  • 8/7/2019 army tm 5-683

    1/180

    ARMY TM 5-683NAVY NAVFAC MO-116

    AIR FORCE AFJ MAN 3 2-10 83

    FACILITIES ENGINEERINGELECTRICAL INTERIOR FACILITIES

    APPROVED FOR PUBLIC RELEASE: Distributionis unlimited

    DEPARTMENTS OF THE ARMY, THE NAVY, AND THE AIR FORCENOVEMBER 1995

  • 8/7/2019 army tm 5-683

    2/180

    REP RODUCTION AUTHORIZATION/RES TRICTIONS

    T h i s m a n u a l h a s b e e n p r e p a r e d b y o r f o r t h e G ov e r n m e n t a n d i s

    p u b l i c p r o p e r t y a n d n o t s u b j e c t t o c o p y r i g h t .

    R e p r i n t s o r r e p u b l i c a t i o n o f t h i s m a n u a l s h o u l d in c l u d e a c r e d i t s u b -

    s t an t i a l ly a s fo l low s : J o i n t D e p a r t m e n t s o f t h e A r m y , t h e N a v y a n d

    t h e Ai r F o r c e , U S A, T e c h n i c a l M a n u a l T M 5 -6 8 3 /N AV F AC

    MO-116/AFJ MAN 32-1083, Elect r ica l I n ter ior Fa ci l i t ies , 30 Novemb er

    1995.

  • 8/7/2019 army tm 5-683

    3/180

    TM 5-68NAVFACMQ-11

    AFJMAN 32-108

    TECH NICAL MANUAL NO. 5-683 H E A D Q U A R T E R S

    NAVY MANUAL NAVFAC MO-116 DEPARTMENT OF THE ARMY,

    THE NAVY, AND THE AIR FORC

    AIR

    FORCE

    MANUAL

    AFJ MAN 32-1083W A S H I N G T O N, DC, 30 November 199

    ELECTRICAL INTERIOR FACILITIES

    cHAPTER 1.

    2.

    3.

    4.

    5.

    6.

    7.

    8.

    INTRODUCTIONPurpose and scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Codes and specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Main ten an ce requ irem ent s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Records . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Pr iorit y an d sch edu ling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Hazards . . . . . . . . . .. .. ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    SWITCHGEAR ASSEMBLIES 600V OR LESSPeriodic maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Metal enclosures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Bus bar an d t erm ina l connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Under floor ducts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Busways . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Power circuit brea ker s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Network protectors.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Auxiliar y swit ch gea r eq uipm ent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Switchgear t rouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .TRANSFORMERS

    Sm all p ower t ra ns former s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Dr y-type t ra ns former s. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    ELECTRIC MOTORS

    Main ten an ce of electr ic motor s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Alter na tin g curr ent (AC) motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Dir ect cur ren t (DC) m otors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Motor opera tin g consider at ions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Motor ins ula tion tes tin g . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Motor trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    MOTOR CONTROLS

    Functions o motor controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Types of motor controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Componen ts an d m ain ten an ce of mot or contr ols. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Pr event ive ma int ena nce an d t rouble-sh ootin g guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    POWER CABLES

    Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Visual inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Cable insulation testing ...... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Over poten tia l tes tin g. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Cable trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    SOLID-STATE ELECTRONIC EQUIPMENT

    Solid-sta te ma int ena nce. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Solid-state components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Electrical disturbances (power quality) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Dist ur ban ce mea sur emen t a nd m onitor ing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Voltage s ur ge su ppr ession . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    GROUNDING

    Grou nd ma int ena nce. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Types of grou ndin g syst ems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Grou nd fault int err upt ing m eth ods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Paragraph

    1 1

    1-21-3

    1-41-5

    1-61-7

    2-1

    2-22-32-42-52-6

    2-72-82-9

    3-13-2

    4-14-24-3

    4-44-54-6

    5-15-25-35-4

    6-16-26-36-4

    6-5

    717-27-37-47-5

    8 -l8-18-3

    P a g e

    11

    1-1111-11-11-21-2

    2-1

    2-12-22-2

    2-22-32-102-122-16

    3-13-1

    4-14-14-13

    4-204-244-24

    5-15-1

    5-66-15

    6-l

    6 -l6-16-2

    6-5

    7 17-17-77-77-8

    8-18-1

    8-9

    *This manual supersedesTM 5-683/NAVFAC MO-116/AFM 91-17, dated 2 March 1972

  • 8/7/2019 army tm 5-683

    4/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    CHAPTER 9.

    10 .

    11 .

    12.

    13.

    14 .

    15 .

    APPENDIX A.

    Figure 21.

    2-2.

    23.

    2-4.

    25.

    2-8.

    2-7.

    28.

    29.

    2-10.

    i i

    ILLUMINATION

    Light ing m ain ten an ce. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Fluorescent lighting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Incandescent lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    High int ens ity d ischa rge ligh tin g (HID ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Relamping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Lamp trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    BACK-UP, SECURITY, AND PROTECTION SYSTEMS

    Other systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Em ergen cy and st an d-by syst ems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Signa l syst ems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Detection systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Monitoring systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    HAZARDOUS SUBSTANCES

    Environmental protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Polychlorinat ed biphenyls (PCBs). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..

    Lighting ballast. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Flammable liquids and gasses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Toxic mat erials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    ELECTRICAL SAFETYHuman factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Equipment isolation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Switchgear. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. . . . . . . . . . . . . . . .

    Rotating equ ipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Tra nsformer s. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Wiring and testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Mecha nical . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Dan ger w ar nin gs a nd fire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Pers onal protective equipmen t . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    TEST EQUIPMENT

    Equ ipm ent ma int ena nce. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Volt-ohm-m illiam met er (VOM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Clamp-on volt-ammeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Megohmmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....

    Ha rm onic mea su rem ent s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Maintenan ce equipment guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    TEST METHODS

    Test evaluation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Ins ula tion tes tin g. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Protective relay testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Equipment ground resistance testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Syst em gr ound res ist an ce tes tin g . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Battery specific gravity test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..

    Infrared inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    MAINTENANCE SCHEDULES

    Personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . .

    Respon sibilit ies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Frequencies and procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    REFERENCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    LIST OF FIGURES

    Paragraph

    9 -1

    9 -2

    9 -3

    9 -4

    9 -5

    9 -6

    9- 7

    10-1

    l 0 - 2

    10-3

    10-4

    10-5

    11-1

    11-2

    11-3

    11-4

    11-5

    12-1

    12-2

    12-3

    12-4

    12-5

    12-8

    12-7

    12-8

    12-9

    12-10

    13-1

    13-2

    13-3

    13-4

    13-513-8

    14-1

    14-2

    14-3

    14-4

    14-5

    14-6

    14-7

    15-1

    15-2

    15-3

    . . . . . . . .

    Typical buswa y insta llation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Dr awout circuit brea ker position s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Power circuit brea ker ma in a nd ar cing conta cts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Arcing contact gap and wipe. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    In ter med iat e conta ct gap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Main contact wipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Electr omecha nical t rip device tim e-curr ent curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Typical dr awou t n etw ork p rot ector a nd enclosur e . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Net work pr otector rem ovable u nit .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Typical cont act constr uction for a net work p rote ctor..... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Page

    9-1

    9 1

    9-1

    9 -2

    9- 4

    9- 4

    9 -5

    10-1

    10-1

    10-1

    10-1

    l 0 - 5

    11-1

    11-1

    11-3

    11-3

    11-3

    12-1

    12-1

    12-3

    12-4

    12-4

    12-5

    12-5

    12-5

    12-5

    12-5

    13-1

    13-1

    13-4

    13-6

    13-813-9

    14-1

    14-1

    14-3

    14-5

    14-5

    14-7

    14-7

    15-1

    15-1

    15-1.

