AR822-II AR861-2II AR861-3II INSTALLATION, OPERATION & MAINTENANCE MANUAL Information and specifications outlined in this manual in effect at the time of printing of this manual. ECR International, Inc. reserves the right to discontinue, change specifications or system design at any time without notice and without incurring any obligation, whatsoever. ARGO AR SERIES CONTROLS AR822-II, AR861-2II, AR861-3II Manufactured by: ECR International, Inc. 2201 Dwyer Avenue, Utica NY 13501 web site: www.ecrinternational.com www.argocontrols.com P/N 24005122 Rev. B [07/30/2016]

Upload: others

Post on 04-Feb-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

  • AR822-II

    AR861-2II

    AR861-3II

    INSTALLATION, OPERATION & MAINTENANCE MANUAL

    Information and specifications outlined in this manual in effect at the time of printing of this manual. ECR International, Inc. reserves the right to discontinue, change specifications or system design at any time without notice and without incurring any obligation, whatsoever.

    ARGO AR SERIES CONTROLS

    AR822-II, AR861-2II, AR861-3II

    Manufactured by:

    ECR International, Inc.2201 Dwyer Avenue, Utica NY 13501

    web site: www.ecrinternational.comwww.argocontrols.com

    P/N 24005122 Rev. B [07/30/2016]

  • Safety Symbols ���������������������������������������������������������������������������������������������������������������������������������3

    Introduction ��������������������������������������������������������������������������������������������������������������������������������������3

    Mounting Instructions ������������������������������������������������������������������������������������������������������������������������3

    Electrical Specifications & Wiring ���������������������������������������������������������������������������������������������������������4

    AR822-II Single Zone Relay

    AR822-II Control Features �����������������������������������������������������������������������������������������������������������4

    AR822-II Sequence Of Operation ��������������������������������������������������������������������������������������������������4

    AR822-II Control Board���������������������������������������������������������������������������������������������������������������5

    AR822-II Wiring Schematic ���������������������������������������������������������������������������������������������������������5

    AR822-II Applications �����������������������������������������������������������������������������������������������������������������6

    AR822-II With Zone Valve Priority ������������������������������������������������������������������������������������������������7

    AR861-2II & AR 861-3II

    AR861-2II & AR 861-3II Control Features �������������������������������������������������������������������������������������8

    AR861-2II & AR 861-3II Sequence of Operation������������������������������������������������������������������������������8

    AR861-2II Control Board & Wiring Schematic................................................................................9

    AR861-3II Control Board & Wiring Schematic��������������������������������������������������������������������������������10

    AR861-2II & AR 861-3II Applications ������������������������������������������������������������������������������������������ 11

    AR861-2II & AR 861-3II Expansion Control���������������������������������������������������������������������������������� 15

    AR Series With DPM-2 Outdoor Reset Control................................................................................16

    Replacement Parts ��������������������������������������������������������������������������������������������������������������������������� 16

    Technical Support ���������������������������������������������������������������������������������������������������������������������������� 16

    DANIMPORTANT: Read and understand the following instructions COMPLETELY before installing!!

    TABLE OF CONTENTS

    Keep this manual near boilerRetain for future reference

    2 P/N 240005122, Rev. B [07/15/2016]

  • INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

    NOTICEUsed to address practices not related to personal injury�

    CAUTIONIndicates a hazardous situation which, if not avoided, could result in minor or moderate injury�

    !

    WARNINGIndicates a hazardous situation which, if not avoided, could result in death or serious injury�

    !

    DANGERIndicates a hazardous situation which, if not avoided, WILL result in death or serious injury

    !

    This is the safety alert symbol� Symbol alerts you to potential personal injury hazards� Obey all safety messages following this symbol to avoid possible injury or death�

    Become familiar with symbols identifying potential hazards�

    WARNINGFire, explosion, asphyxiation and electrical shock hazard� Improper installation could result in death or serious injury� Read this manual and understand all requirements before beginning installation�

    ! Introduction

    This manual is intended to familiarize the installer and user of the Argo AR Series of controls with their installation and operation to assure normal trouble-free operation�

    Argo controls are designed and manufactured with quality components for maximum life and durability and require minimal service� To insure a satisfactory installation, it is imperative that the instructions be followed carefully before operating the control� Failure to do so may result in breach of warranty�

    Mounting InstructionsMount the Argo AR Series Control vertically on a solid wall or partition� For your convenience it is recommended that the control be mounted as close as possible to the device to be controlled� The control should never be mounted more than 75 feet away� Select a location that is easily accessible for installation and service�

    NOTE: To reduce the possible transformer hum and relay noise that is sometimes amplified by mounting surfaces such as sheet metal, plasterboard, and similar materials, place rubber or felt washers between the case and the mounting surface�

    1. Position the control and mark the mounting holes.

    2. Start screws (not provided) for the keyhole type mounting holes in the upper corner(s)� Tighten the screws down to about ⅛” (3mm) from the surface. The AR822-II will require a screw to be installed in the lower left hand corner after the control is hung and leveled�

    3. Hang the control on the screw(s), position the case, and start the bottom screws�

    4. Tighten all screws�

    3 P/N 240005122, Rev. B [07/15/2016]

  • The following describes the function of each terminal.

