apm2000- power supply systm

Upload: anuradha-thilakarathna

Post on 03-Apr-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 APM2000- Power Supply Systm

    1/67

    APM200 Outdoor Power Supply System

    User Manual

    Version: V1.0

    Revision date: December 12, 2005

    BOM: 31011189

    Emerson Network Power provides customers with technical

    support. Users may contact the nearest Emerson local sales

    office or service center.

    Copyright 2005 by Emerson Network Power Co., Ltd.

    All rights reserved. The contents in this document are subject to

    change without notice.

    Emerson Network Power Co., Ltd.

    Address: No.1 Kefa Rd., Science & Industry Park, Nanshan

    District 518057, Shenzhen China

    Homepage: www.emersonnetworkpower.com.cn

    E-mail: [email protected]

  • 7/28/2019 APM2000- Power Supply Systm

    2/67

    Safety Precautions

    To reduce the chance of accidents, please read the safety precautions

    carefully before operation. The Caution, Notice, Warning and Danger

    in this manual do not represent all the safety points to be observed, and

    are only used as supplement to various operation safety points.

    Therefore, the installation and operation personnel must be strictly

    trained and master the correct operations and all the safety points

    before actual operation.

    When operating Emerson products, the safety rules in the industry, the

    general safety points and special safety instructions specified in this

    manual must be strictly observed.

    Electrical Safety

    I. ESD

    Notice

    The static electricity generated by the human body will

    damage the static sensitive elements on PCBs, such as

    large-scale ICs, etc. Before touching any plug-in board, PCB

    or IC chip, ESD wrist strap must be worn to prevent body

    static from damaging the sensitive elements. The other end of

    the ESD wrist strap must be well earthed.

    II. Shortcircuit

    Danger

    During operation, never short the positive and negative poles

    of the DC busbar or the non-earthing pole and the earth. The

    power system is a constant voltage DC power equipment,

    short circuit will result in equipment burning and endangerhuman safety.

    Check carefully the polarity of the cable and connection terminal when

    performing DC live operations.

    As the operation space in the DC distribution unit is very tight, please

    carefully select the operation space.

    Never wear a watch, bracelet, bangle, ring, or other conductive objects

    during operation.

    Insulated tools must be used.

  • 7/28/2019 APM2000- Power Supply Systm

    3/67

    In live operation, keep the arm muscle tense, so that when tool

    connection is loosened, the free movement of the human body and tool

    is reduced to the minimum.

    Others

    I. Safety requirement

    Notice Please use the same model MCB to replace the MCB.

    II. Sharp object

    WaringWhen moving equipment by hand, protective gloves should be

    worn to avoid injury by sharp object.

    III. Cable connection

    NoticePlease verify the compliance of the cable and cable label with

    the actual installation prior to cable connection.

    IV. Binding the signal lines

    NoticeThe signal lines should be bound separately from heavy

    current and high voltage lines, with minimum 150mm binding

    interval.

  • 7/28/2019 APM2000- Power Supply Systm

    4/67

    Contents

    Chapter 1 Overview ................................................................................................1

    1.1 Theory .......................................................................................................1

    1.2 System Features........................................................................................2

    1.3 System Function ........................................................................................2

    1.3.1 Protective Function..........................................................................2

    1.3.2 Alarm Function ................................................................................3

    1.3.3 Communication Function .................................................................7

    1.4 System Composition..................................................................................7

    1.4.1 Embedded Power Supply ................................................................8

    1.4.2 Heat Exchanging Equipment And External Fan...............................8

    1.4.3 Heaters ............................................................................................9

    Chapter 2 Installation............................................................................................10

    2.1 Precautions..............................................................................................10

    2.2 Preparations ............................................................................................10

    2.2.1 Inspecting Location........................................................................10

    2.2.2 Distributing Goods .........................................................................10

    2.2.3 Unpacking......................................................................................11

    2.2.4 Preparing Tools .............................................................................11

    2.2.5 Preparing Cables...........................................................................12

    2.2.6 Opening The Cabinet Door............................................................13

    2.3 Installing Cabinet .....................................................................................15

    2.3.1 Installing Cabinet On A Concrete Stand ........................................15

    2.3.2 Installing Cabinet On A Floorstand ................................................17

    2.4 Installing Battery ......................................................................................19

    2.5 Installing Rectifiers...................................................................................20

    2.6 Connecting Cables ..................................................................................21

    2.6.1 Precautions....................................................................................21

    2.6.2 Cable Tube ....................................................................................22

    2.6.3 Connecting Power Cables .............................................................22

    2.6.4 Connecting Battery Cables ............................................................26

  • 7/28/2019 APM2000- Power Supply Systm

    5/67

    Chapter 3 Testing .................................................................................................28

    3.1 Introduction..............................................................................................28

    3.2 Testing AC Distribution ............................................................................28

    3.3 Testing Rectifier.......................................................................................29

    3.4 Testing Monitoring Module ......................................................................29

    3.4.1 Setting System Parameters ...........................................................30

    3.4.2 System Function Test ....................................................................33

    Chapter 4 Maintenance.........................................................................................36

    4.1 Embedded Power Supply System Maintenance ......................................36

    4.1.1 System Operation..........................................................................36

    4.1.2 Indicator description ......................................................................37

    4.1.3 Routine Maintenance.....................................................................38

    4.1.4 Handling Of Common Faults .........................................................40

    4.2 Battery Maintenance................................................................................414.3 Heat Exchanging Equipment ...................................................................41

    4.4 External Fan Maintenance.......................................................................43

    4.5 Replace Heaters And Relays...................................................................44

    4.5.1 Replace The Heater In Equipment Compartment ..........................44

    4.5.2 Replace The Heater In Battery Compartment................................47

    4.5.3 Replace Heater Relays..................................................................48

    4.6 Replace Door Status Sensors..................................................................49

    4.7 SPD Maintenance....................................................................................50

    Appendix 1 Technical Data...................................................................................53

    Appendix 2 Definitions Of The Monitoring Expansion Board Interface .................55

    Appendix 3 System Schematic Diagram...............................................................60

    Appendix 4 System Wiring Diagram .....................................................................61

  • 7/28/2019 APM2000- Power Supply Systm

    6/67

  • 7/28/2019 APM2000- Power Supply Systm

    7/67

    Chapter 1 Overview 1

    APM200 Outdoor Power Supply System User Manual

    Chapter 1 Overview

    APM200 outdoor power supply system can be used directly outdoors. It can

    supply as much as 60A electric current. There are two models of this

    system: North model and South model. North model has an extra heating

    unit compared with the South model.

    1.1 Theory

    The simplified theoretical block diagram is shown in Figure 1-1. The

    detailed theoretical diagram is shown in Appendix 3 and 4.

    Embedded powersupply

    220

    -48Vdc

    Load 1

    Vac

    48Vdc220Vac

    Distribution unitLoad 1

    Load 11

    220Vac

    Figure 1-1 Simplified theoretical block diagram

    The embedded power system rectifies the 220V AC power into -48V DC

    power and exports the DC power to the distribution unit. It has functions of

    battery management, LLVD (load low voltage disconnection), BLVD

    (battery low voltage disconnection), data acquisition, alarm, and

    communication with the host.

    The distribution unit connects to AC mains and feeds the AC power to the

    embedded power supply. In addition, it has routes of -48V DC output for the

    loads.

  • 7/28/2019 APM2000- Power Supply Systm

    8/67

    2 Chapter 1 Overview

    APM200 Outdoor Power Supply System User Manual

    1.2 System Features

    Power factor of the rectifier can reach 0.99. The efficiency is higher

    than 90%.

    Wide AC input voltage range from 90V to 290V. When the input voltageis between 90~175Vac, the rectifier exports power- limited output.

    When the input voltage is 90Vac, the minimum output power of the

    rectifier is 37.5% of the rated power.

    Perfect battery management. The system has BLVD function, and can

    perform functions such as temperature compensation, auto voltage

    regulation, stepless current limiting, battery capacity calculation, and

    online battery test etc.

    Rectifiers are hot pluggable. It takes less than 1min to replace a

    rectifier.

    Network design: Providing multiple communication ports, which

    enables flexible networking and remote monitoring.

    Perfect lightning protection at both AC side and DC side.

    Complete fault protection and fault alarm functions.

    All system components are accessible from the front.

    The safety guideline satisfies IP55, and satisfies GR487 waterproof

    requirement.

    1.3 System Function

    1.3.1 Protective Function

    LLVD and BLVD

    When mains failure occurs, the battery will supply power. When the battery

    voltage drops to 47.5V (by default, adjustable), the monitoring module will

    cut off the non- priority loads. When the battery voltage drops to the BLVD

    voltage (default: 46.5V), the monitoring module will cut off all the loads to

    avoid battery over- discharge. When the mains resumes, the power system

    will go back to normal state.

  • 7/28/2019 APM2000- Power Supply Systm

    9/67

    Chapter 1 Overview 3

    APM200 Outdoor Power Supply System User Manual

    Over- temperature protection

    If the temperature of the equipment compartment remains over the

    protection point (55C by default) for 30 seconds constantly, the monitoring

    module will cut off the non- priority loads until the ambient temperature

    drops below 45C. If AC side failure occurs, all the loads will be cut off.

    This function is inhibitive by default, though the user can activate or prohibit

    it through the host command.

    Input under-voltage protections

    When the AC input voltage is over 290Vac or below 90Vac, the rectifier will

    perform self- protection. It can recover automatically, and the return

    difference is more than 5Vac.

    Output over-voltage protections

    When the DC output voltage is over 60V, the rectifier will stop exporting

    voltage or current. This protection cannot recover automatically.