    A1

    Page

    2 -4

    2-5

    2 -8

    2-7

    2 -8

    2 -9

    2-11

    2-13

    2-13

    2-14

  • 8/7/2019 army tm 5-683

    5/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-108

    LIST OF FIGURES (cont'd)

    Figure 211. La rge cell for a st at ionar y bat ter y. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3-1. Dry-type transformer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-1. Cut awa y view of squir rel-cage in duct ion m otor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-2. Cut awa y view of wound-r otor in duct ion m otor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-3. Cut awa y view of synchr onous m otor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-4. Pr ima ry pa rt s of an AC indu ction m otor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-5. Clean ing a nd dr ying m otors in p lace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-6. Bear ing in st alla tion pr ecaut ions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-7. Const ru ction of ball a nd roller bear ings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-8. Greasing bearings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-9. Typical sleeve bearings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-10. Cut awa y view of a t ypical DC mot or . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-11. Main types an d connect ions of DCm otors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-12. Arma tu re of a la rge DC mot or on st an ds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-13. Insp ecting a nd inst allin g bru sh es on a lar ge DC m otor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-14. Cut awa y section of a commu ta tor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-15. Brush "chatteraction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-16. Poor commutator conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-17. Good commutator films.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-18. Exa mp le of eccent ric comm ut at or . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-19. Dial ga uge t o mea su re comm ut at or concentr icity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-20. Comm on u nder cutt ing m ist ak es. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-21. Connect ions for t est ing m otor in sula tion res ist an ce. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-1. Man ua l st ar ter s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-2. Typical m agn etic st ar ter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-3. Combina tion s ta rt ers in N EM A enclosur es. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-4. Coordination of motor overload relay and curr ent limit ing fus e. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-5. Autot ra ns former st ar ter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-6. Resis ta nce st ar ter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-7. Pa rt -Windin g st ar ter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-8. Solid St at e st ar ter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-9. Typical motor control center . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-10. Cut awa y view of typical molded ca se circu it br eak er . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-11. Molded case circuit brea ker tim e-curr ent curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-12. Fu se m ain ten an ce pra ctices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-13. Un der writ ers Labor at ories C ar tr idge fus e class ification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-14.Typica l thermal overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-15. Typical heater selection table for thermal overload device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-16. A NEMA size 6 m agn etic conta ctor (court esy of Sieme ns-Allis) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6-1. Connections for tes tin g low volta ge cable in su lat ion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    71. Typical capacitor types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    7-2. Diodes and SCRs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    73. Cha ra cter istics of diodes a nd Zener s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    7-4. Testing Zener voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    75. Tr an sist or t est ing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    8-1. Typical equipment ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    8-2. Typical grounding system for a building and its apparatus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    8-3. Meth ods of syst em groun ding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    8-4. Methods o fsolidly grounding the neutral of three-phase systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    8-5. Methods of resista nce groundin g the neut ra l of th ree-pha se syst ems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    8-8. Groun ding for electr onic an d ADP syst ems .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    8-7. Groun d fau lt cir cuit in ter ru pt er oper at ion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    9-1. Pre hea t fluore scent lam p a nd fixtur e componen ts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    9-2. Mercury lamp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    9-3. Trouble-s hootin g fluores cent light ing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    10-1. Sam ple compu ter -based fire det ection s yste m . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    10-2. Clas s A a nd B fire det ection circu its . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    121. Pa dlock an d m ult iple lock ada pt er . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    122. Typical safety tag. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    123. Ground cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    12-4. Grounding clamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    125. E ye an d face pr otection s election gu ide.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-1. Set -up for m eas ur ing AC volt age . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-2. Set-up for measuring resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Page

    2-15

    3-2

    4 -8

    4 -9

    4-14-1

    4-1

    4-1

    4-14

    4-1

    4-1

    4-1

    4-1

    4-1

    4-1

    4-1

    4-2

    4-2

    4-2

    4-24-2

    4-2

    4-2

    5 -2

    5-2

    5-3

    5-4

    5-5

    5 -6

    5-7

    5 -8

    5-9

    5-1

    5-1

    5-15-1

    5-1

    5-1

    5-1

    6 -2

    7 -3

    75

    7 -6

    7- 6

    7-8

    8 -3

    8- 4

    8-5

    8 -6

    8 -6

    8-1

    8-1

    9-2

    9-3

    9-4

    10-2

    10-3

    122

    122

    123

    12-4

    12-6

    13-4

    13-5

  • 8/7/2019 army tm 5-683

    6/180

    TM 5-683/NAVFAC MO-116/AFJMA N 32 -1083

    LIST OF FIGURES (contd)

    Figure 13-3.

    13-4.

    13-5.

    14-1.14-2.

    14-3.

    14-4.

    14-5.

    14-6.

    14-7.

    14--6.

    14-9.

    14-10.

    14-11.

    Table 2-1.2-2.

    4-1.

    4-2.

    4-3.

    4-4.

    4-5.

    5-1.

    5-2.

    6-1.

    6-2.

    71.

    9-1.

    10-1.

    111.

    13-1.14-1.

    14-2.

    15-1.

    15-2.

    15-3.

    1.54.

    Set -up for t est ing ph as e sequ ence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Megohmmeter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..........

    Diagram of megohmmeter connections...... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ......

    Comparison of water f low wi th elect r ic current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Curves sh owing components of measured current during insulation testing . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Typical curves showing dielectric absorption effect in a time-resistence or double-reading test . . . . . . . . . . .

    Resistive components of a made electrode . . . . . . . . . . . . ..... . . . . . . . . . . . . . . ........

    So i l r es i s t i v i t y v s mo i s t u r e con t e n t o f r ed c l a y so i l . . . . . . . . . . . .. . . . . . . . . . . . -

    Soil resistance vs temperature of clay soil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . .

    Soil resistance vs depth of electrode..... . . . . . . . . . . . . . . . . . . . . . . . . .. ............

    Ea rt h electr ode with hem isph eres . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Fall-of-potential method graph. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Sampling the cell electrolyte . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Reading the hydrometer float . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    LIST OF TABLES

    U.S. standa rd bolt torgues for bus connections hea t t reat ed steel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Trou ble-shootin g procedu re s for swit chgea r e quipm ent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Motor application guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Nam eplate voltage r at ings of sta nda rd indu ction motors . . . . . . . . . . . . . . . . . . . . . . . . . ....

    AC synchronous motor trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..........

    DC motor generator trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Motor control preventative maintenance guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Motor contr ol trouble-shooting char t . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -

    Condu ctor sizes, in su lat ion th icknes s, te st voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Cable maintenance overheating problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

    Power qua lity pr oblems s um ma ry .. ...--. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Lamp trouble-shooting guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....

