APC715 Pump Unit Controller
USER MANUAL
Smartgen Technology
-
5/27/2018 APC715_V1.0_en
2/62
Chinese trademark
English trademark
Smartgenmake your generatorsmartSmartgen Technology Co., Ltd.
No. 28 Jinsuo RoadZhengzhou
Henan Province
P. R. China
Tel:+86-371-67988888/67981888
+86-371-67991553/67992951
+86-371-67981000(overseas)
Fax:0086-371-67992952
Web:http://www.smartgen.com.cn
http://www.smartgen.cn
Email:[email protected]
All rights reserved. No part of this publication may be reproduced in any material form
(including photocopying or storing in any medium by electronic means or other) without
the written permission of the copyright holder.
Smartgen Technology reserves the right to change the contents of this document
without prior notice.
http://www.smartgen.com.cn/http://www.smartgen.cn/mailto:[email protected]:[email protected]://www.smartgen.cn/http://www.smartgen.com.cn/ -
5/27/2018 APC715_V1.0_en
3/62
Version
Date Version Note
2013-08-28 1.0 Original release.
This manual is suitable for APC715 pump unit controller only.
Clarification of notation used within this publication.
SYMBOL INSTRUCTION
NOTE
Highlights an essential element of a procedure to ensure
correctness.
CAUTION!
Indicates a procedure or practice, which, if not strictly observed,
could result in damage or destruction of equipment.
WARNING!
Indicates a procedure or practice, which could result in injury to
personnel or loss of life if not followed correctly.
-
5/27/2018 APC715_V1.0_en
4/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 4 of 62
CONTENTS
1 OVERVIEW........................................................................................ 62 PERFORMANCE AND CHARACTERISTICS .................................... 73 SPECIFICATION ................................................................................ 94 OPERATION .................................................................................... 10
4.1 INDICATOR LIGHT ......................................................................................... 104.2 PUSHBUTTONS ............................................................................................. 114.3 LCD DISPLAY ................................................................................................. 12
4.3.1 MAIN DISPLAY................................................................................... 124.3.2 USER MENU AND PARAMETERS SETTING MENU ........................ 13
4.4 AUTO START/STOP OPERATION ................................................................. 164.5 MANUAL START/STOP OPERATION ............................................................ 174.6 ON-LOAD CONTROL PROCESS ................................................................... 184.7 ADJUST SPEED CONTROL .......................................................................... 19
5 PROTECTION ................................................................................. 205.1 WARNINGS .................................................................................................... 205.2 SHUTDOWN ALARM ..................................................................................... 225.3 TRIP SHUTDOWN ......................................................................................... 245.4 FAULT IDLE .................................................................................................... 24
6 CONNECTIONS .............................................................................. 257 DEFINITION AND RANGE OF PARAMETERS ................................ 28
7.1 PARAMETER CONTENTS AND RANGE (TABLE 1) ...................................... 287.2 PROGRAMMABLE OUTPUT 1-5 (TABLE 2) .................................................. 37
7.2.1 Custom Period Output ........................................................................ 417.2.2 Custom Combined Output .................................................................. 42
7.3 DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS (ALL ACTIVEWHEN CONNECT TO GRAND (B-)) ...................................................................... 437.4 SELECTION OF SENSORS ........................................................................... 457.5 CONDITIONS OF CRANK DINSCONNECT SELECTION ............................. 46
8 PARAMETERS SETTING ................................................................ 479 SENSOR SELECT ........................................................................... 4810 TYPICAL APPLICATION .................................................................. 4911 INSTALLATION ................................................................................ 5012 CONNECTIONS OF CONTROLLER WITH J1939 ENGINE ............ 51
12.1CUMMINS ISB/ISBE ....................................................................................... 5112.2CUMMINS QSL9 ............................................................................................ 51
-
5/27/2018 APC715_V1.0_en
5/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 5 of 62
12.3CUMMINS QSM11(IMPORT) ......................................................................... 5212.4CUMMINS QSX15-CM570 ............................................................................. 5212.5CUMMINS GCS-MODBUS ............................................................................. 5312.6
CUMMINS QSM11 .......................................................................................... 53
12.7CUMMINS QSZ13 .......................................................................................... 5412.8DETROIT DIESEL DDEC III / IV ..................................................................... 5412.9DEUTZ EMR2 ................................................................................................. 5512.10 JOHN DEERE .......................................................................................... 5512.11 MTU MDEC .............................................................................................. 5512.12 MTU ADEC(SMART MODULE) ................................................................ 5612.13 MTU ADEC(SAM MODULE) ..................................................................... 5612.14 PERKINS .................................................................................................. 5712.15 SCANIA .................................................................................................... 5712.16 VOLVO EDC3 ........................................................................................... 5812.17 VOLVO EDC4 ........................................................................................... 5812.18 VOLVO-EMS2 ........................................................................................... 5912.19 YUCHAI .................................................................................................... 5912.20 WEICHAI .................................................................................................. 60
13 USB ................................................................................................. 6114 FAULT FINDING .............................................................................. 62
-
5/27/2018 APC715_V1.0_en
6/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 6 of 62
1 OVERVIEW
APC715 Pump Unit Controller is designed for pump systems which controlled by
engine. It allows automatic start/stop, data measurement, alarm protection as well as
remote control, remote measurement and remote communication function. It fit with
LCD display, optional languages interface, and it is reliable and easy to use.
Utilizing the GOV (Engine Speed Governor) control function, the controller is able to
stabilize the outlet pressure via GOV.
APC715 Pump Unit Controlleralso monitors the engine, indicating the operational
status and fault conditions accurately. When abnormal condition occurs, it can protect
the unit automatically; simultaneously the exact failure mode information is indicated
by the LCD display on the front panel. SAE J1939 interface enables the controller to
communicate with various ECU (ENGINE CONTROL UNIT) which fitted with J1939
interface.
APC715 Pump Unit Controlleradopt powerful 32-bit microprocessor technology with
precision parameters measuring, fixed value adjustment, time setting and set value
adjusting and etc. The majority of parameters can be configured from front panel and
all the parameters can be set using PC (via USB port) and can be adjusted and
monitored with the help of RS485 ports. It can be widely used in a number of pump
control system with compact structure, simple connections and high reliability
-
5/27/2018 APC715_V1.0_en
7/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 7 of 62
2 PERFORMANCE AND CHARACTERISTICS
With ARM-based 32-bit SCM, highly integrated hardware, new reliability level.
480x272 pixel, 4.3 inches LCD with backlight, multilingual interface (including
English, Chinese or other languages) which can be chosen at the site, making
commissioning convenient for factory personnel.
Improved LCD wear-resistance and scratch resistance due to hard screen acrylic.
Silicon panel and pushbuttons for better operation in high/low temperature
environment
RS485 communication port enabling remote control, remote measuring, remote
communication via ModBus protocol.
Equipped with CANBUS port and can communicate with J1939 genset. Not only
can you monitoring frequently-used data (such as water temperature, oil pressure,
engine speed, fuel consumption and so on) of ECU machine, but also control start,
stop, raising speed and speed droop via CANBUS port.