    Output current- limit protection

    The APM200 system can perform current- limited protection.

    Output short- circuit protection

    The APM200 system can perform short- circuit protection. It can short

    circuit for a long while and recover automatically.

    1.3.2 Alarm Function

    The system provides alarm functions. It annunciates alarm in the event of

    mains failure, mains over/ under- voltage, DC output over/ under- voltage,

    charging over- current, load over- temperature protection, ambient over-

    temperature, module failure, module protection, as shown in table 1-1.

  • 7/28/2019 APM2000- Power Supply Systm

    10/67

    4 Chapter 1 Overview

    APM200 Outdoor Power Supply System User Manual

    Table 1-1 Alarm functions

    Remote-

    communication

    values

    Description

    Mains shortage Alarm is raised when mains is below 50V, and resumes when mains is above 60V.

    Mains over-

    voltage

    1. Setting range: between the under- voltage alarm point and 300V. The mains over-voltage alarm point must be set above the AC over- voltage alarm point, and the

    mains over- voltage alarm point is 280V by default.

    2. Alarm recovery conditions:

    When the mains is below the alarm point minus 3V for 10 minutes constantly, the

    alarm recovers.

    3. The mains over- voltage alarm point can be set through the host. AC over/ under-

    voltage alarm and module alarm are shielded when mains shortage.

    Mains under-

    voltage

    1. Setting range: between 60V and the over- voltage alarm point. The mains under-

    voltage alarm occurs when mains is below the under- voltage alarm point, and the

    default mains under- voltage alarm point is 180V.

    2. Alarm recovery conditions:

    When the mains is above the alarm point plus 3V for 10 minutes constantly.

    , the alarm recovers.

    3. The mains over- voltage alarm point can be set through the host. Mains under-

    voltage alarm is shielded when mains shortage.

    DC over- voltage

    1. The alarm point is settable. The setting range is 58V~60V, and the alarm point

    must be above the boost charging voltage plus 1V. The alarm return difference is

    0.5V.

    2.Default: 58V. DC over- voltage alarm occurs when the busbar voltage is over 58V,

    and vanishes when the busbar voltage is below 57.5V.

    DC under-

    voltage

    1. The alarm point is settable. The setting range isbetween the low- voltage

    disconnection point and float charging voltage minus 2V. The alarm return

    difference is 0.5V.

    2.Default: 48.5V. DC under- voltage alarm occurs when the busbar voltage is below

    48.5V, and vanishes when the busbar voltage is over or equal to 49V.

    3. The lower limit voltage is LLVD voltage when load low- voltage disconnection is

    permitted.

    4. The lower limit voltage is BLVD voltage when load low- voltage disconnection is

    prohibited and BLVD is permitted.

    5. The lower limit voltage is 35V when both load low- voltage disconnection and

    BLVD are prohibited.

  • 7/28/2019 APM2000- Power Supply Systm

    11/67

    Chapter 1 Overview 5

    APM200 Outdoor Power Supply System User Manual

    Remote-

    communication

    values

    Description

    Charging over-

    current

    1. The charging over- current alarm will plus 5A when charging current is over the

    current- limit point for 5 minutes constantly..

    2. Alarm recovers when charging current is below the current- limit point for 5

    minutes constantly.

    Load over-

    temperature

    protection

    1.The non- priority load over- temperature protection can be set activated or not

    through the host settings. It is prohibited by default.

    2. If the function is activated and the circumambient temperature is over the over-

    temperature protection point for 30s constantly, the monitoring module will cut off

    the non- priority loads automatically. And the power will resume on automatically

    when the circumambient temperature is lower by 10C than the protection point.

    3. Setting range: 50C ~70C. The protection point is 65C by default.

    4. The temperature sampling point is the external temperature sensor.

    5. The non- priority load over- temperature protection can be set controllable by the

    host. If controllable, the load over- temperature protection can be activated through

    the host command.

    Battery over-

    temperature

    protection

    1.The battery over- temperature protection can be set activated or not through the

    host settings. It is prohibited by default.

    2. If the function is activated and the circumambient temperature is over the over-

    temperature protection point for 30s constantly, the monitoring module will perform

    battery disconnection automatically. And the battery will resume power- on

    automatically when the circumambient temperature is lower by 10C than the

    protection point.

    3. Setting range: 40C ~70C. The protection point is 53C by default.

    4. The temperature sampling point can be set to be battery temperature 1, and is

    subject to the temperature compensation value.

    Circumambience

    over-

    temperature

    The available setting range is -50~100C. When over the over- temperature alarm

    point, the alarm return difference is 3C. The alarm point can be set respectively,

    and is 50C by default.

    Circumambience

    under-

    temperature

    The available setting range is -50~0C. When under the over- temperature alarm

    point, the alarm return difference is 3C. The alarm point can be set respectively,

    and is 0C by default.

    n# module failure Stand for n# module failure (output over- voltage, output shortage, fan failure)

    n# module

    protection

    Stand for n# module protection (over- temperature, intput over/ under-

    voltageprotection).

  • 7/28/2019 APM2000- Power Supply Systm

    12/67

    6 Chapter 1 Overview

    APM200 Outdoor Power Supply System User Manual

    Remote-

    communication

    values

    Description

    Battery loop

    disconnection

    1. One battery- string loop alarms.

    2. Battery loop disconnection (MCB/ fuse, contactor or internal wiring disconnection)

    brings alarm.

    3. The battery loop is the path between the battery string MCB and the battery string

    contactor.

    BLVD

    LLVD

    1. Low- voltage disconnection (LVD) activation and LVD voltage can be set through

    the host. LLVD is inhibited by default, and BLVD is activated by default.

    2. The available setting range of BLVD voltage is between 35V and LLVD voltage,

    and BLVD voltage is 46.5V by default.

    3. The available setting range of LLVD voltage is between BLVD voltage and DC

    under- voltage alarm point, and BLVD voltage is 47.5V by default.

    4. LVD criterion

    1) The system has either following setting cannot perform LVD control: the number

    of system and power module is set zero or battery string capability is set zero.

    2) LVD is activated in accordance with LVD conditions and the host command.Door status

    sensorThe dry contact is disconnected when alarm.

    SPD failure

    alarmCheck the two- route SPDs. The dry contact disconnects when SPD exports alarms.

    Fan failure alarm

    If the fan rev. is measurable and the fan rev. is set to be maximum, the virtual fan

    rev. is less than 80% of the normal rev., fan failure alarm should be raised.

    If the fan rev. is un measurable, fan failure alarm performs in accordance with failure

    description by fan manufacturer.

    Heater failure

    alarm of the

    storage batterycompartment

    When the mains is in normal state and the storage battery temperature is below 5C

    for an hour constantly, heater failure alarm of the storage battery compartment is

    raised.

    Test on backup

    digital data

    1. 3 routes altogether. The monitoring module supplies 24Vdc or 12Vdc operation

    power for the switchable signal examination, disconnect the correlative low power

    level (0V~1V) and connect the correlative high power level (9~24V).

    2. 8/20s impulse current can endure 300A, without damage (bio- transient

    suppressor with model of1.5SMC39CA is commeded).

    3. Alarm power level is adjustable.

  • 7/28/2019 APM2000- Power Supply Systm

    13/67

    Chapter 1 Overview 7

    APM200 Outdoor Power Supply System User Manual

    Note:

    Alarm levels can be set through the host. The alarm levels are divided as

    critical alarm, observation alarm, and inhibit alarm. Alarms that may cause

    load power interruption are defined as critical alarm by default, and the

    rests are observation alarms. Door status sensor alarms, humidity alarms

    and backup equipment alarms can be set as non- alarm and be shielded,

    while the other alarms cannot. Except exposited ones, the alarm affirmance

    time is 10 seconds.

    1.3.3 Communication Function

    The system can communicate with the user host through communication

    port RS232 or RS485, and report sampling data and alarm data to the host.

    The AMP200 system can report some alarms information to the host

    through the 4 couples of dry contacts.

    1.4 System Composition

    The APM200 outdoor power supply is constructed by an equipment

    compartment and a battery compartment. The equipment compartment

    consists of embedded power supply, heat exchanging equipment, external

    fan and distribution unit etc. The battery compartment has two layers, and a

    set of batteries that supplies backup power can be placed in each layer.

    Each heater is placed in the equipment compartment and in the battery

    compartment in the North model system. See Figure 1-2.

  • 7/28/2019 APM2000- Power Supply Systm

    14/67

    8 Chapter 1 Overview

    APM200 Outdoor Power Supply System User Manual

    Rings(4 pieces)Heat exchanging equipment

    External fan

    Monitoring expansion board

    Reserved

    Embedded power supply

    Distribution unit

    Heater in equipment

    compartment (behind

    distribution unit)

    Battery string I

    Heater in battery

    compartment (underthe plate)

    Floorstand

    Batterycompartment

    door

    Battery string II

    Equipment

    compartment

    door

    Figure 1-2 Structure of APM200 outdoor power supply system

    1.4.1 Embedded Power Supply

    The embedded power supply consists of 3 rectifiers, one monitoringmodule, one distribution subrack and one monitoring expansion board. It

    switches the 220V AC voltage to -48V DC voltage, and delivers the -48V

    DC voltage to the distribution units of the system and then to the loads

    through its distribution subrack.

    1.4.2 Heat Exchanging Equipment And External Fan

    The heat exchanging equipment dissipates the heat inside the cabinet with

    the external fan. It consists of an internal fan and a heat exchanger. The

    external fan aspirates the cold air outside and feeds it to the heat

  • 7/28/2019 APM2000- Power Supply Systm

    15/67

    Chapter 1 Overview 9

    APM200 Outdoor Power Supply System User Manual

    exchanger, while the internal fan expels the heat air inside the cabinet to

    the heat exchanger. The heat exchanger exchanges the heat between cold

    air and hot air in it to dissipate the heat.