    Comparison of fire detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Comm on tr ade na mes for PCB by m an ufact ur ers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Tools and equipment for effective electrical maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ........Int erp ret ing in sula tion r esist an ce test res ult s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Condition of insulation indicated by dielectric absorption ratios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Per cent age of failur e cau se s ince m ain ta ined .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Equipment failure rate multipliers vereus maintenance quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    In ter ior wir ing a nd light ing s yst em . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Electric motors a nd contr ols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Page

    13-6

    13-7

    13-7

    14-2

    14-2

    14-3

    14-5

    14-5

    14-6

    14-6

    14-6

    14-7

    14-s

    14-9

    Page

    2 -32-17

    4 -2

    4-24

    4-26

    4-33

    4-36

    5-17

    5-19

    6 -6

    6-7

    79

    9 -6

    10-4

    112

    12-2

    14-3

    14-4

    15-2

    15-2

    15-3

    15-5

    i v

  • 8/7/2019 army tm 5-683

    7/180

    TM5-683/NAVFAC MO-116/AFJMAN 32-1083

    CHAPTER 1

    INTRODUCTION

    1-1 . Pu rpos e and s c op e .

    This ma nu al provides guidan ce to facilities maint e-

    na nce personnel in the ma inten an ce of inter ior elec-

    trical systems of 600 volts and less. These systems

    include such components as illumin at ion, low volt-

    age systems, rota ting equipmen t, motor cont rol cen-

    ters, solid-state equipment, t ransformers, and

    switchgear. It also applies to low voltage controlled

    devices on high-voltage systems. The procedures

    presented in this manual are basic and can be ap-

    plied to the equipment of any manufacturer. De-

    tailed information and instructions should be ob-

    tained from the instruction book for the particulartype of equipment being serviced.

    1-2 . Re fe renc es .

    Appendix A cont ains a list of references used in th is

    manual .

    1-3 . Codes and spec i f i c a t ions .

    Maintenance on electrical systems and equipment

    must adhere to the codes and specifications as they

    apply to the work to be performed. Also, manufac-

    tu rers maint enan ce instr uctions which accompanyselect electr ical component s mu st be applied in con-

    junction with th e codes a nd specifications listed be-

    low and the departmental specifications listed in

    appendix A.

    a. The National Electrical Code [National Fire

    Pr otection Associat ion #70 (NFP A 70)]. This code is

    th e most widely adopted set of electr ical sa fegua rd-

    ing practices. It defines approved types of conduc-

    tors and equipment, acceptable wiring methods,

    mandatory and advisory rules, operating voltages,

    limitations on loading of conductors, requir ed work-

    ing spaces, methods of guarding energized parts,

    interrupting capacity requirements of system pro-tective and control devices, requirements for con-

    nections and splices, insulation resistance require-

    ments, an d grounding requirements.

    b. Recommended Practice for Electrical Equip-

    ment Maintenance (NFPA 70 B).

    C. A m er ican N a t iona l S t andards Ins t i t u t e /

    Institute of Electrical and Electronics Engineers

    Standard (ANSI/IEEE Std.) chapter 15, 242-1986,

    IEEE Recommended Practice for Protection and Co-

    ordination of Industrial and Commercial Power Sys-

    tems. This code provides preventive maintenance

    pra ctices for electr ical systems a nd equipmen t u sedin indust rial-type applicat ions.

    1-4 . Ma in tenance requ i rements .

    Preventive maintenance should not be confused

    with repairs after a breakdown. The definition of

    maintena nce implies tha t t he equipment or system

    is inspected to discover its weaknesses and then

    repair or replace the necessary elements before a

    break down occur s. A mainten an ce progra m for pr o-

    tective devices a nd th e electr ic system could be di-

    vided into the following steps: inspecting, cleaning,

    tightening, lubricating, testing, and recording.

    a. The effectiveness of the distribution system is

    measu red in t erms of volta ge regulation, power fac-

    tor, load ba lan ce, reliability, efficiency of opera tion,

    an d cost s. To ensu re t he syst ems efficiency, lessen

    failures, and maximize safety, an effective mainte-

    nance program must be employed. This program

    should include and/or consider the following:

    (1) Scope of work.

    (2) Intervals of performance.

    (3) Methods of application.(4) Safety requirements, practices and proce-

    dures.

    (5) Adherence to codes, specifications and di-rectives.

    (6) Maintenance management procedures re-

    garding tools, records, and follow-up procedures.

    (7) Hazard s associat ed with work a nd t he facil-

    ity.

    (8) Emergency operating instructions.

    (9) Requirements for periodic review to deter-

    mine a dditiona l loading in circuits such a s in family

    housing, bachelor quarters, and maintenance and

    administrative buildings.

    b. A well executed maintenance program will

    provide benefits in ter ms of:

    (1) Economic operation.

    (2) Improved safety.

    (3) Longer equipment life.

    (4) Reduced repair and overhaul time.

    (5) Fewer unplanned outages.

    (6) Early detection of undesirable changes in

    th e power system.

    (7) Improved operation of the facility.

    1-5. Records.

    A good record keeping system is essential for safe,

    efficient an d economical oper at ion of electrical facil-

    ities and for planning and executing an effective

    1-1

  • 8/7/2019 army tm 5-683

    8/180

    TM5-683/NAVFAC M O-116/AFJMAN 32-1083

    prevent ive maintenance program. I t is recom-

    mended to use the Work Information Management

    System (WIMS) or other data-automated systems to

    keep records rather than paperwork files. Suitable

    forms and reports requirements should be devel-

    oped to suit local needs. When facilities are built,

    instruction documents and spare parts lists for allequipment installed should be obtained prior to

    beneficial occupancy acceptance.

    a. In addition to charts, work orders, and real

    property records, the following records have been

    found useful in analysis and correction of recurring

    trouble ar eas.

    (1) Diagrams. Accurate single-line and sche-matic diagrams of the distribution system should be

    readily accessible in the electrical shop. These are

    essential references when switching circuits and re-

    routing electric power in emergencies. Such dia-

    grams also provide a simple means of locating facil-

    ities and determining the characteristics of electricsupply to buildings requiring maintenance. Electri-

    cal personnel must have access to latest "as-built"

    building drawings for use in tracing out circuitry

    within buildings.

    (2) Equipment lists/ logs. These lists should be

    maintained on all items of equipment such as mo-

    tors, motor contr ollers, met ers, pa nelboards , electri-

    cal controls, and switchgear. Lists should reflect

    detailed information such as the density of all like

    i t em s , i t e m r a t i n g s a n d p h y s i ca l l oc a t i on s .

    Lists/logs will facilitate scheduling of inspections

    and maintenance services.

    (3) Equipment maintenance records. T h e s erecords should be maintained on every individual

    item of electrical equipment that requires mainte-

    nance services. Records should include detailed in-

    formation such as scheduled maintenance and in-

    spec t ion requ i rements , p rev ious tes t r esu l t s ,

    maintenance repairs performed and any other re-

    lated information that would facilitate analyzing

    the equipment performance. Maintenance records

    should be retained on file for as long as needed to

    allow collection of sufficient data to perform the

    equipment performance analyses. By observing the

    equipment performance, downward trends can be

    identified a nd problem ar eas corr ected before majorbreakdowns occur.

    (4) Emergency operating instructions. E m e r -

    gency operation of electrical facilities is safer and

    quicker when instructions are prepared and posted

    in advance. There should be instructions for each

    general type of anticipated emergency, stating what

    each employee in the electrical section should do,

    setting up alternatives for key personnel, and estab-

    lishing follow-up procedures for use after an emer-

    gency has passed. Instructions should be posted in

    the electrical shop, security guard office, all em

    gency generating or operating areas, and other lo

    tions as t he responsible supervisor deems n ecessa

    Employees should be listed by name, title, offi

    telephone number, home address and home t

    phone number (where permissible). These instr

    tions should emphasize safety under conditionsstress, power interruptions and similar emerg

    cies.

