  • APM200 Auxiliary Power Backup System System Description

    Document Version 1.01

    Product Version V200R004

    Huawei Technologies Co., Ltd. provides customers with comprehensive technical support and service. Please feel free to contact our local office or company headquarters.

    Huawei Technologies Co., Ltd. Address: Administration Building, Huawei Technologies Co., Ltd.,

    Bantian, Longgang District, Shenzhen, P. R. China

    Postal Code: 518129

    Website: http://www.huawei.com

  • Copyright 2007 Huawei Technologies Co., Ltd.

    All Rights Reserved.

    No part of this manual may be reproduced or transmitted in any form or by any means without prior

    written consent of Huawei Technologies Co., Ltd.

    Trademarks

    and other Huawei trademarks are the trademarks or registered trademarks of Huawei

    Technologies Co., Ltd. in the Peoples Republic of China and certain other countries.

    All other trademarks and trade names mentioned in this document are the property of their respective

    holders.

    Notice

    The information in this manual is subject to change without notice. Every effort has been made in the

    preparation of this manual to ensure accuracy of the contents, but all statements, information, and

    recommendations in this manual do not constitute the warranty of any kind, express or implied.

  • APM200 System Description

    Commercial in Confidence i

    Contents

    1 Introduction to the APM200........................................................................................................2

    1.1 Purpose............................................................................................................................................................. 2 1.2 Positioning ....................................................................................................................................................... 2

    2 Features of the APM200 ...............................................................................................................3

    2.1 Functional Parts................................................................................................................................................ 3 2.2 Installation Scenarios ....................................................................................................................................... 3 2.3 Environmental Adaptability ............................................................................................................................. 4 2.4 Easy Maintenance ............................................................................................................................................ 4

    3 Overview of the APM200.............................................................................................................5

    3.1 Appearance and Structure................................................................................................................................. 5 3.2 Benefits and Functions ..................................................................................................................................... 6 3.3 Electrical Specifications ................................................................................................................................... 7 3.4 Engineering Specifications............................................................................................................................... 9 3.5 Physical Interfaces ......................................................................................................................................... 10

    4 Typical Application of the APM200........................................................................................12

    4.1 APM200 Working with GSM/CDMA Mini Base Stations ............................................................................. 12 4.2 APM200 Working with GSM/CDMA Mini Base Stations and Transmission Equipment.............................. 12

  • APM200 System Description

    Commercial in Confidence 2

    1 Introduction to the APM200 1.1 Purpose

    Huawei APM200 is developed for advanced solution of Huawei mini base stations in outdoor application scenario.

    1.2 Positioning

    The APM200 provides a comprehensive solution for outdoor mini base stations in terms of the following aspects:

    Power distribution Lightning protection Transmission equipment embedded installation Transmission cable layout DC power backup

    The rollout of the APM200 meets the requirement of fast network construction in urban, suburb and rural area.

  • APM200 System Description

    Commercial in Confidence 3

    2 Features of the APM200 2.1 Functional Parts

    The APM200 is an integrated cabinet consists of the following functional parts:

    Rectifier Monitoring module Power distribution unit Lightning protection unit Temperature control unit Reserved space for batteries Reserved space for users transmission equipment An reserved AC receptacle

    With the above units, the APM200 performs the following functions:

    48V DC power supply

    Battery management Power distribution Monitoring and communication of the power supply system Lightning protection Temperature control DC Power backup Transmission equipment installation A receptacle for maintenance

    2.2 Installation Scenarios

    The APM200 can be installed in the following scenarios:

    On a rooftop On the concrete floor On an overhead platform (Note1) In addition, the external cables of the APM200 are simple and easy to install.

  • APM200 System Description

    Commercial in Confidence 4

    Note1Since the whole weight of APM200 is very heavy with batteries full configuration, the weight bearing ability requirement is much strict for the overhead platform installation and this installation scenario is not recommended.

    2.3 Environmental Adaptability

    The APM200 is adaptable to the following environments:

    In structural design, the APM200 can protect itself from the damage caused by the following factors: Water Moisture Mould Corrosion Theft

    The open holes in the exterior of the APM200 cabinet help prevent the entry of foreign objects into the cabinet. The APM200 is highly adaptable to outdoor environments.

