SS-GARUF www.goodmanmfg.com 1/18 Supersedes 7/17 Contents Nomenclature ....................................... 2 Product Specificaons .......................... 3 Heater Kit Nomenclature ...................... 3 Dimensions ........................................... 4 Airflow Data .......................................... 5 Heat Kit Data ......................................... 6 Wiring Diagrams ................................. 13 Accessories ......................................... 15 * Complete warranty details available from your local dealer or at www.goodmanmfg.com. To receive the 10-Year Parts Limited Warranty, online registraon must be completed within 60 days of installaon. Online registraon is not required in California or Québec. Multi-Position, Multi-speed Air Handler with PSC Motor 1½ to 5 Tons Product Features Check flowrator for cooling and heat pump applicaons Direct drive, mul-speed PSC blower motor All-aluminum evaporator coil Coil mounng track for quick reposioning Cabinet air leakage less than 2.0% at 1.0 inch H₂O when tested in accordance with ASHRAE standard 193 Cabinet air leakage less than 1.4% at 0.5 inch H₂O when tested in accordance with ASHRAE standard 193 AHRI cerfied; ETL listed Rigid SmartFrame cabinet Horizontal or vercal configuraon capabilies 21" depth for easier ac access DecaBDE-free thermoplasc drain pan with secondary drain connecons Screw-less sides and back helps to reduce condensaon when installed in humid locaons Foil-faced insulaon covers the internal casing to reduce cabinet condensaon Galvanized, leather grain-embossed finish Glue-less cabinet insulaon retenon Tool-less filter access Field Installed 3 kW – 25 kW electric heater kits available ARUF Series

Upload: others

Post on 04-Feb-2021

6 views

Category:

Documents


0 download

TRANSCRIPT

  • SS-GARUF www.goodmanmfg.com 1/18Supersedes 7/17

    ContentsNomenclature ....................................... 2Product Specifications .......................... 3Heater Kit Nomenclature ...................... 3Dimensions ........................................... 4Airflow Data .......................................... 5Heat Kit Data ......................................... 6Wiring Diagrams ................................. 13Accessories ......................................... 15

    * Complete warranty details available from your local dealer or at www.goodmanmfg.com. To receive the 10-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Québec.

    Multi-Position, Multi-speed Air Handler

    with PSC Motor 1½ to 5 Tons

    Product Features• Check flowrator for cooling

    and heat pump applications• Direct drive, multi-speed PSC blower motor• All-aluminum evaporator coil• Coil mounting track for quick repositioning• Cabinet air leakage less than 2.0% at

    1.0 inch H₂O when tested in accordance with ASHRAE standard 193

    • Cabinet air leakage less than 1.4% at 0.5 inch H₂O when tested in accordance with ASHRAE standard 193

    • AHRI certified; ETL listed

    • Rigid SmartFrame™ cabinet• Horizontal or vertical

    configuration capabilities• 21" depth for easier attic access• DecaBDE-free thermoplastic drain

    pan with secondary drain connections• Screw-less sides and back helps to reduce

    condensation when installed in humid locations• Foil-faced insulation covers the internal

    casing to reduce cabinet condensation• Galvanized, leather grain-embossed finish• Glue-less cabinet insulation retention • Tool-less filter access• Field Installed 3 kW – 25 kW electric heater

    kits available

    ARUF Series

  • 2 www.goodmanmfg.com SS-GARUF

    Nomenclature

    B 1   7 8

    Brand Engineering  *A Single-‐piece Major/  Minor  Revisions

    Air  Handler *    Not  used  for  inventory  management

    Unit  Application Refrigerant  ChargeC Ceiling  Mount  PSC  Motor 4  =  R-‐410AD Downflow  PSC  MotorE Multi-‐Position  Variable-‐Speed  Motor ElectricalR Multi-‐Position  PSC  Motor 1      208/240  V,  1  Phase,  60  HzS Multi-‐Position  EEM  MotorW Wall  Mount  PSC  Motor Cabinet  Width

    B    17½"Cabinet  Finish C    21"U Unpainted D      24½"P PaintedN Uncased Nominal  Capacity  Range  @  13  SEER

    18      1½  Tons   42      3½  TonsExpansion  Device 24      2  Tons   48      4  TonsF Flowrater 30      2½  Tons 60      5  TonsT Expansion  Valve 36      3  Tons  

    AA11,12

    U3

    F4 10

    4R2 5,6

    181A

    HKS X 03 X A AA

    1 2 3 4 5 6,7

    Unit  Type RevisionsHKS Heat  Kit  for   Engineering  Revisions

    Air  HandlersPhase

    Circuit  Breaker E      Three  Phase  240  VX No  circuit  breaker F      Three  Phase  208/240  VC Circuit  Breaker G      Three  Phase  460  V

    A      Single  Phase  208  VB      Single  Phase  240  VC      Single  Phase  208/240  V D      Three  Phase  208  VH Special case 208 V *Heating  Capacity  @  240  Volts

    03 3.0  kW 15 14.4  kW Cabinet  Size  (MAX)05 4.5  kW 19 19.2  kW  wth  150F  limit C      C  Cabinet06 6.0  kW 20 19.2  kW  with  170F  limit D      D  Cabinet08 8.0  kW 25 25.0  kW X      All  Cabinet  Sizes10 9.6  kW

    *Refer S&R Plate

  • SS-GARUF www.goodmanmfg.com 3

    ARUF25B14*

    ARUF29B14*

    ARUF31B14*

    ARUF37C14*

    ARUF43C14*

    ARUF49C14*

    ARUF37D14*

    ARUF43D14*

    ARUF47D14*

    ARUF49D14*

    ARUF61D14*

    Nominal Ratings

    Cooling (Btu/h) 24,000 25,000 30,000 36,000 42,000 48,000 36,000 42,000 43,000 48,000 60,000

    Piston Size 0.051 0.057 0.065 0.072 0.076 0.080 0.072 0.076 0.076 0.080 0.080

    Blower

    Diameter 9½" 9½" 9½" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝" 1115/16"

    Width 6" 6" 6" 8" 8" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝"

    Coil Connections

    Liquid ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"

    Suction ¾" ¾" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞"

    Coil Drain Connect (FPT) ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾"

    Electrical Data

    Voltage 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230

    Min Circuit Ampacity 2.2/2.2 2.2/2.2 2.2/2.2 4/4 4/4 4/4 4/4 4/4 4/4 4/4 6/6

    Max. Overcurrent Device (Amps) 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15

    Minimum VAC 197 197 197 197 197 197 197 197 197 197 197

    Maximum VAC 253 253 253 253 253 253 253 253 253 253 253

    Blower Motor

    Full Load Amps (FLA) 1.75 1.75 1.75 3.0 3.0 3.1 3.0 3.5 3.5 3.5 4.6

    Horsepower (HP) ⅓ ⅓ ⅓ ⅓ ⅓ ½ ⅓ ½ ½ ½ ¾

    Ship Weight (Lbs.) 100 100 110 130 130 135 140 145 150 145 155

    Note: For a properly matched system and piston sizing information, refer to Amana piston kit chart of the corresponding Amana® outdoor unit. Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental heat installed. Refer to unit nameplate and/or Heat Kit Data for specification with approved accessory heaters installed.