    1-6. Pr ior i ty and schedul ing.

    In regard to the support of the installed phys

    facilities, it is the policy of the Military Dep

    ments that, in order of priority, maintenance sho

    be second only to operations. It must be system

    and timely. Subsequent sections in this docum

    provide generaI suggestions on service frequenc

    and procedures. Although these proposed acti

    and frequencies may appear to be excessive, th

    suggestions are based upon experience and equment man ufacturers recommen dations. They

    not intended to supersede instructions that elec

    cal manufacturers normally provide. Every reali

    effort should be made to adher e to th ese suggesti

    considering existing manpower levels and availa

    test equipment. It is generally good practice to

    spect equipment three to six months after it is f

    put into service and then to inspect and maintai

    every one to three years, depending on its serv

    and operating conditions. Conditions that make

    quent maintenance and inspection necessary

    a. High humidity and high ambient temperatu

    b. Corrosive atmosphere.c. Excessive dust and dirt.

    d. High repetitive duty.

    e. Frequent fault interruption.

    f. Older equipment.

    1-7. Hazards.

    Material specifications, construction criteria, ins

    lat ion s tandards, and safe working procedu

    should be applied to minimize hazards. All w

    should be performed by qualified electricians

    conform to the latest accepted procedures and st

    dards.

    a. Building electrical systems. Fire and safhazards in building electrical systems often re

    from tampering by unqualified personnel. Proba

    the greatest example of tampering is the unaut

    rized changing or replacing of fuses. Careful ob

    vation by maintenance personnel is needed to c

    trol excessive use of items such as extension co

    heaters, air conditioners, and improper ground

    which cause overloading of the wiring syste

    Whenever possible, installation of additional rec

    tacles is preferable to the use of extension co

    1-2

  • 8/7/2019 army tm 5-683

    9/180

    Each building should be inspected for loose wires,

    poor connections, bare conductors, unauthorized or

    nonsta nda rd a tt achment cords, use of wiring or fix-

    tures as support for extraneous items, any condi-

    tions likely to cause fires and lamps larger than the

    sta nda rd size prescribed for outlets.

    b. Hazardous locations. Special occupancy areasinclude gar ages, aircraft ha ngar s, gasoline dispens-

    ing and service stations, bulk storage plants, and

    TM5-683/NAVFAC MO-116/AFJMAN 32-1083

    health care facilities. Such areas designed as "Haz-

    ards Locations," as specified in Article 500 of the

    Nat iona l Electr ical Code, require s pecial an d equip-

    ment considerations. These considerations include

    the use of special fitt ings, rigid conduit, and

    explosion-proof apparatus. Maintenance personnel

    must ensure that al l work performed in a hazardousarea complies with the code requirements for the

    ar eas pa rticular ha zard classification.

    1-3

  • 8/7/2019 army tm 5-683

    10/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    CHAPTER 2

    SWITCHGEAR ASSEMBLIES 600V OR LESS

    2-1 . Pe r i od i c Ma in t e nanc e .

    A periodic maintenance schedule must be estab-

    l i s h e d t o o b t a i n t h e b e s t s e r v i c e f r o m t h e

    switchgear. Annual check should be made on all

    major switchgear devices after installation. After

    trends have been established regarding the equip-

    ment condition and reliability, the maintenance in-

    terval may be extended (1836 months) in keeping

    with the operating conditions. A permanent record

    of all ma intena nce work should be kept. The r ecord

    should include a list of periodic checks and tests

    made (including date of test), condition of the equip-

    ment, repairs or adjustments performed, and test

    data tha t would facilitat e performing a trend ana ly-

    sis. Maintenance personnel must follow all recog-

    nized safety practices, both the nationally published

    standards and military regulations. Some specific

    suggestions in dealing with switchgear mainte-

    na nce are given below:

    a. Tools designed for slowly closing switchgear

    circuit breakers or other devices during mainte-

    nance are not suitable for use on an energized sys-

    tem. The speed necessary for device closing is as

    important as its speed in opening; therefore, a

    wrench or other manual tool is not fast enough.

    b. Before working on a switchgear enclosure,verify that the enclosure is de-energized by check-

    ing for voltage using a voltage detector.

    c. Disconnect all drawout or tilt-out devices such

    as circuit breakers, instrumentation transformers,

    an d control power tra nsformer s.

    d. Do not la y tools on th e equipment while work-

    ing. It is all too common to forget a wrench when

    closing up an enclosur e. Dont t ak e the cha nce.

    e. Never rely upon the insulation surrounding an

    energized condu ctor to pr ovide protection to pers on-

    nel. Use suitable safety clothing and equipment.

    f. Always use the correct maintenance forms and

    equipment. When performing maintenance the fol-lowing should be available:

    (1) Forms for recording the conditions as found

    an d work done.

    (2) Control power connections, test couplers,and spar e parts recommended by the man ufactur er

    to facilitate repair and maintenance of each type of

    circuit breaker.

    (3) Special tools, such as lifting mechanismsfor removing and transporting power circuit break-

    ers, relay test plugs for testing and calibrating pro-

    tective relays, a low resistance ohmmeter for mea-

    s u r i n g t h e r e s i s t a n c e o f c o n t a c t s , a m m e t e r s ,

    voltmeters, megohmmeters, low voltage/high cur-

    rent test set s for testing power circuit break ers, and

    other special test equipment.

    (4) Manu factu rers inst ru ction books regard ing

    the maintenance of switchgear devices such as cir-

    cuit breakers, relays, bus bars, meters, etc. The

    fundamentals that are presented in the upcoming

    sections are designed to supplement these instruc-

    tions, giving the elements of the overall mainte-

    nance program rather than the details.

    2-2 . Me t a l enc los u res .

    Mainten an ce is r ecommended below:a. With power off and t he bu s properly grounded,

    open the enclosure and remove any accumulated

    dust and dirt. Vacuum cleaning is recommended;

    blowing with compr essed air is not.

    b. Check structure and anchor bolts for tight-

    ness . For bus and breaker connect ions ensure

    ma nu factu rers specified torques ar e used.

    c. Clean and lubricate circuit breaker racking

    mechanisms with a non-hardening, non-conductive

    grease.

    d. Inspect operation and adjustment of safety

    shutters, mechanical and key interlocks, auxiliary

    and limit switches.e. Clean and inspect strip heaters.

    f. Clean any air filters that are installed in the

    ventilation openings.

    g. Inspect all relays, contractors, switches, fuses,

    and other auxiliary devices for correct operation

    an d cleanliness.

    h. Tighten control wiring connections.

    i. Inspect alignment and contacting of primary

    disconnecting devices, checking for signs of abnor-

    ma l wear or oth er da ma ge. Discoloration of th ese or

    other silvered surfaces is not usually harmful un-

    less caused by sulphide deposits, which can be re-

    moved by a solvent, su ch as a lcohol, or silver p olish.j. A f t e r c l e a n i n g , m e a s u r e t h e r e s i s t a n c e t o

    ground and between phases of the bus with a

    megohmmeter (para 14-2). It is not possible to give

    definite limits for satisfactory insulation resistance

    values, so that a change in the reading from one

    inspection per iod to an other is t he best indicat ion of

    any weakening tendency. The readings should be

    taken under similar conditions each time, and the

    record should include temperature and humidity.

    k. Before replacing th e breaker , wipe the pr imar y

    disconnecting device contacts. Apply a thin coat of

    2-1

  • 8/7/2019 army tm 5-683

    11/180

    TM 5-683/NAWAC MO-116/AFJMAN 32-1083

    contact lubricant to the stationary studs and to the

    primar y disconnects on t he break er.

    l. Ensure that all metal shields are securely in

    place. These shields must be installed to confine any

    blast in t he event of circuit br eaker failure.