    The APM200 can protect the AC/DC power supply against lightning strokes. It can be installed on a rooftop or on a mountain top where lightning strokes frequently occur.

    The built-in rectifier of the APM200 can work within a wide range of AC voltages from 176 V AC to 290 V AC (corresponding to the rated power of the rectifier).

    The APM200 has a good control of internal temperature and works within the temperature range 40 to +50.

    2.4 Easy Maintenance

    The cables are led out from the bottom of the APM200 cabinet. You can replace faulty parts, maintain the external ports, and connect the cables from the front of the APM200. The rectifier and the monitoring module are hot-swappable. This facilitates the operation and maintenance of the APM200.

  • APM200 System Description

    Commercial in Confidence 5

    3 Overview of the APM200 3.1 Appearance and Structure

    Figure 3-1 shows the appearance and internal structure of APM200.

    Figure 3-1 Appearance and Internal Structure of APM200

  • APM200 System Description

    Commercial in Confidence 6

    3.2 Benefits and Functions

    The APM200 provides the mini base stations with the following benefits:

    48V DC power

    Backup power of the batteries Space for installing the transmission equipment

    The APM200 performs the following functions:

    Battery management Monitoring and communication of the power system Lightning protection Temperature control Table 3-1 describes the functions of the APM200.

    Table 3-1 Functions of the APM200

    Function Description Remarks

    Ensuring temperature in the cabinet

    In cold regions, AC heaters can be added in the APM200 cabinet to ensure the normal operation of components in battery and equipment compartment.

    Optional

    Supplying backup power through batteries

    The APM200 can be configured with 1 set or 2 sets of 48V100Ah built-in batteries to supply backup power to mini base stations.

    Providing space for transmission equipment

    The APM200 can provide a standard 19-inch space of 5U high for user equipment

    Providing a built-in rectifier

    The rectifier converts the input AC mains into 48V DC power. The rectifier is hot-swappable.

    Providing a built-in monitoring module

    The module has the following functions: Supporting online insertion and removal Managing the rectifier Charging or discharging the batteries Supporting load low voltage disconnect and battery low

    voltage disconnect (LLVD + BLVD) of the load and the batteries

    The monitoring module provides one RS485 communication port, four dry contact alarm output ports and reserves three dry contact alarm input ports for remote control, attendance-free monitoring and alarm expansion.

    Mandatory

  • APM200 System Description

    Commercial in Confidence 7

    Function Description Remarks

    Providing AC power distribution

    The APM200 supports single-phase three-wire input (L, N, PE) of 200 V AC to 240 V AC; The APM200 also supports dual live input ((L1, L2, PE)) of 110 V AC.

    AC receptacle 200240V AC 10A Providing DC power distribution

    Five LLVD outputs, 50A140A125A3. One BLVD output, 16A1.

    Protecting the power supply and the signal ports from lightning destroy

    The APM200 provides safe and reliable surge protection and inductive thunder protection for the alarm ports, the communication ports and the input and output of embedded power system with built-in AC and DC lightning protection module.

    Dissipating heat A heat exchanger is integrated in the top layer APM200 cabinet to make sure wide ambient temperature adaptability for the power system.

    Providing the grounding bar

    The external grounding bar on the cabinet provides the grounding bus of the cabinet and the grounding cable of the surge protector; and the protected grounding cable of the outside equipment powered by APM200 can be connected to the same grounding bar.

    3.3 Electrical Specifications

    Table 3-2 lists the electrical specifications of the APM200.

    Table 3-2 Electrical specifications of the APM200

    Item Specification

    Input voltage range 176 V AC to 290 V AC (in this input voltage range, the rectifier in APM200 can output rated power) 90175V ACin this input voltage range, the rectifier in APM200 will output degraded powerNote2

    AC input

    Typical input voltage 200 V AC to 240 V AC

  • APM200 System Description

    Commercial in Confidence 8

    Item Specification

    Frequency of input voltage

    40 Hz to 65 Hz

    Maximum input current 25 A

    Input mode Single-phase AC input through three wires (L, N, and PE) or 110 V AC input through dual live wires (L1, L2, and PE)

    Output voltage range 58 V DC to 44 V DC

    Output current range 0 A to 60 A

    Typical output voltage 53.5 V DC

    DC output

    DC outputs Five LLVD outputs, 50A140A125A3. One BLVD output, 16A1.