    Product Specifications

  • 4 www.goodmanmfg.com SS-GARUF

    Dimensions

    G

    H

    E D

    1 3/4" (4.45 cm)

    2 11/16" (6.83 cm)

    C

    B 5/8" (1.59 cm) 5/8" (1.59 cm)

    A

    1/2" (1.27 cm)

    11 5/16" (28.73 cm)

    " (55.88 cm)21

    9 1/4" (23.50 cm)

    1 3/8" (3.49 cm) 3 1/8" (7.94 cm)

    5 1/8" (13.02 cm)

    7 1/2" (19.05 cm)

    1 3/4" (4.45 cm)

    7 3/16" (18.26 cm)

    K

    J 2 1/8" (5.40 cm)

    4 5/16" (4.31 cm)

    6 1/8" (15.56 cm)

    1 13/16" (4.60 cm) FINLET

    (FRONT VIEW)

    1 13/16" (4.60 cm)" (2.54 cm)1 9/16 (1.43 cm) 19.5" (49.53 cm)

    INLET(RIGHT SIDE VIEW)

    10 3/16" (25.88 cm)

    1 5/8" (4.13 cm)

    1 5/16" (3.33 cm)

    4 1/2" (11.43 cm)

    1 5/8" (4.13 cm) 3 3/4" (9.53 cm)

    2 15/16" (7.46 cm)

    3 1/16" (7.78 cm)

    SEE HORIZONTAL DRAIN PORT DETAIL

    SEE VERTICAL DRAIN PORT DETAIL

    SUCTION TUBE LIQUID LINEINLET TUBE

    HORIZONTAL DRAIN PORT DETAIL

    VERTICAL DRAIN PORT DETAIL

    Model A" B" C" D" E" F" G" H"

    ARUF25B14* 45 16⅜ 17½ 15¼ 12 14⅛ 9⅛ 11⅞

    ARUF29B14* 45 16⅜ 17½ 15¼ 12 14⅛ 9⅛ 12¾

    ARUF31B14* 537/16 16⅜ 17½ 2311/16 20½ 14⅛ 9⅛ 7⅝

    ARUF37C14* 537/16 19⅞ 21 2113/16 18⅝ 1711/16 1013/16 613/16

    ARUF43C14* 537/16 19⅞ 21 2113/16 18⅝ 1711/16 1013/16 613/16

    ARUF49C14* 537/16 19⅞ 21 2113/16 18⅝ 1711/16 1013/16 613/16

    ARUF37D14* 537/16 235/16 24½ 21½ 185/16 213/16 12⅝ 6⅞

    ARUF43D14* 537/16 235/16 24½ 21½ 185/16 213/16 12⅝ 6⅞

    ARUF47D14* 58 235/16 24½ 26⅛ 22⅞ 213/16 12⅝ 252/16

    ARUF49D14* 537/16 235/16 24½ 21½ 185/16 213/16 12⅝ 6⅞

    ARUF61D14* 58 235/16 24½ 26⅛ 22⅞ 213/16 12⅝ 252/16

  • SS-GARUF www.goodmanmfg.com 5

    Model MotorSpeed

    Static Pressure (in w.c) Airflow (CFM)

    0.1 0.2 0.3 0.4 0.5 0.6 0.7

    ARUF25B14

    Low 650 620 595 540 490 420 275

    Med 885 865 825 815 750 690 560

    High 1255 1225 1130 1090 965 925 800

    ARUF29B14

    Low 650 620 595 540 490 420 275

    Med 885 865 825 815 750 690 560

    High 1255 1225 1130 1090 965 925 800

    ARUF31B14

    Low 660 625 595 560 500 430 330

    Med 930 905 865 820 765 700 590

    High 1235 1185 1130 1060 990 910 825

    ARUF37C14

    Low 1120 1085 1040 1000 940 875 800

    Med 1425 1385 1345 1285 1220 1145 1060

    High 1625 1575 1520 1460 1375 1295 1200

    ARUF43C14

    Low 1120 1085 1040 1000 940 875 800

    Med 1425 1385 1345 1285 1220 1145 1060

    High 1625 1575 1520 1460 1375 1295 1200

    ARUF49C14

    Low 1295 1255 1225 1175 1120 1055 970

    Med 1535 1485 1420 1370 1295 1215 1130

    High 1755 1680 1590 1515 1425 1340 1250

    ARUF37D14

    Low 1155 1115 1070 1015 955 895 840

    Med 1505 1470 1430 1375 1300 1210 1105

    High 1785 1735 1680 1625 1555 1440 1330

    ARUF43D14

    Low 1410 1360 1290 1210 1120 1010 920

    Med 1610 1540 1470 1390 1300 1190 1060

    High 1900 1830 1740 1645 1540 1420 1280

    ARUF47D14

    Low 1420 1370 1310 1240 1125 1045 960

    Med 1625 1585 1515 1435 1350 1235 1095

    High 1930 1890 1820 1735 1635 1505 1355

    ARUF49D14

    Low 1410 1360 1290 1210 1120 1010 920

    Med 1610 1540 1470 1390 1300 1190 1060

    High 1900 1830 1740 1645 1540 1420 1280

    ARUF61D14

    Low 1530 1500 1460 1405 1350 1280 1155

    Med 1950 1885 1830 1785 1745 1670 1595

    High 2235 2170 2100 2030 1965 1915 1825

    Notes• Airflow data indicated is at 230V without air filter in place. • The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate.

