Application Package
Version 3.3.1
Release Notes Rev A June 2017
© Westell Technologies
Part # 030-300816 Rev A
WESTELL.COM
RELEASE N
OTES
Application Package Version 3.3.1 Release Notes
Copyright © 2017 by Westell Inc. All Rights Reserved. Westell, Kentrox® and Optima Management System® are registered trademarks of Westell. All other names are trademarks of their respective owners. Information is correct at time of publication and is subject to change without notice. Contact Westell in Aurora, Illinois to verify current product information. Westell, Inc. is an Equal Opportunity/Affirmative Action employer.
Westell, Inc.750 North Commons Drive
Aurora, IL 60504 USAToll Free: (800) 377-8766 | International: +1 (630) 375-4950 | Fax: +1 (630) 375-4931
TABLE OF CONTENTSAffected Types 2
New Supported Devices 3
APP-121 -- SYM ASPOI DAS Tray 3
APP-122 -- Advanced RF DAS Support 3
New Features 3
HVACMonitoring Application Updates 3-8
APP-24 -- Create Fix Actions for Westell Generated Alarms 8
APP-87 -- Phase 2 Integration of the Bard MC4001 8
APP-88 -- Phase 2 Integration of the Bard MV5000 8
APP-89 -- Phase 2 Integration of the QUEST RSC1000 HVAC Controller 8
APP-90 -- Support JMA Teko DAS v3.2.6 9
APP-91 -- Support an Avian designation for Tower Lights 9-10
APP-114 -- Prevent Polling of DAS Systems Older than the Minimum Version 11
APP-116 -- Support DeepSea 7320 Maintenance Alarms 11
APP-133 -- Support Ability to Read Serial Number from Forlong Power Meters 11
Enhancements 11
APP-119 -- Marvair Comstat4 Setting Mismatch Enhancement 11
APP-141 -- SPX 3630xx Type Tower Controller Photocell Alarm Severity Changes 12
APP-137 -- Device Agent Profile Versioning 12
APP-145 -- Device Agent Support for Sub-Component NEs 12
Fixes 12
APP-107 -- Backup Discrete Alarms from SPXVanguardSNMP Temporarily Disabled 12
APP-147 -- Non-Printable Characters Removed from Attributes 13
Device Compatibility Information 14-17
WESTELL.COM
Page 1
1-800-377-8766
Application Package Version 3.3.1 Release NotesAffected Types
Application PackageRelease Notes
Version 3.3.1June 2017
Affected Types
Vendor Models Configured Types Issue(s)
Advanced RF Technologies
ADX DAS ADRFADXH APP-122
BARD MC4001 BardMV4001HVACSystem APP-87
BARD MV5000 BardMV5000HVACSystem APP-88
DeepSea DeepSea 7320 DeepSeaSplitPhasePowerMeterDeepSeaThreePhasePowerMeter
APP-116
Forlong Power meters Forlong301C2SplitPhasePowerMeterForlong301C2ThreePhasePowerMeterForlong301CPowerMeter
APP-133
JMA Teko DAS v. 3.2.6 JMATekoDAS APP-90
Marvair Comstat4 MarvairCS4HVACSystem APP-119
Quest RSC1000 HVAC Controller QuestRSC1000HVACSystem APP-89, APP-109
SPX VanguardSNMP tower light
SPXVanguardSNMP APP-107
SPX 3630XX SPX3630XX APP-141
SYM ASPOI DAS Tray APP-122
WESTELL.COM
1-800-377-8766
Page 2
Application Package Version 3.3.1 Release NotesNew Supported Devices
New Supported Devices
APP-121 -- SYM ASPOI DAS Tray
Version 3.3.1 includes Device Agent basic monitoring support for the SYM Technologies Active SYM Point of Interface (ASPOI) DAS Tray.
APP-122 -- Advanced RF DAS Support
Version 3.3.1 includes support for the Advanced RF Technologies ADX DAS.
Here is a sample configuration:
config site module Tower
application DASMonitoring enable
config site network-element das
type ADRFADXH
param deviceIp 192.168.1.100
New Features
HVACMonitoring Application Updates
Version 3.3.1 includes several updates to the HVACMonitoring application. These updates, described in detail below, involve Application Configuration Changes, Alarm Reporting, Measurement Organization, and Controller Configuration Management.