    • L1: Hot leg of 120VAC power input

    • L2: Common leg of 120VAC power input

    • 3: Input to one pole of relay contacts

    • 4 NO: Normally open output, between 3 and 4 NO

    • 4 NC: Normally closed output, between 3 and 4 NC

    • 5: Input to one pole of relay contacts

    • 6 NO: Normally open output, between 5 and 6NO

    • 6 NC: Normally closed output, between 5 and 6NC

    T/R and T/W are thermostat connections� When Thermostat calls completing the circuit the relay is activated�

    AR822-II Sequence of Operation

    1. When the thermostat connection to TR/TW calls for heat the “circuit ON” LED is illuminated.

    2. The relay will then close.

    3. The contacts between 3/4 NO and 5/6 NO will close.

    4. The contacts between 3/4NC and 5/6NC will open.

    Electrical Specifications

    Part Number

    Model Number

    Transformer Voltage

    Relay Switching

    Action

    Contact/Control

    Amp Draw (120VAC)

    Z140 AR822-II 120V/60Hz/40Va DPDT 7.2

    Z209 AR861-2II 120V/60Hz/75Va DPDT 7.2

    Z210 AR861-3II 120V/60Hz/75Va DPDT 7.2

    AR822-II Control Features

    • Auto-Reset Electronic Fuse Protection – Eliminates Nuisance Service Calls

    • 15VA Transformer – Robust Components Provide Years of Trouble -Free Service

    • Ice Cube Technology – Plug-In Replacement Relays

    • 5-Year WarrantyGeneral Wiring Notice

    All primary wiring must be 14 AWG minimum. Torque terminal screws 6 to 7 inch pounds.

    U.S.A. - National Electric Code and any other nation-al, state, or local code requirements. Wiring must be N.E.C. Class 1.

    CANADA - C.S.A. C22.1 Canadian Electrical Code Part 1 and any other national, provincial, or local code requirements. Wiring must be C.S.A. C22.1 C.E.C. Part 1.

    INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

    Electrical Specifications & Wiring

    WARNINGElectrical shock hazard. Disconnect power before installing or servicing� Failure to follow these instructions could result in death or serious injury�

    !

    4 P/N 240005122, Rev. B [07/15/2016]

  • ELEC

    TRO

    NIC

    FU

    SE

    VAC

    CIRC

    UIT

    ON

    120

    L2NO

    4NC

    4

    SCREWSTORQUE TERMINAL

    6 TO 7 INCH LBSAR822-TTARGO TT

    TTR W

    24V

    C 5 6NO

    6NC

    RE

    LAY

    Factory Installed Jumper Between L1 & 3

    Class 2Terminals

    PrimaryTerminals

    INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

    AR822-II CONTROL BOARD

    AR822-II WIRING SCHEMATICS

    5 P/N 240005122, Rev. B [07/15/2016]

  • TO BURNER

    OR BURNER

    CONTROL

    DO NOT USE

    AR822-II Dual Zone Applicationwithout Tankless Coiler Boiler

    AR822-II Single Zone Applicationwith Tankless Coil Boiler

    AR822-II APPLICATIONS

    INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

    6 P/N 240005122, Rev. B [07/15/2016]

  • L2120VAC

    L1

    CIRC

    UIT

    ON +

    NO

    3NC

    4 4

    ARGO AR822

    WR CTT 24V

    5 6 6NO NC

    BURNER CONTROLTO BURNER OR

    DO NOT USE

    L8148

    2

    1

    T

    C2

    B1

    C1

    B2

    T

    PRIORITYCIRC.