10 analog sensors; sensors can switch between resistor type and current type using
jumper.
More kinds of curves of temperature, oil pressure, fuel level can be used directly
and users can define the sensor curves by themselves.
Precision measure and display parameters about Engine and pump unit.
Protection: automatic start/stop of the pump unit, perfect fault indication and
protection function.
All output ports are relay-out;
Parameter setting: parameters can be modified and stored in internal FLASH
memory and cannot be lost even in case of power outage; most of them can be
adjusted using front panel of the controller and all of them can be modified using
PC via USB or RS485 ports.
Multiple crank disconnect conditions (speed sensor, oil pressure) are optional;
Widely power supply range DC(8~35)V, suitable to different starting battery voltage
environment;
Event log, real-time clock, scheduled start & stop pump unit (can be set as start
pump unit once a day/week/month whether with load or not);
Accumulative total run time and total electric energy of A and B. Users can reset it
as 0 and re-accumulative the value which make convenience to users to count the
-
5/27/2018 APC715_V1.0_en
8/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 8 of 62
total value as their wish.
Can control engine heater, cooler and fuel pump.
With maintenance function. Actions (warning/shutdown) can be set when
maintenance time out;
All parameters used digital adjustment, instead of conventional analog modulation
with normal potentiometer, more reliability and stability;
Waterproof security level IP55 due to rubber seal installed between the controller
enclosure and panel fascia;
Metal fixing clips enable perfect performance in high temperature environment;
Modular design, anti-flaming ABS plastic enclosure, pluggable connection terminals
and embedded installation way; compact structure with easy mounting.
-
5/27/2018 APC715_V1.0_en
9/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 9 of 62
3 SPECIFICATION
Items Contents
Working Voltage DC8. 0V to 35. 0V, Continuous Power Supply.
Overall Consumption
-
5/27/2018 APC715_V1.0_en
10/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 10 of 62
4 OPERATION
4.1 INDICATOR LIGHT
Note: Selected indicators description:
Warning indicator and Alarm indicator:
Alarm Type Warning Indicator Alarm Indicator
Warning Slow flashing Slow flashing
Shutdown Alarm Off Fast flashing
Running indicator: illuminated from crank successful to ETS while off during other
periods.
-
5/27/2018 APC715_V1.0_en
11/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 11 of 62
4.2 PUSHBUTTONS
Stop
Stop running pump unit in Auto/Manual mode;Reset alarm in stop mode; Lamp test (press atleast 3 seconds); During stopping process, pressthis button again to stop pump unit immediately.
Start Start pump unit in Manual/Test mode.
Manual ModePress this key and controller enters in Manualmode.
Auto Mode Press this key and controller enters in Automode.
MuteAlarming sound off; If there is alarm, pressing thebutton at least 3 seconds can reset this alarm.
LoadCan control the clutch to switch on or off in manual
mode.
Adjust Speed Enter/Exit the speed adjust menu.
Up/Increase1) Screen scroll; 2) Up cursor and increasevalue in setting menu.
Down/Decrease1) Screen scroll; 2) Down cursor and decreasevalue in setting menu.
Left1) Screen scroll; 2) Left move cursor in settingmenu.
Right1) Screen scroll; 2) Right move cursor in settingmenu.
Set/Confirm
1. Enter intohelpinterface;2. Pressing and holding for more than 3 seconds
enters parameter configuration menu;3. In settings menu confirms the set value.
Exit1. Returns to the main menu;2. In settings menu returns to the previous menu.
NOTE: In manual mode, pressing and simultaneously will force
generator to crank. Successful start will not be judged according to crank disconnect
conditions, operator will have to crank the starter motor manually; when operator
decides that the engine has fired, he/she should release the button and start relay will
be deactivated, safety on delay will start.
WARNING: Default password is 00318, user can change it in case of others
change the advanced parameters setting. Please clearly remember the password after
changing. If you forget it, please contact Smartgen services and send all information in
the controller page of ABOUTto us.
-
5/27/2018 APC715_V1.0_en
12/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 12 of 62
4.3 LCD DISPLAY
4.3.1 MAIN DISPLAY
Main screen is divided into left and right separate viewing areas, use to select a
viewing area; the selected area is marked with in its upper left corner. Both
viewing areas show pages; use to scroll the pages and to scroll the
screen.
Engine, including as below,
Engine status, engine temperature, engine oil pressure, fuel level, Configurable Sensor 1,
battery voltage, charger voltage, accumulated run time, accumulated start times.
NOTE:If connected with J1939 engine via CANBUS port, this page also includes:
coolant pressure, coolant level, fuel temperature, fuel pressure, inlet temperature,exhaust temperature, turbo pressure, fuel consumption, total fuel consumption and so
on. (Different engine with different parameters)
Pump Unit
Outlet pressure, pump flow, pump head, config. sensor 2~6 (can be set as
temperature sensor, pressure sensor or level sensor)
FormulaPump Head = ( Outlet pressure - Static Pressure)/0.0098.
Alarm:
Display all warnings, shutdown alarms, trip shutdown alarms and the corresponding
information.
NOTE:For ECU alarms and shutdown alarms, if the alarm information is displayed,
check engine according to it, otherwise, please check the manual of generator according
to SPN alarm code.
Event log
Records all start/stop events (shutdown alarm, trip shutdown alarm, manual/auto start or
stop) and the real time when alarm occurs.
Others, including,
Time and Date, maintenance due time, input/output ports status.
About,including,
Issue time of software and hardware version, product PD number.
-
5/27/2018 APC715_V1.0_en
13/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 13 of 62
Status, including as below,
Engine speed, battery voltage 1, engine status
Indicator Status
Green Normal status; No alarm
Yellow Warning or idle speed alarm occurs.
Red Shutdown alarm occurs.
Example:
Engine Pump
On load
Manual Mode
Normal Running
Outlet Pressure
1.0MPa 10Bar 145psi
Config Sensor 2
45 113Engine Temp.85 185 Config Sensor 3
465kPa 4.65Bar 67.4psiOil Pressure
465kPa 4.65Bar
67.4psiConfig Sensor 4
100%
1500rpm 27.6V At Rest
Engine Pump
Fuel Level
100%
Config Sensor 5
55 131
Config Sensor 1
85 185
Config Sensor 6
60 140
Battery Voltage 1
27.6V
Pump Flow
200m/h
Battery Voltage 2
27.6V
Pump Head
102m
1500rpm 27.6V Emergency Stop
4.3.2 USER MENU AND PARAMETERS SETTING MENU
Press and hold for more than 3 seconds to enter into user menu;
Parameter
After entering the correct password (factory default password is 00318), you can enter
into parameter settings interface.
Language
Selectable Chinese, English and others (default: Espanol)
-
5/27/2018 APC715_V1.0_en
14/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 14 of 62
Commissioning
On load, off load or custom commissioning can be chosen. Custom commissioning
can configure on load or not during commissioning, when to commissioning and select
the mode after commissioning (manual mode, auto mode and stop mode).
Clear usersaccumulation
Can clear User Acc. Run A, User Acc. Run B and Engine Acc. Run time.
