ASHRAE 62.1 IAQP
Marwa Zaatari, PhDVP Building Solutions
![Page 2: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/2.jpg)
Agenda
2
The challenge: Energy, indoor air quality, outdoor air qualityThe opportunity: IAQPComplianceVRP versus DCV versus IAQP IAQP Methodology
![Page 3: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/3.jpg)
The Challenge
Ventilation leads to higher energy costs: Outside air is replaced 1-2 time per hour Outside air conditioning represents 30-50% of the
total load on HVAC systems in most climates
Energy Efficiency
Unconditioned outside air
Conditioned indoor air
All air replaced in 1-2 hours
$ • HVAC capacity• Energy usage• Water consumption• Maintenance
![Page 4: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/4.jpg)
The Challenge
4
Ventilation leads to higher energy costs:100,000 ft2 - 20,000 CFM of outside air:
380,000 kWh of cooling energy 1,340,000 kBTU of heating energy
Energy Efficiency
City
Electrical (kWh) Gas/Steam (kBtu)
Cooling Savings
Heating Savings Heating Savings
Boston 9 100New York 14 85Chicago 11 133
Las Vegas 17 3 0Colorado 3 125Phoenix 26 1Atlanta 29 11
Washington 19 67San Antonio 48 4New Orleans 56 2
Miami 75Baton Rouge 51 5 57
Milwaukee 9 139San Diego 5San Juan 116Nashville 25 19
Oklahoma 27 19Kansas 20 30
Baltimore 19 78Fort Smith 32 16Charlotte 29 13Greenville 49 4
Thermal Energy Consumption of Outside AirkWh&kBtu/outside air consumed CFM/Year
![Page 5: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/5.jpg)
The Challenge
5
Indoor Air Quality (IAQ)
VOCs, CO2
Satish et al., LBL, 2012Allen et al., Harvard School of Public Health,
2015
Gain of $6,500 per year per employee
Elevated CO2 has a direct and negative
effect on productivity
![Page 6: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/6.jpg)
The Challenge
6
Ventilation leads to increase of outdoor generated pollutants indoors, PM2.5 - Ozone - CO - NOx - SOx
Outdoor Air Quality (OAQ)
American Lung Association EPA
Outside air ratings 24-Hour Particle Pollution
Ozone Grade 8-Hr Ozone Classification
Boston-Worcester-Providence, MA-RI-NH-CT B F
Chicago-Naperville, IL-IN-WI F F Nonattainment
Dallas-Fort Worth, TX-OK B F Nonattainment
Houston-The Woodlands, TX C F Nonattainment
New York-Newark, NY-NJ-CT-PA F F Nonattainment
Miami-Fort Lauderdale-Port St. Lucie, FL B C
Washington-Baltimore-Arlington, DC-MD-VA-WV-PA C F Nonattainment
![Page 7: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/7.jpg)
The Opportunity
7
IAQP + Air Cleaning: Can be implemented as an energy conservation measure: less ventilation is needed to
maintain IAQ Decrease the intake of outdoor-generated pollutants indoors
Energy Efficiency , IAQ, and OAQ
Solution: IAQP + Air Cleaning
![Page 8: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/8.jpg)
8
Compliance
![Page 9: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/9.jpg)
Compliance
9
ASHRAE Standard 62.1-2016
IAQP: Can be implemented as an energy conservation measure: less ventilation is needed to maintain IAQ
International Building Code (IBC) + ASHRAE 90.1
• Alternative Methods• MD: 2015 versions of IMC and IECC/ASHRAE 90.1 2013• VA and DC: 2012 versions of IMC and IECC/ASHRAE 90.1 2010
American Conference Of Governmental Industrial Hygienists (ACGIH) - 2016: Industrial Ventilation Manual IAQP (including exhaust for IAQP)
USGBC
• Pilot: PC 68 – pre-requisite: EB & NC• Pilot: Performance based indoor air assessment in Existing Buildings
WELL
![Page 10: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/10.jpg)
ASHRAE 62.1
10
![Page 11: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/11.jpg)
ASHRAE 62.1
11
![Page 12: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/12.jpg)
12
ASHRAE Standard 62.1
![Page 13: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/13.jpg)
ASHRAE Standard 62.1 Overview
13
ASHRAE Std. 62.1: Ventilation Rate Procedure (VRP) PRESCRIPTIVE
ASHRAE Std. 62.1: Indoor Air Quality Procedure (IAQP) –since 1979* PERFORMANCE-BASED Pollutant control ventilation (PCV) Cleaning efficiency Compliance report Occupant survey* Since 2006, the International Mechanical Code (IMC) allows for an engineered solution showing control of contaminant concentrations (IAQP).