    (1) A n ote on lubricants. One of the most useful

    lubricants for motors is an extreme pressure (EP)

    lithium-base petroleum grease. As the usage of

    Class F winding temperature ratings has increased,

    however, others have adopted synthetic greases to

    withstan d h igher bearing temperatur es.

    (2) Synthetic oils and greases. Synthetic oils

    and greases compounded from various silicones,

    alkyl benzene, diesters, and fluorinated ethers, are

    available for extremely high-temperature service

    tha t would cau se prema tur e oxidation of petroleum

    lubricants. Some synthetics also suit extremely low

    temperature, down to 40 or 50 degrees below zero.

    The main uses for synthetic lubricants in motorbear ings are reduced f r ic t ion and res is tance to

    moisture and chemical contamination. Such appli-

    cations must be carefully worked out with bearing

    and lubricant suppliers, becau se no universal lubri-

    cant formulation will apply to all environments.

    However, it is not unusual for lubricant to vary

    little more than brand name. Thus substitutions are

    often possible. Consu lt with t he ma nufacturer of the

    switchgear to determine the important characteris-

    tics of the lubricant prior to specifying a substitute

    lubricant. Carefully selected substitutes will reduce

    the cost of procurement, stocking and dispensing.

    2 -3 . Bus ba r an d t e rm ina l c onnec t i ons .

    Many failures are at tribut able to improper term ina-

    tions, poor workm ansh ip, and different characteris-

    tics of dissimilar metals. Loose bus bar or terminal

    connections will cause overheating which can be

    easily spotted by a discoloration of the bus bar. A

    thermographic survey can be conducted to detect

    overheating before discoloration occurs (para 14-7).

    An overheating condition will lead to deterioration

    of the bus system as well as to equipment connected

    to the bus; i.e. protective devices, bus stabs, etc.

    Therefore, bus ba r a nd t erminal connections should

    be regularly checked to ensure that they are prop-

    erly tightened without damaging the conductors.

    Special attention should be given where excessive

    vibration may cause loosening of bolted bus and

    terminal connections. Tightening torque values for

    electrical connections are provided in table 21.

    This information should be used for guidance only

    wher e no tighten ing inform at ion on t he specific con-

    nector is available. It should not be used to replace

    ma nu factu rer s instr uctions which should always be

    followed. Do not assume that once a connection has

    been torqued to its proper value that it remains

    2-2

    tight indefinitely. If signs of arcing are evident , then

    the connections should be broken and the connect-

    ing surfaces cleaned. Because of the different char-

    acteristics of copper and aluminum, they should not

    be intermixed in a terminal or splicing connector

    where physical contact occurs between them, unless

    the device is suitable for the purpose and conditions

    of use. Materials such as solder and compounds

    shall be suitable for the use and shall be of a type

    which will not adversely affect the conductors.

    a. Aluminum connectors. Special considerations

    must be given to aluminum connections. Aluminum

    connectors are plated and should not be cleaned

    with abrasive. If these connectors are damaged,

    they should be replaced. It should be noted that

    when making connections with aluminum conduc-

    tors, be sure to use a joint compound made for the

    purpose. To assist in the proper and safe use of solid

    aluminum wire in making connections to wiringdevices, refer to the National Electrical Code. Make

    aluminum connections with solderless circumferen-

    tial compression-type, aluminum-bodied connectors

    UL listed for AL/CU. Remove surface oxides from

    aluminum conductors by wire brushing and imme-

    diately apply oxide-inhibiting joint compound and

    insert in connector. After joint is made, wipe away

    excess joint compound and insulate splice.

    b. Bus insulators and barriers. Bus bar support

    insulators and/or barriers should be wiped with a

    clean cloth. Do not use steel wool or oxide papers to

    remove dirt; use a cleaning solvent that will not

    leave trace deposits. While cleaning, check insula-tors for cracks and signs of arc tracking. Defective

    units should be replaced. Loose mounting h ardwar e

    should be tightened.

    2-4. Under f loo r duct s .

    All undefloor duct systems require checks for evi-

    dence of oil and water. Entrances and fi t t ings

    should be checked and corrected as necessary to

    prevent entrance of liquids, insects, and rodents.

    Cockroaches, ants, beetles and rodents have been

    known to at tack cable insulat ion, especial ly if

    greases or oils are present. External heat and heat

    caused by overloaded circuits can cause cracking of

    cable insulation and drying of taped splices. Mois-

    ture can then penetrate the cable and could cause a

    fault. Therefore, underfloor conduits and duct sys-

    tems should be kept sufficiently clear of electrical

    and hot water floor-heating systems to prevent un-

    due h eating of the en closures.

    2-5. Busways.

    Feeder busway, trolley busway and plug-in busway

    (fig 21) require annual cleaning and removal of oil

    substa nces and dirt . Ventilated-type busway should

  • 8/7/2019 army tm 5-683

    12/180

    TM 5-683/NAWAC MO-116/AFJMAN 32-1083

    NOTE : REDUCE TORQUE BY 20% WHEN CADMIUM P LATED BOLTS ARE U S ED.

    have the bus bars cleaned annually with clean, dry

    compressed air a t a maximum pressure of 50

    pounds per square inch. Plug-in devices should be

    s e r v i c e d u s i n g t h e s a m e p r o c e d u r e s a s o t h e r

    switches or breakers. The plug-in bus or prongs

    should be checked annually for annealing or corro-

    sion on all connections which are rated in excess to

    75 percent of the r at ing of th e bus d uct. Conn ections

    should not be retorqued as part of a routine main-

    tenance procedure unless visibly loose or shown to

    be loose by an infrared scan. All busway connections

    should be torqued according to manufactures rec-

    ommendations. If this information is not available,

    use the torque specifications in table 2-1. Inspect to

    ensure that :

    a. Ventilation continues to be adequate.

    b. Clearances are maintained and encroachment

    from other equipment facilities has not occurred.

    2-6. Pow er c i rc u i t b reakers .

    Power circuit breakers encompass all breakers ex-

    cept molded case breakers and breakers used for

    control applications. It is recommended that power

    circuit breakers be inspected once a year after in-

    stallation. More frequent inspections are recom-

    mended where severe load conditions, dust, mois-

    ture or other unfavorable conditions exist, or if the

    vital nature of the load warrants it. Any breaker

    that has interrupted a fault at or near its short

    circuit rating should be inspected immediately after

    the interrupt ion and serviced i f necessary. Re-

    energize equipment completely before working on

    any devices, connections, bus work, breaker orfeeder cab le compar tments . Th is inc ludes de-

    energizing any connections to outside primary or

    secondary sources such as transformers, tie lines,

    etc. Manufacturer s inst ru ction docum ents should

    also be obta ined an d rea d carefully before disas sem-

    bly or adjustments are performed.

    a. Drawout circuit breakers. A drawout - type

    breaker should be tested and inspected for proper

    operation as follows:

    (1) Withdraw the breaker to the test position.This position disconnects the primary power circuit

  • 8/7/2019 army tm 5-683

    13/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    FEEDERBUSWAY

    PLUG-IN

    N>

    BUSWAY

    Figure 2 -1 . Typ ica l busw ay ins ta l la t ion .

    but leaves the control circuits energized (fig 2-2). If

    a test position is not provided, then complete-

    ly withdraw the circuit breaker from its compart-

    ment and use a test coupler to provide control

    power.