Parameter setting including as following,
Timer settings
Engine settings
Analog sensor settings (Engine temperature, engine oil pressure, fuel level, config.
1~6, outlet pressure)
Input port settings
output port settings
GOV settings
Pump settings
Module settings
Scheduling and maintenance settings
Example,
Return >Start Delay
>Stop Delay
>Preheat Delay
>Cranking Time
> Crank Rest Time
> Safety On Time
> Start Idle Time
> Warming Up Time
> Cooling Time
> Stop Idle Time> ETS Hold Time
Form1: Use to scroll settings,
to enter settings (form2), to
exit settings menu.
Timers
Engine
Temp. Sensor
OP Sensor
Level Sensor
Config Sensor 1
Config Sensor 2
Config Sensor 3
Config Sensor 4Config Sensor 5
-
5/27/2018 APC715_V1.0_en
15/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 15 of 62
Return Start Delay Form 2: Use to scroll
settings, to enter settings (form3),
to return to previous menu. (form
1).
Timers >Stop Delay
>Preheat Delay
>Cranking Time
>Crank Rest Time
>Safety On Time
>Start Idle Time
>Warming Up Time
>Cooling Time
>Stop Idle Time
>ETS Hold Time
Engine
Temp. Sensor
OP Sensor
Level Sensor
Config Sensor 1
Config Sensor 2
Config Sensor 3
Config Sensor 4
Config Sensor 5
Return >Start Delay
>Stop Delay
>Preheat Delay
Form 3: Use to scroll
settings, to enter settings (form4),
to return to previous menu. (form
1).
Timers
Engine
Temp. Sensor
OP Sensor
Level Sensor
Config Sensor 1
Config Sensor 2
Config Sensor 3
Config Sensor 4
Config Sensor 5
>Cranking Time
>Crank Rest Time
>Safety On Time
>Start Idle Time
>Warming Up Time
>Cooling Time
>Stop Idle Time
>ETS Hold Time
>Start Delay
>Stop Delay
>Preheat Delay
Form 4Press to enter settings
(form 5), to return to previous
menu. (form 6).
00008
Cranking Time
>Crank Rest Time
>Safety On Time
>Start Idle Time
>Warming Up Time
>Cooling Time
>Stop Idle Time
>ETS Hold Time
-
5/27/2018 APC715_V1.0_en
16/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 16 of 62
>Start Delay
>Stop Delay
>Preheat Delay
00008 Form5: Press to change cursor
position, are used for
changing cursor value, Confirm
setting (form 4), exit setting (form
4).
Cranking Time
>Crank Rest Time
>Safety On Time
>Start Idle Time
> Warming Up Time
>Cooling Time
>Stop Idle Time
>ETS Hold Time
>Start Delay
>Stop Delay
>Preheat Delay
00008
Form 6: are used for
changing the setting contents.
Confirm setting (form 4), to return
to previous menu. (form 1).
Cranking Time
>Crank Rest Time
>Safety On Time
>Start Idle Time
> Warming Up Time
>Cooling Time
>Stop Idle Time
>ETS Hold Time
>Wait Stop Time
NOTE:Pressing can exit setting directly during setting.
4.4 AUTO START/STOP OPERATION
Auto mode is selected by pressing the button; a LED besides the button will
illuminate to confirm the operation.
Automatic Start Sequence:
1. When Remote Start is active, Start Delaytimer is initiated;2. When start delay is over, preheat relay energizes (if configured), preheat delay XX s
information will be displayed on LCD;
3. After the above delay, the Fuel Relay is energized, and then one second later, the
Start Relay is engaged. The engine is cranked for a pre-set time. If the pump unit fails
to fire during this cranking attempt then the fuel relay and start relay are disengaged
for the pre-set rest period; crank rest time begins and wait for the next crank
attempt.4. Should this start sequence continue beyond the set number of attempts, the start
-
5/27/2018 APC715_V1.0_en
17/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 17 of 62
sequence will be terminated, the Fail to Start fault will be displayed on LCD.
5. In case of successful crank attempt, the Safety On timer is activated, allowing Low
Oil Pressure, High Temperature, Under speed and Charge Alternator Failure inputs
to stabilize without triggering the fault. As soon as this delay is over, start idle delay
is initiated (if configured).
6. During start idle delay, under speed alarm is inhibited. When this delay is over,
warming up delay is initiated (if configured).
7. After the warming up delay, If engine speed has reached on-load requirements,
then the pump close relay will be energized; pump uint will take load; pump unit will
enter into Normal Running status.
NOTE: In case of Remote Start (off Load), the procedure is the same, except for
step NO. 7: the pump close relay will NOT be energised, generator will NOT accept load.
Automatic Stop Sequence,
1) When the Remote Start signal is deactivated while the Remote Stop signal is
active, the Stop Delay is initiated.
2) Once this stop delay has expired, the Pump Unit Breaker will open and the Cooling
Delay is then initiated. Should the Remote Start signal be re-activated during the
cooling down period, the unit will return running status. Once the Cooling Delay
expires, the Stop Idle delay is initiated.
3) During Stop Idle Delay (if configured), idle relay is energized.
4) ETS Solenoid Hold begins, ETS relay is energized while fuel relay is
de-energized and complete stop is detected automatically
5) "Fail to Stop Delay" begins, complete stop is detected automatically.
6) Pump unit is placed into its After stop timeafter its complete stop. Otherwise, fail
to stop alarm is initiated and the corresponding alarm information is displayed on
LCD (If pump unit stopped successfully after Failed to Stopalarm, it will enter
After stop time and remove alarm).
7) Pump unit is placed into its standby mode after its After stop time.
4.5 MANUAL START/STOP OPERATION
1 Manual Start: Manual mode is selected by pressing the button; a LED
besides the button will illuminate to confirm the operation; then press
button to start the unit; can automatically detect crank successful, and unitaccelerates to high-speed running automatically.
-
5/27/2018 APC715_V1.0_en
18/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 18 of 62
When AfterUnload Idleis enabled, the unit is idle running when crank succeed;
unit accelerates to high-speed running automatically and take load after press
key by manual.
With high temperature, low oil pressure and over speed during pump unit running,controller can protect it to stop quickly (please refer to No.2~7 of Auto start
operation for detail procedures).
2 MANUAL STOP: Press can stop the running pump unit. (please refer to
No.2~7 of Auto stop operation for detail procedures).
NOTE: In manual mode, users can control the pump unit on load or off load via
Loadkey.
4.6 ON-LOAD CONTROL PROCESS
When controller is in Manual mode, manual control will be executed.
Users can control the pump unit on load or off load by pressing key. The pump unit
will unload automatically when it is stopped.
If AfterUnload Idleis selected Disable
Start the pump unit in manual mode and press key during the normal running
process, then the generator will take load; press key again, the generator will
unload.
If AfterUnload Idleis selected Enable
Start the pump unit in manual mode and it enters into idle running process. The pump
unit will not enter into normal running status until key is pressed and it will take
load as soon as the on-load requirements have reached.
When the pump unit is normal running with load, press key once again will lead to
the units offload (i.e. load relay deactivated); then the cooling delaywill be initiated.
Once this has expired, the unit will enter into idle running status.