![Page 14: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/14.jpg)
ASHRAE Standard 62.1–2016
14
Breathing zone outdoor airflow: use Table 6.2.2.1 rates (pages 12-15)
Ventilation Rate Procedure (VRP)
PeopleComponent
BuildingComponent
Breathing Zone Outdoor Airflow CFM
Minimum CFM/Person
Zone PopulationMinimum CFM/ft2
Zone Floor Area
Vbz = Rp Pz + Ra Az
Definition: Breathing zone is the region within an occupied space between planes 3-72 in. above the floor and more than 2 feet from the walls.
![Page 15: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/15.jpg)
ASHRAE Standard 62.1–2016
15
Based on CO2 concentrations as a surrogate for human occupancy
VRP + Demand-Controlled Ventilation (DCV)
Vbz = Rp Pz + Ra AzMinimum
CFM/Person
Actual Zone Population
Minimum CFM/ft2
Zone Floor Area Constant
![Page 16: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/16.jpg)
Example Calculation of Outside Air Requirement using VRP and DCV
16
Office BuildingArea = 80,000 ft2
# People/1,000 ft2 = 5# People = 400
Supply/Return Location = CeilingZone Air Distribution Effectiveness = 0.8
People Outside Rate = 5 CFM/person
Area Outside Rate = 0.06 CFM/ft2
![Page 17: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/17.jpg)
Example Calculation of Outdoor AirRequirement using VRP and DCV
17
VRP Building Component –Min. Outside Air (CFM)
People Component –Min. Outside Air (CFM)
Total Outdoor Air (CFM)
# People = 400 6,000 2500* 8,500
VRP + DCV Building Component –Min. Outside Air (CFM)
People Component –Min. Outside Air (CFM)
Total Outdoor Air (CFM)
# People = 300 6,000 1,875 7,875# People = 200 6,000 1,250 7,250# People = 100 6,000 625 6,625
*For office buildings, DCV can save a maximum of 29%of total Design Outside Air intake.
![Page 18: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/18.jpg)
VRP and DCV Drawbacks
18
VRP Leads to unnecessary energy consumption (prone to over-ventilation) Does not control outdoor-generated pollutants
DCV Does not control outdoor-generated pollutants Does not account for pollutants generated indoors that are independent of human
activities Nine literature studies* documented the above statements by testing formaldehyde, total volatile organic
compounds (TVOC), and radon
Requires CO2 sensor for each ventilation zone; sensors must be calibrated every ~6 months for proper operation.