    (2) Test for voltage to ma ke sur e th at all path sof potent ial ba ckfeed from cont rol power circuits , as

    well as outside sources, are disconnected. This is

    especially important if an external source of control

    power is being used for testing.

    (3) Operate the breaker and check all func-tions. Use both the electrical means (when pro-

    vided) and the mechanical means to charge, close

    and trip the breaker. This is particularly important

    for breakers that normally remain in either the

    opened or closed position for long periods of time.

    (4) Remove the breaker from its compartment

    to a clean maintenance area. Close the compart-

    ment door and cover the breaker cutout to prevent

    access to live parts.

    (5) Check and lubricate all safety rollers and

    auxiliary contacts. Check all mechanical clearances

    to ensure they are within manufacturer specified

    toleran ces. Also inspect an d lubricate bus stabs and2-4

  • 8/7/2019 army tm 5-683

    14/180

    TM 5-683/NAVFAC M116/AFJMAN 32-1083

    \

    ~DISCONNECTEDALL POWER DISCON-NECTED

    WITHDRAWNBREAKER WITHDRAWNREADY FOR REMOVAL

    Figure 2-2. Drawou t c i r cui t break er pos i t i ons .

    ac/dc control block contacts. Verify correct operation

    of trip free and anti-pump mechanisms.

    b. Fixed circuit breakers. Maintenance on fixed-

    or bolter-type circuit breakers is normally per-

    formed with the breaker in place inside its cubicle.

    Special precautions must be exercised to assure

    equipment is de-energized and the circuit in which

    it is connected is properly secured from a safety

    s tandpoint . Al l cont rol c i rcui t s should be de-

    energized. Stored energy c los ing mechanismsshould be discharged.

    c. Power circuit breaker components. M a i n t e -

    nance on all power circuit breakers will encompass

    maintenance on the following components.

    (1) Insulation. The general rule for insulationis keep it clean and dry. Remove interpha se barr iers

    and clean them and all other insulating surfaces

    with dry compressed air and a vacuum cleaner.

    Wipe insulation with clean lint-free rags and sol-

    vents as r ecommended by the ma nufacturer if hard-

    ened or encrusted contamination must be removed.

    Repair moderate damage to bushing insulation by

    sanding smooth and refinishing with a clear insu

    lating varnish. Check insulating parts for evidence

    of overh eat ing an d for cracks t ha t indicate excessive

    thermal aging.

    (2) Contacts. The major function of the power

    circuit breaker depends among other things upon

    correct operation of its contacts. These circui

    breakers normally have at least two distinct sets o

    contacts on each pole, main and arcing (fig 2-3)Some have an intermediate pair of contacts which

    open after the main contacts and before the arcing

    contacts.

    (a) Main contacts. W hen the b reake r i s

    closed, practically the entire load current passe

    through the main contacts. Also, short circuit cur

    rent must pass through them during opening o

    closing faulted lines. If the resistance on these con

    tacts becomes high, they will overheat. Increased

    contact resistance can be caused by pitted contac

    surfaces, foreign material embedded on contact sur

  • 8/7/2019 army tm 5-683

    15/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    FIXED ARCING CONTACT

    MOVABLECONTACT

    MOVABLE MAIN

    CONTACT

    ARCI

    Figure 2-3 . Power c i rcu i t break er m a in an d a rc ing con ta c t s .

    faces, or weakened contact spring pressure. This (c) Contact maintenance. The general rules

    will cause excessive current to be diverted through

    the arcing contacts, with consequent overheatingand burning.

    (b) Arcing contacts. Arcing contacts are the

    last to open; any arcing normally originates on

    them. In circuit interruption, they carry current

    only momenta rily, but tha t current may be equal to

    the interrupting rating of the breaker. In closing

    against a short circuit, they may momentarily carr y

    considerably more than the short circuit interrupt-

    ing rating. Therefore, they must make positive con-

    tact when they are touching. If not, the main con-

    tacts can be badly burned or may r esult in a failure

    to interrupt a fault.

    for maintaining contacts on all types of breakers

    are: keep th em clean, a ligned an d well adjusted. Toinspect t he circuit brea ker conta cts, th e ar c chut es

    must be removed. When doing this, check the arc

    chutes for evidence of damage, and replace dam-

    aged parts. If not damaged, then blow off dust or

    loose part icles. Once the m ain conta cts ar e exposed,

    inspect their condition. Slight impressions on the

    stat ionar y conta cts caused by the pr essure an d wip-

    ing action of the m ovable cont acts is tolerable. Con-

    tacts which have been roughened in service should

    not be filed but large pr ojections, caused by un usu al

    arcing, should be removed by filing. When filing,

    take care to keep the contacts in their original de-

  • 8/7/2019 army tm 5-683

    16/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    sign. That is, if the contact is a line type, keep the

    area of contact linear, and if ball type, keep the ball

    shaped out. Discoloration of silver-plated surfaces is

    not usually harmful unless caused by insulating

    deposits. These deposits should be removed with

    alcohol or a silver cleaner. Whether cleaned or not,lubricate the main contacts by applying a thin film

    of slow aging, heat resistant grease. All excess lubri-

    cant should be removed with a clean cloth to avoid

    accumulation of dirt and dust. Under no circum-

    stances should the arcing contacts be lubricated.

    Where ser ious overhea ting is indicated by discolora -

    tion of metal and surrounding insulation, the con-

    tact and spring assemblies should be replaced in

    accordan ce with m an ufactur ers instr uctions. While

    carefully closing the circuit breaker, check for

    proper gap, wipe and contact alignment. Contact

    gap is the distan ce between t he sta tionar y and mov-

    able contacts with the circuit breaker in the fully

    open position. If th e ar cing cont act gap is too small,

    a circuit breaker may not be able to interrupt a

    fault. If the main contact gap is too small, the mainconta cts will interr upt the fault a long with th e arc-

    ing contacts and possibly burn the main contacts.

    Contact wipe is the amount of over travel between

    the stationary and movable contacts from the time

    when the contacts are just touching to the time

    when the circuit breaker is fully closed (figs 24,

    25, and 26). Check that all contacts make and

    break at approximately the same time. Make ad-

    justments in a ccordance with the man ufactur ers

    recommenda tions. Lam inated copper or brush style

    b

    F i g u r e 2-4. A r c i n g c on t a c t g a p a n d w i p e .

    CONTACT WIPE

    2-7

  • 8/7/2019 army tm 5-683

    17/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    ACRING CONTACTS

    TOUCHING

    CON

    Figure 2-5 In term ed ia te con ta c t gap .

    contacts found on older circuit breakers should be

    replaced when badly burn ed. Repairs ar e not pra c-

    tical because the laminat ions t end t o weld together

    when burning occurs, and contact pressure and

    wipe are greatly reduced. These contacts may be

    filed to remove large projections or to restore their

    original shape. They should be replaced when theyare burned sufficiently to prevent adequate circuit

    breaker operation or when half of the contact sur-

    face is burn ed awa y. Car bon conta cts, used on older

    circuit breakers, require very little maintenance.