When controller is in Auto mode, auto control will be executed.
The pump unit will take load automatically when it is normal running and the on-load
requirements have reached while unload automatically when it is stopped.
-
5/27/2018 APC715_V1.0_en
19/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 19 of 62
4.7 ADJUST SPEED CONTROL
Users can set the outlet pressure as the rated value simply by adjusting the engine
speed. The Adjust Speed Controlwas divided into auto control and manual control.
Manual Adjust Speed:Adjust Speed mode is selected by pressing the button; In
this interface, users can adjust speed using navigational button: , manual adjust
speed; , auto adjust speed; , manual raise speed; , manual drop speed. ,
manual raise speedand , manual drop speedbuttons are active only when pump
unit is normal running under Manual Adjust Speedmode.
Auto Adjust Speed: Under this mode, during the unit is normal running, the
controller will adjust the outlet pressure to rated speed and maintain its steady
automatically according to the set value.
The Auto Adjust Speedwas divided into relay adjust speed, GOV adjust speed and
CAN adjust speed.
Relay Adjust Speed: Control the engine servo motor simply by using speed raise relay
and speed drop relay.
GOV Adjust Speed: Control the electronic speed regulator simply by using GOV
analog signal. Users should set parameters according to the actual situation as
different regulators have different parameters.
CAN Adjust Speed: Control the ECU engine speed simply by using CAN interface.
Parameters setting and speed adjustment method are same as GOV. Some ECU
engine has CAN adjust speed function, e.g. EMS2. Other engine types need the
above two ways to adjust speed.
-
5/27/2018 APC715_V1.0_en
20/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 20 of 62
5 PROTECTION
5.1 WARNINGS
Warnings are not shutdown alarms and do not affect the operation of the genset.
Warning does not lead to shutdown, and when warning condition is no longer present,
warning alarm will be cleared automatically. Warning types are as follows:
No. Type Description
1 Over Speed
When the controller detects that the engine speed has
exceeded the pre-set value, it will initiate a warning
alarm.
2 Under Speed
When the controller detects that the engine speed has
fallen below the pre-set value, it will initiate a warning
alarm.
3Loss of Speed
Signal
When the controller detects that the engine speed is 0
and the action select Warn, it will initiate a warning
alarm.
4 Fail To StopAfter fail to stop delay, if unit is not stop completely, it
will initiate a warning alarm.
5 Charge Alt Fail
When the controller detects that charger voltage has
fallen below the pre-set value, it will initiate a warning
alarm.
6 Battery 1 OverVoltage
When the controller detects that battery 1 voltage hasexceeded the pre-set value, it will initiate a warning
alarm.
7Battery 1 Under
Voltage
When the controller detects that battery 1 voltage has
fallen below the pre-set value, it will initiate a warning
alarm.
8 Maintenance DueWhen maintenance countdown time is 0 and the action
select Warn, it will initiate a warning alarm.
9 ECU WarnIf an error message is received from ECU via J1939, it
will initiate a warning alarm.
10
Temperature
Sensor Open
Circuit
When the controller detects that the temperature
sensor is open circuit and the action select Warn, it
will initiate a warning alarm.
11 High Temperature
When the controller detects that engine temperature
has exceeded the pre-set value, it will initiate a warning
alarm.
12 Low Temperature
When the controller detects that engine temperature
has fallen below the pre-set value, it will initiate a
warning alarm.
13Oil Pressure Open
Circuit
When the controller detects that the oil pressure sensor
is open circuit and the action select Warn, it will
-
5/27/2018 APC715_V1.0_en
21/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 21 of 62
No. Type Description
initiate a warning alarm.
14 Low Oil Pressure
When the controller detects that the oil pressure has
fallen below the pre-set value, it will initiate a warning
alarm.
15 Level Sensor Open
When the controller detects that the level sensor is
open circuit and the action select Warn, it will initiate a
warning alarm.
16 Low Fuel LevelWhen the controller detects that the fuel level has fallen
below the pre-set value, it will initiate a warning alarm.
17Flexible Sensor
1~6 Open
When the controller detects that the sensor is open
circuit and the action select Warn, it will initiate a
warning alarm.
18
Flexible Sensor
1~6 High
When the controller detects the sensor value is higher
than the max. set value, it will initiate a warning alarm.
19Flexible Sensor
1~6 Low
When the controller detects the sensor value is lower
than the min. set value, it will initiate a warning alarm.
20Digital Input 1~9
Warn
When the action of digital input port select Warnand
active, it will initiate a warning alarm.
21Battery 2 Over
Voltage
When the controller detects that battery 2 voltage has
exceeded the pre-set value, it will initiate a warning
alarm.
22Battery 2 Under
Voltage
When the controller detects that battery 2 voltage has
fallen below the pre-set value, it will initiate a warningalarm.
23Outlet Pressure
Sensor Open
When the controller detects that the outlet pressure
sensor is open circuit and the action select Warn, it
will initiate a warning alarm.
24Outlet Pressure
Sensor High
When the controller detects the sensor value is higher
than the max. set value, it will initiate a warning alarm.
25Outlet Pressure
Sensor Low
When the controller detects the sensor value is lower
than the min. set value, it will initiate a warning alarm.
26 Over Flow Warn When the controller detects the flow value is higherthan the max. set value, it will initiate a warning alarm.
27Gearbox Over
speed
When the controller detects that the gearbox speed has
exceeded the pre-set value, it will initiate a warning
alarm.
28Gearbox Under
speed
When the controller detects that the gearbox speed has
fallen below the pre-set value, it will initiate a warning
alarm.
29End Of The
Mandate
When the mandate time has expired and the action
select Warn, it will initiate a warning alarm.
-
5/27/2018 APC715_V1.0_en
22/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 22 of 62
5.2 SHUTDOWN ALARM
When controller detects shutdown alarm, it will send signal to open breaker and stop the
unit. Shutdown alarm must be cleared manually and the fault removed to reset the
module. Shutdown alarm types are as follows:
NO. Type Description
1 Emergency StopWhen the controller detects an emergency stop alarm
signal, it will initiate a shutdown alarm.
2 Over Speed
When the controller detects that the generator speed
has exceeded the pre-set value, it will initiate a
shutdown alarm.
3 Under Speed
When the controller detects that the generator speed
has fallen below the pre-set value, it will initiate a
shutdown alarm.
4Loss of Speed
Signal
When the controller detects that the engine speed is 0
and the action select Warn, it will initiate a shutdown
alarm.
5 Maintenance DueWhen maintenance countdown time is 0 and the action
select Shutdown, it will initiate a shutdown alarm.
6 ECU ShutdownIf shutdown alarm signal is received from ECU via
J1939, it will initiate a shutdown alarm.
7 ECU Fail
If the module does not detect the J1939 data, it will
initiate a shutdown alarm.
8
Temperature
Sensor Open
Circuit
When the controller detects that the temperature
sensor is open circuit and the action select Shutdown,
it will initiate a shutdown alarm.
9 High Temperature
When the controller detects that engine temperature
has exceeded the pre-set value, it will initiate a
shutdown alarm.
