applications of automated protective relay...

34
Applications of Automated Protective Relay Testing Josh LaBlanc

Upload: others

Post on 14-Apr-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

ApplicationsofAutomatedProtectiveRelayTesting

JoshLaBlanc

Page 2: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

First,automatedprotectiverelaytesting….

2

Whatisit?

Page 3: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

Wherecanitbeapplied?

• PreventativeMaintenanceTesting– Theapplicationsareendlessanddependsonyourcompaniestestingprogram

• RelayCommissioning– End-to-EndTesting– TransformerTesting– BusDifferentialTesting

• NERCCIP– DataVerification

3

Page 4: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

Whatarethebenefits?

• Ifdesignedcorrectlycanreducehumanerror.• Cancompleterepetitive,boringtasksinaveryshortamountoftimeallowingtheendusertofocusmoreoftheirtimeintheareasthatneedattention.

• Canbeusedinmaintenancetestingtoprovideconsistencyintestingresultsformatting.

• Canuseautomationasapeercheckontheoverallprotectionsystem.

• Canperformrelaydataverification.(VeryusefulintheCIPrealm)

4

Page 5: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

HumanError

– Nobodymakesmistakes,right?

• CommonRelayMaintenanceTestingMistakes– Forgettingtoremoveofaprotectionsystemdevicefromserviceaspartoftestingisolation.

– Forgettingtotestanelementthatneedstesting.– Testingsomethingandforgettingtomarktheresults.– FlippedorbackwardswiringconnectionswhenperformingA/Dconvertertests.

5

Page 6: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

HumanError

• Examples– PMtestingLineCurrentDifferentialrelays….

6

Page 7: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

HumanError

• Examples– Commonelementsthatgetmissedduringtesting…

• RelayOutputs• RelayInputs• AuxiliaryRelays

– Howcantheseerrorsbeminimized?

7

Page 8: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

HumanError

8

• Outputs

Page 9: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

HumanError

9

• AuxiliaryDevices

Page 10: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

HumanError

• Examples–Whatifthetestingcircuitisincorrectlywired?

• Usingafewsimplecalculationsweknowwhattherelay’sresponse tocommoncircuiterrorsaregoingtobe.– ComparingPhaseRotation– ComparingSystemMagnitudes– Etc.

• Ifthesecalculationsindicateincorrectlywiredcircuits,theendusercanbeinformedbefore thetestingroutinearesenttoprintallowingthemtomakeadjustments towiringbeforeprinting.

10

Page 11: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

TimeisValuable• Howcantimebesaved?– GreenLight,RedLight….

• LoadChecks• InputTesting• OutputTesting• RelayStatusChecks• RelaySettingCompares• A/DConverter Testing

– Automatedtestingroutinescangrabinformationfromrelaysautomatically,thustheenduserdoesn’tneedtospendtimewritingitdown.• Automation isquicker, peoplearesmarter!

11

Page 12: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

TimeisValuable• GreenLight,RedLightPrinciple

Thishasafailureinit!

12

Page 13: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

TimeisValuable• GreenLight,RedLightPrinciple

Thisdoesnot!

13

Page 14: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

TimeisValuable• LoadChecks

– Whenverifyinglegitimacyofaloadcheck,theengineeringbrainismakingalotoflogicaldecisions.

– Whynotuselogicinautomationtofilteronlytheloadcheckresultsthatneeddetailedinvestigation.

– 90%ofloadcheckscanbeverifiedtobesatisfactorybysimpleautomationlogic.

– Theremaining10%areflaggedandverifiedbyanengineer• Automation isquicker, peoplearesmarter!

14

Page 15: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

TimeisValuable• LoadCheckFiltering,3-PhaseApplications

– Comparephaserotationonbothcurrentandvoltage.– Comparephaseangledisplacementiscloseto120°.– Comparemeteredvoltagemagnitudestothenominalvalue.

– Comparemeteredcurrentmagnitudestoverifytheyareroughlybalanced.

– Verifythecircuitpowerfactorisaboveanacceptablelevel.

15

Page 16: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

TimeisValuable• RelaySettingsCheckExample(3-PhaseRoutine)– Isthisafailure?

16

• Notnecessarily

Page 17: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

TimeisValuable

• LoadCheckFiltering,SinglePhase– Comparemeteredvoltagemagnitudestothenominalvalue.

– Comparemeteredneutralvoltagemagnitudestoverifytheyarenon-zerobutsubstantiallylarge.

– Comparemeteredneutralcurrentmagnitudestoverifytheyarenon-zerobutsubstantiallylarge.

17

Page 18: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

TimeisValuable• LoadCheckFiltering,DifferentialSchemes

– Whynotmeterthedifferentialelement?– Shouldseeminimaloperatecurrentandsubstantialrestraintcurrent!

18

Page 19: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

TimeisValuable

• LoadCheckFiltering,Sync– Comparemeteredvoltagemagnitudestothenominalvalue.

– Comparemeteredphaseangledisplacementtoverifyminimaldisplacementbetweenthetwosources.

19

Page 20: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

TimeisValuable• RelaySettingsCheckExample(SyncRoutine)– Cananyoneseetherelaysettingsproblem?

• RelayisaSEL-421• 115kVNominalSystem• PTRY=1000(Corresponds toVpmag)• PTRZ=600(Corresponds toNVS1mag)

20

Page 21: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

TimeisValuable• RelaySettingsCheckExample(SyncRoutine)– Cananyoneseetherelaysettingsproblem?