    However, inadequate contact pressure caused by

    erosion or repea ted filing ma y cau se overh eat ing or

    interfere with their function as arcing contacts.

    (3) Operating mechanism. The purpose of the

    operating mechanism is to open and close the

    breaker contacts. This usually is done by linkages

    conn ected, for most power brea kers , to a power op-

    erating device such as a solenoid or closing spring

    2-8

    for closing, and contains one or more small sole-

    noids or oth er t ypes of electro-ma gnets for t ripping.

    Tripping is accomplished mechanically, independent

    from t he closing device, so th at th e break er cont acts

    will open even though the closing device still may be

    in the closed position. This combination is called a

    mechanically trip-free mechanism. After closing,the primary function of the operating m echan ism is

    to open the breaker when it is desired, which is

    whenever the tripping coil is energized at above its

    rat ed minimum operat ing voltage. The breaker op-

    erating mechanism should be inspected for loose or

    broken part s; missing cotter pins or reta ining keep-

    ers; and missing nuts and bolts. It should also be

    examined for damage or excessive wear on cam,

    latch, and roller surfaces. Excessive wear usually

    results in loss of travel of the breaker contacts. It

    can affect operation of latches; they may stick or

    slip off and prematurely trip the breaker. Adjust-

  • 8/7/2019 army tm 5-683

    18/180

    TM 5 + 5 8 3 / N A V F A C MO-1 1 6 /AFJMA N 32-1083

    11L 1 3nCONTACT WIPE16 32

    Figur e 2-6. Main contact wipe.

    menta for excessive wear are possible for certain lubricate pins and bearings not disassembled. Useparts. For others, replacement is necessary. The non-hardening and non-conductive grease to lubclosing and tripping action of a breaker should be cate the ground or polished surfaces of cam

    quick and positive. While documenting, operate the rollovers, latches and props, pins and bearings th

    breaker several times, checking for obstructions or are removed for cleaning. Check the breaker ope

    excessive friction. Any binding, s low a ction, d elay in ating mechanism adjustments and readjust as d

    speration, or failure to trip or latch must be con- scribed in the manufacture% instruction book.

    rected prior to returning to service. Clean and these adjustments cannot be made within specifie

    relubricate the operating mechanism. Use a tolerances, it will usually indicate excessive we

    nondetergent light machine oil (SAE-20 or 30) to and the need for a complete overhaul.

    2-

  • 8/7/2019 army tm 5-683

    19/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    (4) T rip devices. The tr ip devices on low voltage

    circuit breakers provide the electrical decisions

    needed to detect th e difference between normal a nd

    abnormal conditions of current flow. The mainte-

    nance and adjustment of these devices is just as

    importa nt as t he work per formed on t he ma in con-

    tacts and operating mechanism. The trip devices

    are either electro-mechanical or solid-state. Both

    types are responsible for providing various degrees

    of fixed, short, or inverse time delays based on the

    am ount o f cu r ren t t hey sense . The e l ec t ro -

    mechanical type, with an air or fluid dashpot for

    time delay, should be tested as part of the mainte-

    nance work performed. A dashpot is a pneumatic or

    hydraulic device used for cushioning or damping of

    movement t o avoid mechanical shock an d consist ing

    essent ially of a cylinder cont ainin g air or liquid an d

    a piston moving in i t . Testing of the electro-

    mechan ical devices requ ires th e use of a low voltage

    (abou t 0 -20V ) bu t h igh cu r ren t (usua l ly O -

    50,000A) prima ry injection t est s et des igned specifi-cally for this purpose. Calibration tests should be

    ma de to verify tha t t he per form an ce of the device is

    within the values shown on the m anu factur ers pub-

    lished curves; taking into account that the time-

    current curves are plotted as a band of values

    rather than a single line (fig 27). Pay careful atten-

    tion to how the manufacturer has presented the

    curve data. There is a wide variety of formats.

    Check to see tha t th e curr ent is in amperes or mul-

    tiples of a pickup value and whether temperature

    ranges or previous conditions will affect results.

    Usually, the trip devices are tested one unit at a

    time. There are some devices which m ay use a ther-mal element for time delay. These may have to be

    tested all at once to get results similar to those

    published by the m anu factur er. Check th e test con-

    ditions carefully. If the trip devices do not operate

    properly, the calibration and timing components

    should be adjusted or replaced per the ma nufactur-

    ers recomm enda tions. If repair or r eplacement of

    the electro-mechanical devices is being considered,

    then thought should be given toward retrofitting

    the existing breaker with solid-state trip devices.

    This newer technology is generally more reliable

    because t he par ts used to make t he tr ip unit do not

    drift out of adjus tm ent or suffer t he effects of aging

    or contaminat ion to the same degree as thei r

    electro-mechanical forerunners. If the breakers are

    already equipped with solid-state trip devices, they

    should also be checked for proper operation and

    time delay in accordan ce with th e man ufactur ers

    published curves. The test procedure recommended

    by the manufacturer should be followed.

    (5) Auxiliary devices. Inspect the closing motoror solenoid, shunt trip coil and mechanism, alarm

    2-10

    mechanisms, and the control wiring for correct op-

    erations, insulation condition and tightness of con-

    nections. Check on-off indicators, sprin g-char ge in-

    dicators, mechanical and electrical interlocks, key

    interlocks, and lock-out fixtures for proper opera-

    tion and lubricate where required. In particular,

    test the positive interlock feature which prevents

    th e insert ion or removal of th e break er while it is in

    the closed position. Check control devices for free-

    dom of operation. Replace contacts when badly worn

    or burned. After the breaker has been serviced,

    manually operate it slowly with a closing device to

    check for tightness or friction and to see that the

    contacts move to their fully open and fully closed

    positions. Electrically operate the breaker several

    times to check the performance of the electrical ac-

    cessories using the TEST position, an external

    test /contr ol cabinet, or a t est coupler.

    2-7 . Netw ork pro tec tors .

    The current-carrying parts, main contacts, and op-erat ing mechan ism of a n etwork pr otector a re very

    similar t o th ose of th e air circuit br eaker . This simi-

    larity usually ends with the principal mechanical

    devices. Unlike the usual feeder circuit breaker, the

    network protector is more like a tie circuit breaker;

    that is, it is almost always energized on both sides.

    This condition r equires tha t extreme care be taken

    during inst allation or removal of the un it from ser-

    vice. The net work protector is equipped with special

    relays tha t sense t he net work circuit conditions a nd

    command the mechanism to either open or close

    automatically in response to those conditions. Net-

    work protectors are used where large amounts ofpower must be distributed to high density load ar-

    eas such as commercial buildings and office com-

    plexes. To form a network, several incoming power

    sources may be connected. As a result, a short cir-

    cuit a t any point in the system usu ally involves very

    high fault currents.

    a. Safety precautions. Due to the construction

    and purpose of the network protector, ta king it out

    of service or p lacing it back in service is a procedure

    that must be done while the circuit is energized.

    During th is work, always use t he special insulat ed

    tools provided with the particular model to be ser-

    viced. Alternate or make-shift tools are not recom-

    mended unless they have been laboratory tested

    and are known to have good safety performance.