    The shaded area indicates ranges in excess of maximum design external static pressure.• Use the CFM adjustment factors of 0.98 for horizontal left and 0.96 for horizontal right & downflow orientations

    Airflow Data

  • 6 www.goodmanmfg.com SS-GARUF

    Heat Kit Data

    See notes on page 12.

    Heater Kit ModelCircuit 1 Circuit 2 Single-Point Kit

    Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP²

    ARUF25B14AC 0/0 2.2/2.2 15/15 --- --- --- --- ---

    HKSX03XC - 208 V

    No Breaker

    10.8 16 20 --- --- --- --- ---

    HKSX05XC - 208 V 17.3 24 25 --- --- --- --- ---

    HKSX06XC - 208 V 21.7 29 30 --- --- --- --- ---

    HKSX08XC - 208 V 28.9 38 40 --- --- --- --- ---

    HKSX10XC - 208 V 34.7 46 50 --- --- --- --- ---

    HKSC05XC - 208 V

    Breaker

    17.3 24 25 --- --- --- --- ---

    HKSC08XC - 208 V 28.9 38 40 --- --- --- --- ---

    HKSC10XC - 208 V 34.7 46 50 --- --- --- --- ---

    HKSX03XC - 240 V

    No Breaker

    12.5 18 20 --- --- --- --- ---

    HKSX05XC - 240 V 20 27 30 --- --- --- --- ---

    HKSX06XC - 240 V 25 33 35 --- --- --- --- ---

    HKSX08XC - 240 V 33.3 44 45 --- --- --- --- ---

    HKSX10XC - 240 V 40.0 52 60 --- --- --- --- ---

    HKSC05XC - 240 V

    Breaker

    20 27 30 --- --- --- --- ---

    HKSC08XC - 240 V 33.3 44 45 --- --- --- --- ---

    HKSC10XC - 240 V 40.0 52 60 --- --- --- --- ---

    ARUF29B14AC 0/0 2.2/2.2 15/15 --- --- --- --- ---

    HKSX03XC - 208 V

    No Breaker

    10.8 16 20 --- --- --- --- ---

    HKSX05XC - 208 V 17.3 24 25 --- --- --- --- ---

    HKSX06XC - 208 V 21.7 29 30 --- --- --- --- ---

    HKSX08XC - 208 V 28.9 38 40 --- --- --- --- ---

    HKSX10XC - 208 V 34.7 46 50 --- --- --- --- ---

    HKSC05XC - 208 V

    Breaker

    17.3 24 25 --- --- --- --- ---

    HKSC08XC - 208 V 28.9 38 40 --- --- --- --- ---

    HKSC10XC - 208 V 34.7 46 50 --- --- --- --- ---

    HKSX03XC - 240 V

    No Breaker

    12.5 18 20 --- --- --- --- ---

    HKSX05XC - 240 V 20 27 30 --- --- --- --- ---

    HKSX06XC - 240 V 25 33 35 --- --- --- --- ---

    HKSX08XC - 240 V 33.3 44 45 --- --- --- --- ---

    HKSX10XC - 240 V 40.0 52 60 --- --- --- --- ---

    HKSC05XC - 240 V

    Breaker

    20 27 30 --- --- --- --- ---

    HKSC08XC - 240 V 33.3 44 45 --- --- --- --- ---

    HKSC10XC - 240 V 40.0 52 60 --- --- --- --- ---

    ARUF31B14AC 0/0 2.2/2.2 15/15 --- --- --- --- ---

    HKSX03XC - 208 V

    No Breaker

    10.8 16 20 --- --- --- --- ---

    HKSX05XC - 208 V 17.3 24 25 --- --- --- --- ---

    HKSX06XC - 208 V 21.7 29 30 --- --- --- --- ---

    HKSX08XC - 208 V 28.9 38 40 --- --- --- --- ---

    HKSX10XC - 208 V 34.7 46 50 --- --- --- --- ---

    HKSC05XC - 208 V

    Breaker

    17.3 24 25 --- --- --- --- ---

    HKSC08XC - 208 V 28.9 38 40 --- --- --- --- ---

    HKSC10XC - 208 V 34.7 46 50 --- --- --- --- ---

    HKSC15XA - 208 V 34.7 46 50 17.3 22 25 67 70

  • SS-GARUF www.goodmanmfg.com 7

    Heat Kit Data (cont.)

    See notes on page 12.