    1.4.3 Heaters

    The two heaters will start to work when the environment temperature is

    below 5C5C to ensure the normal operation of the North model system

    segments in low temperature environment.

  • 7/28/2019 APM2000- Power Supply Systm

    16/67

    10 Chapter 2 Installation

    APM200 Outdoor Power Supply System User Manual

    Chapter 2 Installation

    2.1 Precautions1. Only qualified technical person can do the system installation and

    maintenance.

    2. Avoid fire or body injuries.

    3. Provide suitable AC mains supply to the system.

    4. Earth the system according to the requirement.

    5. Keep the environment of the system clean and dry.

    6. Avoid touching the bare part of a circuit.

    7. Switch off the circuit breakers in case of system failure.

    2.2 Preparations

    2.2.1 Inspecting Location

    Before installation, please inspect:

    1. the cable routing such as cable tunnel and so on.

    2. the conditions required for the normal operation of the system, such as

    AC mains supply, earth cable and so on.

    2.2.2 Distributing Goods

    The user needs to distribute the goods if several systems with same model

    are purchased at the same time. Every system has been tested and gone

    through the burn-in test strictly before delivery. In order to ensure the

    optimized operation and track the product quality conveniently, the

    components should be installed in their corresponding cabinet, even

    though these components can be installed in other systems.

    Ensure that all components in the same system have the same No. that is

    marked on the packing case.

  • 7/28/2019 APM2000- Power Supply Systm

    17/67

    Chapter 2 Installation 11

    APM200 Outdoor Power Supply System User Manual

    2.2.3 Unpacking

    Inspect the equipment strictly after unpacking to ensure successful

    installation.

    Unpack and inspect the equipment only after it arrives at the installation site.

    The user representative and the representative from Emerson NetworkPower Co., Ltd. shall inspect the equipment together.

    Open the packing case with a packing list in it first, take out the packing list,

    and inspect according to the packing list, including customer name,

    customer address, machine No., quantity, case No., contract No., and

    others.

    Check the goods one by one according to the packing list after unpacking.

    The procedures are as follows.

    Step 1: Check the quantity and serial number marked on the packing cases

    according to the actual quantity of the packing cases.

    Step 2: Check the correctness of the equipment packing according to the

    packing list.

    Step 3: Check the quantity and model of the accessories according to the

    packing list.

    Step 4: Check the correctness of equipment configuration according to the

    system configuration.

    Step 5: Check the goods visually. For example, check if the cabinet or

    enclosure is distorted or affected with damp; shake gently the rectifier and

    the monitoring module to see if there is any loose component or connection

    caused by shipment.

    Step 6: The user representative signs the packing list.

    Do not unpack the components before installing them to avoid accessory

    loss.

    2.2.4 Preparing Tools

    The installation tools include electric drill, wire cutters, crimping tools,

    wrench set, screwdriver, and electric knife. The tools must be insulation and

    ESD-proof processed before they are used.

  • 7/28/2019 APM2000- Power Supply Systm

    18/67

    12 Chapter 2 Installation

    APM200 Outdoor Power Supply System User Manual

    2.2.5 Preparing Cables

    The cables to be installed include AC power cables, DC power cable and

    grounding cable.

    RVVZ cables such as flame retardant PVC insulation or jacket soft cable

    with copper conductors are recommended.The cables should be able to withstand at least +70C temperature. The

    colors of AC phase cable, neutral cable and grounding cable shall be red,

    Cambridge blue and green and yellow respectively. If the cables have the

    same color, they should be identified with IDs or color labels.

    The sectional area of the AC power cable depends on the current,

    temperature rise, voltage drop and mechanical strength of the cable. The

    2.5A/mm2 current density is recommended to estimate the sectional area of

    the AC power cables and the cable with less than 10mm2sectional area is

    not recommended.

    The sectional area of the DC power cable is shown in Table 2-1.

    Table 2-1 Sectional area of the DC power cable

    Rated current Max. output current Min. sect. area

    Max. cable l. with 0.5V

    voltage drop and Min.

    sect. area

    32 A 16 A 16 mm2

    14 m

    20 A 10 A 10 mm2

    14 m

    16 A 8 A 6 mm2

    11 m

    10 A 5 A 4 mm2

    11 m

    If the rated capacity of a MCB is much bigger than the actual output current,the MCB will not trip when overload happens. So the recommended MCB

    capacity is 1.5 to 2 times of the maximum load current (it is two times in the

    table above).

    Note

    The maximum output current that flows in the DC power cable is calculated

    according to the full load of the system.

    If the acceptable voltage drop is not 0.5V, determine the sectional area of

    the DC power cable according to the following expression.

  • 7/28/2019 APM2000- Power Supply Systm

    19/67

    Chapter 2 Installation 13

    APM200 Outdoor Power Supply System User Manual

    A=I%L/(KU)

    Where:

    Asectional area of a cable (m2)

    Itotal current that flows in the cable (A)

    Lcable length (m)U acceptable voltage drop in the cable (V)

    Kelectric conduction coefficient, here K Copper=57

    Recommended color labels for the positive and negative DC power cables:

    Positive cable black

    Negative cable blue

    The sectional area of the grounding cable should be at least 16mm2. A

    green and yellow cable should be used as the grounding cable.

    Prepare the cables according to the cabling specification and quantity. Do

    not join two separate cables together to form one cable. The blue and blackcables should be used as DC power cables. If the cables are routed outside,

    they should be inserted into a corrugation sleeve.

    2.2.6 Opening The Cabinet Door

    The equipment or battery compartment door needs to be opened during

    system installation or maintenance. The two doors can be opened with

    same method, and the procedures are follows:

    Step 1: Undo the hexagon socket head cap screw in the keyhole sheet with

    the hexagon key widdershins. Remove the keyhole sheet. Insert another

    key into the keyhole and turn the key clockwise until it cannot be turned any

    more, as shown in Figure 2-1.

  • 7/28/2019 APM2000- Power Supply Systm

    20/67

    14 Chapter 2 Installation

    APM200 Outdoor Power Supply System User Manual

    Keyholesheet

    Handle

    Figure 2-1 Unlock sequence

    Step 2: Turn the handle about 120 counter clockwise, and then pull the

    door, as shown in Figure 2-2.

    Handle

    Figure 2-2 Handle position

    Step 3: Use the position pole to fix the position of the door to prevent the

    door from being closed automatically, as shown in Figure 2-3.

    Position pole

    Figure 2-3 Position Pole

    Step 4: Place the pole to its original position before closing the door.

  • 7/28/2019 APM2000- Power Supply Systm

    21/67

    Chapter 2 Installation 15

    APM200 Outdoor Power Supply System User Manual

    Note

    Different cabinets have the same key. If different key is needed, notify Emerson in

    advance.

    2.3 Installing CabinetThe APM200 outdoor power supply system uses bottom cabling mode.

    Make a concrete stand or a floorstand first, and then place the cabinet on

    the concrete stand or the floorstand. The detailed installation procedures

    are follows.

    2.3.1 Installing Cabinet On A Concrete Stand

    Step 1: Make a concrete stand

    The dimensions of the stand are shown in Figure 2-4.

    Cable tunnel

    Cabinet door

    300~500

    800

    250

    100

    800

    Figure 2-4 Dimensions of concrete stand (Unit: mm)

    Step 2: Mark the cabinet installation position

    Determine the center point positions of every installation hole on the stand

    according to the installation dimensions of the cabinet shown in Figure 2-5,

    and mark them with a pencil or an oil pen.

  • 7/28/2019 APM2000- Power Supply Systm

    22/67

    16 Chapter 2 Installation

    APM200 Outdoor Power Supply System User Manual

    Cabinet door

    800

    480

    800

    530

    Figure 2-5 Installation dimensions of cabinet base

    Step 3: Drill holes

    The size of the expansion bolt delivered with the accessories is M1055mm.

    Drill a 70mm-depth hole at each marked point by using a 14 drill bit. Be

    careful not to make the drill be off-center when drilling and keep the drilling

    vertical. Clean the dust from the hole. Insert an expansion pipe into it, and

    knock the pipe gently until its head is in the same level with the floor, as

    shown in Figure 2-6.

    Drillvertically

    Clean thedust

    Knock itinto place

    Tightenthe bolt

    Expansionpipe

    Powercabinet

    70~75mm 14

    Figure 2-6 Drilling holes and Installing expansion pipe and bolt

    Step 4: Place cabinet in position

    Move the cabinet to the installation position, and align the installation holes

    of the cabinet to those on the ground.

  • 7/28/2019 APM2000- Power Supply Systm

    23/67

    Chapter 2 Installation 17

    APM200 Outdoor Power Supply System User Manual

    Step 5: Open the battery compartment door

    Take the key from the ring on the cabinet top, and open the battery

    compartment door according to the method introduced in section 2.2.6.

    Step 6: Fix the cabinet

    Adjust the cabinet horizontally and vertically. Insert an iron flake underneaththe lower edge or the corner that is closer to the ground to adjust the

    vertical tilt to be within 5 degrees. Screw the expansion bolt with plain and

    spring washers into the expansion pipe with a wrench, as shown in Figure

    2-7.

    Battery compartment

    Expansion bolt

    Expansion pipe

    Concrete stand

    Expansion bolt

    Spring washer

    Cabinet base

    Expansion pipeConcrete stand

    Spring washer

    Figure 2-7 Screwing an expansion bolt

    Shake the cabinet in different directions after the installation to check for

    any loose component and loose installation of the cabinet.

