DIMENSIONS ARCHITECTURE INTERIORS CONSTRUCTION SERVICES WEBSITE: http://www.dimensions-architects.com E-MAIL: [email protected] INC. project title sheet project no. AS SHOWN scale revisions date checked by drawn by MEP Engineer 874 Cheltenham Way Avon, IN 46123 317.506.8151 317.745.5761 [email protected] GOODERUM & ASSOCIATES ENGINEERING P: F: E: O I H O F E T A T S P R O F E S S I O N A L E N G I N E E R T S G I RE E GOODERUM O DAVID R. 74178 R E D HAMPTON INN CINCINNATI, OHIO H-16-384 08/10/2017 - - - - - H.V.A.C. SYMBOLS, ABBREVIATIONS & SPECIFICATIONS M001 GNA MECHANICAL SPECIFICATIONS GENERAL 1. BID INSTRUCTIONS: CONTRACTORS SHALL PROVIDE BASE BID IN STRICT ACCORDANCE WITH DESIGN BASIS EQUIPMENT AND MATERIALS. PROJECT DOES ENCOURAGE COMPETITIVE PRICING AND ALLOWS FOR SUBSTITUTIONS OF EQUIPMENT AND MATERIALS AS ALTERNATE DEDUCTS TO BASIS OF DESIGN BIDS. LIST ALL SUBSTITUTIONS ALONG WITH DEDUCTS OFFERED ON BID. OWNER RESERVES THE RIGHT TO REJECT SUBSTITUTIONS FOUND NOT TO BE EQUAL TO ITEMS LISTED IN DESIGN BASIS. 2. CONTRACTORS SHALL REFERENCE APPLICABLE HAMPTON INN DESIGN CRITERIA STANDARDS FOUND AT HILTON.COM AND SHALL COMPLY WITH ALL REQUIREMENTS. 3. PRIOR TO PROCUREMENT CONTRACTOR SHALL SUBMIT TO ARCHITECT FULL SUBMITTALS FOR ALL ENERGY CONSUMING OR PRODUCING ITEMS AND FOR ALL DUCT ACCESSORIES, INSULATION, VAV BOXES, REGISTERS, GRILLES, DIFFUSERS AND LOUVERS. SUBMITTALS SHALL BE DELINEATED WITH TAGS INDICATED ON PRINTS, CONTRACTORS NAME, PROJECT NAME. CLEARLY INDICATE ALL MODEL NUMBERS AND ALL ACCESSORIES AND OPTIONS BEING PROVIDED. SUBMISSIONS SHALL BE IN PDF FORMAT. ALL EQUIPMENT AND ITEMS SHALL BE PER DESIGN BASIS OR APPROVED EQUAL. ENGINEER RESERVES THE RIGHT TO REJECT ANY SUBSTITUTE ITEM. 4. CONTRACTOR SHALL BE RESPONSIBLE TO VISIT THE SITE TO EXAMINE ALL CONDITIONS THAT MAY IN ANY WAY AFFECT THE EXECUTION OF HIS WORK. HE SHALL ALSO EXAMINE THE DRAWINGS AND SPECIFICATIONS FOR OTHER BRANCHES OF WORK MAKING REFERENCE TO THEM FOR DETAILS OF EXISTING BUILDING CONDITIONS. NO EXTRAS WILL BE ALLOWED FOR FAILURE TO INCLUDE ALL REQUIRED WORK IN THE BID. CONTRACTOR SHALL GUARANTEE ALL LABOR AND MATERIALS ENTERING INTO CONTRACT FOR A PERIOD OF ONE (1) YEAR FROM DATE OF ACCEPTANCE. 5. THE DRAWINGS IN THIS SECTION ARE DIAGRAMMATIC AND ARE NOT INTENDED TO DEFINE EXACT QUANTITIES, LOCATIONS OR CODIFIED REQUIREMENTS. DRAWINGS SHOW GENERAL INTENT OF SYSTEMS. M.C. SHALL PROVIDE AND PAY FOR ALL REQUIRED PERMITS. 6. UPON COMPLETION OF THE MECHANICAL INSTALLATION, DEMONSTRATE TO THE ENGINEER AND THE OWNER'S SATISFACTION THAT THE SYSTEMS HAVE BEEN INSTALLED IN ACCORDANCE WITH THE DRAWINGS, SPECIFICATIONS AND APPLICABLE CODES. DEMONSTRATE THE DYNAMIC OPERATION OF EACH SYSTEM. VERIFY PROPER OPERATION OF EQUIPMENT, FILTERS ARE CLEAN AND COMPONENTS OF THE SYSTEM ARE INSTALLED AND ADJUSTED IN FULL ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS. 7. ALL WORK SHALL BE IN FULL ACCORDANCE WITH CURRENT OHIO NON-RESIDENTIAL MECHANICAL CODES. FOR MORE INFORMATION REFERENCE WEB SITE. http://www.com.ohio.gov/DICO/bbs/NonResidential BuildingCodes.aspx#OMC 8. MECHANICAL CONTRACTOR SHALL ENSURE EMPLOYEES ARE MEETING AND DOCUMENTING ALL OSHA AND JOB SPECIFIC SAFETY REQUIREMENTS AS REQUIRED BY LAW AND BY CONTRACT. PERSONAL PROTECTIVE EQUIPMENT SHALL BE PROVIDED AND UTILIZED AS REQUIRED. 9. MECHANICAL CONTRACTOR SHALL PAY ALL FINES LEVIED BY OSHA FOR FAILURE TO COMPLY WITH OSHA REQUIREMENTS. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE ALL REQUIRED CUTTING AND PATCHING FOR INSTALLATION OF MECHANICAL WORK. 10. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE LOCATION OF CONDENSATE DISPOSAL POINTS (HUB DRAINS & FLOOR DRAINS) WITH PLUMBING CONTRACTOR. MECHANICAL CONTRACTOR SHALL PROVIDE ALL PIPING BETWEEN EVAPORATOR COIL CONNECTIONS AND DISPOSAL POINT. PIPING SHALL BE SCHEDULE 40 PVC WITH SOLVENT WELDED FITTINGS. INSTALL TRAPS AS RECOMMENDED BY EQUIPMENT MANUFACTURER. PROVIDE CLEANOUTS IN DRAIN LINES TO FACILITATE CLEANING OF LINES. EQUIPMENT 1. PROVIDE EQUIPMENT AS SHOWN ON EQUIPMENT SCHEDULES AND PLAN NOTES. SUBSTITUTIONS TO LISTED EQUIPMENT SHALL BE AT RISK OF CONTRACTOR. SUBSTITUTIONS SHALL ONLY BE ALLOWED IF ITEMS ARE EQUAL IN ALL ASPECTS. 2. PROVIDE SUBMITTALS TO ELECTRICIAN AS REQUIRED FOR COORDINATION OF ALL ELECTRICAL POWER WIRING. INCLUDE WIRING DIAGRAMS AND CABLING REQUIREMENTS FOR REFERENCE. COORDINATE ALL INTERLOCKS AS NEEDED. PROVIDE SINGLE POINT CONNECTION KITS AS NEEDED. 3. INSTALL ALL EQUIPMENT IN FULL ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS AND CLEARANCE REQUIREMENTS. PROVIDE ALL REQUIRED MOUNTING OR HOUSEKEEPING PADS. G.C. SHALL PROVIDE LEVEL GRADE FOR EXTERIOR MOUNTED EQUIPMENT. M.C. SHALL PROVIDE ALL HOISTING AND RIGGING NEEDED TO SET ALL HVAC EQUIPMENT. 4. ALL EQUIPMENT SHALL BE INSTALLED AS NEEDED TO PREVENT OBJECTIONABLE NOISE AND/OR VIBRATION. M.C. SHALL PROVIDE VIBRATION PADS, SPRING ISOLATORS, ATTENUATORS AND ACCESSORIES AS NEEDED. DUCTWORK 1. CONCEALED ROUND DUCTWORK SHALL BE CONSTRUCTED PER SMACNA LOW PRESSURE STANDARDS 1" PRESSURE CLASS, 5' MAXIMUM JOINT LENGTHS, SEAL CLASS B LONGITUDINAL SEAM SNAP LOCK PIPE AND ADJUSTABLE FITTINGS. 2. EXPOSED ROUND DUCTWORK (OR WHERE SPIRAL IS INDICATED ON THE PLANS) SHALL BE LINDAB OR EQUAL GALVANIZED STEEL CONFORMING TO ASTM STANDARDS A653 AND A924 GASKETED SPIRAL DUCTING WITH NO SEALER. EDPM RUBBER GASKET SHALL BE U.L. CLASSIFIED RATING OF FLAME SPREAD 0 AND SMOKE DEVELOPED 5 IN ACCORDANCE WITH ASTM STANDARD E84-91A SMACNA LEAKAGE CLASS 3. FITTINGS SHALL BE MANUFACTURED USING ONE OR MORE OF THE FOLLOWING CONSTRUCTION METHODS: OVERLAPPED EDGES STITCH WELDED ALONG THE ENTIRE LENGTH OF THE FITTING, STANDING SEAM GORE LOCKED AND INTERNALLY SEALED, BUTTON PUNCHED AND INTERNALLY SEALED. ELBOWS 3-INCH THROUGH 12-INCH DIAMETER WILL BE DIE STAMPED AND CONTINUOUSLY STITCH WELDED. 3. PROVIDE SHEET METAL 90 FOR ALL TURNS DO NOT USE FLEXIBLE DUCT FOR GREATER THAN 45 DEG CHANGES IN DIRECTION. PROVIDE MANUAL BALANCING DAMPERS FOR ALL SUPPLY AIR RUNS. ROUND DAMPERS SHALL BE SECURED ON BOTH SIDES OF DUCT AND SHALL CONTAIN LOCKING HANDLE. SPIRAL DUCTS SHALL USE SPIRAL STYLE DAMPERS WITH FULL WIDTH SHAFT AND NYLON BEARINGS AT EACH END. RECTANGULAR DUCTS SHALL USE MULTI OR SINGLE BLADE WELDED FRAMED DAMPERS WITH JACK SHAFTS AND LOCKING HANDLE. INSTALL NYLON RIBBON ON ALL DAMPER HANDLES TO AID IN LOCATION OF DAMPER. 4. INSULATED FLEXIBLE DUCTING FOR STRAIGHT CONNECTIONS SHALL NOT EXCEED 7 FEET. FLEXIBLE DUCT EQUAL TO FLEXIBLE DUCT CLASS 1 AIR DUCT, DOUBLE LAMINATED POLYESTER FILM ON STEEL WIRE REINFORCING, INSULATED WITH SCRIM REINFORCED METALIZED POLYESTER OUTER FIRE RETARDANT JACKET. R-4.2 FOR CONDITIONED SPACES AND R-6.0 FOR ANY SPACES OUTSIDE BUILDING THERMAL ENVELOPE. FLEX DUCTS SHALL NOT BE RUN THROUGH WALLS OR FLOORS. PROVIDE HARD DUCTED SLEEVES AS NEEDED. 5. RECTANGULAR DUCTWORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH SMACNA LOW PRESSURE DUCT STANDARDS, +/- 1.0" W.C. FROM ASTM A 653/A 653M G-90 COATED GALVANIZED SHEET STEEL. SEAMS SHALL BE PITTSBURGH CONSTRUCTION, NO BUTTON PUNCH OR SNAP LOCK SEAMS ARE ACCEPTABLE. SEAL ALL TRANSVERSE AND LONGITUDINAL SEAMS WITH WATER BASED DUCT SEALER, SEAL CLASS B. GAUGE AND JOINT CLASSIFICATIONS ACCEPTABLE ARE AS FOLLOWS, ALL SECTION LENGTHS ARE 48" MAXIMUM, REFER TO SMACNA RIGIDITY TABLES FOR GAUGES ON LONGER SECTIONS IF REQUIRED: < 12" 26 GAUGE, FLAT S AND DRIVE 12"-24" 24 GAUGE, FLAT S AND DRIVE 25"-34" 22 GAUGE, STANDING S AND FLAT DRIVE 34"-40" 22 GAUGE, STANDING S AND STANDING DRIVE >40" REFER TO SMACNA FOR STANDARDS. 6. DUCT HANGERS: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," CHAPTER 5, "HANGERS AND SUPPORTS." PROVIDE GALVANIZED MINIMUM 22 GAUGE 1" WIDE STRAP TO HANG RECTANGULAR DUCTWORK SMALLER THAN 30" WIDE. DUCT HANGERS FOR RECTANGULAR SHEET METAL DUCTS 30" AND LARGER SHALL BE TRAPEZE STYLE USING UNI-STRUT AND 3/8" OR 1/2" ROD. PROVIDE GRIPPLE, DURODYNE OR EQUAL CABLE HANGERS FOR HANGING ROUND DUCTWORK. SUPPORT ALL HANGERS FROM STRUCTURE PER SMACNA STANDARDS.HANGERS FOR SPIRAL DUCTS GREATER THAN 28" IN DIAMETER SHALL BE HUNG WITH ROD AND DUCT CLAMP. FLEXIBLE DUCTING SHALL BE SUPPORTED USING MINIMUM 2" WIDE NYLON STRAP. ALL INTERVALS ARE PER SMACNA. DUCT ACCESSORIES 1. COORDINATE WITH ARCHITECTURAL DRAWINGS AND PROVIDE FIRE AND FIRE AND SMOKE DAMPERS AT FIRE RATED ASSEMBLY PENETRATIONS IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE AND WHERE SHOWN ON PLANS. 2. PROVIDE SHEET METAL BALANCING DAMPERS FOR EACH SUPPLY BRANCH RUN AT TAKE OFF. DAMPER SHAFT SHALL PENETRATE BOTH SIDES OF DUCTING AND SHALL HAVE HANDLE WITH LOCKING NUT. ON INSULATED DUCTING, INSTALL COLORED RIBBON ON EACH HANDLE FOR IDENTIFICATION.DO NOT INSTALL DAMPERS IN NON ACCESSIBLE LOCATIONS. PROVIDE IN INTEGRAL WITH DIFFUSER OR IN NECK IF NO ACCESSIBLE LOCATION IS POSSIBLE. 3. PROVIDE HIGH EFFICIENCY TAKE OFFS, PEAL AND STICK STYLE ATTACHED TO RECTANGULAR DUCTING WITH SHEET METAL SCREWS FOR ALL ROUND SUPPLY AIR TAKE OFFS AND SADDLES. DUCT INSULATION 1. ALL DUCT INSULATION MATERIALS SHALL HAVE A FLAME SPREAD RATING OF 25 OR LESS (ON THE FLAME SPREAD TEST SCALE) AND SMOKE DEVELOPMENT OF 50 OR LESS (ON THE SMOKE TEST SCALE) OR AS DEFINED BY NFPA 255 STANDARD METHOD OF TESTING OF SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS, LOCAL CODES AND LOCAL AUTHORITIES HAVING JURISDICTION. DUCT WRAP SHALL BE FIBERGLASS MATERIAL PER ASTM C-411,ASTM C-1104,ASTM C665, ASTM C-1338, ASTM E-84, UL723, NFPA 90A,CAN/ULC S102-1188,ASTM C1290, ASTM C553, ASTM C1136. 2. INSULATION: INSTALL ALL INSULATION IN STRICT ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS IN A TIGHT AND NEAT MANOR. NO SAGGING, FRAYED OR TORN INSULATION WILL BE EXCEPTED. UNLESS OTHERWISE NOTED ON PLANS DUCTWORK SHALL BE INSULATED AS FOLLOWS: SA- 1-1/2" FIBERGLASS DUCT WRAP WITH FSK FACING, 75 #/FT3 MINIMUM APPLIED R-3.5 INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURERS REQUIREMENTS. SA/RA IN UNCONDITIONED OR ATTIC SPACES OUTSIDE THE BUILDING INSULATION ENVELOPE; 2" MINIMUM R-6 AS APPLIED FSK DUCT WRAP. SA/RA PLENUMS AND REGISTER BOXES: DUCT LINER MIN 1” THICK, 1-1/2 # DENSITY PER CU. FT., HAVING MAT FACED OR MONOLITHIC CONSTRUCTION WITH SKIN SMOOTH MICROBIAL SURFACE TO WITHSTAND VELOCITIES TO 4000 FPM. INSULATION SHALL FIT SNUGLY AGAINST THE INTERIOR DUCT SURFACES, AND BE FASTENED TO THE DUCT WITH A 50% HEAVY COAT OF RECOMMENDED ADHESIVE AND METAL FASTENERS WHICH DO NOT PIERCE THE DUCT, SPACED ON 12” CENTERS. ALL EXPOSED EDGES OF THE INSULATION SHALL BE COATED WITH MANUFACTURED RECOMMENDED ADHESIVE. EA- NONE REQUIRED UNLESS NOTED ON PLANS. CHECK TEST AND START UP REQUIREMENTS 1. LABEL ALL MAJOR PIECES OF EQUIPMENT WITH LAMACOID PLASTIC, BLACK WITH WHITE LETTERS. SIZE TO BE NOT LESS THAN 3" BY 1" WITH 1/2" LETTERS. LABEL EQUIPMENT AS FOLLOWS: a. APARTMENT CONDENSERS: AC-### WHERE ### = APARTMENT NUMBER. b. APARTMENT FAN COILS: NONE REQUIRED. c. COMMON AREA HEAT PUMP OR AC CONDENSERS HP/AC-### WHERE ### MATCHES EQUIPMENT SCHEDULE FCU NUMBER. d. COMMON AREA FAN COILS FCU-### WHERE ### = EQUIPMENT SCHEDULE NUMBERING. 2. PROVIDE AIR BALANCE BY CONTRACTOR. CONTRACTOR SHALL BALANCE SUPPLY, RETURN, OUTSIDE, RELIEF AND EXHAUST AIR SYSTEMS IN ACCORDANCE WITH CURRENT SMACNA, NEEB OR AABC STANDARDS TO DESIGN VALUES AND PROVIDE WRITTEN REPORT TO ARCHITECT. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL DEVICES, DRIVES, SHEAVES, MOTOR CHANGES AND REWORK AS REQUIRED TO MEET DESIGN REQUIREMENTS. 3. TEMPERATURE CONTROL WORK SHALL BE THE RESPONSIBILITY OF THE HVAC CONTRACTOR. PROVIDE ALL COMPONENTS INCLUDING T/S, T/S WIRE (PLENUM RATED IN RA PLENUMS), SWITCHES, ACTUATORS ETC. AS REQUIRED FOR A COMPLETE SYSTEM. 4. CLOSE OUT: PROVIDE MANUFACTURERS OPERATION AND MAINTENANCE MANUALS, AIR BALANCE REPORT AND AS BUILT DRAWINGS. PROVIDE (1) TRAINING SESSION TO OWNER SELECTED PERSONNEL AS REQUESTED AND PROVIDE WARRANTY INFORMATION FOR ALL MANUFACTURERS WARRANTED EQUIPMENT PIPING 1. PIPING SLEEVES; INTERIOR OR EXTERIOR ABOVE GRADE; GALVANIZED-STEEL-PIPE SLEEVES OR PVC-PIPE SLEEVES. VERIFY, WITH FIRE AUTHORITIES HAVING JURISDICTION, THAT PVC MATERIALS ARE ALLOWED FOR SLEEVES. ALL SLEEVES SHALL BE FIRE STOPPED OR CAULKED. EXTERIOR SLEEVES SHALL PROVIDE WATER/AIR TIGHT PENETRATION SYSTEM. 2. REFRIGERATION PIPING; A. SUCTION AND LIQUID LINES: MANUFACTURED REFRIGERANT LINE SETS: ANNEALED-COPPER SUCTION AND LIQUID LINES FACTORY CLEANED, DRIED, PRESSURIZED WITH NITROGEN, SEALED, AND WITH SUCTION LINE INSULATED. PROVIDE IN STANDARD LENGTHS FOR INSTALLATION WITHOUT JOINTS, EXCEPT AT EQUIPMENT CONNECTIONS OR ACCESSIBLE LOCATIONS. CONNECTIONS AND WROUGHT-COPPER FITTINGS WHERE REQUIRED SHALL BE BRAZED WITH MINIMUM 15% SIL-FLOS. B. INSULATION; SUCTION AND ALL DUCTLESS SPLIT LINES; MINIMUM 1/2" THICK WALL INSULATION SHALL BE A FLEXIBLE, CLOSED-CELL ELASTOMERIC PIPE INSULATION, AP ARMAFLEX OR AC ACCOFLEX. ADHESIVE SHALL BE ARMAFLEX 520, 520 BLACK OR 520 BLV ADHESIVE. THE INSULATION MUST CONFORM TO ASTM C534 GRADE 1, TYPE I ARMAFLEX AND BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS. (3/8" WALL WILL NOT BE ACCEPTED). C. ALL INSULATION EXPOSED TO OUTDOORS SHALL BE EITHER PVC LAGGED OR SHALL BE PAINTED WITH ARMA-FINISH FR UV PROTECTING PAINT. D. LINES SHALL BE RUN KINK FREE AND GENERALLY CONTINUOUS AND AT 90 DEGREE ANGLES TO STRUCTURE. AVOID JOINTS WHEN POSSIBLE. ALL REQUIRED JOINTS SHALL BE MADE IN ACCESSIBLE LOCATIONS OR M.C. SHALL PROVIDE ACCESS PANELS AS NEEDED. ALL BENDS SHALL BE MADE WITH LONG RADIUS FITTINGS OR WITH MECHANICAL BENDING TOOL TO PROVIDE SMOOTH LONG RADIUS TURNS. SUPPORT ALL PIPING WITHOUT CRUSHING OR DEPRESSING INSULATION. USE REFRIGERATION STYLE CUSH CLAMPS MOUNTED TO STRUT, DO NOT LAY PIPING ON STRUCTURAL BUILDING MEMBERS. SLEEVE ALL PENETRATIONS AND SEAL WATER TIGHT. E. PRESSURE TEST, TRIPLE EVACUATE AND PREPARE ALL PIPING IN STRICT ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS. 5. CONDENSTATE PIPING A. PROVIDE TRAPS ON ALL EVAPORATOR DRAIN PANS MINIMUM DEPTH 1.5 TIMES BLOWER BLOCKED TIGHT STATIC PRESSURE. ALL TRAPS SHALL BE CONSTRUCTED WITH PVC 90S (RUNNING TRAP FITTINGS ARE NOT ACCEPTABLE). PROVIDE WITH CLEAN OUTS AND REMOVABLE CAPS AS NEEDED FOR MAINTAINING LINES. B. HVAC CONTRACTOR SHALL COORDINATE CONDENSATE DISPOSAL POINTS WITH P.C. HVAC CONTRACTOR IS RESPONSIBLE FOR PIPING FROM EVAPORATOR COILS TO DISPOSAL POINT. P.C. IS RESPONSIBLE FOR STAND PIPES, FLOOR AND HUB DRAINS AS NEEDED. C. TYPE M OR L COPPER MINIMUM SIZE 3/4" . INSULATED WITH 1 2 " WALL CLOSED CELL INSULATION. D. PROVIDE CONDENSATE PUMPS AS REQUIRED WITH HIGH LEVEL SHUT DOWN SWITCHES INTERLOCKED TO A/C UNITS. E. PITCH ALL PIPING MINIMUM 1 4 " PER FOOT. SUPPORT PIPING AT MINIMUM 5'-0" INTERVALS. SECURE FINAL CONNECTION AT SEWER WITH MINIMUM 1-1/2" AIR GAP CONNECTION. 18. FIRE STOPPING. a. FIRE STOPPING SYSTEMS SHALL BE IN FULL COMPLIANCE WITH SECTIONS 713 OF THE OBC AND SECTION 607 OF THE OMC. b. CONTRACTOR SHALL MAKE REFERENCE TO ARCHITECTURAL PLANS AND PROVIDE ALL REQUIRED FIRE STOPPING. c. CONTRACTOR SHALL PROVIDE FULL SUBMITTAL INDICATING METHODS OF CONSTRUCTION AND UL LISTING OF EACH SYSTEM. d. DUCTS AND AIR TRANSFER OPENINGS. PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS BY DUCTS THAT ARE NOT PROTECTED WITH DAMPERS SHALL COMPLY WITH SECTIONS 713.2 THROUGH 713.3.3 OF THE OBC. PENETRATIONS OF HORIZONTAL ASSEMBLIES NOT PROTECTED WITH A SHAFT AS PERMITTED BY EXCEPTION 4 OF SECTION 708.2, AND NOT REQUIRED TO BE PROTECTED WITH FIRE DAMPERS BY OTHER SECTIONS OF THE IBC CODE, SHALL COMPLY WITH SECTIONS 713.4 THROUGH 713.4.2.2 OF THE OBC. DUCTS AND AIR TRANSFER OPENINGS THAT ARE PROTECTED WITH DAMPERS SHALL COMPLY WITH SECTION 716. e. FIRE DAMPERS, SMOKE DAMPERS, COMBINATION FIRE/SMOKE DAMPERS AND CEILING RADIATION DAMPERS LOCATED WITHIN AIR DISTRIBUTION AND SMOKE CONTROL SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 607 OF THE OMC. AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND LISTING. f. ACCESS DOORS SHALL BE PERMITTED IN CEILINGS OF FIRE-RESISTANCE-RATED FLOOR/CEILING AND ROOF/CEILING ASSEMBLIES PROVIDED SUCH DOORS ARE TESTED IN ACCORDANCE WITH ASTM E 119 OR UL 263 AS HORIZONTAL ASSEMBLIES AND LABELED BY AN APPROVED AGENCY FOR SUCH PURPOSE. ALL ACCESS DOORS SHALL BE PROVIDED BY TRADE MAKING PENETRATIONS. ROOF JACK, MATCH ROOF COLOR ROOF TOP UNIT REVOLUTIONS PER MINUTE SUPPLY AIR FAN RJ RPM RTU SAF STATIC PRESSURE SP TCC TSP TOTAL STATIC PRESSURE WALL CAP WC WALK IN COOLER WIC WALK IN FREEZER WIF ET EXPANSION TANK ELECTRIC WATER COOLER EWC TMV THERMOSTATIC MIXING VALVE AFF ABOVE FINISH FLOOR URINAL SK SINK MOP SINK WATER CLOSET WATER HEATER CO CLEAN OUT PLUMBING CONTRACTOR STORM DRAIN VENT THROUGH ROOF SANITARY SEWER ST STORAGE TANK SD SAN CW COLD WATER DOMESTIC PC PRV PSI PRESSURE RELEIF VALVE POUNDS PER SQUARE INCH MS LAV LAVATORY HWS HWR HOT WATER RETURN DOMESTIC HOT WATER SUPPLY DOMESTIC GPM GALLONS PER MINUTE WH GC GENERAL CONTRACTOR VTR UR WC FOOT FT INCH IN LEAVING AIR TEMPERATURE LINEAR SLOT DIFFUSER MANUAL LAT IR MAN LS 1000 BTUH MECHANICAL CONTRACTOR MOTOR CONTROL CENTER MBH MC MCC MFR MANUFACTURER PRESSURE DROP POOL DEHUMIDIFICATION UNIT PACKAGE TERMINAL AIR CONDITIONER POUNDS PER SQUARE INCH PRESSURE RELEIF VALVE PD PDU PTAC PSI PRV INFRA-RED AIR HANDLING UNIT ACCU AHU BOTTOM OF DUCT BACKDRAFT DAMPER BOD BDD COMBUSTION AIR CUBIC FEET PER MINUTE CA CFM AIR COOLED CONDENSING UNIT ENTERING AIR WET BULB ENTERING AIR DRY BULB ROUND EAWB EADB Ø DRY BULB DB ELECTRICAL CONTRACTOR EC ELECTRIC WALL HEATER EXHAUST FAN EF EWH HOOD EXTERNAL STATIC PRESSURE ELECTRIC REHEAT COIL H ESP ERC EG EXHAUST GRILLE OR REGISTER FURNACE FCU F FIRE DAMPER OR FLOOR DRAIN FIRE AND SMOKE DAMPER FD FD/SD FEET PER MINUTE FPM FAN COIL UNIT ABBREVIATIONS UNLESS OTHERWISE NOTED UON TEMPERATURE CONTROL CONTRACTOR REDUCED PRESSURE ZONED BACKFLOW RPZB FSK FOIL SCRIM VAPOR BARRIER RETURN AIR RA SUPPLY AIR SA EACH EA OUTSIDE AIR OA VARIABLE AIR VOLUME BOX VAV FAN POWERED VAV BOX FPVAV DEGREES FARENHEIT DEG F AIR COOLED CONDENSING UNIT MANUAL VOLUME DAMPER LOCKING WITH SHAFT FIRE DAMPER ROUND MOTORIZED DAMPER M COMBINATION FIRE/SMOKE DAMPER THERMOSTAT LAY-IN EXHAUST GRILLE ROOF EXHAUST FAN TURNING VANES DOUBLE THICKNESS SYMBOLS XXX X-# EQUIPMENT SYMBOLS FD FD SD ROOF TOP UNIT W/D W/D ECH HORIZONTAL FURNACE OR FC WITH DRAIN PAN HORIZONTAL AIR COOLED CONDENSING UNIT RECTANGULAR CENTERED DUCT TRANSISTION RECTANGULAR ECCENTRIC DUCT TRANSITION WALL MOUNTED EXHAUST FAN LAY-IN SUPPLY AIR DIFFUSER LAY-IN RETURN AIR REGISTER OR GRILLE SURFACE MOUNTED SUPPLY AIR DIFFUSER DUCT MOUNTED ROUND DIFFUSER LINEAR OR SLOT DIFFUSER ROOF MOUNTED INTAKE/EXHAUST HOOD RECTANGULAR ROOF MOUNTED INTAKE/EXHAUST HOOD ROUND SURFACE MOUNTED SUPPLY AIR DIFFUSER CEILING MOUNTED EXHAUST FAN MODULAR AIR HANDLING UNIT AHU ACCU REF IH RH IH RH FC F AC EF EF RTU CEILING MOUNTED ELECTRIC HEATER DIFFUSER SYMBOLS DUCT SYMBOLS DIRECT DUCT MOUNTED REGISTER DIFFUSER TAG EWH ELECTRIC WALL HEATER ECCENTRIC SQUARE TO ROUND TRANSITION CENTERED SQUARE TO ROUND TRANSITION SHEET METAL DUCT WIDTH BY DEPTH LINED SHEET METAL DUCT FREE AREA WIDTH BY DEPTH. ACCESS DOOR SQUARE SHEET METAL 90 PROVIDE WITH DOUBLE THICKNESS TURNING VANES. RADIUS SHEET METAL 90, R=1.5*D ROUND HIGH EFFICIENCY BRANCH DUCT TAKE OFF ON ROUND DUCT. ROUND TAP BRANCH DUCT TAKE OFF ON ROUND DUCT. HIGH EFFICIENCY BRANCH DUCT TAKE OFF ON RECTANGULAR. STANDARD ROUND TAP BRANCH DUCT TAKE OFF ON ROUND DUCT. SQUARE SHEET METAL 90 PROVIDE WITH DOUBLE THICKNESS TURNING VANES. FULL BODY ROUND TEE FITTING CONTROL SYMBOLS THERMOSTAT IN LOCK BOX SENSOR CARBON MONOXIDE SENSOR CARBON DIOXIDE SENSOR NITROGEN OXIDE SENSOR M RECTANGULAR MOTORIZED DAMPER DIRECT DUCT MOUNTED REGISTER MARK CFM T T S CO CO2 NO