Application Configuration Changes
In versions issued prior to Version 3.3.1, users would configure multiple network elements to monitor an HVAC system. Beginning with Version 3.3.1, the only network element to be configured is hvacSystem. Once the appropriate communication parameters are configured and the application is able to poll the HVAC controller, the application will automatically add appropriate components to represent the HVAC units and any temperature sensors provided by the HVAC controller.
WESTELL.COM
Page 3
1-800-377-8766
Application Package Version 3.3.1 Release NotesNew Features
Network elements that are no longer availableby default as of Version 3.3.1 are:
hvacUnit1
hvacUnit2
indoorHumidity
indoorTemperature
outdoorHumidity
outdoorTemperature
smokeDetector
hvac1IntakeTemperature
hvac1OutletTemperature
hvac2IntakeTemperature
hvac2OutletTemperature
These network elements will be added automatically as components when appropriate. Additionally, users can add temperature sensor elements with the TemperatureSensor network-element set.
Examples
Here is a configuration example to bring HVAC monitoring online for an IP-connected controller:
config site network-element hvacSystem
type BardMV5000HVACSystemparam deviceIP 192.168.1.100
The following configures online HVAC monitoring for a serial-connected controller:
config site network-element hvacSystem
type MarvairCS4HVACSystemparam controller ‘serial 7’
If users wish to add the same intake/outlet temperature sensors that were previously available by default, the following configuration can be used:
config site network-element-set TemperatureSystem
instance hvac1IntakeTemperaturedisplay-name HVAC 1 Intake Temperatureexit
instance hvac1OutletTemperaturedisplay-name HVAC 1 Outlet Temperatureexit
instance hvac2IntakeTemperature
display-name HVAC 2 Intake Temperature
WESTELL.COM
1-800-377-8766
Page 4
Application Package Version 3.3.1 Release NotesNew Features
exit
instance hvac2OutletTemperature
display-name HVAC 2 Outlet Temperature
exit
config sitebus hvac1IntakeTemperature
description TemperatureSensor
id 00000206094F28
type sbTemp
config site network-element hvac1OutletTemperature
type SiteBusTemperature
param id 0000020603B428
config site network-element hvac2IntakeTemperature
type SiteBusTemperature
param id 00000206140328
config site network-element hvac2OutletTemperature
type SiteBusTemperature
param id 00000206076F28
Alarm Reporting
Version 3.3.1 will employ device alarms to report device-specific alarms. Each HVAC network element type will provide three basic alarms:
1. Communication: This alarm is raised when the application cannot communicate with the controller.
2. Compatibility: This alarm is raised when the software/firmware on the controller is not compatible with the application.
3. Configuration: This alarm is raised when a configurable parameter on the controller is not set to the value configured in the application.
All other alarms are specific to each HVAC controller type.
Measurement Organization
Version 3.3.1 will track lead/lag runtimes via measurements on the HVAC unit components instead of the HVAC system network-element. A transition guide with more specific details will be available upon request.
WESTELL.COM
Page 5
1-800-377-8766
Application Package Version 3.3.1 Release NotesNew Features
Controller Configuration Management
Version 3.3.1 now has a unified approach to controller configuration management across all the HVAC types. Each type now provides a device-specific set of optional parameters in the application. If users opt to configure one or more of these parameters, then the application will read the value of the same parameter on the HVAC controller and raise an alarm if the value of the parameter in the controller does not match the value of the parameter in the application. Additionally, a user may issue a forceConfigSync control-action from the application to update the parameter values in the HVAC controller. This will cause the parameters in the controller to be brought in sync to the application-configured parameters.