    Heater Kit ModelCircuit 1 Circuit 2 Single-Point Kit

    Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP²

    HKSX03XC - 240 V

    No Breaker

    12.5 18 20 --- --- --- --- ---

    HKSX05XC - 240 V 20 27 30 --- --- --- --- ---

    HKSX06XC - 240 V 25 33 35 --- --- --- --- ---

    HKSX08XC - 240 V 33.3 44 45 --- --- --- --- ---

    HKSX10XC - 240 V 40.0 52 60 --- --- --- --- ---

    HKSC05XC - 240 V

    Breaker

    20 27 30 --- --- --- --- ---

    HKSC08XC - 240 V 33.3 44 45 --- --- --- --- ---

    HKSC10XC - 240 V 40.0 52 60 --- --- --- --- ---

    HKSC15XB - 240 V 40.0 52 60 20 25 25 77 80

    ARUF37C14AC 0/0 4/4 15/15 --- --- --- --- ---

    HKSX03XC - 208 V

    No Breaker

    10.8 17 20 --- --- --- --- ---

    HKSX05XC - 208 V 17.3 25 30 --- --- --- --- ---

    HKSX06XC - 208 V 21.7 31 35 --- --- --- --- ---

    HKSX08XC - 208 V 28.9 40 40 --- --- --- --- ---

    HKSX10XC - 208 V 34.7 47 50 --- --- --- --- ---

    HKSC05XC - 208 V

    Breaker

    17.3 25 30 --- --- --- --- ---

    HKSC08XC - 208 V 28.9 40 40 --- --- --- --- ---

    HKSC10XC - 208 V 34.7 47 50 --- --- --- --- ---

    HKSC15XA - 208 V 34.7 47 50 17.3 22 25 69 70

    HKSC19CA - 208 V 34.7 47 50 34.7 43 45 90 100

    HKSC15XF - 208 V ^ 0 4 15 30 38 40 --- ---

    HKSC20XF - 208 V ^ 0 4 15 38 47 50 --- ---

    HKSX03XC - 240 V

    No Breaker

    12.5 19 20 --- --- --- --- ---

    HKSX05XC - 240 V 20 29 30 --- --- --- --- ---

    HKSX06XC - 240 V 25 35 35 --- --- --- --- ---

    HKSX08XC - 240 V 33.3 45 50 --- --- --- --- ---

    HKSX10XC - 240 V 40 54 60 --- --- --- --- ---

    HKSC05XC - 240 V

    Breaker

    20 29 30 --- --- --- --- ---

    HKSC08XC - 240 V 33.3 45 50 --- --- --- --- ---

    HKSC10XC - 240 V 40 54 60 --- --- --- --- ---

    HKSC15XB - 240 V 40 54 60 20 25 25 79 80

    HKSC19CB - 240 V 40 54 60 40 50 50 104 110

    HKSC15XF - 240 V ^ 0 4 15 34.6 43 45 --- ---

    HKSC20XF - 240 V ^ 0 4 15 43 54 60 --- ---

    ARUF37D14AC 0/0 4/4 15/15 --- --- --- --- ---

    HKSX03XC - 208 V

    No Breaker

    10.8 17 20 --- --- --- --- ---

    HKSX05XC - 208 V 17.3 26 30 --- --- --- --- ---

    HKSX06XC - 208 V 21.7 31 35 --- --- --- --- ---

    HKSX08XC - 208 V 28.9 40 40 --- --- --- --- ---

    HKSX10XC - 208 V 34.7 47 50 --- --- --- --- ---

  • 8 www.goodmanmfg.com SS-GARUF

    Heat Kit Data (cont.)

    See notes on page 12.

    Heater Kit ModelCircuit 1 Circuit 2 Single-Point Kit

    Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP²

    HKSC05XC - 208 V

    Breaker

    17.3 26 30 --- --- --- --- ---

    HKSC08XC - 208 V 28.9 40 40 --- --- --- --- ---

    HKSC10XC - 208 V 34.7 47 50 --- --- --- --- ---

    HKSC15XA - 208 V 34.7 47 50 17.3 22 25 69 70

    HKSC20DA - 208 V 34.7 47 50 34.7 43 45 91 100

    HKSC15XF - 208 V ^ 0 4 15 30 38 40 --- ---

    HKSC20XF - 208 V ^ 0 4 15 38 47 50 --- ---

    HKSX03XC - 240 V

    No Breaker

    12.5 19 20 --- --- --- --- ---

    HKSX05XC - 240 V 20 29 30 --- --- --- --- ---

    HKSX06XC - 240 V 25 35 35 --- --- --- --- ---

    HKSX08XC - 240 V 33.3 45.4 50 --- --- --- --- ---

    HKSX10XC - 240 V 40 54 60 --- --- --- --- ---

    HKSC05XC - 240 V

    Breaker

    20 29 30 --- --- --- --- ---

    HKSC08XC - 240 V 33.3 45.4 50 --- --- --- --- ---

    HKSC10XC - 240 V 40 54 60 --- --- --- --- ---

    HKSC15XB - 240 V 40 54 60 20 25 25 79 80

    HKSC20DB - 240 V 40 54 60 40 50 50 104 110

    HKSC15XF - 240 V ^ 0 4 15 34.6 43 45 --- ---

    HKSC20XF - 240 V ^ 0 4 15 43 54 60 --- ---

    ARUF43C14AC 0/0 4/4 15/15 --- --- --- --- ---

    HKSX03XC - 208 V

    No Breaker

    10.8 17 20 --- --- --- --- ---

    HKSX05XC - 208 V 17.3 25 30 --- --- --- --- ---

    HKSX06XC - 208 V 21.7 31 35 --- --- --- --- ---

    HKSX08XC - 208 V 28.9 40 40 --- --- --- --- ---

    HKSX10XC - 208 V 34.7 47 50 --- --- --- --- ---

    HKSC05XC - 208 V

    Breaker

    17.3 25 30 --- --- --- --- ---

    HKSC08XC - 208 V 28.9 40 40 --- --- --- --- ---

    HKSC10XC - 208 V 34.7 47 50 --- --- --- --- ---

    HKSC15XA - 208 V 34.7 47 50 17.3 22 25 69 70

    HKSC19CA - 208 V 34.7 47 50 34.7 43 45 90 100

    HKSC15XF - 208 V ^ 0 4 15 30 38 40 --- ---

    HKSC20XF - 208 V ^ 0 4 15 38 47 50 --- ---

    HKSX03XC - 240 V

    No Breaker

    12.5 19 20 --- --- --- --- ---

    HKSX05XC - 240 V 20 29 30 --- --- --- --- ---

    HKSX06XC - 240 V 25 35 35 --- --- --- --- ---

    HKSX08XC - 240 V 33.3 45 50 --- --- --- --- ---

    HKSX10XC - 240 V 40 54 60 --- --- --- --- ---

  • SS-GARUF www.goodmanmfg.com 9

    Heat Kit Data (cont.)

    See notes on page 12.