Upload: vankhue

Post on 29-Apr-2018

219 views

Category:

Documents


3 download

TRANSCRIPT

DIM

EN

SIO

NS

ARCH

ITEC

TURE

I

NTER

IORS

C

ONST

RUCT

ION

SER

VICE

S

WEB

SITE

: http

://ww

w.dim

ensio

ns-a

rchit

ects.

com

E-M

AIL:

info

@dim

ensio

ns-a

rchit

ects.

com

INC.

project title sheet

proj

ect n

o.

AS

SHO

WN

scal

e

revi

sion

s

date

chec

ked

bydr

awn

by

ME

P E

ng

in

ee

r

87

4 C

he

lte

nh

am

W

ay

Avo

n, IN

4

61

23

31

7.5

06

.8

15

1

31

7.7

45

.5

76

1

gn

ae

ng

in

ee

rin

g@

ao

l.co

m

GO

OD

ER

UM

&

A

SS

OC

IA

TE

S E

NG

IN

EE

RIN

G

P:

F:

E:

O

I

H

O

F

E

T

A

T

S

PR

O

F

E

S

S

I

O

NA

L

E

N

G

I

N

E

E

R

TS

G

I

R

E

E

GOODERUM

O

DAVID R.

74178

R

E

D

HAMP

TON

INN

CINC

INNA

TI, O

HIO

H-16

-384

08/1

0/20

17

- - - - -

H.V.

A.C

. SYM

BOLS

, ABB

REVI

ATI

ON

S &

SPEC

IFIC

ATI

ON

S

M001

GN

A

MECHANICAL SPECIFICATIONS

GENERAL

1. BID INSTRUCTIONS: CONTRACTORS SHALL PROVIDE

BASE BID IN STRICT ACCORDANCE WITH DESIGN

BASIS EQUIPMENT AND MATERIALS. PROJECT DOES

ENCOURAGE COMPETITIVE PRICING AND ALLOWS

FOR SUBSTITUTIONS OF EQUIPMENT AND

MATERIALS AS ALTERNATE DEDUCTS TO BASIS OF

DESIGN BIDS. LIST ALL SUBSTITUTIONS ALONG WITH

DEDUCTS OFFERED ON BID. OWNER RESERVES THE

RIGHT TO REJECT SUBSTITUTIONS FOUND NOT TO

BE EQUAL TO ITEMS LISTED IN DESIGN BASIS.

2. CONTRACTORS SHALL REFERENCE APPLICABLE

HAMPTON INN DESIGN CRITERIA STANDARDS FOUND

AT HILTON.COM AND SHALL COMPLY WITH ALL

REQUIREMENTS.