Configurable Parameters for AirsysMODHVACSystem:
Configurable Parameters for BardMV5000HVACSystem:
Parameter Description Values
coolingSetpoint Cooling setpoint (See Note on page 8) integer (18-95)
leadSwapDelay Lead Swap Delay (Days) (See Note on page 8) integer (1-7)
coolingDifference Cooling Difference (degrees F) floating-point
damperClosedTolerance Tolerance for Damper Closed State Alarm (degrees F)
integer
damperOpenTolerance Tolerance for Damper Open State Alarm (degrees F) integer
heatingDifference Heating Difference (degrees F) floating-point
highTempAlarmTrigger High Temp Alarm Trigger (degrees F above Setpoint)
floating-point
humidityDeadband Humidity Turn Off Deadband (percent) floating-point
lowTempAlarmTrigger Low Temp Alarm Trigger (degrees F below Setpoint) floating-point
maximumFreecoolingHumidity
Maximum Indoor Humidity Allowed for Freecooling (percent)
floating-point
miminumFreecoolingTempDiff
Minimum Outdoor-Indoor Temperature Difference for Freecooling (degrees F)
floating-point
Parameter Description Values
coolingSetpoint Cooling Setpoint (degrees F) (See Note on page 8) integer (18-95)
heatingSetpoint Heating Setpoint (degrees F) integer (1-7)
WESTELL.COM
1-800-377-8766
Page 6
Application Package Version 3.3.1 Release NotesNew Features
Configurable Parameters for QuestRSC1000HVACSystem:
highTempAlarm1Setpoint High Temperature Alarm 1 Setpoint (degrees F) integer
highTempAlarm2Setpoint High Temperature Alarm 2 Setpoint (degrees F) integer
lowTempAlarmSetpoint Low Temperature Alarm 1 Setpoint (degrees F) integer
Parameter Description Values
coolingSetpoint Cooling Setpoint (See Note on page 8) integer (18-95)
leadSwapDelay Lead Swap Delay (days) (See Note on page 8) integer (1-7)
comfortCoolingSetpoint Stage 1 cooling setpoint in comfort mode (degrees F)
floating-point (50.0-80.0)
comfortHeatingSetpoint Stage 1 heating setpoint in comfort mode (degrees F)
floating-point (50.0-80.0)
comfortModeTime The amount of time comfort mode is active when enabled (seconds)
integer (0-14400)
comfortShelterSetpoint Shelter setpoint in comfort mode. Cooling turns off when below this setting (degrees F)
floating-point (50.0-80.0)
coolingStage2Delta Degrees above the cooling setpoint to enable stage 2 cooling mode (degrees F)
floating-point (0.5-5.0)
coolingStage3Delta Degrees above cooling stage 2 to enable stage 3 cooling mode (degrees F)
floating-point (0.5-5.0)
coolingStage4Delta Degrees above cooling stage 3 to enable stage 4 cooling mode (degrees F)
floating-point (0.5-5.0)
heatingStage2Delta Degrees below the heating setpoint to enable stage 2 heating mode (degrees F)
floating-point (0.5-5.0)
minOffCooling The minimum time cooling must be off before it can be turned on (seconds)
integer (0-600)
minOffHeating The minimum time heating must be off before it can be turned on (seconds)
integer (0-600)
minOnCooling The minimum time cooling must be on before turning off (seconds)
integer (0-600)
Parameter Description Values
WESTELL.COM
Page 7
1-800-377-8766
Application Package Version 3.3.1 Release NotesNew Features
Note: Most parameters are configured on the hvacSystem network element. However, the coolingSetpoint and leadSwapDelay parameters are configured on the hvacSystem control. For example:
config site control hvacSystem
param coolingSetpoint 77
param leadSwapDelay 7
APP-24 -- Create Fix Actions for Westell Generated Alarms
Fix actions are now in place for Westell alarms to import into Optima.
APP-87 -- Phase 2 Integration of the Bard MC4001
Version 3.3.1 includes the second phase of integration of the Bard MC4001 HVAC controller. The BardMC4000HVACSystem type now supports Controller Configuration Management.
APP-88 -- Phase 2 Integration of the Bard MV5000
Version 3.3.1 includes the second phase of integration of the Bard MV5000 HVAC controller. The BardMV5000HVACSystem type now supports Controller Configuration Management.
APP-89 -- Phase 2 Integration of the QUEST RSC1000 HVAC Controller
Version 3.3.1 includes the second phase of integration of the QUEST HVAC controller. The QuestRSC1000HVACSystem type now supports Controller Configuration Management.
minOnHeating The minimum time heating must be off before turning off (seconds)
integer (0-600)
normalHeatingSetpoint Stage 1 heating setpoint in normal mode (degrees F)
floating-point (50.0-80.0)
normalShelterSetpoint Shelter setpoing in normal mode. Cooling turns off when below this setting (degrees F)
floating-point (50.0-80.0)
Parameter Description Values
WESTELL.COM
1-800-377-8766
Page 8
Application Package Version 3.3.1 Release NotesNew Features
APP-90 -- Support JMA Teko DAS v3.2.6
Version 3.3.1 supports the JMA Teko DAS firmware version 3.2.6.
APP-91 -- Support an Avian designation for Tower Lights
Version 3.3.1 includes a new parameter called towerAvian for designating the tower as an Avian tower site. When this parameter is used to designate the tower as Avian, the Style status point will have the text "Avian" appended. This allows users to quickly identify the tower as Avian by observing the Style status point events on Optima's Event View page.