    2.3.2 Installing Cabinet On A Floorstand

    Step 1: Mark the floorstand installation position

    Determine the center point positions of the floorstand on the ground and

    mark them with a pencil or an oil pen, as shown in Figure 2-8.

  • 7/28/2019 APM2000- Power Supply Systm

    24/67

    18 Chapter 2 Installation

    APM200 Outdoor Power Supply System User Manual

    Cabinet door14

    4

    50

    400

    Figure 2-8 Installation dimensions of floorstand

    Step 2: Drill holes

    The size of the expansion bolt delivered with the accessories is M1055mm.

    Drill a 70mm-depth hole at each marked point by using a 14 drill bit. Be

    careful not to make the drill be off-center when drilling and keep the drilling

    vertical. Clean the dust from the hole. Insert an expansion pipe into it, and

    knock the pipe gently until its head is in the same level with the floor, as

    shown in Figure 2-4.

    Step 3: Fix the floors tand

    Align the installation holes of the floorstand to those on the ground. Screw

    the expansion bolt with plain and spring washers into the expansion pipe

    with a wrench, as shown in Figure 2-9.

    and floorstand

    Floorstand

    Expansion bolt

    Ground

    Batterycompartment

    Screw for fixing cabinet

    Figure 2-9 Installing the cabinet and floorstand

  • 7/28/2019 APM2000- Power Supply Systm

    25/67

    Chapter 2 Installation 19

    APM200 Outdoor Power Supply System User Manual

    Step 4: Place cabinet in position

    Place the cabinet on the floorstand. Align the installation holes of the

    cabinet to those of the floorstand.

    Step 5: Open battery compartment door

    Take the key from the ring on the top of the cabinet, and open the batterycompartment door according to the method described in section 2.2.6.

    Step 6: Fix cabinet

    Adjust the cabinet horizontally and vertically. Insert an iron flake underneath

    the lower edge or the corner of the cabinet that is closer to the ground to

    adjust the vertical tilt to be within 5 degrees. Screw the screws supplied

    with the accessories to fix the cabinet on the floorstand with a wrench, as

    shown in Figure 2-7.

    Shake the cabinet in different directions after the installationto check for any

    loose component and loose installation of the cabinet.

    2.4 Installing Battery

    Open the battery compartment door according to the method introduced in

    Section 2.2.6.

    The battery compartment has two floors. Each floor can be placed with one

    battery string that has four cells. Install the battery cells according to the

    battery user manual delivered with the battery.

    The battery cells should be installed as close to the right side and rear side

    of the cabinet as possible. Attach the acid and alkali integration box on theside panel of the cabinet.

    Loosen the two baffles in the front of the battery compartment after

    installing the battery cells, and then move the baffles vertically about 10mm

    and screw the screws solidly to block the battery cells, as shown in Figure

    2-8.

    The installation tools must be insulation processed. Do not damage the

    plastic cover of the battery cells and their output terminals during the

    installation.

  • 7/28/2019 APM2000- Power Supply Systm

    26/67

    20 Chapter 2 Installation

    APM200 Outdoor Power Supply System User Manual

    Batterycompartment

    Battery string IBaffle

    Battery string II

    Baffle

    Figure 2-10 Installing battery strings

    2.5 Installing Rectifiers

    The subrack of the embedded power supply has been installed in the

    cabinet of the outdoor power supply system. While the rectifiers of the

    embedded power supply are packed and delivered separately and need to

    be installed on spot.

    Rectifiers should be installed in the three left slots of the subrack. Install the

    rectifiers from left to right when there are less than three rectifiers to be

    installed and mount dummy plate at the remaining position. The installation

    procedures are as follows.

    Step 1: Place the rectifier to the position shown in Figure 2-11.

    Handle

    Rectifier

    Figure2-11 Positions of the rectifier and the handle

  • 7/28/2019 APM2000- Power Supply Systm

    27/67

    Chapter 2 Installation 21

    APM200 Outdoor Power Supply System User Manual

    Step 2: Push the handle into the panel.

    Step 3: Push the rectifier inward until it stops going forward. The rectifier is

    fixed in the subrack.

    Step 4: The procedures to unplug the rectifier-move the latch to Unlock

    position first, and pull out the rectifier then.

    2.6 Connecting Cables

    2.6.1 Precautions

    1. When doing engineering design, AC cables and DC cables should be

    installed separately to avoid interfering with DC output caused by AC

    power.

    Note

    At the point where the DC output cable is led out of the cabinet, drill the cablethrough a steel tube longer than one meter and then connect it to the load to

    prevent radiant disturbance.

    2. AC cables and DC cables should be identified with cable labels and

    polarity markings. The markings should be attached on the cables at a fixed

    distance.

    3. The cables should be identified with different colors, as shown below:

    Positive DC cable black

    Negative DC cable blue

    Grounding cable green and yellow

    AC phase line red

    Neutral line Cambridge blue or black

    If the cables have the same color, black cable is preferred and they should

    be identified with IDs.

    4. The cables to be connected are AC power cables, DC power cables and

    battery cables.

    5. Safety and reliability are most significant factors in electrical connection.

  • 7/28/2019 APM2000- Power Supply Systm

    28/67

    22 Chapter 2 Installation

    APM200 Outdoor Power Supply System User Manual

    6. The AC and DC power cables and grounding cable should be routed

    through the cable tunnel, the battery compartment and the cable tubes

    between the two compartments, and should finally be connected to the

    distribution unit.

    7. The cables shall not have joint, damage or scratch.

    2.6.2 Cable Tube

    This system is configured of 15 cable tubes with different sizes. The

    appearance of the tube is shown in Figure 2-10. The cable tubes are

    located on the separating plate between the equipment compartment and

    the battery compartment, as shown in Figure 2-11. User can select the

    suitable tube to route the cable according to the cable size. Unscrew the

    tube cap, then lead the cable through the tube, and finally screw the cap.

    Cable tube

    Distribution unit

    Figure 2-12 Position of cable tube

    2.6.3 Connecting Power Cables

    Step 1: Remove the panel of the distr ibut ion unit

    The panel is shown in Figure 2-13.

  • 7/28/2019 APM2000- Power Supply Systm

    29/67

    Chapter 2 Installation 23

    APM200 Outdoor Power Supply System User Manual

    The panel of the distribution unit

    Figure 2-13 Panel of the distribution unit

    Step 2: Load Distribution

    The system can supply 11 routes of loads, as shown in Figure 2-16. The

    MCBs (LOAD1~LOAD6) of the distribution unit in the embedded power

    supply controls the 11 loads. The positions of the MCBs in the subrack are

    shown in Figure 2-14, and the relationship between these two levels of

    MCBs is shown in Figure 2-15. The specifications of the MCBs are shown

    in Table 2-2.

    Table 2-2 MCB Specifications

    MCB in

    subrack

    MCB in

    distr. unit

    MCB cap. in

    distr. unit

    Cable size

    in distr. unitRemark

    LOAD 1 1, 2 16A 25mm2

    Total output of two MCBs

    should be less than 15A

    LOAD 2 3, 4 16A 25mm2

    Total output of two MCBs

    should be less than 15A

    LOAD 3 5, 6 16A 25mm2

    Total output of two MCBs

    should be less than 15A

    LOAD 4 7, 8, 9 16A 25mm2

    Total output of three MCBs

    should be less than 15A

    LOAD 5 10 32A 25mm2

    Total output of the MCB

    should be less than 30A

    LOAD 6 11 32A 25mm2

    Total output of the MCB

    should be less than 30A

  • 7/28/2019 APM2000- Power Supply Systm

    30/67

    24 Chapter 2 Installation

    APM200 Outdoor Power Supply System User Manual

    Load MCB Battery force- on buttonBattery MCB

    Figure 2-14 MCBs in subrack of embedded power supply system

    Route Route Route Route Route Route Route Route Route Route

    LOAD2

    Route1 2 4 5 6 7 8 9 10 11

    LOAD4 LOAD5 LOAD6LOAD1 LOAD3

    3

    Figure 2-15 Relationship between two levels of MCBs

    The embedded power supply system has LLVD and BLVD functions. When

    the battery voltage is less than 47.5V (default), the embedded power supply

    system will disconnect the load connected to the MCBs of LOAD5 and

    LOAD6 automatically without interrupting the power to the load connected

    to the MCB of LOAD1~LOAD4. LOAD1~LOAD4 will be disconnected

    automatically when the battery voltage is less than 46.5V (default) to avoid

    battery overdischarge. At this time, all loads are disconnected.

    So the priority loads should be connected to the MCB of LOAD1~LOAD4,

    that is the Route1 to Route 9 in Figure 2-16. The normal loads should be

    connected to the Route 10 to Route 11 in Figure 2-16.

  • 7/28/2019 APM2000- Power Supply Systm

    31/67

    Chapter 2 Installation 25

    APM200 Outdoor Power Supply System User Manual

    Step 3: Connect loads

    As shown in Figure 2-15, connect the negative polarity of every load to the

    lower terminal of the MCB with a negative cable, and connect the positive

    polarity of the load to the bolt on the positive busbar that has one M6 bolt

    and seven M4 bolts.

    Note

    The tools and body shall be insulated strictly before applying a load when the

    system is powered on to avoid shortcircuit.

    Terminal for

    connecting loadPositive busbar Grounding bar AC phase line (L) Neutral line (N)

    Figure 2-16 Terminals for connecting load and AC power

    Note:

    The L & N terminals above are divisional interface of AC SPD and power

    subracks instead of AC input terminals.