3. PRIOR TO PROCUREMENT CONTRACTOR SHALL

SUBMIT TO ARCHITECT FULL SUBMITTALS FOR ALL

ENERGY CONSUMING OR PRODUCING ITEMS AND

FOR ALL DUCT ACCESSORIES, INSULATION, VAV

BOXES, REGISTERS, GRILLES, DIFFUSERS AND

LOUVERS. SUBMITTALS SHALL BE DELINEATED WITH

TAGS INDICATED ON PRINTS, CONTRACTORS NAME,

PROJECT NAME. CLEARLY INDICATE ALL MODEL

NUMBERS AND ALL ACCESSORIES AND OPTIONS

BEING PROVIDED. SUBMISSIONS SHALL BE IN PDF

FORMAT. ALL EQUIPMENT AND ITEMS SHALL BE PER

DESIGN BASIS OR APPROVED EQUAL. ENGINEER

RESERVES THE RIGHT TO REJECT ANY SUBSTITUTE

ITEM.

4. CONTRACTOR SHALL BE RESPONSIBLE TO VISIT THE

SITE TO EXAMINE ALL CONDITIONS THAT MAY IN ANY

WAY AFFECT THE EXECUTION OF HIS WORK. HE

SHALL ALSO EXAMINE THE DRAWINGS AND

SPECIFICATIONS FOR OTHER BRANCHES OF WORK

MAKING REFERENCE TO THEM FOR DETAILS OF

EXISTING BUILDING CONDITIONS. NO EXTRAS WILL

BE ALLOWED FOR FAILURE TO INCLUDE ALL

REQUIRED WORK IN THE BID. CONTRACTOR SHALL

GUARANTEE ALL LABOR AND MATERIALS ENTERING

INTO CONTRACT FOR A PERIOD OF ONE (1) YEAR

FROM DATE OF ACCEPTANCE.

5. THE DRAWINGS IN THIS SECTION ARE

DIAGRAMMATIC AND ARE NOT INTENDED TO DEFINE

EXACT QUANTITIES, LOCATIONS OR CODIFIED

REQUIREMENTS. DRAWINGS SHOW GENERAL

INTENT OF SYSTEMS. M.C. SHALL PROVIDE AND PAY

FOR ALL REQUIRED PERMITS.

6. UPON COMPLETION OF THE MECHANICAL

INSTALLATION, DEMONSTRATE TO THE ENGINEER

AND THE OWNER'S SATISFACTION THAT THE

SYSTEMS HAVE BEEN INSTALLED IN ACCORDANCE

WITH THE DRAWINGS, SPECIFICATIONS AND

APPLICABLE CODES. DEMONSTRATE THE DYNAMIC

OPERATION OF EACH SYSTEM. VERIFY PROPER

OPERATION OF EQUIPMENT, FILTERS ARE CLEAN

AND COMPONENTS OF THE SYSTEM ARE INSTALLED

AND ADJUSTED IN FULL ACCORDANCE WITH

MANUFACTURER RECOMMENDATIONS.

7. ALL WORK SHALL BE IN FULL ACCORDANCE WITH

CURRENT OHIO NON-RESIDENTIAL MECHANICAL

CODES. FOR MORE INFORMATION REFERENCE WEB

SITE.

http://www.com.ohio.gov/DICO/bbs/NonResidential

BuildingCodes.aspx#OMC

8. MECHANICAL CONTRACTOR SHALL ENSURE

EMPLOYEES ARE MEETING AND DOCUMENTING ALL

OSHA AND JOB SPECIFIC SAFETY REQUIREMENTS AS

REQUIRED BY LAW AND BY CONTRACT. PERSONAL

PROTECTIVE EQUIPMENT SHALL BE PROVIDED AND

UTILIZED AS REQUIRED.

9. MECHANICAL CONTRACTOR SHALL PAY ALL FINES

LEVIED BY OSHA FOR FAILURE TO COMPLY WITH

OSHA REQUIREMENTS. MECHANICAL CONTRACTOR

SHALL BE RESPONSIBLE TO PROVIDE ALL REQUIRED

CUTTING AND PATCHING FOR INSTALLATION OF

MECHANICAL WORK.

10. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE

TO COORDINATE LOCATION OF CONDENSATE

DISPOSAL POINTS (HUB DRAINS & FLOOR DRAINS)

WITH PLUMBING CONTRACTOR. MECHANICAL

CONTRACTOR SHALL PROVIDE ALL PIPING BETWEEN

EVAPORATOR COIL CONNECTIONS AND DISPOSAL

POINT. PIPING SHALL BE SCHEDULE 40 PVC WITH

SOLVENT WELDED FITTINGS. INSTALL TRAPS AS

RECOMMENDED BY EQUIPMENT MANUFACTURER.

PROVIDE CLEANOUTS IN DRAIN LINES TO FACILITATE

CLEANING OF LINES.

EQUIPMENT

1. PROVIDE EQUIPMENT AS SHOWN ON EQUIPMENT

SCHEDULES AND PLAN NOTES. SUBSTITUTIONS TO

LISTED EQUIPMENT SHALL BE AT RISK OF

CONTRACTOR. SUBSTITUTIONS SHALL ONLY BE

ALLOWED IF ITEMS ARE EQUAL IN ALL ASPECTS.

2. PROVIDE SUBMITTALS TO ELECTRICIAN AS

REQUIRED FOR COORDINATION OF ALL ELECTRICAL

POWER WIRING. INCLUDE WIRING DIAGRAMS AND

CABLING REQUIREMENTS FOR REFERENCE.

COORDINATE ALL INTERLOCKS AS NEEDED. PROVIDE

SINGLE POINT CONNECTION KITS AS NEEDED.

3. INSTALL ALL EQUIPMENT IN FULL ACCORDANCE

WITH MANUFACTURERS RECOMMENDATIONS AND

CLEARANCE REQUIREMENTS. PROVIDE ALL

REQUIRED MOUNTING OR HOUSEKEEPING PADS.

G.C. SHALL PROVIDE LEVEL GRADE FOR EXTERIOR

MOUNTED EQUIPMENT. M.C. SHALL PROVIDE ALL

HOISTING AND RIGGING NEEDED TO SET ALL HVAC

EQUIPMENT.

4. ALL EQUIPMENT SHALL BE INSTALLED AS NEEDED

TO PREVENT OBJECTIONABLE NOISE AND/OR

VIBRATION. M.C. SHALL PROVIDE VIBRATION PADS,

SPRING ISOLATORS, ATTENUATORS AND

ACCESSORIES AS NEEDED.

DUCTWORK

1. CONCEALED ROUND DUCTWORK SHALL BE

CONSTRUCTED PER SMACNA LOW PRESSURE

STANDARDS 1" PRESSURE CLASS, 5' MAXIMUM JOINT

LENGTHS, SEAL CLASS B LONGITUDINAL SEAM SNAP

LOCK PIPE AND ADJUSTABLE FITTINGS.

2. EXPOSED ROUND DUCTWORK (OR WHERE SPIRAL IS

INDICATED ON THE PLANS) SHALL BE LINDAB OR

EQUAL GALVANIZED STEEL CONFORMING TO ASTM

STANDARDS A653 AND A924 GASKETED SPIRAL

DUCTING WITH NO SEALER. EDPM RUBBER GASKET

SHALL BE U.L. CLASSIFIED RATING OF FLAME

SPREAD 0 AND SMOKE DEVELOPED 5 IN

ACCORDANCE WITH ASTM STANDARD E84-91A

SMACNA LEAKAGE CLASS 3. FITTINGS SHALL BE

MANUFACTURED USING ONE OR MORE OF THE

FOLLOWING CONSTRUCTION METHODS:

OVERLAPPED EDGES STITCH WELDED ALONG THE

ENTIRE LENGTH OF THE FITTING, STANDING SEAM

GORE LOCKED AND INTERNALLY SEALED, BUTTON

PUNCHED AND INTERNALLY SEALED. ELBOWS 3-INCH

THROUGH 12-INCH DIAMETER WILL BE DIE STAMPED

AND CONTINUOUSLY STITCH WELDED.

3. PROVIDE SHEET METAL 90 FOR ALL TURNS DO NOT

USE FLEXIBLE DUCT FOR GREATER THAN 45 DEG

CHANGES IN DIRECTION. PROVIDE MANUAL

BALANCING DAMPERS FOR ALL SUPPLY AIR RUNS.

ROUND DAMPERS SHALL BE SECURED ON BOTH

SIDES OF DUCT AND SHALL CONTAIN LOCKING

HANDLE. SPIRAL DUCTS SHALL USE SPIRAL STYLE

DAMPERS WITH FULL WIDTH SHAFT AND NYLON

BEARINGS AT EACH END. RECTANGULAR DUCTS

SHALL USE MULTI OR SINGLE BLADE WELDED

FRAMED DAMPERS WITH JACK SHAFTS AND LOCKING

HANDLE. INSTALL NYLON RIBBON ON ALL DAMPER

HANDLES TO AID IN LOCATION OF DAMPER.

4. INSULATED FLEXIBLE DUCTING FOR STRAIGHT

CONNECTIONS SHALL NOT EXCEED 7 FEET. FLEXIBLE

DUCT EQUAL TO FLEXIBLE DUCT CLASS 1 AIR DUCT,

DOUBLE LAMINATED POLYESTER FILM ON STEEL

WIRE REINFORCING, INSULATED WITH SCRIM

REINFORCED METALIZED POLYESTER OUTER FIRE

RETARDANT JACKET. R-4.2 FOR CONDITIONED

SPACES AND R-6.0 FOR ANY SPACES OUTSIDE

BUILDING THERMAL ENVELOPE. FLEX DUCTS SHALL

NOT BE RUN THROUGH WALLS OR FLOORS. PROVIDE

HARD DUCTED SLEEVES AS NEEDED.

5. RECTANGULAR DUCTWORK SHALL BE

CONSTRUCTED IN ACCORDANCE WITH SMACNA LOW

PRESSURE DUCT STANDARDS, +/- 1.0" W.C. FROM

ASTM A 653/A 653M G-90 COATED GALVANIZED

SHEET STEEL. SEAMS SHALL BE PITTSBURGH

CONSTRUCTION, NO BUTTON PUNCH OR SNAP LOCK

SEAMS ARE ACCEPTABLE. SEAL ALL TRANSVERSE

AND LONGITUDINAL SEAMS WITH WATER BASED

DUCT SEALER, SEAL CLASS B. GAUGE AND JOINT

CLASSIFICATIONS ACCEPTABLE ARE AS FOLLOWS,

ALL SECTION LENGTHS ARE 48" MAXIMUM, REFER TO

SMACNA RIGIDITY TABLES FOR GAUGES ON LONGER

SECTIONS IF REQUIRED:

< 12" 26 GAUGE, FLAT S AND DRIVE

12"-24" 24 GAUGE, FLAT S AND DRIVE

25"-34" 22 GAUGE, STANDING S AND FLAT

DRIVE

34"-40" 22 GAUGE, STANDING S AND STANDING

DRIVE

>40" REFER TO SMACNA FOR STANDARDS.

6. DUCT HANGERS: COMPLY WITH SMACNA'S "HVAC

DUCT CONSTRUCTION STANDARDS - METAL AND

FLEXIBLE," CHAPTER 5, "HANGERS AND SUPPORTS."

PROVIDE GALVANIZED MINIMUM 22 GAUGE 1" WIDE

STRAP TO HANG RECTANGULAR DUCTWORK

SMALLER THAN 30" WIDE. DUCT HANGERS FOR

RECTANGULAR SHEET METAL DUCTS 30" AND

LARGER SHALL BE TRAPEZE STYLE USING

UNI-STRUT AND 3/8" OR 1/2" ROD. PROVIDE GRIPPLE,

DURODYNE OR EQUAL CABLE HANGERS FOR

HANGING ROUND DUCTWORK. SUPPORT ALL

HANGERS FROM STRUCTURE PER SMACNA

STANDARDS.HANGERS FOR SPIRAL DUCTS GREATER

THAN 28" IN DIAMETER SHALL BE HUNG WITH ROD

AND DUCT CLAMP. FLEXIBLE DUCTING SHALL BE

SUPPORTED USING MINIMUM 2" WIDE NYLON STRAP.

ALL INTERVALS ARE PER SMACNA.

DUCT ACCESSORIES

1. COORDINATE WITH ARCHITECTURAL DRAWINGS AND

PROVIDE FIRE AND FIRE AND SMOKE DAMPERS AT

FIRE RATED ASSEMBLY PENETRATIONS IN

ACCORDANCE WITH THE INTERNATIONAL BUILDING

CODE AND WHERE SHOWN ON PLANS.

2. PROVIDE SHEET METAL BALANCING DAMPERS FOR

EACH SUPPLY BRANCH RUN AT TAKE OFF. DAMPER

SHAFT SHALL PENETRATE BOTH SIDES OF DUCTING

AND SHALL HAVE HANDLE WITH LOCKING NUT. ON

INSULATED DUCTING, INSTALL COLORED RIBBON ON

EACH HANDLE FOR IDENTIFICATION.DO NOT INSTALL

DAMPERS IN NON ACCESSIBLE LOCATIONS. PROVIDE

IN INTEGRAL WITH DIFFUSER OR IN NECK IF NO

ACCESSIBLE LOCATION IS POSSIBLE.

3. PROVIDE HIGH EFFICIENCY TAKE OFFS, PEAL AND

STICK STYLE ATTACHED TO RECTANGULAR DUCTING

WITH SHEET METAL SCREWS FOR ALL ROUND

SUPPLY AIR TAKE OFFS AND SADDLES.

DUCT INSULATION

1. ALL DUCT INSULATION MATERIALS SHALL HAVE A

FLAME SPREAD RATING OF 25 OR LESS (ON THE

FLAME SPREAD TEST SCALE) AND SMOKE

DEVELOPMENT OF 50 OR LESS (ON THE SMOKE TEST

SCALE) OR AS DEFINED BY NFPA 255 STANDARD

METHOD OF TESTING OF SURFACE BURNING

CHARACTERISTICS OF BUILDING MATERIALS, LOCAL

CODES AND LOCAL AUTHORITIES HAVING

JURISDICTION. DUCT WRAP SHALL BE FIBERGLASS

MATERIAL PER ASTM C-411,ASTM C-1104,ASTM C665,

ASTM C-1338, ASTM E-84, UL723, NFPA 90A,CAN/ULC

S102-1188,ASTM C1290, ASTM C553, ASTM C1136.

2. INSULATION: INSTALL ALL INSULATION IN STRICT

ACCORDANCE WITH MANUFACTURERS

INSTRUCTIONS IN A TIGHT AND NEAT MANOR. NO

SAGGING, FRAYED OR TORN INSULATION WILL BE

EXCEPTED. UNLESS OTHERWISE NOTED ON PLANS

DUCTWORK SHALL BE INSULATED AS FOLLOWS:

SA- 1-1/2" FIBERGLASS DUCT WRAP WITH

FSK FACING, 75 #/FT3 MINIMUM APPLIED

R-3.5 INSTALLED IN STRICT

ACCORDANCE WITH MANUFACTURERS

REQUIREMENTS.

SA/RA IN UNCONDITIONED OR ATTIC SPACES

OUTSIDE THE BUILDING INSULATION

ENVELOPE; 2" MINIMUM R-6 AS APPLIED

FSK DUCT WRAP.

SA/RA PLENUMS AND REGISTER BOXES: DUCT

LINER MIN 1” THICK, 1-1/2 # DENSITY

PER CU. FT., HAVING MAT FACED OR

MONOLITHIC CONSTRUCTION WITH SKIN

SMOOTH MICROBIAL SURFACE TO

WITHSTAND VELOCITIES TO 4000 FPM.

INSULATION SHALL FIT SNUGLY

AGAINST THE INTERIOR DUCT

SURFACES, AND BE FASTENED TO THE

DUCT WITH A 50% HEAVY COAT OF

RECOMMENDED ADHESIVE AND METAL

FASTENERS WHICH DO NOT PIERCE

THE DUCT, SPACED

ON 12” CENTERS. ALL EXPOSED EDGES

OF THE INSULATION SHALL BE COATED

WITH MANUFACTURED RECOMMENDED

ADHESIVE.

EA- NONE REQUIRED UNLESS NOTED ON

PLANS.

CHECK TEST AND START UP REQUIREMENTS

1. LABEL ALL MAJOR PIECES OF EQUIPMENT WITH

LAMACOID PLASTIC, BLACK WITH WHITE LETTERS.

SIZE TO BE NOT LESS THAN 3" BY 1" WITH 1/2"

LETTERS. LABEL EQUIPMENT AS FOLLOWS:

a. APARTMENT CONDENSERS: AC-### WHERE ###

= APARTMENT NUMBER.

b. APARTMENT FAN COILS: NONE REQUIRED.

c. COMMON AREA HEAT PUMP OR AC

CONDENSERS HP/AC-### WHERE ### MATCHES

EQUIPMENT SCHEDULE FCU NUMBER.

d. COMMON AREA FAN COILS FCU-### WHERE ###

= EQUIPMENT SCHEDULE NUMBERING.