The tower style will also be available for viewing and reporting as an attribute on the towerLight network-element. This will allow users to easily identify the tower style when viewing events and will also allow users to easily create inventory reports for tower lights.
The Avian designation applies only to the following tower types:
SPX3630XX
SPXVanguard
DialightMediumIntensity
DialightA0_A1Style
DialightA1_A6StyleThe following is a sample configuration for designating a tower as Avian:
config site network-element towerLight
param towerAvian enable
Examples of Optima displays showing an Avian type tower appear in the following three figures.
Figure RN-331-1 Optima Event View showing a status point event involving an avian style tower
WESTELL.COM
Page 9
1-800-377-8766
Application Package Version 3.3.1 Release NotesNew Features
Figure RN-331-2 Event Information Window for status point event involving an avian style tower
Figure RN-331-3 Avian tower style displayed under Device Attributes tab
WESTELL.COM
1-800-377-8766
Page 10
Application Package Version 3.3.1 Release NotesEnhancements
APP-114 -- Prevent Polling of DAS Systems Older than the Minimum Version
Version 3.3.1 will check the version of a DAS controller. If that version is older than the minimum supported version, then the application software will not attempt to poll the DAS for inventory and alarm information.
APP-116 -- Support DeepSea 7320 Maintenance Alarms
Version 3.3.1 will monitor and report the three generic maintenance alarms provided by the DeepSea 7320 generator controller.
APP-133 -- Support Ability to Read Serial Number from Forlong Power Meters
In Version 3.3.1, the serial number of supported Forlong power meters will be read and displayed as a new read-only parameter.
Note: The meters may not come from the manufacturer with the serial number already programmed. In this situation, the application reports a serial number of “0.” If the serial number has not peen programmed in the meter, it is the user’s responsibility to configure the serial number in the Modbus register for the application software to read and display it.
Enhancements
APP-119 -- Marvair Comstat4 Setting Mismatch Enhancement
In Version 3.3.1, settings mismatches will be reported as a “Configuration” alarm. The MarvairCS4HVACSystem type will now handle configuration management in the same manner as the other HVAC controller types (see “Controller Configuration Management” on page 6).
WESTELL.COM
Page 11
1-800-377-8766
Application Package Version 3.3.1 Release NotesDevice Agent Enhancements
APP-141 -- SPX 3630xx Type Tower Controller Photocell Alarm Severity Changes
Effective with Version 3.3.1, photocell alarm (PEC ERR) severities on SPX Tower Controllers of 3630xx type red, white, and dual now report photocell alarms as “TowerCritical” with a severity of “Critical.” The type white previously reported photocell alarms as “Major” severity.
Device Agent Enhancements
APP-137 -- Device Agent Profile Versioning
Device Agent profiles now support versioning to provide backward compatibility with previous versions of the Application Package software.
APP-145 -- Device Agent Support for Sub-Component NEs
Device Agent profiles now support the ability to create a variable number of sub-component NEs under the top-level NE or a component NE. This allows a hierarchical element tree to be created similar to the NE trees created by the more advanced device integration provided by the Application Package software.
Fixes
APP-107 -- Backup Discrete Alarms from SPXVanguardSNMP Temporarily Disabled
Backup discrete alarms from the Intelligent SPXVanguardSNMP tower light controllers are not always reported correctly. Because of this, Westell has temporarily disabled the ability to configure backup discrete alarming on the SPXVanguardSNMP tower light controller. This function will be restored once a logic issue is solved. The issue affects reporting of the backup discrete alarm state when communication to the controller is lost.
WESTELL.COM
1-800-377-8766
Page 12
Application Package Version 3.3.1 Release NotesFixes
APP-147 -- Non-Printable Characters Removed from Attributes
The Application Package software now removes non-printable characters that are read from third-party vendor device SNMP interfaces.
WESTELL.COM
Page 13
1-800-377-8766
Application Package Version 3.3.1 Release NotesApplication Package Version 3.3.1 Device Compatibility Information
Application Package Version 3.3.1 Device Compatibility InformationWestell has pre-configured application support to monitor and manage the following network elements.
