argumentaire rlc gb - profroidthe " rlc " range of profroid is the compact chiller...
TRANSCRIPT
The " RLC " range of PROFROID is the compact chiller specially designed for all your refrigeration applications.
Strong of 12 models, " RLC " covers a very wide range of cooling capacity from 200 kW up to 700 kW (MEG 35% At -8/-4°C and condensation +45°C).
Using screw compressor running with R134a allows a lower impact on the climate warming and optimal energy performance.
Chiller with remote condenser
" RLC "blue:pantone 072CCMYK 100, 88, 0, 5green:pantone 362CCMYK 50, 0, 100, 10
blue:pantone 072CCMYK 100, 88, 0, 5green:pantone 362CCMYK 50, 0, 100, 10
w w w . p r o f r o i d . c o m
Feel free to consult our teams for any supplementary question on the range of PROFROID chillers.
PRACTICAL INNOVATION
A RANGE SPECIALLY DESIGNED FOR THE NEEDS OF THE REFRIGERATION TECHNICIANS
• 12 models up to 700 kW per unit. • 2 cooling circuits (2 or 4 compressors) on all models to secure operations. • Liquid tank integrated or deported with possibility to oversize. • Suction and discharge valve on each circuit. • Integrated electrical cabinet with adaptable Short Circuit Current and neutral system. • Electronic controller with open protocol. • Oil balancing system managed by the Electronic controller to secure the operation. • Option compressors sound insulation (-10dBa).
178, rue du Fauge - Z.I. Les Paluds - BP 1152 - 13782 AuBAgnE Cedex - FrAnCE - Tél. +33 4 42 18 05 00 - Fax +33 4 42 18 05 02 - Fax Export : +33 4 42 18 05 09
A DESIGN FOCUSED ON ENERGY SAVINGS
• Screw Compressor CSH last generation for an optimized COP. • Economiser guaranteeing a permanent liquid sub cooling. • Electronic expansion valve on the heat exchanger. • Innovative algorithm to control the capacity control while optimising continuously the COP. • Option " Desuperheater " preselected for heat recovery. • Option " Inverter " on compressors.
SOLUTIONS FOR OUTDOOR APPLICATIONS
Beyond the " rLC " range PrOFrOID also boasts custom made outdoors chillers up to 700 kW.
MAIN FEATURES
Designationnb
Comp.
PF Pa Dimensions (mm)Discharge (x2)
Ø
Receiver (x2) Hydraulic
kW kW Lenght Widht Height Type Ø In Ø OUT Ø VICTQV
(m3/h)Pdc (hPa)
rLC-2CSH7583-80Y 2 197 91 4200 1730 2400 2"1/8 70 L 2"1/8 1"3/8 Dn150 47.5 35
rLC-2CSH7593-90Y 2 221 102 4200 1730 2400 2"1/8 70 L 2"1/8 1"3/8 Dn150 53.4 43
rLC-2CSH8563-90Y 2 242 114 4200 1730 2400 2"1/8 70 L 2"1/8 1"5/8 Dn150 59.4 51
rLC-2CSH8573-110Y 2 281 128 4200 1730 2400 2"1/8 70 L 2"1/8 1"5/8 Dn200 67.7 42
rLC-2CSH8583-125Y 2 311 144 4700 1730 2400 2"1/8 70 L 2"1/8 1"5/8 Dn200 74.8 23
rLC-2CSH8593-140Y 2 349 162 4700 1730 2400 2"1/8 70 L 2"1/8 1"5/8 Dn200 83 27
rLC-4CSH7583-80Y 4 394 182 5000 2200 2400 2"1/8 140L 2"1/8 2"1/8 Dn200 95 65
rLC-4CSH7593-90Y 4 442 205 5000 2200 2400 2"1/8 140L 2"1/8 2"1/8 Dn200 104.95 77
rLC-4CSH8563-90Y 4 483 229 5000 2200 2400 3"1/8 140L 2"5/8 2"1/8 Dn200 116.4 52
rLC-4CSH8573-110Y 4 563 256 5000 2200 2400 3"1/8 140L 2"5/8 2"1/8 Dn200 135.33 59
rLC-4CSH8583-125Y 4 622 289 5000 2200 2400 3"1/8 140L 2"5/8 2"1/8 Dn200 148.4 69
rLC-4CSH8593-140Y 4 698 325 5000 2200 2400 3"1/8 140L 2"5/8 2"1/8 Dn200 166.2 83