    Step 4: Connect AC power cables

    Connect the AC input grounding cable to the grounding bar shown in Figure

    2-16 or the grounding bar outside the battery compartment of the cabinet.

    Connect the AC input neutral line to the wiring point below the MCB N

    shown in Figure 2-16.

    Connect the AC input phase line to the wiring point below the MCB L shown

    in Figure 2-16.

    Note

    1. The grounding cable shall be connected first, then the neutral line and finally

    the phase lines.

  • 7/28/2019 APM2000- Power Supply Systm

    32/67

    26 Chapter 2 Installation

    APM200 Outdoor Power Supply System User Manual

    2. The AC cables should be routed from the MCB in the external distributionequipment prepared by user. They should be connected to the MCB just before thesystem is powered on. The external distribution equipment should have some

    protection devices to fulfill the overcurrent, shortcircuit and lightning protection

    functions.

    3. The AC cables should be identified with color labels to identify the phase line,

    neutral line and grounding cable.

    4. The AC cables should be routed away from the DC cables.

    Step 5: Re-install the cover

    Re-install the cover to the distribution unit after completing the connection.

    2.6.4 Connecting Battery Cables

    Step 1: Switch on the AC input MCB and battery MCB

    The positions of the AC input MCB and the battery MCB are shown in

    Figure 2-17.

    Battery MCB

    AC input MCB

    Figure 2-17 Position of AC input MCB and battery MCB

    Step 2: Check if the polarities of the battery cables are correct

    Check the polarities of the battery cables in the battery compartment with a

    multimeter. The black cable should be negative pole and the red cable

  • 7/28/2019 APM2000- Power Supply Systm

    33/67

    Chapter 2 Installation 27

    APM200 Outdoor Power Supply System User Manual

    should be positive pole. The cable in the middle is middle voltage sampling

    cable of the battery, as shown in Figure 2-18. If the polarity is incorrect,

    please contact Emerson.

    Middle voltage sampling cable of the battery

    Positive battery cable

    Negative battery cable

    Negative battery cable Middle voltage sampling cable of the battery

    Figure 2-18 Battery cables

    Step 3: Connect battery cells

    Switch off the battery MCB and AC input MCB. Connect the battery cells

    with the cables delivered with the battery according to the battery user

    manual.

    Step 4: Connect the battery string to the cabinet

    Connect the blue and black cables in the battery compartment respectively

    to the negative and positive terminals of the battery string. Connect the

    voltage sampling cable to the middle voltage terminal of the battery.

    Step 5: Recheck if the polarities of the battery cables are correct

    Check the polarities of the battery cables again after completing the

    connection. Make sure that the blue cable in the battery compartment is

    negative and the black cable is positive. If the cable polarity is incorrect,

    repeat Step 4.

  • 7/28/2019 APM2000- Power Supply Systm

    34/67

    28 Chapter 3 Testing

    APM200 Outdoor Power Supply System User Manual

    Chapter 3 Testing

    3.1 IntroductionThe cabinet, rectifiers and monitoring module are subject to vibrations

    during shipment. More over, mistakes might be made during system

    installation. If the system is powered on in haste, a fatal accident may occur

    and the whole power supply system may be damaged. Therefore, the

    system must be tested strictly after it is installed.

    Conduct the test procedures carefully and observe the system in the mean

    time. Shut down the system in case of any abnormal phenomenon and

    continue the test after the fault is eliminated.

    3.2 Testing AC Distribution

    Step 1: Check if the PE cables are reliably connected and the AC cables

    are correctly connected to the system according to the system schematic

    diagram (refer to Appendix 3), and if the screws are loose before powering

    on the system.

    Step 2: Switch on the residual current operated circuit breaker (RCCB).

    Switch off all MCBs (put the handles down) in the subrack and the

    distribution unit. Switch on the SPD MCBs, as shown in Figure 3-1.

    RCCB

    Figure 3-1 MCB positions

  • 7/28/2019 APM2000- Power Supply Systm

    35/67

    Chapter 3 Testing 29

    APM200 Outdoor Power Supply System User Manual

    Step 3: Make sure that there is no short circuit in the input and output

    terminals of the AC

    Step 4: Switch on the MCB in the external distribution equipment to power

    the system. Measure the voltages of the input terminals of the AC MCBs.

    Check the external distribution equipment if the voltages are abnormal.

    Step 6: Switch on the battery MCB.

    Step 5: Switch on the AC MCBs and the operation indicators (green) on the

    rectifier panels should turn on. Otherwise, check the distribution unit

    carefully.

    3.3 Testing Rectifier

    Step 1: Make sure that there is no short circuit in the input and output

    terminals of the rectifier and there is no loose or damaged component

    inside the rectifier.

    Step 2: Switch on the AC MCBs. The green indicator on the rectifier panel

    turns on and the red indicator is on for several seconds. The rectifier starts

    after a start delay and then operates normally. At this time, only the green

    indicator is on and the fan will stop several minutes later if no load is

    applied to the system.

    Step 3: Measure the DC output voltage of the system with a multimeter. It

    should be 53.5V0.5V.

    Note

    Only the engineers from Emerson can adjust the output voltage of the rectifier.After the system test is completed, the output voltage needs not to be adjusted any

    more unless the rectifier is replaced with a new one.

    3.4 Testing Monitoring Module

    The monitoring module must be tested with a host.

  • 7/28/2019 APM2000- Power Supply Systm

    36/67

    30 Chapter 3 Testing

    APM200 Outdoor Power Supply System User Manual

    3.4.1 Setting System Parameters

    Upon delivery, the default parameters of the monitoring module may be

    inconsistent with the actual situation or your needs. In that case, you should

    configure the system parameters through the host before the system

    testing.According to the communication protocol, the parameters that you can

    query through the host are listed in the following table.

    Table 3-1 Parameters that can be queried

    RemotelyAcquiredAnalogSignal

    1) AC Input Voltage

    2) DC Busbar Voltage

    3) Rectifier Total Output Current

    4) Battery String Current

    5) AmbientTemperature/Humidity

    6) Battery Temperature

    RemotelyAcquiredAlarm/DigitalSignal

    1) AC Mains On/Off

    2) AC Mains Status

    3) DC Bus Voltage Status

    4) Load MCB Status

    5) System Current-Limiting Status

    6) Load Connection/Disconnection

    Status

    7) Battery Connection/Disconnection

    Status

    8) Battery MCB Status

    9) Ambient Temperature/Humidity

    Status

    10) Door Status Sensor

    11) Water Sensor Status

    12) Smoke Sensor Status

    13) Rectifiers Operation Status

    14) System Control Mode and Battery

    BC/FC Status

    15) 7 Standby Digital Signal Status16) 2 Digital Signal Output Status

    17) Battery Discharge Test Phase

    Status

    18) Battery Charge Over-Current

    Status

    Remote-ControlParameters

    1) Rectifier On/off Control

    2) BLVD & LLVD

    3) FC/BC Status Control

    4) Start/End Battery Capacity

    Test

    According to the communication protocol, the parameters that you can

    configure through the host are listed in the following table.

  • 7/28/2019 APM2000- Power Supply Systm

    37/67

    Chapter 3 Testing 31

    APM200 Outdoor Power Supply System User Manual

    Table 3-2 Configurable parameters

    Parameter Range Default value

    AC Input Under-Voltage

    Alarm Point

    > 60V and lower than AC Over-Voltage

    Alarm Point180V

    AC Input Over-Voltage

    Alarm Point

    Between AC Under-Voltage Alarm point

    and 300V

    280V

    DC Busbar Low Voltage

    Point

    1, When LLVD enabled: LLVD Voltage

    2, When LLVD disabled but BLVD

    enabled: BLVD voltage

    3, When both LLVD and BLVD disabled:

    35V

    46.5V/47.5V/35V

    (depending on

    the BLVD Status

    and LLVD

    Status)

    DC Busbar Under-Voltage

    Alarm Point

    Between DC Busbar Low Voltage Point

    and 2V below FC voltage48.5V

    DC Busbar Over-Voltage

    Alarm Point

    58V ~ 60V and 1V higher than BC

    voltage58V

    LLVD Status Disabled, Enabled Disabled

    LLVD Voltage

    Between BLVD voltage (when BLVD is

    disabled: >35V) and DC Busbar

    Under-Voltage Alarm Point

    47.5V

    BLVD Status Disabled, Enabled Enabled

    BLVD Voltage

    35V but lower than LLVD voltage

    (when LLVD is disabled, lower than DC

    Busbar Under-Voltage Alarm Point)

    46.5V

    Ambient Temp Alarm

    Lower Limit

    -50C ~ 100C and lower than upper

    limit0C

    Ambient Temp Alarm

    Upper Limit

    -50C ~ 100C and higher than lower

    limit50C

    Ambient Humidity Alarm

    Lower Limit

    0%RH ~ 100%RH and lower than upper

    limit10%RH

    Ambient Humidity Alarm

    Upper Limit

    0%RH ~ 100%RH and higher than

    lower limit80%RH

    Standby Digital Signal

    Alarm LevelHigh level alarm 1, low level alarm 0

    High level alarm

    1

    Number and Addresses of

    Rectifiers(1, 1), (2, 1, 2), (3, 1, 2, 3) (3, 1, 2, 3)

    System Control Mode Host Control, Auto Auto

    FC/BC Status BC, FC FC

  • 7/28/2019 APM2000- Power Supply Systm

    38/67

    32 Chapter 3 Testing

    APM200 Outdoor Power Supply System User Manual

    Parameter Range Default value

    BC voltage

    43.2V ~ 57.6V, between FC voltage and

    1V below DC Busbar Over-Voltage

    Alarm Point

    56.5V

    FC voltage

    43.2V ~ 57.6V, between BC voltage and

    2V below DC Busbar Under-Voltage

    Alarm Point

    53.5V

    Number of Battery Strings 0 ~ 1 1

    Capacity of Battery String 30Ah ~ 600Ah

    100Ah (when no

    specific

    requirement is

    made)

    Coefficient of Charge

    Current Limiting Point0.1 ~ 0.25 0.15

    Scheduled BC Interval 30 days ~ 240 days 60 days

    Temp Compensation

    Coef. of Battery String0mV/C ~ 500mV/C 80mV/C

    Temp Measurement

    Lower Limit-50C ~ 0C -50C

    Temp Measurement

    Upper Limit0 C ~ 100 C 50 C

    Humidity Measurement

    Lower Limit

    0%RH ~ 100%RH and lower than

    Upper Limit0%RH

    Humidity Measurement

    Upper Limit

    0%RH ~ 100%RH and higher than

    Lower Limit100%RH

    Power Distribution Analog

    Signal Calibration

    Coefficient

    Not configurable by the user

    Battery Over-TempProtection Point

    40C ~ 70C 53C

    When setting system parameters through the host, please note that:

    1. Make sure that the power system address set at the host is identical with

    the address set through the DIP switch, or the communication will fail.