2. PROVIDE AIR BALANCE BY CONTRACTOR.

CONTRACTOR SHALL BALANCE SUPPLY, RETURN,

OUTSIDE, RELIEF AND EXHAUST AIR SYSTEMS IN

ACCORDANCE WITH CURRENT SMACNA, NEEB OR

AABC STANDARDS TO DESIGN VALUES AND PROVIDE

WRITTEN REPORT TO ARCHITECT. MECHANICAL

CONTRACTOR SHALL BE RESPONSIBLE FOR

PROVIDING ALL DEVICES, DRIVES, SHEAVES, MOTOR

CHANGES AND REWORK AS REQUIRED TO MEET

DESIGN REQUIREMENTS.

3. TEMPERATURE CONTROL WORK SHALL BE THE

RESPONSIBILITY OF THE HVAC CONTRACTOR.

PROVIDE ALL COMPONENTS INCLUDING T/S, T/S

WIRE (PLENUM RATED IN RA PLENUMS), SWITCHES,

ACTUATORS ETC. AS REQUIRED FOR A COMPLETE

SYSTEM.

4. CLOSE OUT: PROVIDE MANUFACTURERS OPERATION

AND MAINTENANCE MANUALS, AIR BALANCE REPORT

AND AS BUILT DRAWINGS. PROVIDE (1) TRAINING

SESSION TO OWNER SELECTED PERSONNEL AS

REQUESTED AND PROVIDE WARRANTY

INFORMATION FOR ALL MANUFACTURERS

WARRANTED EQUIPMENT

PIPING

1. PIPING SLEEVES; INTERIOR OR EXTERIOR ABOVE

GRADE; GALVANIZED-STEEL-PIPE SLEEVES OR

PVC-PIPE SLEEVES. VERIFY, WITH FIRE AUTHORITIES

HAVING JURISDICTION, THAT PVC MATERIALS ARE

ALLOWED FOR SLEEVES. ALL SLEEVES SHALL BE

FIRE STOPPED OR CAULKED. EXTERIOR SLEEVES

SHALL PROVIDE WATER/AIR TIGHT PENETRATION

SYSTEM.

2. REFRIGERATION PIPING;

A. SUCTION AND LIQUID LINES: MANUFACTURED

REFRIGERANT LINE SETS: ANNEALED-COPPER

SUCTION AND LIQUID LINES FACTORY CLEANED,

DRIED, PRESSURIZED WITH NITROGEN, SEALED, AND

WITH SUCTION LINE INSULATED. PROVIDE IN

STANDARD LENGTHS FOR INSTALLATION WITHOUT

JOINTS, EXCEPT AT EQUIPMENT CONNECTIONS OR

ACCESSIBLE LOCATIONS. CONNECTIONS AND

WROUGHT-COPPER FITTINGS WHERE REQUIRED

SHALL BE BRAZED WITH MINIMUM 15% SIL-FLOS.

B. INSULATION; SUCTION AND ALL DUCTLESS SPLIT

LINES; MINIMUM 1/2" THICK WALL INSULATION SHALL

BE A FLEXIBLE, CLOSED-CELL ELASTOMERIC PIPE

INSULATION, AP ARMAFLEX OR AC ACCOFLEX.

ADHESIVE SHALL BE ARMAFLEX 520, 520 BLACK OR

520 BLV ADHESIVE. THE INSULATION MUST

CONFORM TO ASTM C534 GRADE 1, TYPE I

ARMAFLEX AND BE INSTALLED IN STRICT

ACCORDANCE WITH MANUFACTURERS

RECOMMENDATIONS. (3/8" WALL WILL NOT BE

ACCEPTED).

C. ALL INSULATION EXPOSED TO OUTDOORS SHALL BE

EITHER PVC LAGGED OR SHALL BE PAINTED WITH

ARMA-FINISH FR UV PROTECTING PAINT.

D. LINES SHALL BE RUN KINK FREE AND GENERALLY

CONTINUOUS AND AT 90 DEGREE ANGLES TO

STRUCTURE. AVOID JOINTS WHEN POSSIBLE. ALL

REQUIRED JOINTS SHALL BE MADE IN ACCESSIBLE

LOCATIONS OR M.C. SHALL PROVIDE ACCESS

PANELS AS NEEDED. ALL BENDS SHALL BE MADE

WITH LONG RADIUS FITTINGS OR WITH MECHANICAL

BENDING TOOL TO PROVIDE SMOOTH LONG RADIUS

TURNS. SUPPORT ALL PIPING WITHOUT CRUSHING

OR DEPRESSING INSULATION. USE REFRIGERATION

STYLE CUSH CLAMPS MOUNTED TO STRUT, DO NOT

LAY PIPING ON STRUCTURAL BUILDING MEMBERS.

SLEEVE ALL PENETRATIONS AND SEAL WATER

TIGHT.

E. PRESSURE TEST, TRIPLE EVACUATE AND PREPARE

ALL PIPING IN STRICT ACCORDANCE WITH

MANUFACTURERS RECOMMENDATIONS.

5. CONDENSTATE PIPING

A. PROVIDE TRAPS ON ALL EVAPORATOR DRAIN PANS

MINIMUM DEPTH 1.5 TIMES BLOWER BLOCKED TIGHT

STATIC PRESSURE. ALL TRAPS SHALL BE

CONSTRUCTED WITH PVC 90S (RUNNING TRAP

FITTINGS ARE NOT ACCEPTABLE). PROVIDE WITH

CLEAN OUTS AND REMOVABLE CAPS AS NEEDED

FOR MAINTAINING LINES.

B. HVAC CONTRACTOR SHALL COORDINATE

CONDENSATE DISPOSAL POINTS WITH P.C. HVAC

CONTRACTOR IS RESPONSIBLE FOR PIPING FROM

EVAPORATOR COILS TO DISPOSAL POINT. P.C. IS

RESPONSIBLE FOR STAND PIPES, FLOOR AND HUB

DRAINS AS NEEDED.

C. TYPE M OR L COPPER MINIMUM SIZE 3/4" .

INSULATED WITH

1

2

" WALL CLOSED CELL INSULATION.

D. PROVIDE CONDENSATE PUMPS AS REQUIRED WITH

HIGH LEVEL SHUT DOWN SWITCHES INTERLOCKED

TO A/C UNITS.

E. PITCH ALL PIPING MINIMUM

1

4

" PER FOOT. SUPPORT

PIPING AT MINIMUM 5'-0" INTERVALS. SECURE FINAL

CONNECTION AT SEWER WITH MINIMUM 1-1/2" AIR

GAP CONNECTION.

18. FIRE STOPPING.

a. FIRE STOPPING SYSTEMS SHALL BE IN FULL

COMPLIANCE WITH SECTIONS 713 OF THE OBC

AND SECTION 607 OF THE OMC.

b. CONTRACTOR SHALL MAKE REFERENCE TO

ARCHITECTURAL PLANS AND PROVIDE ALL

REQUIRED FIRE STOPPING.

c. CONTRACTOR SHALL PROVIDE FULL SUBMITTAL

INDICATING METHODS OF CONSTRUCTION AND

UL LISTING OF EACH SYSTEM.

d. DUCTS AND AIR TRANSFER OPENINGS.

PENETRATIONS OF FIRE-RESISTANCE-RATED

WALLS BY DUCTS THAT ARE NOT PROTECTED

WITH DAMPERS SHALL COMPLY WITH SECTIONS

713.2 THROUGH 713.3.3 OF THE OBC.

PENETRATIONS OF HORIZONTAL ASSEMBLIES

NOT PROTECTED WITH A SHAFT AS PERMITTED

BY EXCEPTION 4 OF SECTION 708.2, AND NOT

REQUIRED TO BE PROTECTED WITH FIRE

DAMPERS BY OTHER SECTIONS OF THE IBC

CODE, SHALL COMPLY WITH SECTIONS 713.4

THROUGH 713.4.2.2 OF THE OBC. DUCTS AND AIR

TRANSFER OPENINGS THAT ARE PROTECTED

WITH DAMPERS SHALL COMPLY WITH SECTION

716.

e. FIRE DAMPERS, SMOKE DAMPERS,

COMBINATION FIRE/SMOKE DAMPERS AND

CEILING RADIATION DAMPERS LOCATED WITHIN

AIR DISTRIBUTION AND SMOKE CONTROL

SYSTEMS SHALL BE INSTALLED IN ACCORDANCE

WITH THE REQUIREMENTS OF SECTION 607 OF

THE OMC. AND THE MANUFACTURER'S

INSTALLATION INSTRUCTIONS AND LISTING.

f. ACCESS DOORS SHALL BE PERMITTED IN

CEILINGS OF FIRE-RESISTANCE-RATED

FLOOR/CEILING AND ROOF/CEILING ASSEMBLIES

PROVIDED SUCH DOORS ARE TESTED IN

ACCORDANCE WITH ASTM E 119 OR UL 263 AS

HORIZONTAL ASSEMBLIES AND LABELED BY AN

APPROVED AGENCY FOR SUCH PURPOSE. ALL

ACCESS DOORS SHALL BE PROVIDED BY TRADE

MAKING PENETRATIONS.

ROOF JACK, MATCH ROOF COLOR

ROOF TOP UNIT

REVOLUTIONS PER MINUTE

SUPPLY AIR FAN

RJ

RPM

RTU

SAF

STATIC PRESSURESP

TCC

TSP TOTAL STATIC PRESSURE

WALL CAPWC

WALK IN COOLERWIC

WALK IN FREEZERWIF

ET EXPANSION TANK

ELECTRIC WATER COOLEREWC

TMV THERMOSTATIC MIXING VALVE

AFF ABOVE FINISH FLOOR

URINAL

SK SINK

MOP SINK

WATER CLOSET

WATER HEATER

CO CLEAN OUT

PLUMBING CONTRACTOR

STORM DRAIN

VENT THROUGH ROOF

SANITARY SEWER

ST STORAGE TANK

SD

SAN

CW COLD WATER DOMESTIC

PC

PRV

PSI

PRESSURE RELEIF VALVE

POUNDS PER SQUARE INCH

MS

LAV LAVATORY

HWS

HWR HOT WATER RETURN DOMESTIC

HOT WATER SUPPLY DOMESTIC

GPM GALLONS PER MINUTE

WH

GC GENERAL CONTRACTOR

VTR

UR

WC

FOOTFT

INCHIN

LEAVING AIR TEMPERATURE

LINEAR SLOT DIFFUSER

MANUAL

LAT

IR

MAN

LS

1000 BTUH

MECHANICAL CONTRACTOR

MOTOR CONTROL CENTER

MBH

MC

MCC

MFR MANUFACTURER

PRESSURE DROP

POOL DEHUMIDIFICATION UNIT

PACKAGE TERMINAL AIR CONDITIONER

POUNDS PER SQUARE INCH

PRESSURE RELEIF VALVE

PD

PDU

PTAC

PSI

PRV

INFRA-RED

AIR HANDLING UNIT

ACCU

AHU

BOTTOM OF DUCT

BACKDRAFT DAMPER

BOD

BDD

COMBUSTION AIR

CUBIC FEET PER MINUTE

CA

CFM

AIR COOLED CONDENSING UNIT

ENTERING AIR WET BULB

ENTERING AIR DRY BULB

ROUND

EAWB

EADB

Ø

DRY BULBDB

ELECTRICAL CONTRACTOR

EC

ELECTRIC WALL HEATER

EXHAUST FAN

EF

EWH

HOOD

EXTERNAL STATIC PRESSURE

ELECTRIC REHEAT COIL

H

ESP

ERC

EG EXHAUST GRILLE OR REGISTER

FURNACE

FCU

F

FIRE DAMPER OR FLOOR DRAIN

FIRE AND SMOKE DAMPER

FD

FD/SD

FEET PER MINUTEFPM

FAN COIL UNIT

ABBREVIATIONS

UNLESS OTHERWISE NOTEDUON

TEMPERATURE CONTROL CONTRACTOR

REDUCED PRESSURE ZONED BACKFLOWRPZB

FSK FOIL SCRIM VAPOR BARRIER

RETURN AIRRA

SUPPLY AIRSA

EACHEA

OUTSIDE AIROA

VARIABLE AIR VOLUME BOXVAV

FAN POWERED VAV BOXFPVAV

DEGREES FARENHEITDEG F

AIR COOLED CONDENSING UNIT

MANUAL VOLUME DAMPER LOCKING WITH SHAFT

FIRE DAMPER

ROUND MOTORIZED DAMPER

M

COMBINATION FIRE/SMOKE DAMPER

THERMOSTAT

LAY-IN EXHAUST GRILLE

ROOF EXHAUST FAN

TURNING VANES DOUBLE THICKNESS

SYMBOLS

XXX

X-#

EQUIPMENT SYMBOLS

FD

FD

SD

ROOF TOP UNIT

W/D

W/D

ECH

HORIZONTAL FURNACE OR FC WITH

DRAIN PAN

HORIZONTAL AIR COOLED CONDENSING UNIT

RECTANGULAR CENTERED DUCT TRANSISTION

RECTANGULAR ECCENTRIC DUCT TRANSITION

WALL MOUNTED EXHAUST FAN

LAY-IN SUPPLY AIR DIFFUSER

LAY-IN RETURN AIR REGISTER OR GRILLE

SURFACE MOUNTED SUPPLY AIR DIFFUSER

DUCT MOUNTED ROUND DIFFUSER

LINEAR OR SLOT DIFFUSER

ROOF MOUNTED INTAKE/EXHAUST HOOD

RECTANGULAR

ROOF MOUNTED INTAKE/EXHAUST HOOD

ROUND

SURFACE MOUNTED SUPPLY AIR DIFFUSER

CEILING MOUNTED EXHAUST FAN

MODULAR AIR HANDLING UNIT

AHU

ACCU

REF

IH

RH

IH

RH

FC

F

AC

EF

EF

RTU

CEILING MOUNTED ELECTRIC HEATER

DIFFUSER SYMBOLS

DUCT SYMBOLS

DIRECT DUCT MOUNTED REGISTER

DIFFUSER TAG

EWH

ELECTRIC WALL HEATER

ECCENTRIC SQUARE TO ROUND TRANSITION

CENTERED SQUARE TO ROUND TRANSITION

SHEET METAL DUCT WIDTH BY DEPTH

LINED SHEET METAL DUCT FREE AREA WIDTH

BY DEPTH.

ACCESS DOOR

SQUARE SHEET METAL 90 PROVIDE WITH

DOUBLE THICKNESS TURNING VANES.

RADIUS SHEET METAL 90, R=1.5*D

ROUND HIGH EFFICIENCY BRANCH DUCT

TAKE OFF ON ROUND DUCT.

ROUND TAP BRANCH DUCT TAKE OFF ON

ROUND DUCT.

HIGH EFFICIENCY BRANCH DUCT TAKE OFF

ON RECTANGULAR.

STANDARD ROUND TAP BRANCH DUCT TAKE

OFF ON ROUND DUCT.

SQUARE SHEET METAL 90 PROVIDE WITH

DOUBLE THICKNESS TURNING VANES.

FULL BODY ROUND TEE FITTING

CONTROL SYMBOLS

THERMOSTAT IN LOCK BOX

SENSOR

CARBON MONOXIDE SENSOR

CARBON DIOXIDE SENSOR

NITROGEN OXIDE SENSOR

M

RECTANGULAR MOTORIZED DAMPER

DIRECT DUCT MOUNTED REGISTER

MARK

CFM

T

T

S

CO

CO2

NO

DIM

EN

SIO

NS

ARCH

ITEC

TURE

I

NTER

IORS

C

ONST

RUCT

ION

SER

VICE

S

WEB

SITE

: http

://ww

w.dim

ensio

ns-a

rchit

ects.

com

E-M

AIL:

info

@dim

ensio

ns-a

rchit

ects.

com

INC.

project title sheet

proj

ect n

o.

AS

SHO

WN

scal

e

revi

sion

s

date

chec

ked

bydr

awn

by

ME

P E

ng

in

ee

r

87

4 C

he

lte

nh

am

W

ay

Avo

n, IN

4

61

23

31

7.5

06

.8

15

1

31

7.7

45

.5

76

1

gn

ae

ng

in

ee

rin

g@

ao

l.co

m

GO

OD

ER

UM

&

A

SS

OC

IA

TE

S E

NG

IN

EE

RIN

G

P:

F:

E:

O

I

H

O

F

E

T

A

T

S

PR

O

F

E

S

S

I

O

NA

L

E

N

G

I

N

E

E

R

TS

G

I

R

E

E

GOODERUM

O

DAVID R.

74178

R

E

D

HAMP

TON

INN

CINC

INNA

TI, O

HIO

H-16

-384

08/1

0/20

17

- - - - -

H.V.

A.C

. PLA

N -

DET

AIL

S

M002

GN

A

LAY-IN DIFFUSER DETAIL

NO SCALE

1

SECURE FLEXIBLE DUCT TO SUPPLY DIFFUSER

ELBOW FITTING WITH DRAWBAND.