    Heater Kit ModelCircuit 1 Circuit 2 Single-Point Kit

    Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP²

    HKSC05XC - 240 V

    Breaker

    20 29 30 --- --- --- --- ---

    HKSC08XC - 240 V 33.3 45 50 --- --- --- --- ---

    HKSC10XC - 240 V 40 54 60 --- --- --- --- ---

    HKSC15XB - 240 V 40 54 60 20 25 25 79 80

    HKSC19CB - 240 V 40 54 60 40 50 50 104 110

    HKSC15XF - 240 V ^ 0 4 15 34.6 43 45 --- ---

    HKSC20XF - 240 V ^ 0 4 15 43 54 60 --- ---

    ARUF43D14AC 0/0 4/4 15/15 --- --- --- --- ---

    HKSX03XC - 208 V

    No Breaker

    10.8 18 20 --- --- --- --- ---

    HKSX05XC - 208 V 17.3 26 30 --- --- --- --- ---

    HKSX06XC - 208 V 21.7 31 35 --- --- --- --- ---

    HKSX08XC - 208 V 28.9 40.5 45 --- --- --- --- ---

    HKSX10XC - 208 V 34.7 48 50 --- --- --- --- ---

    HKSC05XC - 208 V

    Breaker

    17.3 26 30 --- --- --- --- ---

    HKSC08XC - 208 V 28.9 40.5 45 --- --- --- --- ---

    HKSC10XC - 208 V 34.7 48 50 --- --- --- --- ---

    HKSC15XA - 208 V 34.7 48 50 17.3 22 25 69 70

    HKSC20DA - 208 V 34.7 48 50 34.7 43 45 91 100

    HKSC15XF - 208 V ^ 0 4 15 30 38 40 --- ---

    HKSC20XF - 208 V ^ 0 4 15 38 47 50 --- ---

    HKSX03XC - 240 V

    No Breaker

    12.5 20 20 --- --- --- --- ---

    HKSX05XC - 240 V 20 29 30 --- --- --- --- ---

    HKSX06XC - 240 V 25 36 40 --- --- --- --- ---

    HKSX08XC - 240 V 33.3 46 50 --- --- --- --- ---

    HKSX10XC - 240 V 40 54 60 --- --- --- --- ---

    HKSC05XC - 240 V

    Breaker

    20 29 30 --- --- --- --- ---

    HKSC08XC - 240 V 33.3 46 50 --- --- --- --- ---

    HKSC10XC - 240 V 40 54 60 --- --- --- --- ---

    HKSC15XB - 240 V 40 54 60 20 25 25 79 80

    HKSC20DB - 240 V 40 54 60 40 50 50 104 110

    HKSC15XF - 240 V ^ 0 4 15 34.6 43 45 --- ---

    HKSC20XF - 240 V ^ 0 4 15 43 54 60 --- ---

    ARUF47D14AC 0/0 4/4 15/15 --- --- --- --- ---

    HKSX03XC - 208 V

    No Breaker

    10.8 18 20 --- --- --- --- ---

    HKSX05XC - 208 V 17.3 26 30 --- --- --- --- ---

    HKSX06XC - 208 V 21.7 31 35 --- --- --- --- ---

    HKSX08XC - 208 V 28.9 40.5 45 --- --- --- --- ---

    HKSX10XC - 208 V 34.7 48 50 --- --- --- --- ---

  • 10 www.goodmanmfg.com SS-GARUF

    Heat Kit Data (cont.)

    See notes on page 12.

    Heater Kit ModelCircuit 1 Circuit 2 Single-Point Kit

    Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP²

    HKSC05XC - 208 V

    Breaker

    17.3 26 30 --- --- --- --- ---

    HKSC08XC - 208 V 28.9 40.5 45 --- --- --- --- ---

    HKSC10XC - 208 V 34.7 48 50 --- --- --- --- ---

    HKSC15XA - 208 V 34.7 48 50 17.3 22 25 69 70

    HKSC20DA - 208 V 34.7 48 50 34.7 44 45 91 100

    HKSC15XF - 208 V ^ 0 4 15 30 38 40 --- ---

    HKSC20XF - 208 V ^ 0 4 15 38 47 50 --- ---

    HKSX03XC - 240 V

    No Breaker

    12.5 20 20 --- --- --- --- ---

    HKSX05XC - 240 V 20 29 30 --- --- --- --- ---

    HKSX06XC - 240 V 25 36 40 --- --- --- --- ---

    HKSX08XC - 240 V 33.3 46 50 --- --- --- --- ---

    HKSX10XC - 240 V 40 54 60 --- --- --- --- ---

    HKSC05XC - 240 V

    Breaker

    20 29 30 --- --- --- --- ---

    HKSC08XC - 240 V 33.3 46 50 --- --- --- --- ---

    HKSC10XC - 240 V 40 54 60 --- --- --- --- ---

    HKSC15XB - 240 V 40 54 60 20 25 25 79 80

    HKSC20DB - 240 V 40 54 60 40 50 50 104 110

    HKSC15XF - 240 V ^ 0 4 15 34.6 43 45 --- ---

    HKSC20XF - 240 V ^ 0 4 15 43 54 60 --- ---

    ARUF49C14AC 0/0 4/4 15/15 --- --- --- --- ---

    HKSX03XC - 208 V

    No Breaker

    10.8 17 20 --- --- --- --- ---

    HKSX05XC - 208 V 17.3 26 30 --- --- --- --- ---

    HKSX06XC - 208 V 21.7 31 35 --- --- --- --- ---

    HKSX08XC - 208 V 28.9 40 40 --- --- --- --- ---

    HKSX10XC - 208 V 34.7 47 50 --- --- --- --- ---

    HKSC05XC - 208 V

    Breaker

    17.3 26 30 --- --- --- --- ---

    HKSC08XC - 208 V 28.9 40 40 --- --- --- --- ---

    HKSC10XC - 208 V 34.7 47 50 --- --- --- --- ---

    HKSC15XA - 208 V 34.7 47 50 17.3 22 25 69 70

    HKSC19CA - 208 V 34.7 47 50 34.7 43 45 91 100

    HKSC15XF - 208 V ^ 0 4 15 30 38 40 --- ---

    HKSC20XF - 208 V ^ 0 4 15 38 47 50 --- ---

    HKSX03XC - 240 V

    No Breaker

    12.5 20 20 --- --- --- --- ---

    HKSX05XC - 240 V 20 29 30 --- --- --- --- ---

    HKSX06XC - 240 V 25 35 40 --- --- --- --- ---

    HKSX08XC - 240 V 33.3 46 50 --- --- --- --- ---

    HKSX10XC - 240 V 40 54 60 --- --- --- --- ---

    HKSC05XC - 240 V

    Breaker

    20 29 30 --- --- --- --- ---

    HKSC08XC - 240 V 33.3 46 50 --- --- --- --- ---

    HKSC10XC - 240 V 40 54 60 --- --- --- --- ---

    HKSC15XB - 240 V 40 54 60 20 25 25 79 80

    HKSC19CB - 240 V 40 54 60 40 50 50 104 110

    HKSC15XF - 240 V ^ 0 4 15 34.6 43 45 --- ---

    HKSC20XF - 240 V ^ 0 4 15 43 54 60 --- ---

  • SS-GARUF www.goodmanmfg.com 11

    Heat Kit Data (cont.)

    See notes on page 12.

