Page 1: ASHRAE 2006 - BVNHS

James E. Megerson, PEVice PresidentASHRAE Member

Blue Valley NorthHigh SchoolOverland Park, Kansas

ASHRAE Technical Energy and Governmental Affairs

2005 Honorable Mention – Existing Institutional

Page 2: ASHRAE 2006 - BVNHS

Displacement Ventilation

Page 3: ASHRAE 2006 - BVNHS

Original school Built in 1986

270,000 sq. ft.

Student enrollment

1605 in 2004-2005 school year

Displacement Ventilation

Page 4: ASHRAE 2006 - BVNHS

Displacement Ventilation

Page 5: ASHRAE 2006 - BVNHS

1986 Design 14 - DX VAV Rooftop units w/ hot water heat

- 7 Constant Volume

- 7 Variable Air Volume

- Discharge air Damper

Single duct VAV air distribution

97 Fan-Powered Series – VAV Boxes w/ HW reheat

Displacement Ventilation

Pneumatic controls – Later revised to Legacy DDC

Water Tube Boilers (Oversized heat exchangers)

Reverse return HW distribution

Constant Volume pumping

Ventilation design for 5 CFM / student

T12 lights with magnetic ballast

Page 6: ASHRAE 2006 - BVNHS

Problems IAQ Complaints from Students and Teachers

Multiple studies by EPA & Industrial Hygienist

CO2 levels in excess of 3000ppm common

20% of VAV boxes not operating

All VAV boxes programmed for intermittent occupancy

Displacement Ventilation

Page 7: ASHRAE 2006 - BVNHS

Concerns Bring Building to current ASHRAE 62 standards

Requires adding 26,000 cfm OA– double original design

Reduce or minimize impact on energy usage

Add 95 tons of cooling to building for increased OA

Humidity in space from decreased sensible load

Displacement Ventilation

Page 8: ASHRAE 2006 - BVNHS

Solutions Devise a plan to solve all

the problems

Balance the energy increase by upgrading lighting

Displacement Ventilation Air Distribution

Provide heat in RTU

Additional heating at space

Displacement Ventilation

Page 9: ASHRAE 2006 - BVNHS

Displacement Ventilation

Displacement Ventilation

Page 10: ASHRAE 2006 - BVNHS

Displacement Ventilation

Page 11: ASHRAE 2006 - BVNHS

Displacement Ventilation

Page 12: ASHRAE 2006 - BVNHS

Making 65 Degree Air

Displacement Ventilation

Page 13: ASHRAE 2006 - BVNHS

26904483Occupants

5121024Electric Equipment

934215509Total Space Sensible Load:

4501349Roof Transmission

18023153Lighting

4201120Wall Transmission

DisplacementConventional

3911302Window Transmission

30783078Window Solar

Space Sensible Load (Qs)Space Loads

0.9

718

55

75

CFM/SF=

Supply CFM=Qs/(1.08*(75-55))=

Supply Air Temperature (ºF)=

Space Temperature Setpoint (ºF)=

0.9

721

63

75

Typical Classroom Load Profile

Displacement Ventilation

Page 14: ASHRAE 2006 - BVNHS

Annual Weather Data(US Air Force Weather Manual - 9:00a.m. to 5:00p.m.)

CITY 55F & Below 55-65F

7 days Mon-Fri 7 days Mon-Fri

Albany, NY 1470 1050 413 295

NYC – Islip 1797 1283 490 350

Chicago, Ill 1414 1010 384 416

Albuquerque 1001 715 442 315

Phoenix 204 145 452 322

San Francisco 1170 835 1335 953

Kansas City 1198 855 428 305

Denver 1280 914 716 511

Seattle 1321 943 800 571

Displacement Ventilation

Page 15: ASHRAE 2006 - BVNHS

IAQ Typical Example

Displacement Ventilation

Page 16: ASHRAE 2006 - BVNHS

IAQ Typical Example

Displacement Ventilation

Page 17: ASHRAE 2006 - BVNHS

16% Gas Consumption

9% Electrical Consumption

Utility Savings

Displacement Ventilation

Page 18: ASHRAE 2006 - BVNHS

Two phases

2002 summer

2004 summer

Phase I - $2,285,000

Phase II - $1,115,000

Cost of Upgrade

Displacement Ventilation

Page 19: ASHRAE 2006 - BVNHS

Typical Airflow

0.9 cfm / sq. ft.

1.1 – 1.2 cfm / sq. ft.

Sheet metal

.46 lbs - .61lbs/ sq. ft.

.8 - .9 lbs / sq. ft.

Interesting Data

Displacement Ventilation

Page 20: ASHRAE 2006 - BVNHS

Other Sustainable Features Pulse Combustion Boilers

Boiler Management System Lonworks BAS

Web Enabled GUI

Variable Speed Pumping CO2 Monitoring Ventilation air monitoring

Indirect Lighting with T8 fixtures

Occupancy sensor lighting control

Displacement Ventilation