooled ceilings
![Page 6: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/6.jpg)
Suspended cooled ceilings
Capillary Tubes
Radiant surface heatingand cooling systems
Floor Wall
Thermo Active Building Systems
Ceiling
Reinforcement
Floor
Concrete Pipes
Room
Room
Window
![Page 7: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/7.jpg)
GENERAL THERMAL COMFORT
• Personal factors– Clothing
– Activity
• Environmental factors– Air temperature
– Mean radiant temperature
– Air velocity
– Humidity
![Page 8: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/8.jpg)
Mean Radiant Temperature
• tr = ΣFp-i tsi
– Fp-i = Angle factor from person to surface i
– tsi = Surface temperature of surface i
– ΣFp-i = 1
Mean Radiant Temperature
Figure 2.2 Mean value of angle factor between a seated person and a) horizontal rectangle b) vertical rectangle
Figure 2.3 mean value of angle factor between a standing person and a) horizontal rectangle b) vertical rectangle
![Page 9: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/9.jpg)
GENERAL THERMAL COMFORTFLOOR TEMPERATURE
• OPERATIVE TEMPERATURE– to = (hcta + hrtr)/(hc + hr)
– to = 0.5ta + 0.5tr ( low air velocity)
• ta = Air temperature• tr = Mean radiant temperature• hc = Convective heat exchange coefficient• hr = Radiative heat exchange coefficient
• 1 (1.8F) degree change of floor temperature will change operative temperature 0.2 (0.4F) degree
![Page 10: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/10.jpg)
MODERATE ENVIRONMENTS
• GENERAL THERMAL COMFORT– PMV / PPD, OPERATIVE TEMPERATURE
• LOCAL THERMAL DISCOMFORT– Radiant temperature asymmetry
– Draught
– Vertical air temperature difference
– Floor surface temperature
Determination of Heating and Cooling Capacity
![Page 11: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/11.jpg)
SURFACE HEATING AND COOLING
Heat transfer coefficient
8,08,0
6,0
11,011,0
7,0
5,5
6,5
7,5
8,5
9,5
10,5
11,5
Floor
Ceiling
Wall
W/m2K
HeatingCooling
SURFACE HEATING AND COOLING
Max. - Min. Surface temperature
40
17
27
17
35
20
29
20
15
20
25
30
35
40
45
Floor
Ceiling Wall
oC
HeatingCooling
Perimeter
![Page 12: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/12.jpg)
MAXIMUM HEATING AND COOLING CAPACITY
160
72
42
99
165
42
99
42
020406080100120140160180200
Floor
Ceiling Wall
HeatingCooling
Perimeter
W/m2
ALUMINUM HC device: Floor Heating & Cooling (type B), R=0.01~0.1, T=150 & 300
0
20
40
60
80
100
120
140
160
-15 -10 -5 0 5 10 15 20 25 30
Heating/cooling medium differential temperature ∆θH=θH-θi [°C]
He
at e
xc
ha
ng
e [
W/m
2]
T=150, R=0.01
T=150, R=0.1
T=300, R=0.01
T=300, R=0.1
Figure 4.17 Heat exchange between the surface (with ceramic tiles, wooden
parquets or carpet R?B=0.1 and no covering R?B=0) and the space when aluminium heat conductive device used
Heating/ cooling capacity, ISO 11855
![Page 13: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/13.jpg)
Method for verification of FEM and FDM
calculation programs
Method for verification of FEM and FDM
calculation programs
![Page 14: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/14.jpg)
Radiant Floor Cooling
More than 100 W/m2 or 32 Btu/ft2 h
TABSThermo Active Building Systems
InsulationFloor
Concrete
Reinforcement
Pipe
Room
Room
Window
![Page 15: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/15.jpg)
Control of radiant heating and cooling systems
![Page 16: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/16.jpg)
CONTROL OF A COMBINED FLOOR HEATING-COOLING SYSTEM
Boiler Chiller
Room temp.-Humidity
Outside temp.
SupplyLimiter
Return
Mixing valve
Valves
VIVALDI
CONTROL COOLING
10
15
20
25
30
0 2 4 6 8 10 12 14 16 18 20 22 0 2 4 6
3-Min. Floor temp.t t
1-Operative Temperature
2-Floor temperature
4-Water temperature5-Dewpoint temp.
5
4
3
2
1
°C
TIME hours
degC F18 64,419 66,220 6821 69,822 71,623 73,424 75,225 7726 78,827 80,628 82,429 84,230 86
![Page 17: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/17.jpg)
BoilerChiller
Temperature-Humidity
Outsidetemperature
Floor temp.
Supply Limiter
Return
Mixing valve
Shut off valves
Control
Room sensor Control unit
Valve
Manifold
Pump
Control of a combined floor heating-cooling system
with individual room control
SELF CONTROL
80W/m?
40W/m?
20W/m?
10W/m?