• TherelaysyncelementKS1Msettingwassentto1.• PerSEL-421logic,PTratiosshouldbeaccounted forinthesetting,therefore itshouldhavebeensetto1.66.

• Automatedchecksprevented abreaker reclosing failure.

21

Page 22: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

FormatConsistency

• Auditorsloveformattingconsistencies!– Automationguaranteesthetestingresultsforeachparticularelementareprintedthesameevery time.

– Testingresultsformatsarenotdependentoneachindividualsdocumentationmethods.

– Consistentformatsaremucheasiertoprovideanengineeringreviewascomparedresultswithformattinginconsistencies.

22

Page 23: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

CommissioningPeerCheck• Delta-WyeTransformerTesting

23

Page 24: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

CommissioningPeerCheck• ThingstoconsiderwhencommissioningaDelta-WyeTransformerRelay– Howarethedeltawindingsofthetransformerinternallyconnected?DABorDAC?

– Howarethetransformerdeltawindingsexternallyconnectedtothepowersystem?ABCorACB?

– HowaretheCTsconnected?Samepolarityoropposingpolarity?

– CTratios?– TransformerTurnsRatio?

• GatheringData– AlwaysformulatequestionssothatyouaretestingthesystemandNOTtherelay!

24

Page 25: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

CommissioningPeerCheck• TransformerExampleQuestions– Fromthetransformernameplate,howarethedeltawindingsinternallyconnectedtooneanother?

– Fromthesystemthreelinediagram,howarethetransformer’sdeltawindingsconnectedtothepowersystem?

– Fromthesystemthreelinediagram,arethedifferentialrelay’scurrenttransformersconnectedinopposingorthesamepolarity?

– Fromthesystemthreelinediagram,whataretheratiosoftheprimaryandsecondarycurrenttransformerratiosusedinthedifferentialscheme?

– Fromthetransformernameplate,whataretheoperatingprimaryandsecondaryvoltagesofthetransformer?

25

Page 26: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

CommissioningPeerCheck• Delta-WyeTransformerTesting– Themostimportanttestisathroughlinetogroundfaultofthetransformer.

– Withminimaloperateandsubstantialrestraintcurrentduringthistest,thecorrecttransformervoltageandcompensationangleisconfirmed.

– Notethatthewaythistestissetup,theprotectionsystemwastestedandnottheprotectiverelay!• Ifrelaysettingsareusedasinputsintothetestsetup,youareonlytestingthattherelaybehavesaccordingtohowyouhaveprogrammed it.Thisisn’tmuchdifferent thananA/Dconverter testduringapreventativemaintenance test.

26

Page 27: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

CommissioningPeerCheck

• TransmissionLineEnd-to-EndTesting– Again,teststheprotectionsystemandnottherelay!– FaultquantitiescanbeexportedoutofpowersystemmodelingsoftwaretobeusedasrealtimefaultsimulationwhenperformingEnd-to-Endtesting.

– ThetransmissionlinerelaycommunicationschemeisreallybeingtestedinatransmissionlineEnd-to-Endtest.• Careshouldbetakenwhendecidingwhere toplacefaultsforsimulationinthemodelingsoftware.

27

Page 28: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

CommissioningPeerCheck

• TransmissionLineEnd-to-EndTesting– AutomationcanbeusedonrelaystoautomaticallysavetherelaySER’storesultswhichinturnspeedsuptesting.

– Whenusingautomationduringtesting,theusershouldpayattentiontoeverydevicetoverifythecorrectoperationofeachdeviceduringthetests.

– TheusershouldthenreviewtheSERssavedwitheachtesttoverifythecorrectrelaylogicoperations.

28

Page 29: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

CIP• WhatbenefitcanautomationhaveinCIP?– CIPisextremelyinformation,comparison,andtrackingintensive.

– AutomationcanperformalargeamountofthemindnumbingtasksCIPrequires!• Automated routinescancompare relayinformationtoverifynodiscrepancies whereexpected.

• Automated routinescantelltheenduser thepasswordcomplexityallowedfromthedevicesimplybygatheringandanalyzingtherelayfirmwarestring.

• Automationcangatherandprintalltherelayportsettingsusingterminalprograms.

• Relayinformationcanbeautomaticallyupdated toarelaynameplateinthesystemdatabasebysimplyusingimportfunctions.

29

Page 30: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

CIP• DataVerificationExample

30

Page 31: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

CIP• CIPFlowDiagram

31

Page 32: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

LessonsLearnedandAdvise• LessonsLearned– Haveanoverallvisionandsticktothatvision.– Gatherallpossibilitiesofapplicationoftherelaybeforescriptingthetestingroutine.

– Whenfirstusingatestingroutine,printmoretoresultsthanneeded.Ithelpsfordebuggingifprogramerrorsoccur.

– Whencreatingroutines,therewillbebugsjustgetusedtoitandbeproactiveinfixingthem.

– Startwiththehardestroutine.Often,partsofthisroutinecanbecopiedtootherroutines.

– Automatedtestingroutinescanalwaysbemadebetter.Beacceptingofconstructivefeedback.

32

Page 33: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

LessonsLearnedandAdvise

• Advise– Theprogrammershouldhaveasolidfamiliarityofathreephasepowersystem.

– Askthetesterforfeedbackwhereverpossible,especiallyifprogrambugsarefound.Thetesterisyourbesthelp!

– Havefamiliarityoftheentireautomatedprocess.

33

Page 34: Applications of Automated Protective Relay Testingcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power... · 2016-11-11 · testing that the relay behaves according to how you have

Questions?

34