SHEET METAL ELBOW

INSULATE BACK OF

DIFFUSER WITH

1-1/2" DUCT WRAP

SUPPLY DIFFUSER

CEILING

FULLY FRAMED OPENING IN

DRYWALL CEILING.

CONCEALED FASTENER LINEAR

SLOT DIFFUSER PER SCHEDULE.

INTERNALLY LINED PLENUM BOX

WITH RECTANGULAR, OVAL OR

ROUND TAKE OFF.

LINEAR DIFFUSER DETAIL

NO SCALE

2

1/4" MIN.3/4" MAX.

DUCT

CON

NECT

IONS

MODE

L A

VERTICAL MOUNT

DUCT CONNECTIONSMODEL A

1/4" MIN3/4" MAX

HORIZONTAL MOUNT

Single sided or conventional

retaining angle ea side

Break away duct connection

Sheet Metal Duct

UL Listed Fire damper do not caulk

Conventional retaining angle

4

SCALE: None

Fire Damper Register/Duct Penetrations

1

2

1

3

4

3

2

5

5

4

2

3

4

1

5

ATTACH DUCT TO BOTTOM

LOUVER BLADE. PROVIDE BUTYL

GASKET ON FULL PERIMETER.

WALL

WALL

BIRD SCREEN

DUCT JOINT PER

SMACNA PRESSURE

CLASS.

ACCESS DOOR WITH

CAM LOCK DOOR.

SAME MATERIAL AS

DUCTING.

CAULK INTERIOR AND

EXTERIOR PERIMETER

WEATHER TIGHT WITH

SILICON CAULKING.

LOUVER WITH

KYNAR FINISH

TO MATCH

BLDG. COLOR

EXTERIOR

INTERIOR

1"X1"X1/8" STEEL ANGLE. SCREW TO

LOUVER BOX 6" O.C. # 10 SCREWS

AND ANCHORED TO WALL 12" O.C.

TYPICAL TOP, BOTTOM AND SIDES.

WALL LOUVER DETAIL

3

NO SCALE

ROOF DECK

FAN HOUSING

EXHAUST

SECURE WITH

PREFABRICATED CURB WITH

FOR CONTINUATION.

DUCTWORK SEE PLANS

BACKDRAFT DAMPER

INSULATION

EXHAUST FAN DETAIL

NO SCALE

5

#10 SCREWS 12" O.C.

PERIMETER SUPPORT

ANGLES, 2" X 2" X 5/16"

TACK TO ROOF

FRAMING.

12" HIGH PRE-FABRICATED

ROOF CURB BY FAN

MANUFACTURER.

PROVIDE NEOPRENE

GASKET AND ENSURE

AIR TIGHT SEAL AT

CURB NAILER.

3/4 TRAPPED COND. DRAIN.

PROVIDE CLEAN OUT AND

CONCRETE SPLASH BLOCK.

FRESH AIR INTAKE HOOD

MAINTAIN MINIMUM OF 10'-0"

FROM ALL EXHAUST AND

PLUMBING VENTS

3" MIN.

SHEET METAL DROP FROM

BASE OF PLENUM CURB WITH

1" DUCT LINER AND WITH FLEX

CONNECTOR

NOT TO SCALE

CUT ROOF DECK ONLY AS

NEEDED FOR DUCT DROPS.

PROVIDE R-13 BATT OR

ROOFING INSULATION PLACED

ON REMAINING DECK.

ROOFTOP DETAIL

ELECTRICAL DISCONNECT

BY UNIT MANUFACTURER

6

MAINTAIN MINIMUM OF 10'-0"

FOR EDGE OF ROOF

AGA GAS SHUT OFF, DIRT LEG

AND UNION. PROVIDE TREATED

WOOD BLOCKING AND

GALVANIZED CLAMP SUPPORT.

PROVIDE NEOPRENE CURB

TAPE AT DUCT CONNECTION

SEAL AIR TIGHT.

PLACE EXTRA ROOF

MEMBRANE BETWEEN BLOCK

AND ROOF MEMBRANE. TYP.

30° MAX

O

AIR FLOW

45 DEG.

OCL CONNECTION

TAKE OFF. HAMMER

LOCKED OR FLANGED AND FULLY SEALED

RECTANGULAR

DUCT

BRANCH

CONCENTRIC TRANSITION

MAX, 45 DEG. DIVERGING

AND 60 DEG. CONVERGING

OFFSET. PROVIDE

MINIMUM 2" STRAIGHT

SECTION AT EACH END.

MAX 30 DEG.

ECCENTRIC TRANSITION MAX, 30 DEG.

30° MAX

AIR

F

LO

W

V.D.

HIGH EFFICIENCY

FLANGED TAKE OFF

COMPLETELY SEALED

ROUND SHEET METAL

DUCT TO WITH IN

5'-0" OF

DIFFUSER

RL

NOTE:

AIRFOIL BLADES TO BE USED WHERE

NORMAL RADIUS ELBOW IS

IMPRACTICAL

& WHERE ELBOW IS WITHIN 5 FT OF A

BRANCH TAKE-OFF.

NOTE:

IN GENERAL, ELBOWS TO HAVE

FULL TURNING RADIUS (R=A).

WHERE "R" IS EQUAL TO OR

GREATER THAN "A" MINIMUM

RADIUS (R) = 4 INCHES.

R=A

1

1

8

"

A

DUCT CONSTRUCTION DETAILS

NO SCALE

9

SHEET METAL GAUGES AND RIGIDITY SHALL BE IN

ACCORDANCE WITH SMACNA PRESSURE CLASS 1.0" UNLESS

OTHERWISE SPECIFIED.

DETAIL FOR REFERENCE ONLY, INSTALL PERMANUFACTURERS FIRE DAMPER INSTALLATIONINSTRUCTIONS.

ea. side on through pennetrations

Removable HVAC Register where shown

6

6

7

Access door per IMC on through pennetrations

7

24 GAUGE MINIMUM

SHEET METAL

TRANSISTION

System No. F-C-7013

F Rating - 1 Hr

T Rating - 0 Hr

1C

2

3

1B

3

2

1A

A

A

1. Floor-Ceiling assembly - The 1 hr fire rated solid or trussed lumber joist floor-ceiling

assembly shall be constructed of the materials and in the manner specified in the individual

L500 Series Floor - Ceiling Designs in the UL fire Resistance Directory, as summarized below:

A. Floor System - Lumber or plywood subfloor with finish floor of lumber, plywood or

floor topping mixture. Maximum diameter of floor opening is 5-1/4"

B. Wood Joists - Nominal 2 by 10 lumber joists spaced 16" o.c. with nominal 1 x 3

lumber bridging, Steel or combination lumber and steel joist, trusses or structural

wood members with bridging as required.

C. Gypsum Board - Thickness, type, number of layers and fasteners shall be as

specified in the individual Wall and Partition Design.

1.1 Chase Walls (not shown optional) - The through penetrates, item 2 may be routed through a 1

hr fire rated single, double or staggered wood stud/gypsum wallboard chase wall having a fire

rating consistent with that of the floor-ceiling assembly. The chase wall shall be constructed of

the materials and in the manner specified in tthe individual U300 Series Wall and Partition

Designs in the UL fire resistance director and shall include the following feature:

a. Flooring system- Lumber or plywood subfloor with finish floor of lumber, plywood or

Floor topping mixture as specified in the floor ceiling design. Max diam. of opening shall

be 5-1/4"

b. Wood Joist - Nominal 10" deep lumber, steel or combination lumber and steel joists,

trusses or structural wood members with bridging.

c. Gypsum board - Nom. 4 ft by

5

8

" thick as specified in the individual floor-ceiling design.

Max diam. of opening shall be 5-1/4"

2. Steel Duct - Max Nominal 4" diameter No. 28 gauge or heavier steel duct. One duct to be

within the firestop system. Diameter of openings hole sawed through flooring system and

through gypsum board ceiling to the nominal dimension of 1.25" larger than the outside

diameter of the through penetrate. Steel duct to be rigidly supported on both sides of

floor-ceiling assembly.

3. Fill void or cavity material - Fire sealant minimum 3/4" thickness of material applied within the

annulus on the top surface of the floor, Minimum 5/8" thickness of fill material applied within

the annulus on bottom suface of ceiling or lower top plate of the chase wall. Additional fill

material to be applied such that 1/8" crown is formed around the penetrating item on bottom

surface of ceiling or lower top plate of chase wall.

1C

1B

3

2

THROUGH

PENETRATIONS

MEMBRANE

PENETRATIONS

NOT TO SCALE

FIRE STOPPING DETAILS

8

WOOD FLOOR GYPSUM WALLBOARD ASSEMBLIES

TYPE OF PENETRANT F-RATING UL-CLASSIFIEDSYSTEM TYPE OF PENETRANT F-RATING UL-CLASSIFIED

SYSTEM

METAL PIPES ORCONDUIT

1 FC 1009, FC 1059

METAL PIPES ORCONDUIT

1 WL 1054, WL 1058,WL 1164

2 FC 1009, FC 10592 WL 1054, WL 1058,

WL 1164

4 WL 1110, WL 1111,WL 1165

NON-METALLIC PIPEOR CONDUIT

1FC 2232, FC 2030,FC 2160, FC 2127,

FC 2128 NON-METALLIC PIPEOR CONDUIT

1 WL 2078, WL 2075,WL 2128

2FC 2029, FC 2030,FC 2128, FC 2127,

FC 2160

2 WL 2078, WL 2075,WL 2128

4 WL 2184, WL 2245

INSULATED PIPES

1 FC 5004, FC 5037,FC 5036 CABLE TRAY

1 WL 4011, WL 40192 WL 4011, WL 40194 WL 8014

2 FC 5004, FC 5037 INSULATED PIPES

1 WL 5028, WL 5029,WL 5047

2 WL 5028, WL 5029,WL 5047

4 WL 5073NON-INSULATED

MECHANICALDUCTWORK WITHOUT

DAMPERS

1 FC 7013FC-7002

NON-INSULATEDMECHANICAL

DUCTWORK WITHOUTDAMPERS

1 WL 7017, WL 7040,WL 7042, WL 7155

2 WL 7040, WL 7042,WL 7155

INSULATEDMECHANICAL

DUCTWORK WITHOUTDAMPERS

1 N/A** INSULATEDMECHANICAL

DUCTWORK WITHOUTDAMPERS

1 WL 7059, WL 7153,WL 7156, WL 7151

2 N/A** 2 WL 7059, WL 7153,WL 7156, WL 7151

MIXED PENETRANTS 1 FC 8009, FC 8014,FC 8026, FC8025 MIXED PENETRANTS

1 WL 1095, WL 80132 WL 1095, WL 80134 WL 8014

NOTES:1. Jobsite conditions of each through-penetration firestop system must meet ALL details of the UL-Classified Systemselected.2. Where more than one applicable UL-Classified System is listed in the schedules, choose the UL System which is mosteconomical for each through-penetration firestop system.3. Coordinate work with other trades to assure that penetration opening sizes are appropriate for penetrant locations, andvice versa.

SCHEDULES OF THROUGH PENETRATION FIRESTOP SYSTEMS

4. List above is not all inclusive of allowable UL listed penetrate systems. Contractor may use any UL listed system provideddocumentation is submitted and approved by local authority having jurisdiction.

1

2

3

4

5

6

Closed

Normally

Motor / Actuator

120 V Circuit

Addressable Fire Alarm

Relay Module by FAC.

Fire Alarm Riser wiring is by

others. Coordinate with Owners

Fire alarm contractor.

Smoke damper

M

120 v

by E.C.

1. SINGLE SIDED OR CONVENTIONAL RETAINING

ANGLE.

2. ACCESSIBLE MOTORIZED ACTUATOR

3. SLEEVE/DUCT DROP

4. ELECTRICAL FLEX CONNECTOR.

5. FUSIBLE FIRE DAMPER LINK

6. UL555 & UL555S LISTED GREENHECK FSD-151

(OR EQUAL) COMBINATION FIRE/SMOKE

DAMPER.

NOT TO SCALE

SHAFT FIRE AND SMOKE DETAIL

10

SHAFT WALL SYSTEM

REFERENCE ARCHITECTURAL

DRAWINGS FOR DETAILS.

REFRIGERANT PIPING SIZED AND INSTALLED PER

MANUFACTURERS. REFERENCE LONG LINE

APPLICATION REQUIREMENTS WHEN APPLICABLE

REFRIGERANT TUBING WITH 1/2" WALL ARMAFLEX

INSULATION. PVC SLEEVE AND SEAL WALL

PENETRATIONS WATER TIGHT AND FLUSH TO

SURROUNDING FINISH. INSULATION LOCATED

OUTDOORS SHALL BE PAINTED WITH UV

RESISTANT ARMAFLEX PAINT.

CONCRETE PAD BY GC UNIT SHALL

BE SET LEVEL ON MANUFACTURERS

HEAT PUMP LEGS.

TXV METERING DEVICE

PITCH SUCTION LINE TOWARD

COMPRESSOR. PROVIDE OIL

RETURN TRAPS PER

MANUFACTURES PIPING

RECOMMENDATIONS.

AIR COOLED CONDENSER INSTALL

WITH MANUFACTURERS

RECOMMENDED CLEARANCES..

EVAPORATOR COIL SHALL COME INTEGRAL

WITH FAN COIL FROM MANUFACTURER.

INSTALL ALL REFRIGERATION

SPECIALTIES AS INDICATED ON

EQUIPMENT SCHEDULES.

GRADE MOUNTED HEAT PUMP DETAIL

SCALE: NONE

7

DIM

EN

SIO

NS

ARCH

ITEC

TURE

I

NTER

IORS

C

ONST

RUCT

ION

SER

VICE

S

WEB

SITE

: http

://ww

w.dim

ensio

ns-a

rchit

ects.

com

E-M

AIL:

info

@dim

ensio

ns-a

rchit

ects.

com

INC.

project title sheet

proj

ect n

o.

AS

SHO

WN

scal

e

revi

sion

s

date

chec

ked

bydr

awn

by

ME

P E

ng

in

ee

r

87

4 C

he

lte

nh

am

W

ay

Avo

n, IN

4

61

23

31

7.5

06

.8

15

1

31

7.7

45

.5

76

1

gn

ae

ng

in

ee

rin

g@

ao

l.co

m

GO

OD

ER

UM

&

A

SS

OC

IA

TE

S E

NG

IN

EE

RIN

G

P:

F:

E:

O

I

H

O

F

E

T

A

T

S

PR

O

F

E

S

S

I

O

NA

L

E

N

G

I

N

E

E

R

TS

G

I

R

E

E

GOODERUM

O

DAVID R.

74178

R

E

D

HAMP

TON

INN

CINC

INNA

TI, O

HIO

H-16

-384

08/1

0/20

17

- - - - -

H.V.

A.C

. PLA

N -

SCHE

DUL

ES

M003

GN

A

DIFFUSER, REGISTERS AND GRILLES

DESCRIPTIONTAG MFR MODEL CFMMAT'L.

MOUNTING

STYLE

NOTES:

S-1

S-2

S-3

24"X24" LAY-IN DIFFUSER - 6" NECK PRICE

PRICE

PRICE

SCD STL 0-100

100-225

225-400

1-100

LAY-IN

PAINT AREA BEHIND GRILLE FLAT BLACK.

PROVIDE WITH OBD STYLE DAMPER.

24"X24" LAY-IN DIFFUSER - 8" NECK

24"X24" LAY-IN DIFFUSER -10" NECK

S-5

PRICE9"X9" MODULAR CORE - BEVEL FRAME

L-1

SCD

SCD

SMD

STL

STL

STL

LAY-IN

LAY-IN

SURFACE

200

L-2

PRICE48" X 4.5" 2-SLOT LINEAR DIFFUSER SDS75 SURFACE

S-4

100-250PRICE

12" X 6" DOUBLE DEFLECTION W/DMP

520 STL SURFACE

0-1000R-1 PRICE24/24 LAY IN BAR FACE GRILLE 530 STL LAY-IN

24/12 LAY IN BAR FACE GRILLER-2 0-2000PRICE 530 STL LAY-IN

20/36 SURFACE BAR FACE GRILLER-3 2000PRICE 630 AL SURFACE

Al

PROVIDE SQUARE TO ROUND CONNECTOR FOR GRILLE

PROVIDE WITH OPPOSED BLADE DAMPER.

300PRICE72" X 4.5" 2-SLOT LINEAR DIFFUSER SDS75 SURFACEAl

RECESSED ARCHITECTURAL WALL HEATER, PROVIDE WITH INTEGRAL THERMOSTAT.1

11

PHASE

ELECTRIC HEATER SCHEDULE

MODEL NO.

AWH4800EWH-1

MARK MANUFCTR

QMARK

HEATING KW

4.0 208

VOLTAGE ACCESSORIES/REMARKS

4

3

2

1

MBH DEG. F.

MOCP

ELECTRICAL DATA

MCAVOLTS/PH/HZEATINPUT

HEATING CAPACITY

TAG

MUA SCHEDULE (DESIGN CONDITIONS, WINTER; 0 DB SUMMER; 82 DB 77 WB)

MANUFACTURER MODEL WEIGHT CFM

E.S.P.