Heat load
FloortemperatureHeat. level temp. tiles
Heat. level temp. carpet
38,4
29,4
24,9
22,5
31,9
26,2
23,321,7
27,3
23,922,1
21,12022242628303234363840
C°
Floortemperature at 20 °C Roomtemperature
degC F18 64,419 66,220 6821 69,822 71,623 73,424 75,225 7726 78,827 80,628 82,429 84,230 86
![Page 18: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/18.jpg)
SELF CONTROL
80W/m?
40W/m?
20W/m?
10W/m?
Heat load
Floor temperature
Heat. level temp. tiles
91
48
26
14
59
30
16
80
102030405060708090
100
%
% decrease in heat output by 1 K room temperature increase
Radiant surface heatingand cooling systems
Floor Wall
Thermo Active Building Systems (TABS)
Ceiling
Reinforcement
Floor
Concrete Pipes
Room
Room
Window
![Page 19: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/19.jpg)
The analysed building
West room
Width of the room: 3.6 m
Window portion of the outside wall: 50%
Office building
![Page 20: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/20.jpg)
Internal heat sources
0
100
200
300
400
500
600
hea
t p
rod
uct
ion
[W
]
1 3 5 7 9 11 13 15 17 19 21 23
daytime [h]
50% Radiation50% Konvection 100g/h moisture
550W = 27.8 W/m² 8.6Btu/ft2
Monday to Friday
Time of operation
• Four different schedules
• 24 hour
• 8:00-17:00
• 18:00-06:00
• 22:00-06:00
![Page 21: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/21.jpg)
Intermittent operation of circulation pump
• Pump on for 1 hour – Pump off for 1 hour
• Pump on for ½ hour – Pump off for ½ hour
• Pump on for ¼ hour - Pump off for ¾ hour
Control of water temperature
• Supply water temperature equal to internal dew point temperature.
• Supply water temperature a function of outside temperature according to the equation:
• Average water temperature a function of outside temperature according to:
• Supply water temperature constant equal to: 18 °C, 20 °C and 22 °C
• Average water temperature constant equal to: 18 °C, 20 °C and 22 °C
2020*4,0*3,1sup externalply tt
2020*4,0*3,1 externalaverage tt
degC F18 64,419 66,220 6821 69,822 71,623 73,424 75,225 7726 78,827 80,628 82,429 84,230 86
![Page 22: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/22.jpg)
Evaluation parameters
• Range of operative temperatures
• Pump running time
• Energy consumption
Operative temperature range, May to September Different control concepts for water temperature, Time of operation 18:00 - 6:00 Uhr
33
14
54 54 52
38
0
10
20
30
40
50
60
70
80
90
100
Tsup =Tdp
Pump Tsup =F(ext)
Pump Tavg =F(ext)
Pump Tavg =22 °C
Pump Tavg =20 °C
Pump Tavg =18 °C
Pump
Control of water temperature
Op
erat
ive
tem
per
atu
re r
ang
e [%
]
>27
26-27
25-26
22-25
20-22
<20
Pump %
degC F18 64,419 66,220 6821 69,822 71,623 73,424 75,225 7726 78,827 80,628 82,429 84,230 86
![Page 23: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/23.jpg)
Energy consumption and pump running hours, May to September Different control concepts for water temperature, Time of operation 18:00 - 6:00 Uhr
1031
0
200
400
600
800
1000
1200
1400
1600
1800
2000
Tsup =Tdp
Pump Tsup =F(ext)
Pump Tavg =F(ext)
Pump Tavg =22 °C
Pump Tavg =20 °C
Pump Tavg =18 °C
Pump
Control of water temperature
En
erg
y co
nsu
mp
tio
n, k
Wh
(H
ou
rs)
Heating
Cooling
Pump hours
degC F18 64,419 66,220 6821 69,822 71,623 73,424 75,225 7726 78,827 80,628 82,429 84,230 86
Construction and Installation Technologies
Examples
![Page 24: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/24.jpg)
Transportation of modules
![Page 25: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/25.jpg)
Installation – pressure test
49
Prefabrication
50
![Page 26: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/26.jpg)
Thermo active hollow-core slabThermoMax
51
Produced in Denmark by Spæncom 1.2 m wide, thicknes 220, 270, 320 and 400 mm 20 mm PEX-pipes
PSO-ELFORSK/COWI (2012)
Industry
![Page 27: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/27.jpg)
Radiant Floor Cooling
Airport Bangkok
![Page 28: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/28.jpg)
Airport Bangkok
Airport Bangkok
![Page 29: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/29.jpg)
Airport Bangkok
June 30 2008
Installation of PEX pipes
![Page 30: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/30.jpg)
June 30 2008
Terminal building
Ta = 16 oCTd = 10 oC
TsupplyW
= 13 oC
![Page 31: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/31.jpg)
ART MUSEUM BREGENZ
ART MUSEUM IN BREGENZ
• Design requirements– Air temperature variations during a day within 4 K
– Relative humidity variations less than 6 % during a day.