    2. Make sure that the rectifier number is set consistent with the actual

    condition. After a rectifier is added to or removed from the power system,

    the rectifier number parameter must be accordingly modified, or a rectifier

    alarm will be raised.

  • 7/28/2019 APM2000- Power Supply Systm

    39/67

    Chapter 3 Testing 33

    APM200 Outdoor Power Supply System User Manual

    3. The battery string capacity is set to customer required specific capacity

    according to order requirement before delivery. If there is no specific

    capacity of the battery strings required in the order, the default battery string

    capacity is 100AH. If the actual battery capacity is different from that, reset

    the configuration through the host to make the configuration consistent with

    the actual situation and prevent improper battery management. (Note: the

    200Ah and 100Ah capacities are set through DIP switch. You can only set

    other capacities through the host.)

    4. The management over the battery strings is realized through a common

    BLVD and a shunt, and the battery current measured by the monitoring

    module is actually the total current of the two. Therefore, at the host, the

    battery string number should be set to 1, and the battery capacity be set to

    the sum of the two strings.

    5. The DIP switch is in the PCB board of the monitoring module. Pull out the

    monitoring module (hot pluggable) before changing the DIP switch settings.Then you can change the DIP switch settings

    Description of DIP switch settings:

    DIP switch 1~4: Address DIP switch. ON acts 1, OFF acts 0.

    DIP switch 7: ON denotes that the battery string capacity is 200Ah; OFF

    denotes that the battery string capacity is 100Ah. As shown in Figure 3-2.

    DIP switch7 ON

    DIP switch7 OFF

    Figure 3-2 DIP switches

    3.4.2 System Function Test

    After setting the system parameters, you can go on to carry out the system

    function test.

    For the requirements of the test on system AC over/under-voltage alarm

    and protection are rather strict, you do not need to do them. After all, the

    system has passed strict tests before delivery.

  • 7/28/2019 APM2000- Power Supply Systm

    40/67

    34 Chapter 3 Testing

    APM200 Outdoor Power Supply System User Manual

    Battery Auto-Management Test

    Cut off AC mains supply and power the load with the battery for above 15

    minutes (!1 minute), then recover the AC mains, all rectifiers will be in

    current-limiting BC status.

    During the current-limiting BC status, it is normal that the rectifier output

    voltage is sometimes below 53.5V.

    For the test of battery auto-management has strict requirements for the

    system, it is not necessary to carry out this test if your test conditions are

    limited.

    Rectifier On/Off Test

    Set the control mode to background control through the host software and

    try turning on/off each module. The corresponding module should act

    correctly.

    Note to change the control mode to automatic control after the test is

    finished.

    Under-voltage Alarm And LLVD/BLVD Test

    Cut off the AC power and power the load with batteries. Set the DC

    under-voltage alarm point, LLVD and BLVD voltage to higher values to

    shorten the test duration. Then observe the battery under-voltage alarm,

    LLVD and BLVD situation. The monitoring module should send out the

    corresponding alarms one by one. The red indicator on the front panel of

    monitoring module should be on, and the dry contact controlling the

    external audible/visual alarm equipment should output alarm signal.

    Recover the AC power, restore the settings of under voltage alarm point,

    LLVD and BLVD voltage, and the above alarms should disappear.

    Rectifier On Position Test

    Set the power system address and rectifier number correctly, insert and pull

    out the rectifiers one by one, and the host should display the

    communication state of corresponding rectifiers correctly.

  • 7/28/2019 APM2000- Power Supply Systm

    41/67

    Chapter 3 Testing 35

    APM200 Outdoor Power Supply System User Manual

    Battery MCB Off Alarm Test

    Connect the battery to the system, and switch off its MCB. There should be

    a corresponding battery MCB off alarm raised at the host. The alarm will

    disappear when the MCB is turned on.

    Load MCB Off Alarm TestConnect a load to the system and switch off its MCB. There should be a

    corresponding load MCB off alarm raised at the host. The alarm will

    disappear when the MCB is turned on.

    Note

    1. If the terminal of corresponding load and battery route is not connected with

    load or battery during the test, but is suspended, the MCB Off Alarm forcorresponding load or battery may not be reported accurately.

    2. Make sure that system configurations are restored to normal status after the test.

    Viewing Operation Information

    After the system power on, you can get simple operation information

    through the indicators on the monitoring module front panel. For detailed

    information, you must query through the host.

    Canceling Battery Protection

    If you think it more important powering the loads than protecting the battery,

    thus do not want the battery protection in the case of mains failure, you can

    set the LLVD and BLVD status to Disabled through the host.

    NoteWhen the battery is discharged to the BLVD voltage, the battery backup time isvery short. It is impossible to obtain long time operation of loads by sacrificing the

    battery.

  • 7/28/2019 APM2000- Power Supply Systm

    42/67

    36 Chapter 4 Maintenance

    APM200 Outdoor Power Supply System User Manual

    Chapter 4 Maintenance

    Inspect the outdoor power supply system periodically and shoot the trouble

    in time.

    4.1 Embedded Power Supply System Maintenance

    4.1.1 System Operation

    After installation and testing, the system is ready for use. When necessary,

    it can be put into normal operation just by switching on the corresponding

    MCB. During the operation, the following issues may call your attention:

    Fan speed control technologyThe fan may run for a second and stop when the rectifier is powered on for

    the first time. If load is connected to the system, the inner temperature of

    the rectifier will increase after operation for a period of time, and the fan will

    begin running and speed up with the increase of inner temperature. That

    phenomenon is due to the fan speed adjusting technology, and thus

    absolutely normal.

    Over temperature protection

    A rectifiers inner temperature may be high during operation. If you reset it

    by turning it off and on at that time, you may observe that the rectifier has

    no output but the fan is running. That is because the OTP circuit within is

    working. The output will recover after the temperature decreases 1 minute

    later.

    If the fan does not run, and the rectifier has no output for more than 5

    minutes, the rectifier may have been damaged. Please replace the faulty

    rectifier or contact Emerson local service center.

  • 7/28/2019 APM2000- Power Supply Systm

    43/67

    Chapter 4 Maintenance 37

    APM200 Outdoor Power Supply System User Manual

    4.1.2 Indicator description

    Indicator description of the rectifier

    The appearance of the rectifier is shown in Figure 4-1. There are 3

    indicators on the panel: ALM (alarm indicator), FAN-ALM (indicator of fan

    faulty alarm) and RUN (power indicator)

    Figure 4-1 Rectifier appearance

    When the rectifier runs in normal condition, the power indicator RUN is on,

    and the other two indicators are off. When fan failure occurs, FAN- ALM

    indicator is on and RUN indicator is off. When other faults or protectionalarm occur, ALM indicator is on and RUN indicator is off. The operation

    state of the rectifier should be estimated according to the indicator state

    when maintenance.

    Indicator description of the monitoring modu le

    The appearance of the monitoring module is shown in the following figure.

    There are 2 indicators on the panel: RUN (power indicator) and ALM (alarm

    indicator). Descriptions are as shown in Table 4-1.

  • 7/28/2019 APM2000- Power Supply Systm

    44/67

    38 Chapter 4 Maintenance

    APM200 Outdoor Power Supply System User Manual

    Figure 4-2 Appearance of monitoring module

    Table 4-1 Monitoring module indicator description

    Indicator

    MeaningRUN indicator (green)

    ALM indicator

    (red)

    Normal Slow blinking (Once per second) Off

    No system alarm, with abnormal

    communication Fast blinking (Once per 120ms) Off

    System alarm, with normal

    communicationSlow blinking (Once per second) On

    System alarm, with abnormal

    communicationFast blinking (Once per 120ms) On

    4.1.3 Routine Maintenance

    Fan Maintenance

    Dust will accumulate on the baffle plate if the rectifier works in a dusty and

    windy environment. To ensure long-term reliable and smooth operation ofthe rectifier, it is necessary to clean the fan regularly (once 6 months).

    In addition, the fan performance will deteriorate after long-term operation.

    You need to replace the fan regularly (once every 3-5 years).