10Oil Pressure Open
Circuit
When the controller detects that the oil pressure sensor
is open circuit and the action select Shutdown, it will
initiate a shutdown alarm.
11 Low Oil Pressure
When the controller detects that the oil pressure has
fallen below the pre-set value, it will initiate a shutdown
alarm.
12Level Sensor Open
Circuit
When the controller detects that the sensor is open
circuit and the action select Shutdown, it will initiate a
shutdown alarm.
13Flexible Sensor
1~6 Open
When the controller detects that the sensor is open
circuit and the action select Shutdown, it will initiate a
shutdown alarm.
-
5/27/2018 APC715_V1.0_en
23/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 23 of 62
NO. Type Description
16Flexible Sensor
1~6 High
When the controller detects the sensor value is higher
than the max. set value, it will initiate a shutdown
alarm.
17Flexible Sensor
1~6 Low
When the controller detects the sensor value is lower
than the min. set value, it will initiate a shutdown alarm.
18Digital Input 1~9
Shutdown
When the action of digital input port select Shutdown
and active, it will initiate a shutdown alarm.
19Outlet Pressure
Sensor Open
When the controller detects that the outlet pressure
sensor is open circuit and the action select Shutdown,
it will initiate a shutdown alarm.
20Outlet Pressure
Sensor High
When the controller detects the sensor value is higher
than the max. set value, it will initiate a shutdown
alarm.
21Outlet Pressure
Sensor Low
When the controller detects the sensor value is lower
than the min. set value, it will initiate a shutdown alarm.
22Over Flow
Shutdown
When the controller detects the flow value is higher
than the max. set value, it will initiate a shutdown
alarm.
23Gearbox Over
speed
When the controller detects that the gearbox speed has
exceeded the pre-set value, it will initiate a shutdown
alarm.
24Gearbox Under
speed
When the controller detects that the gearbox speed hasfallen below the pre-set value, it will initiate a shutdown
alarm.
25End Of The
Mandate
When the mandate time has expired and the action
select Shutdown, it will initiate a shutdown alarm.
-
5/27/2018 APC715_V1.0_en
24/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 24 of 62
5.3 TRIP SHUTDOWN
On initiation of the trip shutdown condition the controller will de-energize the loadoutput
to remove the load from the unit. Once this has occurred the controller will start the
Cooling delay and allow the engine to cool before shutting down the engine. Trip
shutdown alarm must be cleared manually and the fault removed to reset the module.
Trip shutdown alarm types are as follows:
NO. Types Description
1 Maintenance Due
When maintenance countdown time is 0 and the action
select Trip Shutdown, it will initiate a trip shutdown
alarm.
2 Digital Input 1~9
When the action of digital input port select Trip
Shutdown and active, it will initiate a trip shutdown
alarm.
5.4 FAULT IDLE
On initiation of the trip condition the controller will de-energize the loadoutput to remove
the load from the unit. Once this has occurred the controller will start the Cooling delay
and allow the engine to cool before idle running process. Fault idle alarm must be
cleared by pressing Mutebutton more than 3s manually. Fault idle alarm types are as
follows:
No. Types Description
1 Digital Input 1~9When the action of digital input port select Fault idle
and active, it will initiate a trip shutdown alarm.
-
5/27/2018 APC715_V1.0_en
25/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 25 of 62
6 CONNECTIONS
APC715 controller back panel is shown below:
Description of terminal connections:
Pin FunctionCable
SizeDescription
1 B- 2.5mm2 Connected with negative of starter battery.
2 B+ 2.5mm2
Connected with positive of starter battery. If
wire length is over 30m, better to double wires
in parallel. Max. 20A fuse is recommended.
3 Emergency Stop 2.5mm2Connected with B+ power supply via
emergency stop button.
4 Fuel Relay Output 1.5mm2
B+ power is supplied by terminal 3, rated 16A
5 Start Relay Output 1.5mm2B+ power is supplied by
terminal 3, rated 16A
Connected
to starter
coil
6 Aux. Output 1 1.5mm2B+ power is supplied by
terminal 2, rated 7A
Details see
form 2
7 Aux. Output 2 1.5mm2B+ power is supplied by
terminal 2, rated 7A
8 Aux. Output 3 1.5mm2B+ power is supplied by
terminal 2, rated 7A9 Aux. Output 4 1.5mm2
B+ power is supplied by
terminal 2, rated 7A
-
5/27/2018 APC715_V1.0_en
26/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 26 of 62
Pin FunctionCable
SizeDescription
10 Aux. Output 5 1.5mm2B+ power is supplied by
terminal 2, rated 7A
11 Aux. Output 6 1.5mm2
B+ power is supplied by
terminal 2, rated 7A
12 Charger(D+) 1.0mm2
Connected with charger starters D+ (WL)
terminals. Being hang up If there is no this
terminal.
13 Aux. Input 1 1.0mm2 Ground connected is active (B-)
Details seeform 3
14 Aux. Input 2 1.0mm2 Ground connected is active (B-)
15 Aux. Input 3 1.0mm2 Ground connected is active (B-)
16 Aux. Input 4 1.0mm2 Ground connected is active (B-)
17 Aux. Input 5 1.0mm2 Ground connected is active (B-)
18 Aux. Input 6 1.0mm2 Ground connected is active (B-)
19 Aux. Input 7 1.0mm2 Ground connected is active (B-)
20 Aux. Input 8 1.0mm2 Ground connected is active (B-)
21 Aux. Input 9 1.0mm2 Ground connected is active (B-)
22 Common GND(B-) 1.0mm2(B-) has already connected
innerly.
23Gearbox Magnetic
Pickup 10.5mm2
Connected with Gearbox Speed Sensor,
shielding line is recommended. (B-) has
already connected with speed sensor 2
innerly.24
Gearbox Magnetic
Pickup 2
25Magnetic Pickup
GND
(B-) has already connected with ground
innerly.
26Engine
Magnetic Pickup 20.5mm2
Connected with Engine Speed Sensor,
shielding line is recommended. (B-) has
already connected with speed sensor 2
innerly.27
Engine
Magnetic Pickup 1
28 Battery 2 Volt 1.0mm2 Connected with positive of battery 2.
29
Aux. Output 7 1.5mm2
Normally close output, rated 7A
Details see
form 2
30 Public points of relay31 Normally open output, rated 7A
32
Aux. Output 8 1.5mm2
Normally close output, rated 7A
33 Public points of relay
34 Normally open output, rated 7A
35
Aux. Output 9 1.5mm2
Normally close output, rated 7A
36 Public points of relay
37 Normally open output, rated 7A
38
Aux. Output 10 1.5mm2
Normally close output, rated 7A
39 Public points of relay40 Normally open output, rated 7A
-
5/27/2018 APC715_V1.0_en
27/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 27 of 62
Pin FunctionCable
SizeDescription
41 GOV B2+ 0.5mm2120k resistance had been connected to
GOV B+ innerly.