(IN W.G.)

MAU-1 4051.5AAON 175140208/3/600

REMARKS

DEG.F.

LAT

76.4

1. FACTORY ASSEMBLED, PIPED, WIRED AND TESTED AS A SINGLE PACKAGE

2. UNIT SHALL INCLUDE A 100% OUTSIDE AIR HOOD WITH 2 POSITION MOTORIZED DAMPER

3. UNIT SHALL INCLUDE 2 STAGE COOLING, 2 COMPRESSOR CIRCUITS WITH INTERLACED-CIRCUIT DX COIL (HORIZONTAL SPLIT NOT ACCEPTABLE)

4. UNIT SHALL INCLUDE MINIMUM 10:1 TURNDOWN MODULATING NATURAL GAS HEATING WITH 304 SERIES STAINLESS STEEL HEAT EXCHANGER WITH A 25 YEAR WARRANTY (PARTS ONLY)

5. UNIT SHALL INCLUDE HOT GAS BYPASS ON ALL REFRIGERATION CIRCUITS (FROST-STAT COMPRESSOR CYCLING NOT ACCEPTABLE)

6. UNIT SHALL INCLUDE MODULATING HOT GAS REHEAT COIL FOR DEHUMIDIFICATION (2-POSITION OR DEDICATED HEAT PUMP CIRCUIT NOT ACCEPTABLE)

7. UNIT SHALL INCLUDE STAINLESS STEEL DRAIN PAN

8. UNIT SHALL INCLUDE MANUAL RESET HIGH PRESSURE SWITCHES & AUTO RESET LOW PRESSURE SWITCHES

9. UNIT SHALL INCLUDE EC CONDENSER FAN MOTORS FOR CONDENSER HEAD PRESSURE CONTROL.

10. UNIT SHALL INCLUDE 2" MERV 7 AND 4" MERV 12 FILTERS. PROVIDE 0.5" A 1.0" 16 GAUGE WIRE SCREEN FASTENED TO LEAVING SIDE OF FILTER RACK TO PREVENT FILTER COLLAPSE

11. CONTROLS: WATTMASTER/ORION VCMX CONTROLLER WITH AMBIENT DEWPOINT SENSOR; ELECTRONIC SEQUENCING OF COMPRESSORS, HEATING AND MODULATING HOT GAS RE-HEATING.THE INTENTION OF

THIS UNIT IS TO PROVIDE CONTINUOUS DEHUMIDIFICATION OF OUTSIDE AIR WHILE ALSO PROVIDING TEMPERATURE CONTROL TO THE SPACE IT SERVESIF THIS CAUSES OVERCOOLING IN THE SPACE, THE

MODULATING HOT GAS REHEAT VALVE SHALL OPEN TO SATISFY THE CONDITIONED SPACE REQUIREMENT FIELD MOUNTED CONTROLS SHALL INCLUDE A DUCT MOUNTED LEAVING AIR STAT AND A WALL MOUNTED

STAT (SEE PLANS FOR LOCATION) ALL UNIT MOUNTED CONTROLS FOR COMPLETE OPERATION SHALL BE INSTALLED BY THE EQUIPMENT MANUFACTURER

12. 2" FOAM INJECTED INSULATED (MINIMUM R13 VALUE) DOUBLEWALL CABINET CONSTRUCTION

13. UNIT SHALL INCLUDE INTEGRAL NON-FUSED DISCONNECT

14. R410A15. DUCT MOUNTED SMOKE DETECTOR PROVIDED BY ELECTRICAL, INSTALLED BY MECHANICAL.

16. UNIT SHALL INCLUDE A FACTORY ASSEMBLED AND INSULATED ROOF CURB/PLENUM WITH VIBRATION ISOLATION RAILS. CURB HEIGHT TO BE DETERMINED

17. UNIT SHALL BE AHRI LISTED AND CERTIFIED (COIL ONLY CERTIFICATION IS NOT ACCEPTABLE).

18. COMPRESSORS SHALL HAVE 5 YEAR WARRANTY (PARTS ONLY)20. CONTACT GORHAM/SCHAFFLER, INC. FOR INFORMATION PHONE: 1-901-345-6100

DX COOLING CAPACITY

MBH DB/WB

EATTOTAL

316 82/77

DB/WB

LAT (COIL)

52.9/52.7

MBH

SENSIBLE

125

MBH

DX REHEAT

73

DB/RH

LAT (UNIT)

70

HP RPM

FANMOTOR

FAN DATA

3.0 1281

EER

11.7

NOTES

41003400RN-025-8-0-BA02-38B

MBH

OUTPUT

328

CARRIER

HIGH EFFICIENCY HEAT PUMP SCHEDULE (3 PHASE)

MANUFACTURERMARK MODEL

HP-4

ELECTRICAL SPECIFICATIONS

MOCP

(V-Ph-Hz)

ELEC.

COOLING

REFG.

TONS

NOMINAL

MCASEER EER

HEAT PUMP MODE

@ 17 DEG

CAPACITY

COP

AHRI

HSPF

AHRI

NOTES:

MBHMBH

4.0

25HCD5 60 A005

CARRIERHP-1

5.0 R-410A 208-1-6015 12.5 59000 3.8637,200

8.7 1 2 334.2 50

OUTSIDE

FAN COIL SCHEDULE ELECTRIC HEAT (3 PHASE)

MANUFACTURERMARK MODEL NOTES:

1

HEATING CAPACITY @17 DEG

KW

BTUH

COOLING

REFG.

TONS

NOMINAL

ELECTRICAL

(V-Ph-Hz)

ELEC.

CFM

TOTAL

PRESS.

STATIC

CFM

AIR

2

PROVIDE MANUFACTURERS 2" FILTER RACK WITH 2" MERV 12 PLEATED FILTER.

FC-3 CARRIER

3.0FX4DN-F037-000

MCA MOCP

208

FC-1 CARRIER

FC-6 CARRIER

PROVIDE WITH TXV AND COPPER TUBE ALUMINUM FIN COIL.

DUCTLESS SPLIT SCHEDULES

MANUFACTURERTAG NOTES:

1

AIR FLOW

CFM

COOLING

REFG.

ELECTRICAL SPECIFICATIONS

MCA

(V-Ph-Hz)

ELEC.

2

PROVIDE REMOTE WIRED MHK-1 T/S CONTROLLER

MODEL

INDOOR OUTDOOR

MBH

TOTAL

SEER

COOLING ONLY DUCTLESS SPLIT

R410A 208/230-1-60 18 118000 2PKA-A18KA4 PUY-A18NHA4 VARIES 17.0MITSUBISHIMS-1

MOCP

30

AREA

CFM

LOUVERS, INTAKES, RELIEFS

TAG MODEL # LOCATION/SERVICE NOTES

FGR, 30X16 ELEVATOR VENTINGSHAFT VENT 3.0 FT2 1

RH-1

GREENHECK

FREE

LV-11

POOL AREA INTAKE

1 PROVIDE KYNAR PAINT COLOR TO MATCH BUILDING.

PROVIDE WITH MINIMUM 22 GAUGE EXTERNALLY INSULATED LOUVER BOX WITH CLEAN OUT ACCESS DOOR2

PROVIDE WITH MINIMUM 22 GAUGE EXTERNALLY INSULATED LOUVER BOX.3

LV-31

LV-4

PROVIDE WITH 12" TALL INSULATED CURB AND FIRE AND SMOKE DAMPER WITH 120V ACTUATOR.4

ESD-435 CHNL FRAME

ESD-435 CHNL FRAME

30/16

SIZE

MIN

2

3

FGR, 30X16 ELEVATOR VENTINGSHAFT VENT 1

RH-230/16

BLOWER

FC-2

FC-4

.5 150R410A 208-60-36.8 30,708 120032.0 35

3

PROVIDE DIGITAL NON-PROGRAMMABLE THERMOSTAT WITH REMOTE SENSOR (WHERE SHOWN) ALL LIKE HONEYWELL 8000 SERIES.

25HCD5 36 A005

CARRIERHP-2 1 2 3

22.1 353.0 R-410A 208-1-6015 12.5 33000 3.9220,000

8.7 1 2 3

ESD-435 CHNL FRAME

ESD-435 CHNL FRAME POOL AREA EXHAUSTLV-1

CARRIERHP-5

CARRIERHP-6 1 2 3

25HCD5 48 A005 R-410A 208-1-6015 12.5 45000 3.8428,600

8.4 1 2 328.7 40

R-410A 208-1-6015.3 12.5 3.92 8.6

4.0

1.5

ACCESSORIES

PROVIDE WITH MANUFACTURER PROVIDED FIBER MOUNTING PAD, CRANKCASE HEATER, LOW AND HIGH PRESSURE SWITCHES. PROVIDE ADDITIONAL LONG LINE SET ACCESSORIES AS

REQUIRED BY MANUFACTURER FOR SPECIFIC APPLICATIONS.

INSTALL SIGHT GLASS AND FILTER DRIER AT UNIT CONNECTIONS.

1

2

25HCD5 48 A005

25HCD5 18 A005 11.8 203300020,000

AUX

BTUH

REFG

DEG F

DT

20,000

4

PROVIDE MANUFACTURERS UNIT MOUNTED 3 PHASE HEATER KFCEH1601315 WITH SINGLE POINT KIT.

5

PROVIDE MANUFACTURERS UNIT MOUNTED 3 PHASE HEATER KFCEH2901N09 WITH SINGLE POINT KIT.

40

CARRIER

CARRIER 5.0 R410A 208-60-3 1990 1 2.5 30011.3 38,500FX4DN-F061-000 47.7 50 337,200 35 5

1 2 31 2 3 4

FC-5

CARRIER 4.0 1 2 31 2 3 4

3.0FX4DN-F024-000 .5R410A 208-60-36.8 30,708 120032.0 3520,000 40 1 2 31 2 3 40

R-410A 208-1-6015 12.5 45000 3.8428,600

8.4 28.7 40

R410A 208-60-3 1600 .5 25047.7 50FX4DN-F049-00011.3 38,555

28,60039

300 0.4818/12

DRYER EXHAUST

2000 5.6030/20DRYER INTAKE

2000 5.60

1

1

4

4

3

3

MODEL NO.

NE-004-PV-I-A3NT1202E5C4AE3DHU

MARK MANUFCTR

SERESCO

PROVIDE WITH UNIT MOUNTED SCR CONTROLLED ELECTRIC HEATING COIL

POOL DEHUMIDIFICATION EQUIPMENT SCHEDULE R410A

208/3/60

TOTAL

1990

ESP

1.0

MTR

CFM HP

OA

CFM

3.0 300

COOLED DX COOLING

SENS

ELECTRIC HEATING COIL

55.5 6029.1

BTUH

47,768 20.0

KW LAT

88.5

TOTAL

52.0

LBS/H

25.0 66.5

EAT

ELECTRICAL DATA

VOLTAGE MCA MOCP

NOTES:

1

PROVIDE WITH POOL HEATING OPTION, 7 GPM, 36,000 BTUH.

1

2

2

AC-P NC-B-1VSERESCO

208/3/60

4.0 1564.7 64.7

BTUH BTUH 50RH

SEE 1. - 18. BELOW

2

ELECTRICAL DATACOOLINGHEATING

MANUFACTURER

HIGH EFFICIENCY PTAC/VTAC SCHEDULE

MARK

O.A.CFMPHASEVOLT MCABTUKW REMARKSHEAT PUMP

PROVIDE DIGISMART THERMOSTAT, ACCESSIBLE ROOMS TO BE MOUNTED AT 48" OTHERS 60"

PROVIDE INSULATED METAL WALL SLEEVE WITH EMERGENCY DRAIN KIT

NOTES:

PROVIDE ELECTRICAL SUBBASE WITH GFI RECEPTICAL.

AMANNA

EERBTU COP

HIGH

MOCP

208

3.5PTAC-A

8,9008,100 3.3

HEH-09-3H-35R

12.519.4 20 310 01

Nominal HP

208

5.0VTAC-1

17,40016,700 3.0

VTH-24-3E-05A

9.0

24 25 650 1301

PROVIDE WITH DOOR SWITCH AND MOTION SENSOR HARD WIRED TO PTAC SYSTEM. 4

1

2

3

1 2 3 4

5

PROVIDE WITH SINGLE POINT POWER CONNECTION WITH DISCONNECT, WALL SLEEVE WITH KYNAR PAINTED LOUVER TO MATCH BUILDING.5

PROVIDE WITH LOUVERED 82" TALL WALL PANEL WITH INTEGRAL FILTERED INTAKE.6

4.0 1 2 31 2 3 4R410A 208-60-3 1600 .5 25047.7 50FX4DN-F049-000

11.3 38,55528,600

39

3.0FX4DN-F037-000 .5 150R410A 208-60-36.8 30,708 120032.0 3520,000 40 1 2 31 2 3 4

CARRIERHP-3 25HCD5 36 A005 22.1 353.0 R-410A 208-1-6015 12.5 33000 3.9220,000

8.7 1 2 3

S-A100-250PRICE

6" X 6" DOUBLE DEFLECTION W/DMP520D STL SURFACE

E-APRICE

6X6 ALUMINUM EXHAUST AIR GRILL

AL 30-50 SURFACE 2

2

2

1 2

1 2

630

3

3

30/20

400 0.4818/12

3.0 FT2

DIM

EN

SIO

NS

ARCH

ITEC

TURE

I

NTER

IORS

C

ONST

RUCT

ION

SER

VICE

S

WEB

SITE

: http

://ww

w.dim

ensio

ns-a

rchit

ects.

com

E-M

AIL:

info

@dim

ensio

ns-a

rchit

ects.

com

INC.

project title sheet

proj

ect n

o.

AS

SHO

WN

scal

e

revi

sion

s

date

chec

ked

bydr

awn

by

ME

P E

ng

in

ee

r

87

4 C

he

lte

nh

am

W

ay

Avo

n, IN

4

61

23

31

7.5

06

.8

15

1

31

7.7

45

.5

76

1

gn

ae

ng

in

ee

rin

g@

ao

l.co

m

GO

OD

ER

UM

&

A

SS

OC

IA

TE

S E

NG

IN

EE

RIN

G

P:

F:

E:

O

I

H

O

F

E

T

A

T

S

PR

O

F

E

S

S

I

O

NA

L

E

N

G

I

N

E

E

R

TS

G

I

R

E

E

GOODERUM

O

DAVID R.

74178

R

E

D

HAMP

TON

INN

CINC

INNA

TI, O

HIO

H-16

-384

08/1

0/20

17

- - - - -

H.V.

A.C

. PLA

N -

SCHE

DUL

ES A

ND

DET

AIL

S

M004

GN

A

SONESESPCFM

TYPE FAN AND

DESCRIPTION

EXHAUST FAN SCHEDULE

TAG MODEL # LOCATION FLA

MOTOR DATA

HP

VOLT NOTES

EF-3

1 PROVIDE WITH BROAN STEEL WALL CAP AS SHOWN ON PLANS.

WATTS

REF-1

SPA-090

250

CEILING

FAN DATA

VARIOUS

4.5

ROOF

.375 5.5 1/8ROOF

115DIRECT DRIVE

DIRECT DRIVE

DIRECT DRIVEROOF

ROOF

DIRECT DRIVE

DIRECT DRIVE

DIRECT DRIVE4

POOL AREA CEILING 400

2

ROOF

ROOF

REF-2

REF-3

REF-4

REF-5

REF-6

REF-7

REF-8

DIRECT DRIVE4ROOFREF-9

PROVIDE PLASTIC WET LOCATION CHEMICAL RESISTANCE PVC CONSTRUCTION OR COATINGS.

4

4

4

4

4

4GREENHECK G-097-VG

GREENHECK G-097-VG4.55.5 1/8 115

4.55.5 1/8 115

4.55.5 1/8 115

4.55.5 1/8 115

4.55.5 1/8 115

4.55.5 1/8 115

EF-1

VARIOUSSPA-070EF-2

GREENHECK

CEILING 50 .125

EF-4LAUNDRY CEILING 200

SPA-250 .375

70

.723.5 80 120

<1 120 .3030.125

240

240

330

180

270

270

.375

.375

GREENHECK G-097-VG

GREENHECK G-097-VG

GREENHECK G-097-VG

GREENHECK G-097-VG

GREENHECK G-097-VG

VENTILATION AIR CALCULATIONS

AREA TYPE

OFFICE

OCCUPANTS

PER 1000 FT

CALCULATED

OCCUPANCY

CFM/PERSON

REQUIRMENT

CFM REQ.

RESTROOMS

5 3 5 52

TOTAL

NET AREA

CFM

30 7.5

CIRCULATION/HALLWAYS

--

621

800

450 (4) WC

-- 50/70

.06

.0624 228

--

3248.06-- -- -- 194

--

--

--

PEOPLE

FRESH AIR

TOTAL

SUB TOTALS

CALCULATIONS ARE BASED ON OMC 2017 TABLE 403.3.

REFERENCE HVAC PLANS AND SCHEDULES FOR INDIVIDUAL UNIT AND DIFFUSER BALANCE AMOUNTS

AREA CFM

REQUIRMENT

LOBBIES/PREFUNCTION

STORAGE/MECH RMS

-- -- --1760

.06

70 7.51758

.18123 439 --

DINING LOUNGE

CFM REQ.