– Seasonal variations between 48 and 58 %
– Room temperature in winter 18 oC to 22 oC
– Room temperature in summer 22 oC to 26 oC, occasional up to 28 oC
• Design load 250 persons pr. day, 2 hours
• Displacement ventilation < 0,2 h-1
• Floor area 2.800 m² , 4 floors
• 28.000 m plastic pipes embedded in walls and floor slabs
![Page 32: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/32.jpg)
ART MUSEUMBREGENZ
• 3.750 m² floor area
• 4.725 m² embedded pipes
• Condensing boiler
• Ventilation 750 m3/h per floor (first design was 25.000 m3/h
ART MUSEUM IN BREGENZ
![Page 33: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/33.jpg)
ART MUSEUM BREGENZ
ART MUSEUM BREGENZ
![Page 34: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/34.jpg)
Balanced Office Building (BOB.1)Aachen, Germany
• Gross floor area 2,151 m²
• 4 storeys• Efficiently insulated
external envelope• Ground-coupled heating
and cooling with TABS• Ventilation system with
heat recovery• Daylight-controlled
lighting• Rainwater collection for
use in toilet flushing
Energy concept in BOB.1
![Page 35: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/35.jpg)
cooling period in BOB.1
Dockland, Hamburg
![Page 36: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/36.jpg)
Viborg Town Hall
72
Photo: Henning Larsen Architects
6 storeys, central open space
19363 m2
Natural & mechanical ventilation
Combined radiant floor
heating/cooling and convectors
under windows
![Page 37: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/37.jpg)
Viborg Town Hall
73
Graphics: Viborg Townhall brochure & COWI
IDOM Company Headquaters, Madrid, Spain
74
16 000 m2
Natural & Mechanical ventilation
External solar shading & green
facade
TABS combinned with free cooling
(covers 40-50 kWh/m2)
(kWh/m²y) IDOM HQ CTE - MADRID %Heating + DHW 27,35 77,00 -64,5
Cooling 12,58 85,00 -85,2Lighting 11,37 34,00 -66,6
Total 51,30 196,00 -73,8
Energy use
![Page 38: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/38.jpg)
IDOM Company Headquaters, Madrid, Spain
75
Radiant Floor CoolingOPERA HOUSE
SHOPPING CENTER MUSEUM
![Page 39: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/39.jpg)
Yearly indoor comfort evaluation and energy consumption, and assessment of thermal activated building systems
in Middelfart Sparekasse.
Technical University of Denmark
![Page 40: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/40.jpg)
Slide 79
Opera House in CopenhagenSummer indoor climate in Foyer
• Radiant floor cooling with stone cover down the structural slabs to reduce peak cooling load
• High air change by displacement ventilation system.
• Humidity control prevents condensation on floor.
References / South, West Europe
• Modern Old Port of Savona, NW coast of Italy
– Underfloor heating for 140 high-end residential apartments and shopping area at ground level
• Dolce Vita Tejo, Lisbon, Portugal
– one of Europe’s largest shopping centres to be built, heating and cooling by Uponor
![Page 41: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/41.jpg)
References / Nordic
• The world’s most modern opera house in Oslo, Norway – Uponor ventilation ducts and floor heating
• Nupurinkartano, Espoo, Finland– first turnkey bedrock heating/cooling in Finland
• Renovation with underfloor heating and tap water in Västerås, Sweden– a 1978 office building turned into 50 apartments and 13 unique terraced houses on the rooftop
Industrial heating/cooling application: BWM World Munich, Germany - 2007
• 16.500 m² of floor, glass and steel, architecture in the BWM museum
• 5,000 m² of industrial radiant cooling and heating with PE-Xa pipes integrated into the hall floor = massive invisible cooling or heating panel
• Full architectural freedom provided: An experience which appeals to all senses, allowing visitors to experience the fascination of mobility
• Energy-saving and environmentally friendly operation
![Page 42: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/42.jpg)
Sun shading and daylight penetrationRADIANT VAV
![Page 43: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/43.jpg)
Energy
Thermal Comfort
![Page 44: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/44.jpg)
DOE-USA
![Page 45: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/45.jpg)
DOE-USA
DOE-USA
![Page 46: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/46.jpg)
COOPER UNION NEW YORK
First costs
![Page 47: ASHRAE DL Atlanta Application of Embedded Radiant Cooling ... · Balanced Office Building (BOB.1) Aachen, Germany • Gross floor area 2,151 m² s y e r o t s •4 • Efficiently](https://reader036.vdocuments.us/reader036/viewer/2022081404/5f04bf447e708231d40f80d1/html5/thumbnails/47.jpg)
REHVA GUIDEBOOK NO: 7Jan Babiak-Bjarne W . Olesen-Dusan Petras
Low Exergy Hydronic Radiant Heating and CoolingWhy?
• Water based systems
• Low temperature heating - High temperature cooling
• More economical to move heat by water:
– Greater heat capacity than air
– Much smaller diameter pipes than air-ducts
– Electrical consumption for circulation pump is lower than for fans
• Lower noise level
• Less risk for draught
• Lower building height
• Higher efficiency of energy plant
• But
– Reduced capacity?
– Acoustic?
– Latent load?