42 GOV B1+ 0.5mm2 2-core shielding wire is recommended, its
GOV end earthed.43 GOV A+ 0.5mm2
44 ECU CAN L 0.5mm2Impedance-120 shielding wire is
recommended, its single-end earthed.45 ECU CAN H 0.5mm2
46 ECU CAN COM /
47 NC Not connect.
48Outlet Pressure
Sensor1.0mm2 Connect to outlet pressure sensor
49 Aux. sensor 6 1.0mm2Spare sensor of pump unit
Details see
form 4
50 Aux. sensor 5 1.0mm2
51 Sensor COM 3 1.0mm2Public terminal of sensor, (B-)
has already connected.
52 Aux. sensor 4 1.0mm2
Spare sensor of pump unit53 Aux. sensor 3 1.0mm2
54 Aux. sensor 2 1.0mm2
55 Sensor COM 2 1.0mm2Public terminal of sensor, (B-)
has already connected.
56 Aux. sensor 1 1.0mm2 Spare sensor of engine
57
Oil pressure
sensor 1.0mm
2
Connected to oil pressure sensor
58Temperature
sensor1.0mm2 Connected to temperature sensor
59 Fuel level sensor 1.0mm2 Connected to fuel level sensor
60 Sensor COM 11.0mm2 Public terminal of sensor, (B-) has already
connected.
61 RS485 /Impedance-120 shielding wire is
recommended, its single-end earthed.62 RS485+ 0.5mm2
63 RS485- 0.5mm2
NOTE:USB ports in controller rear panel are programmable parameter ports, user
can directly configure controller via PC in stop mode.
-
5/27/2018 APC715_V1.0_en
28/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 28 of 62
7 DEFINITION AND RANGE OF PARAMETERS
7.1 PARAMETER CONTENTS AND RANGE (TABLE 1)
No. Items Parameter Default Description
Timer Setting
1 Start Delay (0-3600)s 1Time from remote start signal is
active to start the pump unit.
2 Stop Delay (0-3600)s 1Time from remote stop signal is
deactivated to stop the pump unit.
3Preheat
Delay(0-3600)s 0
Time of pre-powering heat plug
before starter is powered up.
4Cranking
Time(3-60)s 8 Time of starter power up
5 Crank RestTime
(3-60)s 10 The waiting time before secondpower up when engine start fail.
6Safety On
Delay(0-3600)s 10
Alarms for low oil pressure, high
temperature, under speed, under
frequency/voltage, charge fail are
inactive.
7Start Idle
Time(0-3600)s 0
Idle running time of the pump unit
when starting.
8
Warming Up
Time (0-3600)s 10
Warming time between the pump
unit take load and high speedrunning.
9Cooling
Time(0-3600)s 10
Radiating time before stop the pump
unit, after it unloads.
10Stop Idle
Time(0-3600)s 0
Idle running time when pump unit
stop.
11
ETS
Solenoid
Hold
(0-3600)s 20Stop electromagnets power on time
when pump unit is stopping.
12Fail to Stop
Delay(0-3600)s 0
Time between ending of pump unitidle delay and stopped when ETS
time is set as 0;
Time between ending of ETS hold
delay and stopped when ETS Hold
output time is not 0.
13After Stop
Time(0-3600)s 0
Time between pump unit stopped
and standby.
Engine Setting
1 Engine Type (0-39) 0
Default: Conventional genset (not
J1939)
When connected to J1939 engine,
-
5/27/2018 APC715_V1.0_en
29/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 29 of 62
No. Items Parameter Default Description
choose the corresponding type.
2Flywheel
Teeth
(10-300) 118
Tooth number of the engine, for
judging of starter separation
conditions and inspecting of engine
speed. See the following Installation
Instruction.
3 Rated Speed (0-6000)RPM 1500Offer standard to judge
over/under/loading speed.
4Speed on
Load(0-1000)% 90%
Setting value is percentage of rated
speed. Controller detects when it is
ready to load. It wont enter into
normal running process when speed
is lower than loading speed.
5Loss ofSpeed
Signal
(0-3600)s 5Time from detecting speed is 0 to
confirm the action.
6
Loss of
Speed
Action
(0-1) 0 0:Warn; 1:Shutdown
7Over Speed
Shutdown(0-1000)% 114%
Setting value is percentage of rated
speed and delay value can be set.8
Under
SpeedShutdown
(0-1000)% 80%
9Over Speed
Warn(0-1000)% 110% Setting value is percentage of rated
speed. Delay value and return value
can be set.10Under
Speed Warn(0-1000)% 86%
11
Battery 1
Rated
Voltage
(0-60.0)V 24.0Standard for detecting over/under
voltage of battery.
12 Battery 1Over Volts
(0-1000)% 120% Setting value is percentage of rated
voltage of battery. Delay value &
return value can be set.13Battery 1
Under Volts(0-1000)% 85%
14
Battery 2
Rated
Voltage
(0-60.0)V 24.0Standard for detecting over/under
voltage of battery.
15Battery 2
Over Volts(0-1000)% 120% Setting value is percentage of rated
voltage of battery. Delay value &
return value can be set.16 Battery 2Under Volts
(0-1000)% 85%
17 Charge Alt (0-60.0)V 8.0 In normal running, when charger
-
5/27/2018 APC715_V1.0_en
30/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 30 of 62
No. Items Parameter Default Description
Fail D+(WL) voltage under this value,
charge failure alarms.
18Start
Attempts
(1-10) times 3
Max. Crank times of crank attempts.
When reach this number, controller
will send start failure signal.
19Crank
Disconnect(0-2) 2
See form 5.
There are 3 conditions of
disconnecting starter with engine.
Each condition can be used alone
and simultaneously to separating the
start motor and genset as soon as
possible.
20DisconnectEngine
Speed
(0-1000)% 24%
Setting value is percentage of rated
speed. When engine speed is higherthan the set value, starter will be
disconnected. See the following
Installation Instruction.
21Disconnect
Oil Pressure(0-1000)kPa 200
When generator oil pressure is
higher than the set value, starter will
be disconnected. See the following
Installation Instruction.
22 After UnloadIdle
(0-1) 0
0: Disable1: Enable Active when
system is in manual mode. After startthe unit, it is enter into idle running
when the unit is not on-load.
Module Setting
1Power on
Mode(0-2) 0
0: Stop mode 1: Manual mode 2:
Auto mode
2Module
Address(1-254) 1
Controllers address during remote
sensing.
3 Stop Bits (0-1) 0 0: 2 stop bits; 1: 1 stop bit
4 Language (0-2) 0 0: Simplified Chinese 1: English2: Others
5 Password (0-65535) 00318For entering advanced parameters
setting.
Scheduling And Maintenance Setting
1Scheduled
Run(0-1) 0 0: Disable1: Enable
2Scheduled
Not Run(0-1) 0 0: Disable1: Enable
3 Maintenance (0-1) 0 0: Disable
1: EnableAnalog Sensors Setting
Temperature Sensor
-
5/27/2018 APC715_V1.0_en
31/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 31 of 62
No. Items Parameter Default Description
1 Curve Type (0-15) 7 SGX. See form 5.
2Open Circuit
Action(0-2) 0 0: Warn; 1: Shutdown; 2: No action
3High Temp.
Shutdown(0~300)C 98
Shutdown when external sensor
temperature is higher than this
value. Detecting only after safety
delay is over. The delay value can
be set.
