areaclassification t ratings

7
CLASS I (Gas and Vapors) Hazardous Substances CHART (PDF) Class I locations are those in which flammable gases or vapors are or may be present in the air in quantities sufficient to produce explosive or ignitable mixtures. (“Gases” refers to materials that are in a gaseous state under normal atmospheric conditions. Examples of this would be hydrogen or methane. “Vapors” refers to the gases over a material that is a liquid under normal atmospheric conditions but emits gases within the flammable range under these atmospheric conditions.) Division 1 locations are those where the volatile flammable gases or vapors exists under normal conditions, or where volatile flammable gases or vapors may exist frequently because of repair or maintenance operations or leakage, or where breakdown or faulty operation of electrical equipment or processes might release ignitable concentrations of flammable gases or vapors, and might also cause simultaneous failure of electrical equipment in such a way as to directly cause the electrical equipment to become the source of ignition. An example of this might be an area where a flammable liquid is stored under cryogenic conditions, and a leak directly into the electrical equipment could cause a failure of the electrical equipment at the same time the vapors of the evaporating liquid are within the flammable range.) locations are those locations where ignitable concentrations of flammable gases or vapors are not likely to exist under normal conditions, or in locations that are adjacent to Class I, Division 1

Upload: ger80

Post on 18-Jul-2016

10 views

Category:

Documents


1 download

DESCRIPTION

LDPI Lighting area classification t ratings

TRANSCRIPT

Page 1: AreaClassification T Ratings

HOME PRODUCTS APPLICATIONS PRODUCT CONFIGURATOR RESOURCES ABOUT LDPI CONTACT

Home • Resources • Codes • Class1

CLASS ICEC/NEC (North American) Area ClassificationsFlammable gases, vapors or liquidsCLASS I (Gas and Vapors) Hazardous Substances CHART (PDF)

Class I locations are those in which flammable gases or vapors are or may be present in the air in

quantities sufficient to produce explosive or ignitable mixtures. (“Gases” refers to materials that are in

a gaseous state under normal atmospheric conditions. Examples of this would be hydrogen or

methane. “Vapors” refers to the gases over a material that is a liquid under normal atmospheric

conditions but emits gases within the flammable range under these atmospheric conditions.)

Division 1

locations are those where the volatile flammable gases or vapors exists under normal conditions, or

where volatile flammable gases or vapors may exist frequently because of repair or maintenance

operations or leakage, or where breakdown or faulty operation of electrical equipment or processes

might release ignitable concentrations of flammable gases or vapors, and might also cause

simultaneous failure of electrical equipment in such a way as to directly cause the electrical

equipment to become the source of ignition. An example of this might be an area where a flammable

liquid is stored under cryogenic conditions, and a leak directly into the electrical equipment could

cause a failure of the electrical equipment at the same time the vapors of the evaporating liquid are

within the flammable range.)

Division 2locations are those locations where ignitable concentrations of flammable gases or vapors are not

likely to exist under normal conditions, or in locations that are adjacent to Class I, Division 1

Bright IdeasInnovative SolutionsLighting for Hazardous Locations, Industrial & Commercial Applications

Search Log In

Page 2: AreaClassification T Ratings

likely to exist under normal conditions, or in locations that are adjacent to Class I, Division 1

locations where there are no barriers or partition to separate the Division 1 space from a non-

hazardous location or where ventilation failure extend the area where flammables exist under normal

conditions.

Groups

The gases and vapors of Class I locations are broken into four groups (NEC 500-503), by the codes

A, B, C & D. These divisions are because different materials have different explosion and ignition

characteristics. The grouping permits equipment to be tested based on the type of flammable

material in which it is intended to be used. It also permits area classification to be based on the type

of material anticipated in that location. The grouping is based on two major factors: the explosion

pressure generated during an explosion; and the maximum gap between ground flat mating metal

surfaces that will prevent propagation of an explosion through the gap to a flammable atmosphere of

the same flammable material and concentration. This chart shows common gases in Class I and how

they differ by ignition temperature and explosive pressure:

NFPA C Ignition F Ignition Hydrostatic Zone

Class I Group Temperature Temperature Pressure * Gas Groups

Acetylene A 305 581 6,000 PSI IIC

Hydrogen B 520 968 6,000 PSI IIC

Ethylene C 450 842 1,200 PSI IIB

Gasoline D 280 536 600 PSI IIA

* Typical tested hydrostatic pressure required for electrical fittings such as unions, elbows, seals,

etc.