  • APM200 System Description

    Commercial in Confidence 9

    Item Specification

    Power Internal heat consumption 200 W This is the maximum total heat consumption

    restriction for the 5U reserved user space in APM200.

    Input Over-voltage protection and under-voltage protection

    Protection

    Output Over-voltage protection, over-current protection and short-circuit protection.

    Lightning protection for AC input

    Rated through-current capacity In (8/20 s): 25kA Maximum through-current capacity Imax (8/20 s): 60 kA

    Lightning protection for DC output

    Rated through-current capacity In (8/20 s): 15 kA

    Lightning protection

    Lightning protection for signal ports

    Differential mode In (8/20 s): 3 kA Common mode In (8/20 s): 5 kA

    Note2 When the input voltage is within 90V AC ~ 175V AC, the rectifiers output is linear degraded. When the voltage input is 90V AC, the minimum rectifier output power is 37.5% of rated power.

    3.4 Engineering Specifications

    Table 3-3 lists the engineering specifications of the APM200.

    Table 3-3 Engineering specifications of the APM200

    Item Specification

    Weight 120kg (without batteries and transmission equipment)

    Cabinet dimensions (W x H x D) 600mm1600mm600mm (without the base)

    Base dimensions (W x H x D) 600mm100mm600mm Space for the user equipment (W x H x D)

    482 mm222mm480mm Standard 19-inch space of 5 U high for user

    equipment. There is 360mm depth after the vertical shaft; and 120mm depth in the front of the vertical shaft for maintenance.

  • APM200 System Description

    Commercial in Confidence 10

    Item Specification

    Working temperature

    40 to +45 When the ambient temperature is lower than 20, AC heaters are required.

    Direct sunlight intensity

    1120 W/m2

    Relative humidity 5% RH to 100% RH

    Working environment

    Altitude 4000 m The maximum working temperature decreases by 1 each time the altitude increases by 200 m from 2000 m.

    Dustproof and waterproof IP55Equipment compartment IP34Battery compartment

    Annual failure rate of the rectifier < 1%

    Annual failure rate of the monitoring module

    < 0.5%

    Fan life L1040 40000hours

    3.5 Physical Interfaces

    Table 3-4 describes the external physical interfaces of the APM200.

    Table 3-4 External physical interfaces of the APM200

    Physical Interface Quantity Interface No.

    Note3

    Interface size specification

    AC power input port 1 port 1

    48V DC power output port 1~6 ports 49 Outlet for the RS485 communication cable

    1 port 15

    Outlet for the dry contact alarm cable

    1 port 15

    The size of No.1 4~15 outlets can meets leading through requirement for the cable with outer diameter 10mm14mm.

  • APM200 System Description

    Commercial in Confidence 11

    Inlet/outlet for the optical cable or the E1 cable to the user equipment

    6 ports 1015

    Inlet/outlet for the optical cable or the IF cable

    2 ports 23 The size of No.2 and 3 outlets can meets leading through requirement for the cable with outer diameter 13mm18mm.

    External Grounding Bar 8 terminals / All the grounding nuts are M8 nuts.

    Note3The physical interfaces with the same interface no. share the same physical outlet in the cabinet and they are not used at the same time.

  • APM200 System Description

    Commercial in Confidence 12

    4 Typical Application of the APM200 4.1 APM200 Working with GSM/CDMA Mini Base Stations

    APM200 with built-in batteries are applied to the GSM/CDMA mini base station to provide -48V DC power and battery backup for it, as shown in Figure 4-1.

    Figure 4-1 Typical application of the APM200 (1)

    4.2 APM200 Working with GSM/CDMA Mini Base Stations and Transmission Equipment

    AC Mini-BTS

    485 Signal Cable -48V DC

  • APM200 System Description

    Commercial in Confidence 13

    APM200 with built-in batteries and transmission equipment are applied to the GSM/CDMA mini base stations to provide -48V DC power and battery backup for them, as shown in Figure 4-2.

    Figure 4-2 Typical application of the APM200 (2)

    Mini-BTS

    485 Signal Cable -48V DC AC

    Relay fiber/IF cables (up) Relay fiber/IF cables (down)

    Transmission equipment

    E1