    Heater Kit ModelCircuit 1 Circuit 2 Single-Point Kit

    Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP²

    ARUF49D14AC 0/0 4/4 15/15 --- --- --- --- ---

    HKSX03XC - 208 V

    No Breaker

    10.8 18 20 --- --- --- --- ---

    HKSX05XC - 208 V 17.3 26 30 --- --- --- --- ---

    HKSX06XC - 208 V 21.7 31 35 --- --- --- --- ---

    HKSX08XC - 208 V 28.9 40.5 45 --- --- --- --- ---

    HKSX10XC - 208 V 34.7 48 50 --- --- --- --- ---

    HKSC05XC - 208 V

    Breaker

    17.3 26 30 --- --- --- --- ---

    HKSC08XC - 208 V 28.9 40.5 45 --- --- --- --- ---

    HKSC10XC - 208 V 34.7 48 50 --- --- --- --- ---

    HKSC15XA - 208 V 34.7 48 50 17.3 22 25 69 70

    HKSC20DA - 208 V 34.7 48 50 34.7 43 45 91 100

    HKSC15XF - 208 V ^ 0 4 15 30 38 40 --- ---

    HKSC20XF - 208 V ^ 0 4 15 38 47 50 --- ---

    HKSX03XC - 240 V

    No Breaker

    12.5 20 20 --- --- --- --- ---

    HKSX05XC - 240 V 20 29 30 --- --- --- --- ---

    HKSX06XC - 240 V 25 36 40 --- --- --- --- ---

    HKSX08XC - 240 V 33.3 46 50 --- --- --- --- ---

    HKSX10XC - 240 V 40 54 60 --- --- --- --- ---

    HKSC05XC - 240 V

    Breaker

    20 29 30 --- --- --- --- ---

    HKSC08XC - 240 V 33.3 46 50 --- --- --- --- ---

    HKSC10XC - 240 V 40 54 60 --- --- --- --- ---

    HKSC15XB - 240 V 40 54 60 20 25 25 79 80

    HKSC20DB - 240 V 40 54 60 40 50 50 104 110

    HKSC15XF - 240 V ^ 0 4 15 34.6 43 45 --- ---

    HKSC20XF - 240 V ^ 0 4 15 43 54 60 --- ---

    ARUF61D14AC 0/0 6/6 15/15 --- --- --- --- ---

    HKSX03XC - 208 V

    No Breaker

    10.8 19 20 --- --- --- --- ---

    HKSX05XC - 208 V 17.3 27 30 --- --- --- --- ---

    HKSX06XC - 208 V 21.7 33 35 --- --- --- --- ---

    HKSX08XC - 208 V 28.9 42 45 --- --- --- --- ---

    HKSX10XC - 208 V 34.7 49 50 --- --- --- --- ---

    HKSC05XC - 208 V

    Breaker

    17.3 27 30 --- --- --- --- ---

    HKSC08XC - 208 V 28.9 42 45 --- --- --- --- ---

    HKSC10XC - 208 V 34.7 49 50 --- --- --- --- ---

    HKSC15XA - 208 V 34.7 49 50 17.3 22 25 71 80

    HKSC20DA - 208 V 34.7 49 50 34.7 43 45 92 100

    HKSC15XF - 208 V ^ 0 6 15 30 38 40 --- ---

    HKSC20XF - 208 V ^ 0 6 15 38 47 50 --- ---

    HKSC25DA - 208 V 52 71 80 35 43 45 114 125

  • 12 www.goodmanmfg.com SS-GARUF

    Heat Kit Data (cont.)

    Heating kW Correction Factor

    Supply Voltage 240 230 220 210 208

    Correction Factor 1.00 0.92 0.84 0.77 0.75

    Multiply the 240-volt heating capacity by correction factors.

    Heater Kit ModelCircuit 1 Circuit 2 Single-Point Kit

    Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP²

    HKSX03XC - 240 V

    No Breaker

    12.5 21 25 --- --- --- --- ---

    HKSX05XC - 240 V 20 31 35 --- --- --- --- ---

    HKSX06XC - 240 V 25 37 40 --- --- --- --- ---

    HKSX08XC - 240 V 33.3 47 50 --- --- --- --- ---

    HKSX10XC - 240 V 40 56 60 --- --- --- --- ---

    HKSC05XC - 240 V

    Breaker

    20 31 35 --- --- --- --- ---

    HKSC08XC - 240 V 33.3 47 50 --- --- --- --- ---

    HKSC10XC - 240 V 40 56 60 --- --- --- --- ---

    HKSC15XB - 240 V 40 56 60 20 25 25 81 90

    HKSC20DB - 240 V 40 56 60 40 50 50 106 110

    HKSC15XF - 240 V ^ 0 6 15 34.6 43 45 --- ---

    HKSC20XF - 240 V ^ 0 6 15 43 54 60 --- ---

    HKSC25DB - 240 V 60 81 90 40 50 50 131 150

    ¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25 ² Maximum Overcurrent Protection = 2.25 X Motor Amps + Heater Amps --- indicates Not Required Note : The 208 or 240 in the heat kit part number field is for clarification of the nominal voltage for this model. ^ Three Phase 3 Notation is correct as XB because technically the 240V heater kit application can be used here without any issues.

  • SS-GARUF www.goodmanmfg.com 13

    USE

    CO

    PPER

    WIR

    E

    SPEE

    DUP

    CO

    PPER

    PO

    WER

    SUP

    PLY

    (SEE

    RAT

    ING

    PLA

    TE)

    EQU

    IPM

    ENT

    GR

    OUN

    D

    BLBL

    SEE

    NOTE

    3

    BK

    M1

    BRBR

    RC

    EM

    RD

    BL

    BK

    RD

    PU

    WH EB

    TDR

    SR

    BL

    G

    RD

    XFM

    R-R

    XFM

    R-C

    CR

    RD

    GR

    SEE

    NO

    TES

    2 &

    6

    BLR

    DG

    RW

    HBR

    5

    NO

    CO

    M

    NC

    K1K1

    PU

    PU

    RD

    RD

    C

    BK

    BR

    PLF

    BK1

    RD

    PU

    23

    240

    24V

    4

    12

    3

    TR

    RD

    SEE

    NO

    TE 4

    BLBR

    45

    WH6

    78

    9PL

    M

    GR

    ND

    1BK

    23

    RDL2

    L1

    45

    67

    89

    0140

    A002

    42-A

    PLM

    PLF

    TRFACT

    OR

    Y W

    IRIN

    G

    FIEL

    D W

    IRIN

    G

    NOTE

    S:

    TIM

    E DE

    LAY

    REL

    AY

    STR

    AIN

    REL

    IEF

    EVAP

    ORA

    TOR

    MO

    TOR

    ELEC

    TRO

    NIC

    BLO

    WER

    RUN

    CAP

    ACIT

    OR

    SREM

    EBTD

    R

    RCBK RD BLYL

    BLU

    E

    BLAC

    KR

    EDYE

    LLO

    W

    CO

    MPO

    N ENT

    CO

    D E

    BROW

    NPU

    RPL

    EG

    REE

    NPU BRG

    R

    FEM

    ALE

    PLUG

    CO

    NNEC

    TOR

    MAL

    E PL

    UG C

    ON

    NECT

    OR

    TRAN

    SFO

    RM

    ER

    H

    IGH

    VO

    LTAG

    E

    LOW

    VO

    LTAG

    E

    H

    IGH

    VO

    LTAG

    E

    LOW

    VO

    LTAG

    E

    PLF

    32

    CO

    LOR

    CO

    DE

    RD

    TR

    WH6

    BR5PL

    M4

    424

    V5

    SEE

    NOTE

    11

    23

    RC

    HI

    EM

    GR

    WIR

    ING

    CO

    DE

    BL

    EBTD

    R

    LOC

    OM

    NC

    M1

    EBTD

    R

    NO

    208/

    240

    VOLT

    S

    11PL

    F

    PLM

    L1

    PLM

    2L2

    (M2)

    PU RC

    (M1)

    BKBLM

    EDIU

    M

    3 SP

    EED

    BRHIG

    H

    EM

    (CO

    M)

    RD

    LOW

    IF R

    EPLA

    CEM

    ENT

    OF

    THE

    OR

    IGIN

    AL W

    IRES

    SUPP

    LIED

    WIT

    H TH

    IS A

    SSEM

    BLY

    IS N

    ECES

    SAR

    YUS

    E W

    IRE

    THAT

    CO

    NFO

    RM

    S TO

    TH

    ENA

    TIO

    NAL

    ELE

    CTR

    IC C

    ODE

    .

    M2

    PU(TR

    1)

    M2

    RG

    CEB

    TDR

    SEE

    NOTE

    1

    FLFU

    SE L

    INK

    TLTH

    ERM

    AL L

    IMIT

    SEE

    NOTE

    5

    RR

    ELAY

    TER

    MIN

    AL B

    LOC

    K SH

    OW

    NFO

    R 5

    0HZ

    MO

    DEL

    S O

    NLY

    THR

    EE S

    PEED

    MO

    TOR

    WIR

    ING

    (SEL

    ECT

    MO

    DEL

    S O

    NLY

    )SE

    E N

    OTE

    3

    WHI

    TEW

    HUS

    E M

    IN. 7

    5°C

    FIE

    LD W

    IRE

    1. R

    ED W

    IRES

    TO

    BE

    ON

    TR

    ANSF

    OR

    ME

    R T

    ERM

    INAL

    "3" F

    OR

    240

    VO

    LTS

    A

    ND

    ON

    TER

    MIN

    AL "2

    " FO

    R 2

    08 V

    OLT

    S.2.

    SEE

    CO

    MP

    OSI

    TE W

    IRIN

    G D

    IAG

    RA

    MS

    IN IN

    STAL

    LATI

    ON

    INST

    RU

    CTI

    ON

    S

    FO

    R P

    RO

    PER

    LO

    W V

    OLT

    AGE

    WIR

    ING

    CO

    NN

    ECTI

    ON

    S.3.

    CO

    NFI

    RM S

    PEED

    TAP

    SEL

    ECTE

    D IS

    APP

    RO

    PRIA

    TE F

    OR

    APP

    LIC

    ATIO

    N.

    IF

    SPE

    ED T

    AP N

    EED

    S TO

    BE

    CHA

    NG

    ED, C

    ON

    NEC

    T AP

    PRO

    PRIA

    TE

    MO

    TOR

    WIR

    E (R

    ED F

    OR

    LO

    W, B

    LUE

    FOR

    MED

    IUM

    , AN

    D B

    LACK

    FO

    R

    HIG

    H S

    PEED

    ) ON

    "CO

    M" C

    ON

    NEC

    TIO

    N O

    F TH

    E EB

    TDR

    .

    INAC

    TIVE

    MO

    TOR

    WIR

    ES M

    US

    T BE

    CO

    NN

    ECTE

    D T

    O "M

    1 O

    R M

    2"

    O

    N E

    BTD

    R.

    4. B

    RO

    WN

    AN

    D W

    HIT

    E W

    IRES

    AR

    E U

    SED

    WIT

    H H

    EAT

    KITS

    ON

    LY.

    5. E

    BTD

    R H

    AS A

    7 S

    ECO

    ND

    ON

    DEL

    AY W

    HEN

    "G" I

    S EN

    ERG

    IZED

    A

    ND

    A 6

    5 SE

    CON

    D O

    FF D

    ELAY

    WH

    EN "G

    " IS

    DE-

    ENER

    GIZ

    ED.

    6. L

    OW

    VO

    LTAG

    E FI

    ELD

    WIR

    ING

    TO

    BE

    N.E

    .C C

    LASS

    2 W

    IRES

    .

    GRN

    DG

    RO

    UND

    SEE

    NOTE

    S 2

    & 6

    Wiring Diagram – Air Handler

    Wiri

    ng is

    sub

    ject

    to c

    hang

    e. A

    lway

    s re

    fer

    to t

    he w

    iring

    dia

    gram

    on

    the

    unit

    for t

    he m

    ost u

    p-to

    -dat

    e w

    iring

    .⚠

    War

    ning

    High

    Vol

    tage

    : D

    isco

    nnec

    t al

    l po

    wer

    bef

    ore

    serv

    icin

    g or

    ins

    talli

    ng t

    his

    unit.

    Mul

    tiple

    pow

    er

    sour

    ces

    may

    be

    pres

    ent.

    Failu

    re to

    do

    so m

    ay c

    ause

    pro

    pert

    y da

    mag

    e, p

    erso

    nal i

    njur

    y, o

    r de

    ath.⚡

    ¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25 ² Maximum Overcurrent Protection = 2.25 X Motor Amps + Heater Amps --- indicates Not Required Note : The 208 or 240 in the heat kit part number field is for clarification of the nominal voltage for this model. ^ Three Phase 3 Notation is correct as XB because technically the 240V heater kit application can be used here without any issues.

  • 14 www.goodmanmfg.com SS-GARUF

    Wiri

    ng is

    sub

    ject

    to c

    hang

    e. A

    lway

    s re

    fer

    to t

    he w

    iring

    dia

    gram

    on

    the

    unit

    for t

    he m

    ost u

    p-to

    -dat

    e w

    iring

    .⚠

    War

    ning

    High

    Vol

    tage

    : D

    isco

    nnec

    t al

    l po

    wer

    bef

    ore

    serv

    icin

    g or

    ins

    talli

    ng t

    his

    unit.