Ambient temperature is the surrounding temperature of the environment in which a piece of equipment

is installed, whether it is indoors or outdoors. A heat producing product is considered acceptable for

the location, provided the minimum ignition temperature of the hazardous material present and the

ambient temperature of the location do not exceed the limits set by the manufacturer. If the ambient

temperature is higher than the maximum stated on the nameplate, it might still be acceptable to use

the product under certain conditions, providing the minimum ignition temperature of the hazardous

material has not been exceeded. In all cases, consult the factory for assistance.

Operating temperature

The rated operating temperature for hazardous (classified) products is determined by conducting

laboratory tests in an ambient temperature of 40 ° C. Products certified by the various agencies

Page 3: AreaClassification T Ratings

laboratory tests in an ambient temperature of 40 ° C. Products certified by the various agencies

consider products certified to their standards to be suitable for different temperature ranges. The

range for CSA ( Canada) is -50 ° C to +40 C to +40 ° C; the range for UL ( United States) is -25 ° C to

+40 ° C; the range for IEC and CENELEC (International) is -20 ° C to +40 ° C.

Temperature Codes (T-Codes)

The ignition temperature or auto-ignition temperature (AIT) is the minimum temperature required to

initiate or cause self-sustained combustion in a substance without any apparent source of ignition.

The lowest published ignition temperature should be the one used to determine the acceptability of

equipment. This is of particular concern when selecting heat producing equipment such as lighting

fixtures or motors which could generate sufficient heat to ignite the surrounding atmosphere.

Class I and Class II areas use T-Codes or are subject to maximum temperature limitations as shown

in the following chart. North America and the IEC are consistent in their temperature or T-Codes.

However, unlike the IEC, North America includes incremental values as shown. Equipment tested

must have nameplates and marked showing class, group and operating temperature based on

operation in a 40 ° C ambient (see NEC 500-3 for exceptions). Non-heat producing equipment does

not have this requirement.

North America Temp. Codes(NEC-500) & CSA

IE / CENELEC / US(NEC 505) T-CODES

Maximum Temperature

° C ° F

T1 T1 450 842

T2 T2 300 572

T2A 280 536

T2B 260 500

T2C 230 446

T2D 215 419

T3 T3 200 392

T3A 180 356

T3B 165 329

T3C 160 320

T4 T4 135 275

T4A 120 248

Page 4: AreaClassification T Ratings

T5 T5 100 212

T6 T6 85 185

NEC ARTICLE 505 TO INCLUDE ZONESThe rewritten Article 505 of the 1999 National Electrical Code (NEC) provides for the use of the Zone

Classification System from the Division System. Prior to insertion of the Zone Classification, the

IEC/CENELEC (for the European Union) utilized this classification system whereas the Division

System was utilized only by the NEC (for the United States). Article 505 was rewritten because the

Division Classification and the Zone Classification were difficult to merge.

Both the Zone System and the Division group classify the different gases in ascending order of “more

easily ignitable”; Group “A” in the NEC (Division System) is the most easily ignitable – Acetylene,

whereas Group “A” in the IEC (Zone System) is the least easily ignitable. Further, the IEC uses three

groups for the representative gases and the NEC uses four. AD to this confusion, the IEC and NEC

do not use the same terminology and neither have the same number of categories to identify the

likelihood of the hazard being present.

Both Division and Zone Classification Systems start with a definition if what the hazard is and the

probability the hazard will be present. The NEC Division Classification Systems uses Classes and

Groups to identify hazards:

Class I represents gases & vapors

Class II represents explosive dusts

Class III represents hazardous (flammable) fibers

Groups further define the hazard in Class I and Class II areas. In Class I, there are Group A

(Acetylene and similar gases), Group B (Hydrogen and similar gases), Group C (Ethylene and similar

gases) and Group D (Propane and similar gases). Hazardous dusts and fibers (Class II & III

respectively) are not treated in Article 505.