    24 VAC

    COM

    TX-X TT TT T TT TTON

    ZONE 2

    END SW 2

    X2X1

    END SW 1

    X1 X2

    ZONE 121 3 4 1 2

    AZ-

    3

    ARG

    O

    Zone

    Val

    ve C

    ontr

    olle

    r

    ZONE 343 1 2 43

    AZ-

    5

    ZONE 41 2 43 3

    ZONE 51 2 4

    SUPPLIEDWITH RELAY AZ-5

    STAT STAT STAT STAT STAT

    VALVE VALVE VALVE VALVE VALVE

    DOMESTICHOT

    WATER

    L

    N

    120VAC

    JUMPER

    N120VAC L

    HEATINGZONEPUMP

    120VAC

    L

    N

    NOTE: Thermostats must be mercury switch style or battery powered for this installation to function properly�

    AR822-II Indirect Tank Prioritywith Zone Valve Control

    INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

    AR822-II APPLICATIONS

    7 P/N 240005122, Rev. B [07/15/2016]

  • INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

    AR861-2II & AR861-3II Control Features

    • 2-Zone AR861-2II or 3-Zone AR861-3II

    • Auto-Reset Electronic Fuse Protection – Eliminates Nuisance Service Calls

    • 15VA Transformer – Robust Components Provide Years of Trouble -Free Service

    • Ice Cube Technology – Plug-In Replacement Relays

    • Priority Function

    • 5-Year Warranty

    AR861-2II & AR861-3II Sequence of Operation

    If the Priority Switch is in the “OFF” Position:

    1. When a zone calls for heat the corresponding zone LED is illuminated.

    2. The relay for the corresponding zone will then close.

    3. A/R terminals will close starting the boiler.

    4. The corresponding GZ/HZ terminals will be energized with 120 Volts.

    If the Priority Switch is in the “ON” Position:

    1.Zone 1 becomes the priority zone.

    2. When zone 1 calls for heat, the priority zone is activated and all other zones are deactivated (circulators for zones 2 and higher will not operate). Zone 1 LED is illuminated indicating a call for heat.

    3. Zone 1 relay will close.

    4. A/R terminals will close starting the boiler.

    5. GZ 1/HZ 1 will be energized with 120 Volts.

    8 P/N 240005122, Rev. B [07/15/2016]

  • RE

    LAY

    RE

    LAY

    RE

    LAY

    Class 2 Terminals

    Primary Terminals

    INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

    AR861-2II CONTROL BOARD & WIRING SCHEMATIC

    9 P/N 240005122, Rev. B [07/15/2016]

  • RE

    LAY

    RE

    LAY

    RE

    LAY

    RE

    LAY

    Class 2 Terminals

    Primary Terminals

    INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

    AR861-3II CONTROL BOARD & WIRING SCHEMATIC

    10 P/N 240005122, Rev. B [07/15/2016]

  • The diagrams on the following pages represent the AR861-3II. The AR861-2II is wired in a similar fashion.

    Priority T-Stat

    Primary Wiring

    Class 2 Wiring

    AR861-3II

    Primary WiringJumper

    Priority Circ L4006A

    T-StatT-Stat

    Circ

    L2G W L A R GZ1

    T1 T1 T2 T2 T3 T3

    HZ1 GZ2 HZ2 GZ3 HZ3

    G Circ

    120 VACL1Hot

    Milli VoltGas Valve

    RE

    LAY

    RE

    LAY

    RE

    LAY

    RE

    LAY

    Each of the low voltage controllers (SPST Thermostats) will actuate a circulator and start the burner when used in conjunction with an isolated switch aquastat.

    Jumper: To be placed between terminals L and W . In this position A and R become the isolated end switch. (Jumper is factory installed in this position)

    Terminals A and R Isolated End Switch

    INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

    AR861-2II & AR861-3II APPLICATIONS

    11 P/N 240005122, Rev. B [07/15/2016]

  • Priority T-Stat

    Primary Wiring

    Class 2 Wiring

    AR861-3II

    Primary WiringJumper

    Priority Circ L4006A

    T-StatT-Stat

    Circ

    L2G W L A R GZ1

    T1 T1 T2 T2 T3 T3

    HZ1 GZ2 HZ2 GZ3 HZ3

    G Circ

    Milli VoltGas Valve

    120 VACL1Hot

    24VTransformer

    Priority T-Stat

    L8148

    Primary Wiring

    To Burner or

    Burner Control

    DoNotUse

    Class 2 Wiring

    AR861-3II

    Primary WiringJumper

    Priority Circ

    T-Stat

    T-Stat

    TT

    1

    2

    Circ

    G W L A R GZ1

    T1 T1 T2 T2 T3 T3

    C1

    C2

    B2

    B1

    HZ1 GZ2 HZ2 GZ3 HZ3

    CircL2

    G

    120 VACL1Hot

    AR861-2II & AR861-3II APPLICATIONS

    INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

    12 P/N 240005122, Rev. B [07/15/2016]

  • RE

    LAY

    RE

    LAY

    RE

    LAY

    RE

    LAY

    Terminals W and R to Aquastat( W to ZC and R to ZR)

    Each of the low voltage controllers (SPST Thermostats) will actuate a circulator and start the burner when used in conjunction with a boiler aquastat control. If the boiler temperature drops below the low limit (circulator) setting, all circulating will cease until the temperature of the boiler water is increased.