For certain spaces, such as offices, portion of ventilation related to ”people” component is low (29% in case of offices), leaving little margin to save energy using this methodology*(Gabel et al., 1986; Donnini et al., 1991; Carpenter, 1996; Enermodal, 1995; Persily et al., 2003; Chao & Hu, 2004; Jeong et al., 2010; Mui & Chan, 2006; Herberger & Ulmer 2012)
![Page 19: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/19.jpg)
19
IAQP Methodology
![Page 20: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/20.jpg)
IAQP Methodology
20
The IAQP allows compliance based on:1. Objective Evaluation (contaminants concentrations)2. Subjective Evaluation (survey)
Contaminants and/or mixtures,
sources, and emissions
Concentration limits
Identify air cleaning solution
and efficiency
Use mass balance equation
IAQ Testing Survey
ASHRAE Standard 52.2 Particulate Filtration
ASHRAE Standard 145.2 Gaseous FiltrationONLY Sorbent
Design
Verification
32 VOCs 5 inorganics Include top 10 contaminants
if not included in the above
Locations at breathing level
EPA methods
ASHRAE + LEED
LEED
![Page 21: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/21.jpg)
IAQP Methodology: Design Phase
21
VOC
VOCCO2
CO2
CO2
CO2
OutsideConcentration, C0
IndoorConcentration, Cbz
Emissions, N
Supply Air, VS
VOC
Vot
![Page 22: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/22.jpg)
IAQP Methodology: Design Phase
22
VOC
VOCCO2
CO2
CO2
OutsideConcentration, C0
IndoorConcentration, Cbz
Emissions, NAir CleaningEfficiency, Ef
QHLR
Vot
VOC
CO2
Supply Air, VS
![Page 23: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/23.jpg)
IAQP Methodology: Design Phase
23
VOC
VOCCO2
CO2
CO2
OutsideConcentration, C0
IndoorConcentration, Cbz
Emissions, NAir CleaningEfficiency, Ef
QHLR
Vot
VOC
CO2
Supply Air, VS
![Page 24: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/24.jpg)
IAQP: Objective Evaluation Steps
24
Mass Balance Analysis
VOC
VOCCO2
CO2
CO2
OutsideConcentration, C0
IndoorConcentration, Cbz
Emissions, NAir CleaningEfficiency, Ef
QHLR
Vot
VOC
CO2
Supply Air, VS
N CleaningDilution
![Page 25: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/25.jpg)
Example Calculation of Outside Air Requirement using VRP, DCV, IAQP
25
Office BuildingArea = 80,000 ft2
# People/1,000 ft2 = 5# People = 400
Supply/Return Location = CeilingZone Air Distribution Effectiveness = 0.8
![Page 26: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/26.jpg)
Outside Air Requirements Comparison
26
Method OfficeVRP (CFM) 8,500
DCV (CFM) - # People = 80 7,875DCV (CFM) - # People = 50 7,250DCV (CFM) - # People = 20 6,625
IAQP (CFM) 1,992
ASHRAE Standard 62.1-2016
* Outside air requirements will be the max between IAQP and exhaust
![Page 27: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/27.jpg)
ASHRAE IAQP Compliance Design Report
27
Outside Air Requirements = X CFM Number of HLR Modules = Qty. Y
![Page 28: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/28.jpg)
Summary of ASHRAE Testing Standards
28
ASHRAE Standard 145.2: Laboratory Test Method for Assessing the Performance of Gas-Phase Air
Cleaning Systems: Air Cleaning Devices Applies to sorbent testing only (excludes electronic air cleaning) Gases: VOCs, aldehydes, ozone, basic and acidic gases
ASHRAE Standard 52.2: Method of Testing General Ventilation Air-Cleaning Devices for Removal
Efficiency by Particle Size
![Page 29: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/29.jpg)
Sorbent-based Air Cleaning Performance
29
Air cleaning certification data according to ASHRAE Standards is needed to apply the Indoor Air Quality Procedure (IAQP) and LEED IAQP
Third party certifications according to ASHRAE Standard 145.2 and 52.2 for sorbent-based cartridges from Research Triangle Institute (RTI)
Example: Ozone test data from RTI: Efficiency = 70% By-product VOCs and ozone
concentrations = 0 ppb
![Page 30: ASHRAE 62.1 IAQP - nafahq.org · ASHRAE Standard 52.2 Particulate Filtration ASHRAE Standard 145.2 Gaseous Filtration ONLY Sorbent Design Verification 32 VOCs 5 inorganics Include](https://reader030.vdocuments.us/reader030/viewer/2022033121/5e9b6ada999e9811e96c7d63/html5/thumbnails/30.jpg)
IAQP Use Cases
30
Conditions OutcomeOutdoor air is non-attainment for NAAQS or polluted Reduces burden of ambient sources of particulate
and gaseous pollutantsReduces frequency of PM filter replacement
Buildings with existing capacity limitations (aging of HVAC equipment, re-purpose of the space, adding more people)
Enables compliance with the code using existing equipment with adding additional HVAC capacity
Identified COC concentrations are high, requiring additional ventilation
Enables better indoor air quality
New buildings with limited HVAC capacity (e.g., geothermal projects)
Engineers or owners gain from the economic advantages of the IAQP
Building is located in cold or hot/humid climates Allows reduction in kWh and operating peak demand
LEED buildings Allows earning LEED points related to energy, indoor air quality, and innovation.