    Fan replacing method:

    1. Remove the fan baffle plate

    2. Remove the screws on the top right corner of the fan

    3. Pull out the power cable

    4. Replace the fan with a new one

  • 7/28/2019 APM2000- Power Supply Systm

    45/67

    Chapter 4 Maintenance 39

    APM200 Outdoor Power Supply System User Manual

    5. Connect the power cable, and fix the fan with the screw on the top right

    corner

    6. Mount the baffle plate back

    The fan structure is shown below:

    Figure 4-3 Fan of the rectifier

    Note

    1. Only trained professionals are allowed to clean and replace the fan.

    2. Do not touch any internal parts of the rectifier during fan maintenance.

    Rectifi er Pull-Out & Plug-in

    Upon abnormities, the rectifier may need to be pulled out and plugged in.

    The rectifiers and monitoring modules are all hot swappable.

    To pull out the rectifier, you should first draw out the handle at rectifier front

    panel to detach the latch at rectifier bottom from the distribution frame.

    Then you can pull the rectifier out by the handle. The handle position is

    shown in Figure 4-4.

  • 7/28/2019 APM2000- Power Supply Systm

    46/67

    40 Chapter 4 Maintenance

    APM200 Outdoor Power Supply System User Manual

    When replacing new monitoring modules, communication cable and signal

    cable shoule be connected as well. See Figure 4-4.

    Handle of therectifier

    Rectifier

    Handle of themonitoringmodule

    Monitoringmodule

    Communicationcable to theexpanding board

    Signal cable to theexpanding board

    Figure 4-4 Handle of the modules

    Note

    The rectifiers connecting part is a delicate device. Although the rectifiers aredesigned to be hot swappable, the pull-out and plug-in operation should be gentle

    lest the connecting part should be damaged. Non-professionals are not allowed to

    replace the rectifier on-line.

    4.1.4 Handling Of Common Faults

    Fault Symptom1:

    The rectifier quits operation automatically and a corresponding alarm is

    raised at the host.

    Solution: replace the faulty rectifier.

    Fault Symptom2:

    Rectifier(s) is/are shut down upon over-voltage and the corresponding

    alarm is raised at the host.

    Solution: 1) Upon single rectifier shutdown: Switch off the faulty rectifier.

    Wait till its indicators are off, and switch it on again. If the over-voltage still

    exists, the rectifier may have been damaged and need replacing. 2) Upon

    multiple-rectifier shutdown: Pull output all rectifiers and insert them one by

  • 7/28/2019 APM2000- Power Supply Systm

    47/67

    Chapter 4 Maintenance 41

    APM200 Outdoor Power Supply System User Manual

    one to find out the real faulty one. Replace the faulty rectifier after

    confirmation.

    4.2 Battery Maintenance

    Refer to the battery user manual supplied with the battery. (Note: It isrecommended to use T12V100SEF/A battery within this system. If you

    choose to use battery of other models, please consult with Emerson to

    prevent improper configuration.)

    4.3 Heat Exchanging Equipment

    The heat exchanging equipment consists of an internal fan and a heat

    exchanger. Its position is shown in Figure 4-5.

    Heatexchangeequipment

    Cableconnector

    Fixingscrews

    Figure 4-5 Position of heat exchanging equipment

    The internal fan rev is settable. The higher the temperature of the

    equipment compartment is, the larger the internal fan rev is.

    Replace the internal fan or adjust the fan position if it stops running or there

    is an abnormal noise in it. And clean the heat exchanger if there is much

    dust on it. The procedures are as follows.

    Step 1: Disconnect the cable connector at the left side of the heat

    exchanging equipment, as shown in Figure 4-5. Do not disconnect when

    power is on.

    Step 2: Remove the fixing screws shown in Figure 4-5 and then remove the

    heat exchanging equipment from the cabinet.

  • 7/28/2019 APM2000- Power Supply Systm

    48/67

    42 Chapter 4 Maintenance

    APM200 Outdoor Power Supply System User Manual

    Step 3: Remove the screws that fix the cover and the internal fan baffle and

    then remove the cover and the baffle, as shown in Figure 4-6.

    Cover

    Screws for fixing the

    cover (4 pieces)

    Fan baffle

    Screws for fixing the

    baffle (3 pieces)

    Figure 4-6 Remove the cover and baffle

    Step 4: Remove the fixing screws of the internal fan shown in Figure 4-7.

    Adjust the fan position or replace the fan with a new one. Take out the heatexchanger to clean it if there is much dust on it.

    Heat exchanger

    Fan screws

    (4 pieces)Internal fan

    position

    Figure 4-7 Remove internal fan and heat exchanger

    Step 5: Follow step 5 to step 1 to install the new fan and the clean heat

    exchanger into the cabinet. Take care when installing the heat exchanger to

    avoid damaging the waterproof bar on it.

  • 7/28/2019 APM2000- Power Supply Systm

    49/67

    Chapter 4 Maintenance 43

    APM200 Outdoor Power Supply System User Manual

    4.4 External Fan Maintenance

    The external fan rev is settable. The higher the temperature of the

    equipment compartment is, the larger the external fan rev is. Replace the

    external fan or adjust the fan position if it stops running or there is anabnormal noise in it. The procedures are as follows.

    Step 1: Disconnect the cable connector at the left side of the heat

    exchanging equipment, and disconnect the fan cables from the terminals,

    as shown in Figure 4-8. Do not disconnect when power is on.

    Heat ex-changeequipment

    Cable con-nector of theheat exchangeequipment

    Fixingscrews

    Cable con-nector of theexternal fan

    Fixingscrews

    External fan

    Figure 4-8 Positions of heat exchanger and external fan

    Step 2: Remove the fixing screws of the heat exchanging equipment shown

    in Figure 4-8, and then remove the equipment.

    Step 3: Remove the fixing screw of the fan box shown in Figure 4-4 and

    then remove the fan box.

    Step 4: Remove the fixing screw of the external fan shown in Figure 4-9.

    Adjust the fan position or replace it with a new one.

  • 7/28/2019 APM2000- Power Supply Systm

    50/67

    44 Chapter 4 Maintenance

    APM200 Outdoor Power Supply System User Manual

    External fan

    Fixing screws

    of external

    fan (4 pieces)

    Figure 4-9 Remove the external fan

    Step 5: Follow step 4 to step 1 to install the new fan into the cabinet. Install

    the heat exchanging equipment into the cabinet. Take care when installing

    the heat exchanging equipment to avoid damaging the waterproof bar on it.

    4.5 Replace Heaters And Relays

    The two heaters of the system do not need to be repaired. Be sure to pay

    attention to their operation status. The heaters will heat when the

    environment temperature is below 5C5C, and stop heating above

    15C5C. If they operate abnormally, check the heater relays (refer to

    section 4.6.3). If the relays operate abnormally, replace them. Otherwise,

    replace the heaters.

    4.5.1 Replace The Heater In Equipment Compartment

    Step 1: Switch off the AC MCB and the heater fuse, as shown in Figure

    4-10.

  • 7/28/2019 APM2000- Power Supply Systm

    51/67

    Chapter 4 Maintenance 45

    APM200 Outdoor Power Supply System User Manual

    Heater MCB AC input MCBPanel of distribution unit

    Figure 4-10 Position of AC MCB and heater MCB

    Step 2: Remove the panel of the distribution unit, as shown in Figure 4-11.

    The position is shown in Figure 4-10.

    Figure 4-11 Remove the panel of the distribution unit

    Step 3: Unscrew the 4 pieces of screws on the panel of the distribution unit

    and then remove the right segment of the distribution unit. Do not

    disconnect its components and cables and be sure to pay attention to

    personnel safety.

  • 7/28/2019 APM2000- Power Supply Systm

    52/67

    46 Chapter 4 Maintenance

    APM200 Outdoor Power Supply System User Manual

    Screw 1

    Screw 2 Screw 3

    Screw 4

    Figure 4-12 Screw positions

    Step 4: Unscrew the fixing screws of the heater cover and disconnect the

    cable connector from the heater relays. The heater relays are the two

    cables marked L and N in Figure 4-14. Remove the heater cover. The

    heater is fixed on the heater cover, as shown in Figure 4-13.

    Heater of the equipmentcompartment

    Screws

    Heater

    Heater cover

    Figure 4-13 Disassembly of the equipment compartment heater

    Cable connector ofthe heater

    Cable connector ofthe heater

    Figure 4-14 Heater relays

  • 7/28/2019 APM2000- Power Supply Systm

    53/67

    Chapter 4 Maintenance 47

    APM200 Outdoor Power Supply System User Manual

    Step 5: Unscrew the fixing screws of the heater on the heater cover and

    then remove the damaged heater, as shown in Figure 4-12.

    Step 6: Fix the new heater on the heater cover and mount the cover on the

    cabinet. Connect the cable connector to the heater relay. Finally, mount the

    distribution unit on the cabinet.

    Step 7: Check if each cable connector is tight and the connection is reliable.

    Switch on the AC MCB and heater fuse after making sure every thing is OK.

    4.5.2 Replace The Heater In Battery Compartment

    Step 1: Switch off the AC MCB and the heater fuse, as shown in Figure

    4-10.

    Step 2: Take out the battery string on the lower floor of the battery

    compartment.

    Step 3: Disconnect the cable connector from the heater relay. Remove the

    heater cover after removing the screws on the cover, as shown in Figure

    4-15.

    Heater of the battery

    compartment

    Figure 4-15 Position of the heater in battery compartment

    Step 4: Replace a new heater and fix it. Connect the cable connector to the

    heater relay. Move the battery string to its original position.

    Step 5: Check if each cable connector is tight and the connection is reliable.

    Switch on the AC MCB and heater fuse after making sure every thing is OK.