The IEC Zone Classification System identifies the hazard by 2 Main Groups

Group I for mining (underground locations and Group II for surface (not underground) locations.

[Further Section 90-2(b)(2) states the NEC does not cover underground mining installations.)

Group II is divided into 3 sub-groups in order of hazard to threat of ignition – Group A – the

least likely to ignite (such as Propane); Group B (gases such as Ethylene) and Group C – the

easiest to ignite (such as Acetylene and Hydrogen).

DEFINITION OF DIVISIONS

Page 5: AreaClassification T Ratings

DEFINITION OF DIVISIONSA Class I, Division 1 location is one where an explosive atmosphere is presumed to be present in

normal operation either all or part of the time.

A Class I, Division 2 location is one where volatile flammable liquids or gases are handled, processed

or used, but which are normally enclosed in containers from which they can only escape in the case

of accidental rupturing or abnormal operation of equipment.

DEFINITION OF ZONESClass I locations can further be divided into Zones based upon the frequency of occurrence and

duration of and explosive gas or vapor atmosphere as follows:

Zone 0 areas are locations in which explosive gas or vapor atmospheres are present continuously or

for long periods of time. Zone 0 areas are those where there is a flammable mixture typically more

than 1,000 hours per year.

Zone 1 areas are those in which (a) explosive gas atmospheres are likely to occur in normal

operation, or (b) explosive gas atmospheres may exist frequently because of repair or maintenance

operations or because of leakage, or (c) the location is adjacent to a Class I, Zone 0 location from

which explosive gas atmospheres could be transmitted. Zone 1 areas are those where there is a

flammable mixture more than 10 hours per year and less than 1,000 hours per year.

Zone 2 areas are those in which (a) explosive gas or vapor atmospheres are not likely to occur and if

they do occur, will exist for a short period of time, or (b) flammable liquids, gases or vapors are

handled, processed or used, but in which liquids, vapors or gases are normally confined within closed

containers or closed systems from which they can escape only as a result of accidental rupture or

breakdown of the containers or systems or the abnormal operation of the equipment by which the

liquids, gases or vapors are handled, processed or used, or (c) explosive gas atmospheres are

normally prevented by adequate ventilation but which may occur as a result of failure of the ventilation

system, or (d) the location is adjacent to a Class I, Zone 1 location from which explosive gas

atmospheres could be transmitted unless this is prevented by adequate positive-pressure ventilation

from a source of clean air and effective safeguards against failure of the ventilation system. Zone 2

areas are those where explosive gas atmospheres will exist for less than 10 hours per year.

EXAMPLES OF AREA ZONE CLASSIFICATIONZONE 0 (Continuous Grade – 1,000 hours per year)

Areas within process equipment developing flammable gas or vapors

Areas within enclosed pressure vessels or storage areas

Areas around vent pipes which discharge continually or for long periods

Page 6: AreaClassification T Ratings

Areas around vent pipes which discharge continually or for long periods

Areas over or near the surface of flammable materials

ZONE 1 (Primary Grade – 100 hours per year)

Areas above roofs outside storage tanks

Areas above floating storage tanks

Areas within specified radii around the outlet pipes and safety valves

Rooms without ventilation openings from a Zone 1 area

Areas around flexible pipelines and hoses

Areas around sample taking points

Areas around seals of pumps, compressors and similar primary sources

ZONE 2 (Secondary Grade – 10 hours per year)

Areas around flanges and connecting valves

Areas outside Zone 1 around outlet pipes and safety valves

Areas around vent openings from Zone 2.

Call (800) 854-0021 or online FIND YOUR LDPI CONTACTInterested in a quote for your next project?

LEGAL INFORMATION HELPFUL LINKS CONTACT

LDPI, INCORPORATED | 4404 ANDERSON DRIVE | EAU CLAIRE, WI 54703 | PHONE (715) 839-9585 | TOLL FREE (800) 854-0021 | FAX (715) 839-8145

LDPI® is a Registered Trademark of LDPI, Inc.Names of companies and/or products mentioned in this siteare trademarks of their respective owners.

Copyright © 2014 LDPI, Inc. All rights reserved. Terms & Conditions | Site Map

FOLLOW US ON:

Back to Top

Page 7: AreaClassification T Ratings