    Mul

    tiple

    pow

    er

    sour

    ces

    may

    be

    pres

    ent.

    Failu

    re to

    do

    so m

    ay c

    ause

    pro

    pert

    y da

    mag

    e, p

    erso

    nal i

    njur

    y, o

    r de

    ath.⚡

    Wiring Diagram – Three-Phase Heater Kit

    RC

    BR BREM

    35

    214

    RD

    TR

    WH

    BR

    BK

    L2

    L1

    RD

    RD

    BL

    BK

    PU

    BLPU

    REL

    AY/S

    EQU

    ENC

    ER

    THER

    MAL

    LIM

    ITTR

    ANSF

    OR

    MER

    RU

    N C

    APAC

    ITO

    R

    ELEC

    . BLO

    WER

    TIM

    E D

    ELAY

    REL

    AYEV

    APO

    RA

    TOR

    MO

    TOR

    HEA

    T EL

    EMEN

    TH

    TR

    EBTD

    REM R

    S

    TL TRRCCO

    MPO

    NEN

    T C

    OD

    E

    24 V

    OLT

    TR

    RC

    EM

    EBTD

    R

    EBTD

    R

    CO

    MNO

    NC

    208/

    240

    VOLT

    S

    0140

    M00

    273-

    A

    WH

    BK

    GND L3

    T3

    CC

    L2L1

    BL

    T2T1

    R

    BL

    RD

    BR

    M3 M

    4PU

    M2

    PUW

    H

    M1

    WH

    WH

    RS

    BL

    WH

    PU

    BL

    RD

    1 2 3 5 7 8 964

    WH

    PC

    EBTD

    R

    TER

    MIN

    AL B

    LOC

    KC

    ON

    TAC

    TOR

    9-PI

    N C

    ON

    NEC

    TOR

    PCCC

    TB

    M2

    RS

    M1

    M3

    M4

    L1L2

    LOW

    HIG

    H

    CC

    HEA

    TER

    CO

    NTR

    OL

    AR P

    OW

    ER S

    UPP

    LY

    1 2 3 4 5 6 7 8 9PC

    (CIR

    CU

    IT 1

    )

    NC

    SPEE

    DU

    P

    GR

    CRD

    XFM

    R-R

    XFM

    R-C

    M1

    CO

    MK1

    NO

    K1

    L1

    RD

    GR P

    K BL

    PU

    SR

    STR

    AIN

    REL

    IEF

    M1

    YL

    YEL

    LOW

    BK

    BLA

    CK

    BL

    BLU

    EBR

    BR

    OW

    NG

    R

    GR

    EEN

    OR

    O

    RAN

    GE

    PK

    PIN

    KPU

    PU

    RP

    LER

    D

    RED

    WH

    W

    HIT

    E

    CO

    LOR

    CO

    DE

    (CIR

    CU

    IT 2

    )H

    KR P

    OW

    ER S

    UPP

    LYL1

    L2L3

    FLSRFU

    SE L

    INK

    W2

    W1

    WBR

    GR

    BLPK

    GR

    CR

    D

    T1T2

    T3

    12

    3

    45

    FLH

    TR3

    TL

    FLH

    TR2

    TL

    FLH

    TR1

    TL

    TLFL

    HTR

    3TL

    FLH

    TR2

    TLFL

    HTR

    1

    CB

    CIR

    CU

    IT B

    REA

    KER

    L1L2

    L3

    BKBK

    BK

    BK BK

    BK

    BKBK

    BK

    BKBK

    BK

    BKBK

    BK

    BK

    BK

    BK

    BK

    WIR

    ING

    CO

    DE

    HIG

    H V

    OLT

    AGE

    LOW

    VO

    LTAG

    E

    BK

    NO

    TE: W

    HEN

    INST

    ALLI

    NG

    HEA

    TER

    KIT

    , EN

    SUR

    E SP

    EED

    TAP

    MU

    ST E

    XCEE

    D O

    R E

    QU

    AL T

    HE

    MIN

    IMU

    M B

    LOW

    ER S

    PEED

    (MBS

    ) SPE

    CIF

    IED

    FO

    R T

    HE

    AIR

    HAN

    DLE

    R/H

    EATE

    R K

    IT C

    OM

    BIN

    ATIO

    N O

    N T

    HIS

    UN

    IT'S

    SER

    IAL

    PLAT

    E.AF

    TER

    INST

    ALLI

    NG

    OPT

    ION

    AL H

    EAT

    KIT,

    MAR

    K AN

    "X" I

    N T

    HE

    PR

    OVI

    DED

    BEL

    OW

    .N

    O M

    ARK

    IND

    ICAT

    ES N

    O H

    EAT

    KIT

    INST

    ALLE

    D.

    NO

    TE:-

    THIS

    LAB

    EL M

    UST

    BE

    ATT A

    CH

    ED O

    N T

    HE

    AIR

    HAN

    DLE

    R IN

    A P

    RO

    MIN

    ENT

    LOC

    ATIO

    N

    BKRD

    TB

    L1L2

    CIR

    CU

    IT 1

    1 PH

    208

    -240

    V

    CIR

    CU

    IT 2

    3 PH

    . 208

    -240

    V

  • SS-GARUF www.goodmanmfg.com 15

    Accessories

    Expansion Valve Kits for Air Conditioning and Heat Pump Applications

    Kit Number Description Application Refrigerant

    Tonnage: Outdoor Unit

    TX2N4A Non-bleed Valve AC or HP R-410A 1½ - 2 Ton

    TX3N4 Non-bleed Valve AC or HP R-410A 2½ - 3 Ton

    TX5N4 Non-bleed Valve AC or HP R-410A 3½ - 5 Ton

    Downflow Insulation Kit

    DFK-B DFK-C DFK-D

    ARUF25B14** ARUF37C14** ARUF37D14**

    ARUF29B14** ARUF43C14** ARUF43D14**

    ARUF31B14** ARUF49C14** ARUF47D14**

    ARUF49D14**

    ARUF61D14**

    Filters

    Chassis Part # Size

    B ALFH16201E 16.0” x 20.0”

    C ALFH1912201E 19.5” x 20.0”

    D ALFH20231E 23.0” x 20.0”

  • 16 www.goodmanmfg.com SS-GARUF

    Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations. © 2016 Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA.

    Notes