  • 7/28/2019 APM2000- Power Supply Systm

    54/67

    48 Chapter 4 Maintenance

    APM200 Outdoor Power Supply System User Manual

    4.5.3 Replace Heater Relays

    There are two heater relays in one heater circuit. When the environment

    temperature is below 5C5C, the relay contacts are closed to switch on

    the heater circuit. When the environment temperature is above 15C5C,

    the relay contacts are opened to switch off the heater circuit. Replace therelay if its contact cannot be closed or opened normally. Every

    compartment has two heater relays that are connected in series in the

    phase line and the neutral line separately, as shown in Appendix 3.

    The position of the heater relay in equipment compartment is shown in

    Figure 4-14, and that of the heater relay in battery compartment is shown in

    Figure 4-16.

    Heater relay of thebattery compartment

    Figure 4-16 Position of the heater relay in battery compartment

    Replacement processes:

    Step 1: Switch off the AC MCB and the heater fuse, as shown in Figure 4-7.Step 2: Disconnect the cable connector of the relay and remove the screws.

    Step 3: Replace a new relay and connect the cable connector of the relay to

    its terminal.

    Step 4: Switch on the AC MCB and the heater fuse.

  • 7/28/2019 APM2000- Power Supply Systm

    55/67

    Chapter 4 Maintenance 49

    APM200 Outdoor Power Supply System User Manual

    4.6 Replace Door Status Sensors

    There is one door status sensors installed in the equipment compartment

    and the battery compartment separately for detecting the close or open

    status of the compartment doors. The two sensors are connected in series,so the monitoring module will generate an alarm when one of the doors is

    open. The alarm will be eliminated only when both doors are closed.

    The door status sensors are not intended for service or repair, just replace

    them when they are damaged. If the doors are closed, when the door status

    sensor alarm occurs, the sensors must have been damaged. The positions

    of the sensors are shown in Figure 4-17.

    Remove the sensor cap and then the two pieces of screws. Replace the old

    sensor with a new one and finally fix the sensor and the signal cables with

    the screws.

    Door statussensor A inequipmentcompartment

    Door statussensor B inequipmentcompartment

    Door statussensor A inbatterycompartment

    Door statussensor B inbattery

    compartment

    Figure 4-17 Replace door status sensor

  • 7/28/2019 APM2000- Power Supply Systm

    56/67

    50 Chapter 4 Maintenance

    APM200 Outdoor Power Supply System User Manual

    4.7 SPD Maintenance

    The AC SPD is behind the distribution unit. The appearance is shown in

    Figure 4-18.

    Figure 4-18 AC SPD

    Check the SPD indicator on the monitoring expansion board, as shown in

    Figure 4-19. The position of the monitoring expansion board is shown in

    Figure 1-2.

    Alarm ind icato r of DC SPD

    Alarm ind icato r of AC SPD

    Figure 4-19 AC/ DC SPD indicator

    If the indicator on the left is on, the DC SPD fails and needs replacement.

    The replacement procedures of the DC SPD are easy to take and not

    expatiated on here. If the indicator on the right is on, the AC SPD fails and

    needs replacement.

    The replacement procedures of AC SPD are as follows:

    Step1: Switch off the AC MCB. The position is shown in Figure 4-10.

  • 7/28/2019 APM2000- Power Supply Systm

    57/67

    Chapter 4 Maintenance 51

    APM200 Outdoor Power Supply System User Manual

    Step 2: Remove the cover of the distribution unit. The position is shown in

    Figure 4-10.

    Step 3: Remove the 4 screws shown in Figure 4-12, pull out the SPD alarm

    interface and remove the right segment of the distribution unit, as shown in

    Figure 4-20, Figure 4-21, Figure 4-22. Be sure to pay attention to personnel

    safety.

    SPD alarm

    interface

    Figure 4-20 Pull out the SPD alarm interface

    Figure 4-21 Take out SPD and heater

  • 7/28/2019 APM2000- Power Supply Systm

    58/67

    52 Chapter 4 Maintenance

    APM200 Outdoor Power Supply System User Manual

    Figure 4-22 SPD and heater

    Step 4: Remove the 4 fixing screws of the SPD shown in Figure 4-21, and

    screw4 and screw2 are on the cross. Disconnect the connection cables of

    the SPD.

    Figure 4-23 Remove the fixing screws of SPD

    Step 5: Reverse previous steps 4~1 and replace the new SPD. Connect the

    cables, fix the screws and the SPD.

    Step 6: Fix the distribution unit to the cabinet.

    Check if each cable connector is tight and the connection is reliable. Switch

    on the AC MCB and restart operation after making sure everything is OK.

  • 7/28/2019 APM2000- Power Supply Systm

    59/67

    Appendix 1 Technical Data 53

    APM200 Outdoor Power Supply System User Manual

    Appendix 1 Technical Data

    Environmental parameters

    1. Operating temperature:

    North model: -40C to +45C; South model: -5C to +45C;

    2. Storage temperature: -40C to +70C

    3. Relative humidity: 5% to 100%, no condensing

    4. Altitude: 0 to 2000m. The system should be derated where the altitude is

    higher than 2000m. The highest operating temperature should be reduced

    by 1C at every 200m higher. And the highest altitude is 4800m.

    5. Solar radiation

    Direct radiation:1120W/m

    2

    Dispersion radiation:224W/m

    2

    Electrical parameters

    1. Rated input voltage: 220Vac

    2. Input voltage range: 90Vac to 290Vac, single phase three wire. When the

    voltage input is between 90Vac~176Vac, the rectifiers output is allowed of

    linear derating. When the voltage input is 90Vac, the minimum rectifier

    output power is 37.5% of rated power.

    3. Maximum input current of the system: 25A (with no user connector- jack

    output)

    4. Maximum output current of standard configuration: 60A5. Rated frequency: 50Hz

    6. Input frequency range: 40Hz to 65Hz

    Mechanical parameters

    Dimensions (H%W%D): 1600mm%600mm%600mm (without base)

    Weight: 450kg

    Audible noise

    61dB.

  • 7/28/2019 APM2000- Power Supply Systm

    60/67

    54 Appendix 1 Technical Data

    APM200 Outdoor Power Supply System User Manual

    Anti -erosive performance

    Coating:

    1. Adhesion test satisfies ISO2409 Class 0.

    2. The pencil rigidity test satisfies ASTM D3363 2H.

    3. Shock test satisfies 50kg.cm according to ASTM D2794.4. The coating is not changed after 500 hours salt-fog test according to

    ASTM B117.

    5. The coating of the external surface of the cabinet is suitable at the -40C

    to +55C environmental temperature and 1120W/m2

    solar radiation. The

    coating should not blister, flake or flaw after 250 hours test according to

    ASTM D822. But it is allowed to have slight pulverization, that is, a little

    paint particle is allowed to adhere when the coating is wiped at full tilt. The

    slight change of color is allowed, that is, it is acceptable if the color

    difference value (NBS) is less than 6.0.

    Protection requirement

    1. The cabinet of the equipment compartment satisfies GB4208 IP55.

    2. The cabinet of the battery compartment satisfies GB4208 IP23.

    Lightning protection

    1. The system has a Level B+C SPD on AC side.

    2. The AC input can withstand the maximum strike through current capacity

    of 60kA, and the nominal through current capacity is 25kA. The simulated

    lightning strike is carried out in term of YD1235.1 and YD1235.2.

    3. The test of which the DC side can withstand through current capacity of15kA requires: -48V-RTN can withstand the strike of 15kV with the

    waveform 8/20s 5 times, for positive and negative polarity respectively of

    10/700s 5 times, for positive and negative polarity respectively, and the

    interval between every two tests is one minute; RTN-PE can withstand the

    strike of 15kV with the waveform 8/20s 5 times, for positive and negative

    polarity respectively of 10/700s 5 times, for positive and negative polarity

    respectively, and the interval between every two tests is one minute

  • 7/28/2019 APM2000- Power Supply Systm

    61/67

    Appendix 2 Definitions Of The Monitoring Expansion Board Interface 55

    APM200 Outdoor Power Supply System User Manual

    Appendix 2 Definitions Of The Monitoring

    Expansion Board Interface

    All the sensors are connected to the monitoring expansion board. The

    screen print diagram of the wiring port of the monitoring expansion board is

    as follows.

    Screen print of Monitoring expansion board socket

    Figure 1 Screen print diagram of the monitoring expansion board

    Connector models of the monitoring expansion board terminals and

    recommended connection cables are in the following table.

    Table 1 Connector models and recommended connection cables

    Signal portScreen print

    marks

    Socket- connector

    model

    commended

    cablesAWG

    Waterlogging J_WATER P2500-4 26~22

    Circumambient

    temperature/ humidityTEM_HU P2500-4 26~22

    main distribution frame J_WIRE P2500-2 26~22

    Smoke sensor J_SMOKE P2500-2 26~22

    Door status sensor JTM1 P2500-2 26~22

    Alarm dry contact JK1,JK2 P2500-2 26~22

    Optical- coupler output JAC1,JAC2 P2500-2 26~22

  • 7/28/2019 APM2000- Power Supply Systm

    62/67

    56 Appendix 2 Definitions Of The Monitoring Expansion Board Interface

    APM200 Outdoor Power Supply System User Manual

    Signal portScreen print

    marks

    Socket- connector

    model

    commended

    cablesAWG

    Backup digital data input J9 MSTB2.5/2-ST-5.08 26~22

    RS422 communication

    portJ8 MSTB2.5/4-ST-5.08 26~22

    Preset dry contact port J12 MSTB2.5/2-ST-5.08 26~22

    The functional definitions of port- pins of the monitoring expansion board

    are shown in the following table.

    Table 2 Port- pin definitions of the monitoring expansion board

    Port nameScreen

    print marks

    Correlative

    pinsSignal