Vendor Model/Variant Version(s)
In-B
uild
ing
Ant
enna
Sys
tem
s an
d D
AS
Advanced RF Technologies
ADX DAS 13000F0200401045
Corning SC-450 7.0, 7.2
Commscope
ION/MMC Plus ION-M Linux 6.50.0, 7.20.0
ION/MMC Plus ION-M Windows 5.30.0
ION/RMC1600 ION-M Linux 6.50.0, 7.0.1, 7.10.0, 7.20.0
ION/RMC1600 ION-M Windows 6.50.0, 7.20.0
ION/RMC1600 ION-U Linux 1.64.1, 1.70.0, 1.75.0, 1.80.0
ION/TSUN1/2 ION-B 5.1.1, 5.1.2
ION/TSUN4 ION-M Linux 6.50.0, 7.20.0
ION/TSUN4 ION-M Windows 5.30.0
JMA Wireless Teko 3.2.0, 3.2.6
Microwave Photonics OFW3478
SOLiD DMS-1200 4.2.0, 6.1.0, 6.1.1
SYM Technologies ASPOI DAS Tray 1.9.1
TE Connectivity FlexWave Prism 8.1.0, 8.1.7
Westell UDIT 1.03.00, 1.03.01, 1.04.02, 2.00.01A, 2.00.02
Zinwave 3000 4.5, 4.6
WESTELL.COM
1-800-377-8766
Page 14
Application Package Version 3.3.1 Release NotesApplication Package Version 3.3.1 Device Compatibility Information
Tow
er L
ight
s
Dialight
A0-A1 Style A.1, A.2
High Intensity A.31, A.40, A.41, A.42
Medium Intensity B.6, B,8, B.10, B.61, B.63
Medium Intensity Red A.6, A.7
Medium Intensity Small Red A.1, A.2
Red Only A1-A6 Style A.6, A.7
SPX Flash Technology
Eagle 4747/9038
Eagle Ethernet 4747/9038
LED Jun 26 2012 10:47:38
3630XX Jun 26 2012 10:47:38
9038XX 4747/9038
Vanguard 2.7, 2.8, 2.9, 3.0, 3.1, 3.2
Vanguard Ethernet 2.7, 2.8, 2.9, 3.0, 3.1, 3.2
Vanguard SNMP 3.3
Rect
ifier
s an
d U
PS
APC Galaxy 5000 GDENA95300IC303
Delta Orion 6.50B17
Eaton 9130 4.30, 4.32, 4.34, 4.36, 4,38
EltekSmartPack 4.6, 4.7, 4.8, 4.9, 4.10
SmartPack2 4.6, 4.7, 4.8, 4.9, 4.10
Emerson NetSure Rectifier 4.00, 4.02, 4.04, 4.10, 4.21
GE Infinity M/S with NE843A Slot Controller
3.3.24 (pending validation)
Huawei SMU v500R001C20SPC901T
ZTE
ZXDU
ZXDU68 W301 V.5.0 1.0G
ZXDU68 W301 V.5.0R06M04 1.12.01.01
Vendor Model/Variant Version(s)
WESTELL.COM
Page 15
1-800-377-8766
Application Package Version 3.3.1 Release NotesApplication Package Version 3.3.1 Device Compatibility Information
HVA
C Co
ntro
llers Airsys ASLLC.2 13B64
BardMC4001 2.7
MV5000 2.7
Marvair CommStat4 v62
Quest Controls RSC 1000 0.6.4.4 (pending validation)
Gen
erat
ors
and
Gen
erat
or C
ontr
olle
rs
Basler DGC-2020 3.17.02
Deep Sea Electronics 521052205220/73207320
6.2a6.2a
9.x.x
Generac
EPanel
EPanel with Annunciator
H100 3.4-4.0
HTS 4.0
HTS Ethernet 4.0
Intellilite AMF25 1.4
Kohler DEC3000 4.04
LovatoEXM10
RGK60 42
Polar Power Supra Digital Control System 2.0.0.15
Vendor Model/Variant Version(s)
WESTELL.COM
1-800-377-8766
Page 16
Application Package Version 3.3.1 Release NotesApplication Package Version 3.3.1 Device Compatibility Information
Pow
er E
quip
men
t and
Sen
sors
Acrel PZ Series
Alpha TechnologiesAMPS24 3.13
FXM 2.00.01
BatteryDAQ 2402W2/M6
CCS WattNode
Elkor
WattsOn Split Phase
WattsOn Three Phase
WattsOn Mark II Split-Phase
WattsOn Mark II Three-Phase
FenceHawk RG-7781
ForlongDRT-301C
DRT-301C2
GreystoneRH310A02C2E6
RH310A03C2A6
iSnail
VC
VC10
VC25
Measurlogic DTS DC
Novus RHT-WM
Standardel DPS520