    Jumper: To be placed between terminals L and A . In this position a line voltage message is sent out R to ZR terminal on the aqustst and returns to W from the ZC terminal on the aqustst.

    INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

    AR861-2II & AR861-3II APPLICATIONS

    WARNINGAR relays will not work properly if 120 VAC polarity is not the same at 120 VAC L and N terminals on both AR control and boiler aquastat� The neutral and hot wires must not be reversed� Reversing the L and N wires could result in a secondary source of power that may activate the boiler under certain circumstances which could result in death or serious injury�

    !

    WARNINGWhen using ZC-ZR attention must be paid to keep the polarity of the wiring consistent between the Argo control and boiler aquastat� Failure to do so could result in a secondary source of power activating the boiler under certain circumstances which could result in serious injury or death� Always disconnect power to both the Argo control and boiler when installing or servicing this product�

    !

    13 P/N 240005122, Rev. B [07/15/2016]

  • Priority T-Stat

    Primary Wiring

    Burner

    Class 2 Wiring

    AR861-3II

    Primary WiringJumper

    Priority Circ

    T-StatT-Stat

    L8124A or C

    T

    T

    L1

    L2

    Circ

    G W L R GZ1

    T1 T1 T2 T2 T3 T3

    C1

    C2

    B2

    B1

    ZR

    ZC

    HZ1 GZ2 HZ2 GZ3 HZ3

    CircL2

    G

    120 VACL1Hot

    A

    Priority T-Stat

    Primary Wiring

    Burner

    Class 2 Wiring

    AR861-3II

    Primary WiringJumper

    Priority Circ

    T-StatT-Stat

    L8124A or C

    T

    T

    L1

    L2

    Cad

    Cell

    Circ

    G W L R GZ1

    T1 T1 T2 T2 T3 T3

    C1

    C2

    B2

    B1

    ZR

    ZC

    HZ1 GZ2 HZ2 GZ3 HZ3

    CircL2

    G

    120 VACL1Hot

    A

    AR861-2II & AR861-3II APPLICATIONS

    INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

    14 P/N 240005122, Rev. B [07/15/2016]

  • THERMOSTATS

    GZ2120 V CIRCULATOR

    15VA

    120VACG W L RA

    PRIORITYGZ1 HZ1

    PRIORITY OFF

    PRIORITY ON

    PRIORITYT1 T1 T2

    GZ3HZ2 HZ3

    T3T3T2

    STATSTAT

    CIRC CIRCDO NOTUSE

    N

    L

    120VAC

    CIRC

    STAT

    T2

    120 V CIRCULATORGZ2

    THERMOSTATS

    15VA

    L

    120VAC

    N

    W120VAC

    G L A GZ1PRIORITY

    R HZ1

    PRIORITY OFF

    PRIORITY ON

    2.7 K

    1.0 K

    2.7 K

    1.0 K

    PRIORITYT1 T2T1

    CIRC

    HZ2 GZ3 HZ3

    1.0 K

    2.7 K

    T3 T3

    STAT

    CIRC

    TO BOILERT-T

    TO BOILERT-T

    DOMESTIC

    WATERHOT

    JUMPER

    JUMPER

    TRIPLE RELAY AR861-3 IIARGO

    TRIPLE RELAY AR861-3 IIARGO

    The two controls on this page are capable of running six zones. When they are installed as shown below, only one priority and four standard zones (for a total of five zones) are available.

    Important:Both left-hand T1 terminals must be connected together and both right-hand T1 terminals must be connected together� Reversing the wiring will result in the transformers being out of phase�

    INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

    AR861-2II & AR861-3II EXPANSION TECHNIQUE

    15 P/N 240005122, Rev. B [07/15/2016]

  • The DPM-2 Outdoor Reset Control is designed to raise or lower the temperature of the boiler supply water based upon a proportionate drop or rise in temperature at the outside sensor� This control plugs into Argo control equipment with a data port or as a stand alone device that can be easily wired into almost any system� See the separate DPM-2 Installation Manual for more information.

    Replacement PartPart Description Argo Part Number

    Replacement Control Relay R35C

    For technical support on this and all Argo products, please contact ECR International Technical Service at 1-800-325-5479. Please have your model number available when calling.

    Information Needed When Calling

    Model Number

    Installation Date

    Installer

    INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

    AR SERIES WITH DPM-2 OUTDOOR RESET CONTROL

    Technical Support

    ECR International2201 Dwyer Avenue

    Utica, NY 13501www.ecrinternational.com

    www.argocontrols.com