    Electrical grade, safety gloves should still be worn

    by the person servicing the unit regardless of the

    type or condition of th e tools u sed.

    b. Main tenance. A routine maintenance schedulefor network protectors should be observed. The fre-

    quen cy of inspection will var y based on th e locat ion

    and environment in which t he un it is installed, and

  • 8/7/2019 army tm 5-683

    20/180

  • 8/7/2019 army tm 5-683

    21/180

    TM 5 -683/NAVFAC MO-116/AFJMAN 32-1083

    the number of operations the unit has made. In all

    cases, open the circuit first. This is done by moving

    t h e c o n t r o l h a n d l e f r o m A U T O M A T I C t o

    MANUAL and then manually opening the circuit.

    The control handle and/or operating mechanism

    should t hen be locked in t he OPEN position beforefurther work is done. Maintenance should include

    cleaning any accumulation of dust, dirt or corrosion

    deposits, a thorough visual inspection, and overall

    performa nce tests. Should the opera tion of any par t

    be suspect, refer t o the m anu factur ers instr uctions

    describing operation, adjustment, and replacement

    of these part s. If th e network sensing relays are out

    of calibration, they should be recalibrated by com-

    petent shop personnel. The network protector is

    housed in a cell or enclosure similar to those used

    for air circuit breakers (fig 2-8). The circuit breaker

    mechanism and the network relay panel assembly

    of a net work protector ar e usu ally constructed aa anintegral, drawout unit which must be withdrawn

    fmm the housing for proper maintenance. Removal

    is done by unbolting the fuses at the top (usually)

    and the disconnecting links at the bottom (some

    models have bolt-actuated disconnecting fingers at

    the bottom). After removing any additional lock-

    down bolts or latches, the drawout unit may be

    carefully withdrawn using the rails provided for

    support . Although this provides a comparative

    measure of safety, work should be done cautiously

    since there is voltage present within the enclosure.

    It is better to move the unit completely away fromth e en closure (fig 29). The following insp ection an d

    maint enan ce operat ions can be done on t he dra wout

    unit :

    (1) Clean the breaker assembly. Use of avacuum cleaner is preferred. Use cloth rags free of

    oil or grease for removing clinging dirt.

    (2) Remove arc quenchers. Replace if damaged.

    (3) Inspect main contacts (fig 2-10). Smooth

    any heavily frosted area with a very fine file or a

    burnishing stone which does not shed abrasive par-

    ticles. Protect hinged joints from falling particles

    during filing.

    (4) File smooth any especially high projections

    of metal on arcing contacts.

    (5) See that all electrical connections are tight.

    (6) Look for any abrasion of wire insulation

    and repair .(7) Check for signs of overheating of control

    wire and current carrying parts.

    (8) See that all springs are in good condition

    and are properly seated in place.

    (9) See tha t a ll nuts, pins, snap r ings or r etain-

    ers, and screws are in place and tight.

    (10) Replace any broken or missing barriers.(11) With the rollout unit still set aside, per-

    form the following maintenance operations inside

    the enclosure:

    **WARNING**B o t h s o u r c e a n d l o a d t e r m i n a l s a r e p r o b a b l y s t i l l e n e r g i z e d . U s e i n s u l a t e d t o o l s a n d s a f e t y

    p r o t e c t i v e e q u i p m e n t f o r t h i s w o r k . D o n o t r e m o v e a n y b a r r i e r s f r o m t h e e n c l o s u r e .

    (a) Look for loose hardware on the enclosurebottom or beneath the frame. If any is found, trace

    to source and correct problem or replace.

    (b) Clean sta nd-off bus insulators.

    (c) Remove oxide film from ter mina l cont actsif necessary.

    (12) M anua l ly c lose and t r i p t he b reake r

    mechanism according to instructions furnished for

    the particular model.(13) Perform an operational test using a net-

    work protector test kit.

    (14) Conduct insulation resistance tests, di-

    electric test and electrical operating test in accord-

    ance with the man ufactur ers r ecommenda tions.

    (15) Carefully replace the drawout unit in theenclosure. Make a final inspection to be sure no

    control wiring has become snagged, and that no

    plugs or connecting surfaces have been bent or dam-

    aged.

    2-8 . Aux i l ia ry sw i t chgear equ ipment .

    Auxiliary equipment includes devices such as fuses,

    capacitors, meters, relays, etc. This equipment

    should be serviced along with the major switchgear

    components, unless there is some indication that a

    device is being heavily or improperly used, in which

    case it should be inspected more often. Protective

    relays and meters should be inspected and cali-brated on a scheduled basis. Critical service equip-

    ment should have the protective relays checked at

    every maintenance turn (annually or according to

    ma nu facturer s recommen dat ions). Relays applied

    to other general distribution circuits may be done

    less frequently (see para 2-8h).

    a. Fuses. Fuse maintenance is covered as a sepa-

    rate category of electrical equipment (para 5-4d).

    b. Capacitors.

    power capacitor

    The maintenance requirement on

    installations is so small that its

    2-12

  • 8/7/2019 army tm 5-683

    22/180

    TM 5-683/NAVFAC MO-116/AFJMA N 32-1083

    ) INGs

    BREAKER UNIT J COUPLING

    Figure 2-8 . Typ ica l dr awou t ne twork pro tec tor and enc losure .

    H o l e s Fo r

    M o u n t i n g

    Sc rew s

    ( Two OnEach Side

    Figu re 29. Net work protect or rem ovable un it .

    importance is often overlooked. The voltage of the

    system at the capacitor location should be checked

    at light load periods to determine if an overvoltage

    condition exists . Any cha nges in circuit conn ections,

    which may increase voltage levels, warrant a re-

    check of operating conditions. The conductor sizes

    should provide for not less than 135 percent of ca-

    pacitor current at rated voltage and WA. As a gen-

    eral rule, if the side of the capacitor unit casing is

    operat ing at a tempera tur e above 55 degrees C (131

    degrees F a temperature almost too hot for bare-

    hand contact), then a more complete investigationof operating conditions should be made. The case

    temperatures should never exceed 65 degrees C

    (149 degrees F) under any conditions. Adequate

    ventilation is therefore necessary to remove the

    heat generated by continuous full-load duty. Re-

    move any obstructions at ventilation openings in

    capacitor h ousings to ensur e th at this ventilation is

    maintained. A disconnected capacitor retains its

    electrical charge for some time and may even retain

    the full-line voltage across its terminals. Therefore

    always discharge a capacitor before handling or

    making connections. An insulat ion short circuitjumper may be used for this purpose; however, it

    should only be applied with full knowledge of the

    circuit, and with the use of appropriate protective

    equipment. Power capacitors are generally provided

    with individual fuses to protect the system in case

    of a short circuit within the capacitor. In addition to

    a faulty capacitor, a fuse may be blown by an abnor-

    mal voltage surge. Check for blown fuses and re-

    place them with a type recommended by the manu-

    facturer. Do not remove fuses by hand until the

    capacitor has been completely discharged. Clean the

    case of a capacitor, the insu lating bush ings, and a ny

    2-13

  • 8/7/2019 army tm 5-683

    23/180

    TM 5-683/NAVFAC MO-1 16/AFJ MAN 32-1083

    ARCQUENCHER

    BLOWOUT

    COIL

    ARC

    QUENCHERSUPPORTINGSCREWS

    SCREWS FORMOVABLE

    ARCING

    CONTACT

    LOCKING

    PLATE

    FLEXIBLECONNECTION

    STOP PINFOR MOVABLE

    ARCINGCONTACT

    CONTACT

    SUPPORT

    CROSS BAR