EXHAUST

--

a

(a) - Rate is per water closet or urinal.

REQUIRED

AREA CFM

REQUIRED

15

180

--

--

--

123

CFM/FT2

37

48

--

194

105

316

1S

T F

LO

OR

105--

187 1794 --13815

MECH/HALLWAYS -- -- -- 1111850

.06 --

-- --300

-- 18 --

STORAGE

--

--

111

18.06

2N

D F

LO

OR

GRAND TOTALS

4170

39,997

327

CONFERENCE/MTG RMS

458

--

BEDROOMS

10 22 52240 (10)

.06112 134 246--

BATH ROOMS

-- --

1360 (10)

-- --

POOL DECK

-- -- --620

.48-- -- 297--

-- 15 5 103.0675 28

25/50

(b) - Continuous/Intermittent requirement.

--

--

280

--

--

CFM REQ.

EXHAUST

TOTAL

--

530

--

--

250

--

b

ab

BEDROOMS

10 70 56975 (31)

.06350 418

768--

BATH ROOMS

-- --

4216 (31)

-- -- 25/50

--

775

ab

SUB TOTALS

70 1188 --13341 775

MECH/HALLWAYS -- -- -- 1111850

.06 --

-- --

300

-- 18 --

STORAGE

--

--

111

18.06

3R

D F

LO

OR

BEDROOMS10 70 5

6975 (31)

.06350 418

768--

BATH ROOMS

-- --4216 (31)

-- -- 25/50

--

775

ab

SUB TOTALS

70 1188 --13341 775

2080

FITNESS ROOM

10 5 20

500

.06100 30 130-- --

LEVEL 1, SUPPLY FRESH AIR

SUPPLY FC-1 --> FC-6. 8200 580

10 PTACS 2900 0

VTAC 800 130

MINI SPLI 600 0

POOL UNIT 1990 300

DOAS (AAON) 650 650

TOTAL CFMS 9230 1660

EXHAUST SYSTEMS EXH

EXHAUST FANS 1200

CENTRAL EXHAUST 350

TOTAL EXHAUST 1550

FLOOR BALANCE +110

LEVEL 2, SUPPLY FRESH AIR

31 PTACS 8990

DOAS (AAON) 1535 1535

TOTAL CFMS 10525 1535

EXHAUST SYSTEMS EXH

EXHAUST FANS 100

CENTRAL EXHAUST 1030

TOTAL EXHAUST 1130

FLOOR BALANCE +405

LEVEL 3, SUPPLY FRESH AIR

31 PTACS 8990

DOAS (AAON) 1535 1535

TOTAL CFMS 10525 1535

EXHAUST SYSTEMS EXH

EXHAUST FANS 100

CENTRAL EXHAUST 1030

TOTAL EXHAUST 1130

FLOOR BALANCE +405

TOTALS,

FRESH AIR EXHAUST AIR

4730 3810

BUILDING BALANCE +920

VENTILATION

PROVIDED

<1 120 .3020

SPA-510

.375

4.5 120 3.3224

1

1

1

2

2

3 PROVIDE WITH 36" TALL INSULATED FAN CURB.

300

DIRECT DRIVEROOF 4

4.55.5 1/8 115270GREENHECK G-097-VG

.375

.375

.375

.375

.375

4.5.375 5.5 1/8ROOF

115DIRECT DRIVEGREENHECK G-097-VG

G

J

H

E

F

K

L

M

2 18 19

3 45

6 7 8

9 10 11 12

13 14 15 16 17

3.9

9.9 11.1

16.1

DNUP

1

DNUP

C

A

10.4 12.6

B

D

G

J

H

E

F

K

L

M

C

B

D

KING

101

KING

103

MANAGER

029

COMPUTER/

PBX

027

WORK

AREA

026

FRONT

DESK

021

VESTIBULE

001

MAIN

LOBBY

006

ELEV.

LOBBY

191

MENS

RR

018

WMNS

RR

019

MTG.

STOR.

015

MEETING

ROOM

013

BREAKFAST

AREA

006

PANTRY

009

FOOD

PREP.

012

FOOD

PREP

STOR.

011

MECH.

010

KING

129

KING

131

ACCESSIBLE

KING

127

KING

128

KING

130

VEST.

003

VEST.

004

DOUBLE QUEEN

125

MECH.

014A

MECH.

014B

EMP.

RR

040

LINEN

STORAGE/

FOLDING

035

EMP.

BREAK

ROOM

038

E.W.

HOUSKPG

MANAGER

LO

CK

ER

S

WORK

TABLE

FITNESS CENTER

020

POOL

050

MECH.

031

POOL

RR

052

GUEST

LAUND.

025

ELEV.

1

WWDD

MOP

LAUNDRY

034

MAINTENANCE/

MECHANICAL/

ELECTRICAL

017

MAINT.

BENCH

ELEC.

PANELS

SPRK. RISER

WH

WH

WH

WH

DOUBLE QUEEN

105

DOUBLE QUEEN

107

STORAGE

005

POOL PATIO

--

POOL

EQUIPMENT

051

WORK

TABLE

LC

TREATS

002

MECH.

016

ELEV.

2

VENDING

193

A

G.2 G.2

VTAC

ELECTRICAL

043

STAIR 2

181

STAIR 1

180

CORRIDOR

198

CORRIDOR

197

CORR.

199

DRYERS

036

C

C

CCC

C

C C

C

C

9'-0" A

9'-0" A

9'-0" A

10'-8" A

9'-0" B

10'-0" B

8'-6" B

8'-6" D8'-6" B

8'-6" B

9'-0" B

B

8'-6" B

8'-6" A

9'-0" B

9'-0" B

9'-0" A

8'-6" A

9'-0" B9'-0" B 9'-0" B 9'-0" B 9'-0" B

8'-6" A 8'-6" A

8'-0" A

8'-6" B

9'-0" B

9'-0" B

9'-0" B

8'-6" B

8'-6" B

8'-6" B

8'-6" B

9'-0" B 9'-0" B 9'-0" B

8'-6" B8'-6" D

8'-6" D

8'-0"

A

8'-0" A

8'-0" A

8'-0" A

8'-0" A8'-0" A

8'-0" A

8'-0" A

8'-0" A

8'-0"

A8'-0"

A

8'-0"

A8'-0"

A

S-1

150

S-2

150

S-1

150

S-1

100

S-3

350

S-1

150

S-1

150

S-1

150

8547 sq ft

S-2

200

S-1

50

S-3

300

S-1

50

S-4

100

S-3

350

S-1

70

S-1

200

S-1

150

S-1

300

S-1

100

S-3

350

L-1

200

S-3

300

DTEXT DTEXT

MTEXT MTEXT

(6) Rooms, 180 exh

210 mua

PTAC-A PTAC-A

PTAC-A PTAC-A PTAC-APTAC-A

PTAC-A

PTAC-A

L-1

200

L-1

200

S-3

350

S-3

350

S-2

100

12/10

R-4

600

COMMON AREA

14,184 TOTAL

(10) RMS = 3600 FT, 7.5 TONS, 480 FT2/TON.

COMMON = 10584 FT2 22 TONS TOTAL. 516 FT/TON (NO VENT LOAD)

AAON = XX CFM, XX TONS, XX FT/TON

OVERALL, XX FT/TON WITH AAON

M

6"Ø

S-5

50

6"Ø

10"Ø

10"Ø

14"Ø

FC-6

1.5 Ton

T

T

T T

14/12

S-A

35

S-A

35

S-A

35

S-A

35

E-A

30

E-A

30

E-A

30

E-A

30

FC-5

4.0 Ton

S-2

150

S-2

150

S-2

150

E-A

50

4"Ø

S-A

35

S-A

35

E-A

30

E-A

30

16"Ø

R-2

150

R-2

70

FC-4

5.0 Ton

10"Ø Typ

S-3

400

S-A

35

S-A

35

E-A

30

E-A

30

S-A

35

S-A

35

E-A

30

E-A

30

EF-1

75

24/12

10"Ø

10"Ø

10"Ø

24/12

18/12

EF-1

75

8"Ø

10"Ø W.C.

EF-2

75

18"Ø

16/12

PTAC-A

PTAC-A

L-2

380

L-2

380

L-2

380

L-2

380

DHU

R-3

1990

18"Ø

10"Ø

10"Ø

EF-3

400

LV-1

300

LV-2

400

ACCESS

10' AFF

10' AFF

22/12

22/12 18/12

L-2

380

10"Ø Typ.

EF-1

75

6" W.C.

6"Ø

12/12

EWH

EWHEWH

EWH

EWH EWH

EF-1

50

6" W.C.

S-2

200

10' AFF

S-4

35

S-2

200

S-2

200

12/12

VTAC-A

2 Ton

10/10

S-5

50

6"Ø

FC-1

3.0 Ton

MS-1

1.5 Ton

16/12

16/12

R-2

200

R-1

700

10"Ø

S-2

200

6"Ø

4"Ø

8"Ø

FD

8"Ø

FD

EF-1

75

8" W.C.

EF-1

75

8" W.C.

FC-2

4.0 Ton

EF-1

75

R-2

350

S-3

350

20/14

16/16

10"Ø

S-5

50

EF-4

200

10" W.C.

LV-3

2000

LV-4

2000

M

14"Ø

R-1

1200

S-3

400

10"Ø

S-2

200

S-1

50

10"Ø

10"Ø

14"Ø

R-1

1380

18/18

R-1

995

R-1

995

R-1

1200

14"Ø

12/10 12/10

8/8

EF-2

50

4" W.C.

8/10

6/6

R-X

--

R-1

--

12"Ø

R-2

200

8/816/12

16/12

S-3

350

S-3

350

FC-3

3.0 Ton

10/12

12/12

8"Ø

8"Ø

6"Ø

8"Ø

14/12

12/12

S-1

150

8/812/10

8"Ø

8"Ø

8"Ø

6"Ø

8"Ø 10"Ø

8"Ø

8"Ø

8"Ø

8"Ø

TT

TT

T T

T

T

S

S

T

T

T

T

T

POOL

AC

HP-2

4 Ton

HP-3

3 Ton

HP-6

1.5 Ton

HP-4

5 Ton

HP-5

4 Ton

MS-1

1.5 Ton

30/24 30/24

HP-1

3 Ton

24/12

7'0 AFF

EF-2

50

4" W.C.

6"Ø W.C.

6"Ø

6"Ø

10"Ø

4" Dryer

Vent

20/12

4"Ø

103 CFM

130 CFM

100 CFM

350 CFM

DIM

EN

SIO

NS

ARCH

ITEC

TURE

I

NTER

IORS

C

ONST

RUCT

ION

SER

VICE

S

WEB

SITE

: http

://ww

w.dim

ensio

ns-a

rchit

ects.

com

E-M

AIL:

info

@dim

ensio

ns-a

rchit

ects.

com

INC.

project title sheet

proj

ect n

o.

AS

SHO

WN

scal

e

revi

sion

s

date

chec

ked

bydr

awn

by

ME

P E

ng

in

ee

r

87

4 C

he

lte

nh

am

W

ay

Avo

n, IN

4

61

23

31

7.5

06

.8

15

1

31

7.7

45

.5

76

1

gn

ae

ng

in

ee

rin

g@

ao

l.co

m

GO

OD

ER

UM

&

A

SS

OC

IA

TE

S E

NG

IN

EE

RIN

G

P:

F:

E:

O

I

H

O

F

E

T

A

T

S

PR

O

F

E

S

S

I

O

NA

L

E

N

G

I

N

E

E

R

TS

G

I

R

E

E

GOODERUM

O

DAVID R.

74178

R

E

D

HAMP

TON

INN

CINC

INNA

TI, O

HIO

H-16

-384

08/1

0/20

17

- - - - -

1

SCALE: 1/8" = 1'-0"

FIRST FLOOR HVAC PLAN

FIRS

T FL

OO

R HV

AC

PLA

N

M100

GN

A

1. REFERENCE SHEET M-001 FOR LEGENDS,

ABBREVIATIONS, SPECIFICATIONS AND NOTES.

2. REFERENCE SHEETS M-002 AND M-003 FOR

DETAILS.

3. REFERENCE SHEET M-004 FOR SCHEDULES.

4. REFERENCE ARCHITECTURAL RCP, SPRINKLER

SHOP DRAWINGS AND FINAL LIGHTING

LAYOUTS AND COORDINATE FINAL LOCATIONS

OF ALL CEILING DIFFUSERS AND REGISTERS.

5. REFERENCE ARCHITECTURAL ENLARGED

GUEST UNIT PLANS FOR EXACT LOCATIONS OF

THERMOSTATS AND EXHAUST GRILLES.

GENERAL NOTES:

PROVIDE AND INSTALL POOL HOT WATER HEATER

FLUES AND COMBUSTION AIR VENTING PER

HEATER MANUFACTURE. PIPE POOL WATER TO

SERESCO UNIT WITH 1" PVC PER SERESCO

INSTALLATION MANUAL. COORDINATE WITH POOL

CONTRACTOR.

PROVIDE AND INSTALL POOL ROOM

DEHUMIDIFICATION UNIT WITH FRESH AIR INTAKE.

BALANCE FRESH AIR TO 300 CFM. COORDINATE

WITH POOL EQUIPMENT AND MAINTAIN ALL

REQUIRED CLEARANCES.

PROVIDE AND INSTALL FAN COIL UNIT WITH 15

SEER HEAT PUMP. SEE DETAIL ON SHEET M-002

FOR MORE INFORMATION.

PROVIDE LOUVER WITHOUT SCREEN FOR DRYER

EXHAUSTS. PROVIDE LOUVER WITH SCREEN AND

MOTORIZED DAMPER INTERLOCKED TO BLOWER

MOTORS FOR COMBUSTION AIR. COORDINATE

FINAL SIZING AND REQUIREMENTS IN FULL

ACCORDANCE WITH DRYER MANUFACTURERS

VENTING SPECIFICATIONS.

PROVIDE DEDICATED COOLING ONLY MINI SPLIT

SYSTEM FOR PBX ROOM HEAD IN EQUIPMENT.

COORDINATE LOCATION WITH EQUIPMENT

PROVIDERS.

KEY NOTES:

1

2

1

3

4

4

3

3

3

3

3

3

PROVIDE AND INSTALL RECESSED ARCHITECTURAL

ELECTRIC WALL HEATERS. COORDINATE WITH E.C.

PROVIDE REMOTE SENSOR FOR THERMOSTAT AND

INSTALL THERMOSTAT IN MECHANICAL ROOM.

PROVIDE WIRED ROOM THERMOSTAT, WIRED

MOTION SENSOR, PTAC ANTENNA AND WIRELESS

GATEWAY WITH WEB ACCESS AND PROPERTY

MANAGEMENT INTERFACE IN ALL GUEST ROOMS.

SEE SCHEDULES FOR MORE INFORMATION.

TYPICAL ALL GUEST ROOMS. COORDINATE FINAL

THERMOSTAT LOCATION WITH ROOM LAYOUTS.

ALL DISTRIBUTION VENTILATION AIR DUCTING BOTH

SUPPLY AND EXHAUST OUTSIDE OF GUEST ROOMS

SHALL BE CONTINUOUS RIGID SHEET METAL DUCT

(MINIMUM 26 GAUGE) FROM ROOF MOUNTED

EQUIPMENT TO GUEST ROOM AND SHALL BE FIRE

STOPPED AT ALL 1 HR RATED WALLS. TYPICAL ALL

DUCTING.

ZZ X ZZ UP INTO SHAFT ABOVE. PROVIDE FIRE AND

SMOKE DAMPER AT SHAFT PENETRATION WITH

ACCESS DOORS AS REQUIRED FOR INSPECTION

PER OMC.

PROVIDE 10" ROUND CONNECTION WITH DAMPER

BETWEEN MUA DUCTING AND RA ON FC-4. BALANCE

TO 350 CFM.

PROVIDE 6" ROUND CONNECTION WITH DAMPER

BETWEEN MUA DUCTING AND RA ON FC-2. BALANCE

TO 100 CFM.

KEY NOTES:

6

5

5

6

6

6

7

7

7

8

8

8

9

9

9

10

10

11

11

12

12

PROVIDE AND INSTALL RECESSED METAL FIRE

RATED DRYER VENT BOX AND ROUTE SHEET

METAL DRYER VENT TO BACK WALL. SEE DETAIL ON

SHEET M002.

INSTALL VENTILATION AIR REGISTER WITH

INTEGRAL DAMPER CENTERED HORIZONTALLY

OVER OPENING AND VERTICALLY IN DRYWALL BULK

HEAD. TYPICAL ALL ROOMS.