4High Temp.
Warn(0~300)C 95
Warn when external sensor
temperature is higher than this
value. Detecting only after safety
delay is over. The delay value and
return value can be set.
5 Low Temp.Warn
(0-1) 0 0: Disable1: Enable
6Custom
Curve
Users should set the corresponding
curve when select resistor curve
type or current curve type.
Oil Pressure Sensor
1 Curve Type (0-15) 7 SGX. See form 5.
2Open Circuit
Action(0-2) 0 0: Warn; 1: Shutdown; 2: No action
3Low OP
Shutdown(0-1000)kPa 103
Shutdown when external oilpressure is lower than this value.
Detecting only after safety delay is
over. The delay value can be set.
4Low OP
Warn(0-1000)kPa 124
Warn when external oil pressure is
higher than this value. Detecting
only after safety delay is over. The
delay value and return value can be
set.
5Custom
Curve
Users should set the correspondingcurve when select resistor curve
type or current curve type.
Liquid Level Sensor
1 Curve Type (0-15) 4 SGH. See form 5.
2Open Circuit
Action(0-2) 0 0:Warn; 1:Shutdown; 2:No action
3Low Level
Warn
(0-1000)% 10
Warn when external level is lower
than this value. It is detecting all the
time. The delay value and returnvalue can be set.
4 Custom Users should set the corresponding
-
5/27/2018 APC715_V1.0_en
32/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 32 of 62
No. Items Parameter Default Description
Curve curve when select resistor curve
type or current curve type.
Flexible Sensor 1~6
1
Flexible
Sensor
Setting
(0-1) 0
0: Disable1: Enable (can be set as
temperature/oil pressure/liquid lever
sensor)
2 Curve Type Depends on sensor type.
3Open Circuit
Action(0-2) 0 0:Warn; 1:Shutdown; 2:No action
4High
Shutdown(0-9000) 100
Shutdown when external sensor
value is higher than this value. The
delay value and warn enable can
be set.
5Low
Shutdown(0-9000) 10
Shutdown when external sensor
value is lower than this value. The
delay value and warn enable can
be set.
6 High Warn (0-9000) 90
Warn when external sensor value is
higher than this value. The delay
value, warn enable and return
value can be set.
7 Low Warn (0-9000) 20
Warn when external sensor value is
lower than this value. The delayvalue, warn enable and return
value can be set.
8Custom
Curve
Users should set the corresponding
curve when select resistor curve
type or current curve type.
Outlet Pressure Sensor
1 Curve Type (0-15) 2
2Open Circuit
Action
(0-2) 1 0:Warn; 1:Shutdown; 2:No action
3High
Shutdown(0-9000)% 120
Shutdown when external sensor
value is higher than this value. The
delay value and warn enable can
be set.
4Low
Shutdown(0-9000)% 10
Shutdown when external sensor
value is lower than this value. The
delay value and warn enable can
be set.
5 High Warn (0-9000)% 110Warn when external sensor value ishigher than this value. The delay
value, warn enable and return
-
5/27/2018 APC715_V1.0_en
33/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 33 of 62
No. Items Parameter Default Description
value can be set.
6 Low Warn (0-9000)% 20
Warn when external sensor value is
lower than this value. The delay
value, warn enable and return
value can be set.
7Custom
Curve
Users should set the corresponding
curve when select resistor curve
type or current curve type.
8Rated Outlet
Pressure(0-9000)kPa 1000
Set the outlet ports rated working
pressure of pump unit.
9Static
Pressure(0-9000)kPa 0
Set the outlet ports static pressure
of pump unit.
10
Flow
Function (0-1) 0 0: Disable
1: Enable
11 Rated Flow (0-10000)m/h 1000 Pump units rated working pressure.
12Over Flow
Warn(0-1000)% 110
During normal running process, it
will initiated a warning alarm signal
when flow value has exceed the set
value. The delay value, warn
enable and return value can be set.
13Over Flow
Shut (0-1000)% 120
During normal running process, it
will initiate a shutdown alarm signal
when flow value has exceeded theset value. The warn enable and
delay value can be set.
14 Flow CurveDifferent outlet pressures
correspond to different flow value.
Flexible Input Ports
Flexible Input Port 1
1Contents
Setting(0-53) 28 Remote start (on load). See form 3.
2 Active Type (0-1) 0 0: Closed to active 1: Open toactive
Flexible Input Port 2
1Contents
Setting(0-53) 26
High temperature shutdown.
See form 3.
2 Active Type (0-1) 00: Closed to active 1: Open to
active
Flexible Input Port 3
1Contents
Setting
(0-53) 27Low oil pressure shutdown.
See form 3.
2 Active Type (0-1) 00: Closed to active 1: Open to
active
-
5/27/2018 APC715_V1.0_en
34/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 34 of 62
No. Items Parameter Default Description
Flexible Input Port 4
1Contents
Setting(0-53) 0
User defined.
See form 3.
2 Active Type (0-1) 0
0: Closed to active 1: Open to
active
3 Arming (0-3) 20: From safety on 1: From starting
2: Always 3:Never
4Active
Actions(0-4) 0
0: Warn; 1: Shutdown; 2: Trip
Shutdown 3: Fault Idle 4: Indication
5 Active Delay (0-20.0)s 2.0Time from detecting active to
confirm.
6 Description User defined.
Flexible Input Port 5
1Contents
Setting(0-53) 0
User defined.
See form 3.
2 Active Type (0-1) 00: Closed to active 1: Open to
active
3 Arming (0-3) 20: From safety on 1: From starting
2: Always 3:Never
4Active
Actions(0-4) 0
0: Warn; 1: Shutdown; 2: Trip
Shutdown 3: Fault Idle 4: Indication
5 Active Delay (0-20.0)s 2.0
Time from detecting active to
confirm.6 Description User defined.
Flexible Input Port 6
1Contents
Setting(0-53) 0 User defined. See form 3.
2 Active Type (0-1) 00: Closed to active 1: Open to
active
3 Arming (0-3) 20: From safety on 1: From starting
2: Always 3:Never
4 ActiveActions
(0-4) 1 0: Warn; 1: Shutdown; 2: TripShutdown 3: Fault Idle 4: Indication
5 Active Delay (0-20.0)s 2.0Time from detecting active to
confirm.
6 Description User defined.
Flexible Input Port 7
1Contents
Setting(0-53) 5 Lamp Test. See form 3.
2 Active Type (0-1) 00: Closed to active 1: Open to
activeFlexible Input Port 8~9
-
5/27/2018 APC715_V1.0_en
35/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 35 of 62
No. Items Parameter Default Description
1Contents
Setting(0-53) 0 User defined. See form 3.
2 Active Type (0-1) 00: Closed to active 1: Open to
active
3 Arming (0-3) 00: From safety on 1: From starting
2: Always 3:Never
4Active
Actions(0-4) 0
0: Warn; 1: Shutdown; 2: Trip
Shutdown 3: Fault Idle 4: Indication
5 Active Delay (0-20.0)s 2.0Time from detecting active to
confirm.