KEY NOTES:

13

13

14

14

14

DN

UP

DN

UP

KING SOFA

200

KING SOFA

202

DOUBLE

QUEEN

204

DOUBLE

QUEEN

206

KING

201

KING

203

DOUBLE

QUEEN

205

DOUBLE

QUEEN

207

DOUBLE

QUEEN

209

DOUBLE

QUEEN

211

DOUBLE

QUEEN

213

DOUBLE

QUEEN

215

DOUBLE

QUEEN

219

DOUBLE

QUEEN

221

DOUBLE

QUEEN

223

DOUBLE

QUEEN

225

KING

231

KING

229

KING

230

KING

228

ACCESSIBLE

KING

226

ACCESSIBLE

KING

227

ACCESSIBLE

DOUBLE

QUEEN

216

STORAGE

294

ELEV.

1

LC

8"

ELECTRICAL/

HOUSE

KEEPING

295

ELEV.

2

G

J

H

E

F

K

L

M

2 18 19

3 45

6 7 8

9 10 11 12

13 14 15 16 17

3.9

9.9 11.1

16.11

C

D

G

J

H

E

F

K

L

M

C

D

STORAGE

292

G.2 G.2

DOUBLE

QUEEN

208

DOUBLE

QUEEN

210

DOUBLE

QUEEN

212

DOUBLE

QUEEN

214

DOUBLE

QUEEN

218

DOUBLE

QUEEN

220

DOUBLE

QUEEN

222

DOUBLE

QUEEN

224

D.5D.5

VENDING

293

ELEVATOR

LOBBY

297

CORRIDOR

291

CORRIDOR

290

STAIR 1

280

STAIR 2

281

8'-0" B

8'-0" A

8'-0" A

8'-0" A

7'-6" A 7'-6" A 7'-6" A 7'-6" A 7'-6" A 7'-6" A 7'-6" A 7'-6" A

8'-0" B 8'-0" B 8'-0" B 8'-0" B 8'-0" B 8'-0" B 8'-0" B 8'-0" B

8'-0" B

8'-0" B

S-1

75

S-1

75

S-1

75

S-1

75

2492 sq ft

.06 = 150

(31) Rooms,

930 exh + 150 = 1080

1085 mua + 450 = 1535

S-1

75

S-1

75

E-A

30

PTAC-A PTAC-A

PTAC-A PTAC-A PTAC-A PTAC-A

PTAC-A

PTAC-A

PTAC-A PTAC-A PTAC-A PTAC-A PTAC-A

PTAC-A PTAC-A

PTAC-A PTAC-A PTAC-A PTAC-A PTAC-A PTAC-A PTAC-A PTAC-A PTAC-A

PTAC-A

PTAC-A

PTAC-A PTAC-A

PTAC-A PTAC-A

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

14/10 12/10

6"Ø

10/10

8/8

6"Ø

14/10

6"Ø

12/1010/10

6"Ø

6"Ø

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

18/12

8/8

T T T T T T T T T T T T

T

T T

T

T

TT

T

T

T

T

TTTTT

T

PTAC-A

E-A

50

EF-2

50

4" W.C.

E-A

50

4"Ø

EF-2

50

4" W.C.

20/12

DWN

36/12

UP

T

T T

TT

DIM

EN

SIO

NS

ARCH

ITEC

TURE

I

NTER

IORS

C

ONST

RUCT

ION

SER

VICE

S

WEB

SITE

: http

://ww

w.dim

ensio

ns-a

rchit

ects.

com

E-M

AIL:

info

@dim

ensio

ns-a

rchit

ects.

com

INC.

project title sheet

proj

ect n

o.

AS

SHO

WN

scal

e

revi

sion

s

date

chec

ked

bydr

awn

by

ME

P E

ng

in

ee

r

87

4 C

he

lte

nh

am

W

ay

Avo

n, IN

4

61

23

31

7.5

06

.8

15

1

31

7.7

45

.5

76

1

gn

ae

ng

in

ee

rin

g@

ao

l.co

m

GO

OD

ER

UM

&

A

SS

OC

IA

TE

S E

NG

IN

EE

RIN

G

P:

F:

E:

O

I

H

O

F

E

T

A

T

S

PR

O

F

E

S

S

I

O

NA

L

E

N

G

I

N

E

E

R

TS

G

I

R

E

E

GOODERUM

O

DAVID R.

74178

R

E

D

HAMP

TON

INN

CINC

INNA

TI, O

HIO

H-16

-384

08/1

0/20

17

- - - - -

1

SCALE: 1/8" = 1'-0"

SECOND FLOOR HVAC PLAN

SECO

ND

FLO

OR

HVA

C PL

AN

M200

GN

A

GENERAL NOTES:KEY NOTES:

1 PROVIDE WIRED ROOM THERMOSTAT, WIRED

MOTION SENSOR, PTAC ANTENNA AND WIRELESS

GATEWAY WITH WEB ACCESS AND PROPERTY

MANAGEMENT INTERFACE IN ALL GUEST ROOMS.

SEE SCHEDULES FOR MORE INFORMATION.

TYPICAL ALL GUEST ROOMS. COORDINATE FINAL

THERMOSTAT LOCATION WITH ROOM LAYOUTS.

ALL DISTRIBUTION VENTILATION AIR DUCTING BOTH

SUPPLY AND EXHAUST OUTSIDE OF GUEST ROOMS

SHALL BE CONTINUOUS RIGID SHEET METAL DUCT

(MINIMUM 26 GAUGE) FROM ROOF MOUNTED

EQUIPMENT TO GUEST ROOM AND SHALL BE FIRE

STOPPED AT ALL 1 HR RATED WALLS. TYPICAL ALL

DUCTING.

DUCTING FROM SHAFT. PROVIDE FIRE AND SMOKE

DAMPER AT SHAFT PENETRATIONS WITH ACCESS

DOORS AS REQUIRED FOR INSPECTION PER OMC.

INSTALL VENTILATION AIR REGISTER WITH

INTEGRAL DAMPER CENTERED HORIZONTALLY

OVER OPENING AND VERTICALLY IN DRYWALL BULK

HEAD. TYPICAL ALL ROOMS.

2

3

4

1. REFERENCE SHEET M-001 FOR LEGENDS,

ABBREVIATIONS, SPECIFICATIONS AND NOTES.

2. REFERENCE SHEETS M-002 AND M-003 FOR

DETAILS.

3. REFERENCE SHEET M-004 FOR SCHEDULES.

4. REFERENCE ARCHITECTURAL RCP, SPRINKLER

SHOP DRAWINGS AND FINAL LIGHTING

LAYOUTS AND COORDINATE FINAL LOCATIONS

OF ALL CEILING DIFFUSERS AND REGISTERS.

5. REFERENCE ARCHITECTURAL ENLARGED

GUEST UNIT PLANS FOR EXACT LOCATIONS OF

THERMOSTATS AND EXHAUST GRILLES.

1

1

22

3

4

4

DN

DN

KING SOFA

300

KING SOFA

302

DOUBLE

QUEEN

304

DOUBLE

QUEEN

306

DOUBLE

QUEEN

308

DOUBLE

QUEEN

310

DOUBLE

QUEEN

312

DOUBLE

QUEEN

314

DOUBLE

QUEEN

320

DOUBLE

QUEEN

322

DOUBLE

QUEEN

324

KING

301

KING

303

DOUBLE

QUEEN

305

DOUBLE

QUEEN

307

DOUBLE

QUEEN

309

DOUBLE

QUEEN

311

DOUBLE

QUEEN

313

DOUBLE

QUEEN

315

DOUBLE

QUEEN

319

DOUBLE

QUEEN

321

DOUBLE

QUEEN

323

DOUBLE

QUEEN

325

KING

331

KING

329

KING

330

KING

328

ACCESSIBLE

KING

SOFA

316

ACCESSIBLE

KING

327

STORAGE

394

ELEV.

1

LC

8"

ELEV.

2

ELECTRICAL/

HOUSE

KEEPING

395

G

J

H

E

F

K

L

M

2 18 19

3 45

6 7 8

9 10 11 12

13 14 15 16 17

3.9

9.9 11.1

16.11

C

D

G

J

H

E

F

K

L

M

C

D

G.2 G.2

STORAGE

392

DOUBLE

QUEEN

318

ACCESSIBLE

KING

326

VENDING

393

ELEVATOR

LOBBY

397

CORRIDOR

391

CORRIDOR

390

STAIR 2

381

STAIR 1

380

PTAC-A PTAC-A PTAC-A PTAC-A PTAC-A PTAC-A PTAC-A PTAC-A PTAC-A

PTAC-A

PTAC-A

PTAC-A PTAC-A

PTAC-A PTAC-A

PTAC-A PTAC-A

PTAC-A PTAC-A PTAC-A PTAC-A

PTAC-A

PTAC-A

PTAC-A PTAC-A PTAC-A PTAC-A PTAC-A

PTAC-A PTAC-A

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

S-1

75

S-1

75

S-1

75

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

E-A

30

E-A

30

E-A

30

E-A

30

14/10 12/10

6"Ø

10/10

6"Ø

14/10

6"Ø

12/1010/10 6"Ø

6"Ø

36/12

8/8

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

T

T T T T T T T T T T

T

T

TT

T

TT

TT

T

T

T

TT

T

TT

E-A

30

E-A

30

PTAC-A

EF-2

50

4" W.C.

E-A

50

4"Ø

EF-2

50

4" W.C.

E-A

50

S-1

75

S-1

75

6"Ø 6"Ø

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

S-1

35

E-A

30

E-A

30

E-A

30

E-A

30

E-A

30

T

T

T

S-1

75

DIM

EN

SIO

NS

ARCH

ITEC

TURE

I

NTER

IORS

C

ONST

RUCT

ION

SER

VICE

S

WEB

SITE

: http

://ww

w.dim

ensio

ns-a

rchit

ects.

com

E-M

AIL:

info

@dim

ensio

ns-a

rchit

ects.

com

INC.

project title sheet

proj

ect n

o.

AS

SHO

WN

scal

e

revi

sion

s

date

chec

ked

bydr

awn

by

ME

P E

ng

in

ee

r

87

4 C

he

lte

nh

am

W

ay

Avo

n, IN

4

61

23

31

7.5

06

.8

15

1

31

7.7

45

.5

76

1

gn

ae

ng

in

ee

rin

g@

ao

l.co

m

GO

OD

ER

UM

&

A

SS

OC

IA

TE

S E

NG

IN

EE

RIN

G

P:

F:

E:

O

I

H

O

F

E

T

A

T

S

PR

O

F

E

S

S

I

O

NA

L

E

N

G

I

N

E

E

R

TS

G

I

R

E

E

GOODERUM

O

DAVID R.

74178

R

E

D

HAMP

TON

INN

CINC

INNA

TI, O

HIO

H-16

-384

08/1

0/20

17

- - - - -

1

SCALE: 1/8" = 1'-0"

HVAC PLAN - 3RD FLOOR

H.V.

A.C

. PLA

N -

3RD

FLO

OR

M300

GN

A

GENERAL NOTES:KEY NOTES:

1 PROVIDE WIRED ROOM THERMOSTAT, WIRED

MOTION SENSOR, PTAC ANTENNA AND WIRELESS

GATEWAY WITH WEB ACCESS AND PROPERTY

MANAGEMENT INTERFACE IN ALL GUEST ROOMS.

SEE SCHEDULES FOR MORE INFORMATION.

TYPICAL ALL GUEST ROOMS. COORDINATE FINAL

THERMOSTAT LOCATION WITH ROOM LAYOUTS.

ALL DISTRIBUTION VENTILATION AIR DUCTING BOTH

SUPPLY AND EXHAUST OUTSIDE OF GUEST ROOMS

SHALL BE CONTINUOUS RIGID SHEET METAL DUCT

(MINIMUM 26 GAUGE) FROM ROOF MOUNTED

EQUIPMENT TO GUEST ROOM AND SHALL BE FIRE

STOPPED AT ALL 1 HR RATED WALLS. TYPICAL ALL

DUCTING.

DUCTING FROM SHAFT. PROVIDE FIRE AND SMOKE

DAMPER AT SHAFT PENETRATIONS WITH ACCESS

DOORS AS REQUIRED FOR INSPECTION PER OMC.

INSTALL VENTILATION AIR REGISTER WITH

INTEGRAL DAMPER CENTERED HORIZONTALLY

OVER OPENING AND VERTICALLY IN DRYWALL BULK

HEAD. TYPICAL ALL ROOMS.

INSTALL SHEET METAL COLLECTOR BOX FROM

EXHAUST FAN CURB AND INDIVIDUALLY CONNECT

EACH EXHAUST DUCT. TYPICAL EACH FAN. FIRE

STOP ALL WALL AND FLOOR PENETRATIONS.

2

3

4

3

4

4

2

2

2

5

5

5

1. REFERENCE SHEET M-001 FOR LEGENDS,

ABBREVIATIONS, SPECIFICATIONS AND NOTES.

2. REFERENCE SHEETS M-002 AND M-003 FOR

DETAILS.

3. REFERENCE SHEET M-004 FOR SCHEDULES.

4. REFERENCE ARCHITECTURAL RCP, SPRINKLER

SHOP DRAWINGS AND FINAL LIGHTING

LAYOUTS AND COORDINATE FINAL LOCATIONS

OF ALL CEILING DIFFUSERS AND REGISTERS.

5. REFERENCE ARCHITECTURAL ENLARGED

GUEST UNIT PLANS FOR EXACT LOCATIONS OF

THERMOSTATS AND EXHAUST GRILLES.

RS

RS RS

RS

RS RS

RS

RS

RSRSRS

RS

REF-2

420

REF-3

270

REF-4

240

REF-6

240

REF-7

270

REF-8

270

REF-9

330

REF-5

180

REF-1

250

MAU-1

4050

RH-1

3 FT2

RH-1

3 FT2

DIM

EN

SIO

NS

ARCH

ITEC

TURE

I

NTER

IORS

C

ONST

RUCT

ION

SER

VICE

S

WEB

SITE

: http

://ww

w.dim

ensio

ns-a

rchit

ects.

com

E-M

AIL:

info

@dim

ensio

ns-a

rchit

ects.

com

INC.

project title sheet

proj

ect n

o.

AS

SHO

WN

scal

e

revi

sion

s

date

chec

ked

bydr

awn

by

ME

P E

ng

in

ee

r

87

4 C

he

lte

nh

am

W

ay

Avo

n, IN

4

61

23

31

7.5

06

.8

15

1

31

7.7

45

.5

76

1

gn

ae

ng

in

ee

rin

g@

ao

l.co

m

GO

OD

ER

UM

&

A

SS

OC

IA

TE

S E

NG

IN

EE

RIN

G

P:

F:

E:

O

I

H

O

F

E

T

A

T

S

PR

O

F

E

S

S

I

O

NA

L

E

N

G

I

N

E

E

R

TS

G

I

R

E

E

GOODERUM

O

DAVID R.

74178

R

E

D

HAMP

TON

INN

CINC

INNA

TI, O

HIO

H-16

-384

08/1

0/20

17

- - - - -

ELEVATOR SHAFT VENTING. INSTALL ONE VENT

PER SHAFT WITH 120V FIRE AND SMOKE DAMPER.

SEE DETAIL THIS SHEET.

ECM EXHAUST FAN. SET CFMS AS SHOWN FOR

EACH STACK AND BALANCE EACH GRILLE PER

PLANS. COORDINATE OPENING AND FLASHING

WITH ROOFING CONTRACTOR. TYPICAL OF (9)

LOCATIONS.

KEY NOTES:

GENERAL NOTES:

1

1

SCALE: 1/8" = 1'-0"

ROOF HVAC PLAN

ROO

F HV

AC

PLA

N

M400

GN

A

1. Single-sided or conventional retaining angle.

2. Actuator

3. Sleeve or duct connection

4. Electrical flex conduit

5. HS-10 one temperature manually re-settable link

6. FSD-151 combination fire smoke damper

7. Damper sleeve

8. UL555 & UL555S listing #: R11767

CSFM listing #'s: 3225-0368:115 & 3230-0368:116

MEA listing #: 295-98E

SCALE : NONE

ELEVATOR FIRE/SMOKE DAMPER DETAIL

2

1

2

3

4

5

6

6

Normal

Closed

Motor / Actuator

Fused Circuit

Addressable

Relay Module

M1

by others

Fire Alarm Riser wiring is by others.

Coordinate with Fire alarm

contractor.

14" HIGH MINIMUM

PRE-FABRICATED ROOF

CURB ATTACHED TO

ROOF STRUCTURE

WITH ANCHORS.

SECURE VENT TO

ROOF CURB AS

REQUIRED WITH

SHEET METAL

SCREWS.

DAMPER OPENING

TO BE SAME SIZE

AS RELIEF VENT

FREE AREA.

ROOF CONSTRUCTION.

REFER TO ARCHITECTURAL

DRAWINGS FOR TYPE.

SEAL ALL JOINTS.

FIRE AND SMOKE DAMPER

RELIEF VENT LIKE

GREENHECK

FABRAHOOD WITH

MINIMUM FREE AREA

OF 3 FT2 PER SHAFT.

1

1. REFERENCE SHEET M-001 FOR LEGENDS,

ABBREVIATIONS, SPECIFICATIONS AND NOTES.

2. REFERENCE SHEETS M-002 AND M-003 FOR

DETAILS.

3. REFERENCE SHEET M-004 FOR SCHEDULES.

2

2