6 Description User defined.
Flexible Output Ports
Flexible Output Port 1
1Contents
Setting(0-239) 1
User defined period output (default
output is in preheating) See form 4.
2 Active Type (0-1) 00:Normally open; 1:Normally
close
Flexible Output Port 2
1Contents
Setting(0-239) 35 Idle speed control. See form 4.
2 Active Type (0-1) 0 0:Normally open; 1:Normally close
Flexible Output Port 3
1ContentsSetting
(0-239) 29 On-load control. See form 4.
2 Active Type (0-1) 0 0:Normally open; 1:Normally close
Flexible Output Port 4
1Contents
Setting(0-239) 31 Reserved. See form 4.
2 Active Type (0-1) 0 0:Normally open; 1:Normally close
Flexible Output Port 5
1
Contents
Setting (0-239) 38 ETS solenoid hold. See form 4.2 Active Type (0-1) 0 0:Normally open; 1:Normally close
Flexible Output Port 6
1Contents
Setting(0-239) 48 Common alarm. See form 4.
2 Active Type (0-1) 0 0:Normally open; 1:Normally close
Flexible Output Port 7~10
1Contents
Setting(0-239) 0 Not used. See form 4.
2 Active Type (0-1) 0 0:Normally open; 1:Normally closeGOV Setting
-
5/27/2018 APC715_V1.0_en
36/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 36 of 62
No. Items Parameter Default Description
1Adjust
Speed Type(0-2) 2
0Not Used; 1Relay Adjust Speed
2GOV Adjust Speed
2GOV Output
Reverse(0-1) 0 0Disable1Enable.
3GOV Center
Voltage SW1(0-10.0) 0 Default central voltage: 0V
4GOV Voltage
Range SW2(0-10.0) 2.0 Default volt. range: (-2.5~+2.5)V
5 GOV Gain (0-100) 20 GOV gain control
6GOV
Stability(0-100) 20 GOV stability control
7
Relay Adjust
Speed Dead
Band
(0-10.0)% 1.0
GOV relay control8
GOV Relay
Gain(0-100)% 10
9GOV Relay
Stability(0.05-1.60)s 0.10
10GOV Relay
Response(0.25-4.00) 0.5
Pump Unit Setting
1Speed
Enabled(0-1) 0 0Disable1Enable.
2Flywheel
Teeth(1-300) 118 Tooth number of the engine.
3 Rated Speed (0-6000)RPM 500Offer standard to judge over/under
speed.
4Over Speed
Shut(0-1000)% 114%
Setting value is percentage of rated
speed and delay value can be set.5
Under
Speed Shut(0-1000)% 80%
6 Over SpeedWarn
(0-1000)% 110% Setting value is percentage of rated
speed. Delay value and return value
can be set.7Under
Speed Warn(0-1000)% 86%
-
5/27/2018 APC715_V1.0_en
37/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 37 of 62
7.2 PROGRAMMABLE OUTPUT 1-5 (TABLE 2)
No. Type Description
0 Not Used
1 Custom Period 1
Details of function description please
see the following.
2 Custom Period 23 Custom Period 3
4 Custom Period 4
5 Custom Period 5
6 Custom Period 6
7 Custom Combined 1
8 Custom Combined 2
9 Custom Combined 3
10 Custom Combined 4
11 Custom Combined 512 Custom Combined 6
13 Reserved
14 Reserved
15 Reserved
16 Reserved
17 Air Flap
Action when over speed shutdown and
emergence stop. It can close the air
inflow to stop the engine as soon as
possible.
18 Audible Alarm
Action when warning or shutdown
occurs. Can be connected annunciator
externally. When alarm muteinput port
is active, the alarm will be prohibit.
19 Louver ControlAction in genset starting and disconnect
when genset stopped completely.
20 Fuel Pump ControlIt is controlled by fuel pump of level
sensors limited threshold.
21 Heater Control It is controlled by heating of temperaturesensors limited threshold.
22 Cooler ControlIt is controlled by cooler of temperature
sensors limited threshold.
23Oil Pre-supply Actions in period of cranking to safety
run.
24 Reserved
25 Pre-LubricateActions in period of pre-heating to safety
run.
26 Remote PC Output This port is controlled by RS485communication (PC).
27 Reserved
-
5/27/2018 APC715_V1.0_en
38/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 38 of 62
28 Reserved
29 On-load OutputControl generator to take load or off
load.
30 Reserved
31 Reserved
32 Reserved
33 Crank RelayAction when genset is starting and
disconnect when crank successful.
34 Fuel RelayAction when genset is starting and
disconnect when stop is completed.
35 Idle Control
Used for engine which has idles. Close
before starting and open in warming up
delay; Close during stopping idle
process and open when stop is
completed.
36 Raise Speed
Action in warming up delay and be
controlled by GOV in normal running
process.
37 Drop Speed
Action between the period from stop
idleto failed to stopand be controlled
by GOV in normal running process.
38 ETS Control
Used for engines with ETS
electromagnet. Close when stop idle is
over and open when pre-set ETSdelayis over.
39 Pulse Drop speed
Active 0.1s when controller enter into
stop idle, used for control part of ECU
dropping to idle speed (temporary
reserved).
40 ECU StopSuitable for engines which fitted with
ECU; used for control ECU stop.
41 ECU Power Supply
Suitable for engines which fitted with
ECU; used for control ECU powersupply.
42 Pulse raise speed
Active 0.1s when controller enter into
warming up delay; used for control part
of ECU raising to normal speed
(temporary reserved).
43 Crank SuccessClose when detects a successful start
signal.
44 Reserved
45 Reserved46 Reserved
47 Start Battery Cycle During cranking process, start battery
-
5/27/2018 APC715_V1.0_en
39/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 39 of 62
will be switchover circularly if multiple
crank is needed.
48 Common AlarmAction when pump unit common
warning, common shutdown alarm.
49 Common Trip Action when common trip alarm.
50 Common Shutdown Action when common shutdown alarm.
51 Common Fault Idle Alarm Action when fault idle alarm.
52 Common Warn Alarm Action when common warning alarm.
53 Reserved
54 Battery 1 High VoltsAction when battery 1 over voltage
warning alarm.
55 Battery 1 Low VoltsAction when battery 1 low voltage
warning alarm.
56
Charge Alt Fail Action when charge failure warning
alarms.
57 Reserved
58 Reserved
59 Reserved
60 ECU Warn Indicate ECU sends a warning signal.
61 ECU Shutdown Indicate ECU sends a shutdown signal.
62 ECU COM FailIndicate controller cannot communicate
with ECU.
63 Reserved
64 Reserved
65 Reserved
66 Reserved
67 Reserved
68 Reserved
69 Aux Input 1 Active Action when input port 1 is active.
70 Aux Input 2 Active Action when input port 2 is active.
71 Aux Input 3 Active Action when input port 3 is active.
72 Aux Input 4 Active Action when input port 4 is active.
73 Aux Input 5 Active Action when input port 5 is active.
74 Aux Input 6 Active Action when input port 6 is active.
75 Aux Input 7 Active Action when input port 7 is active.
76 Aux Input 8 Active Action when input port 8 is active.
77 Aux Input 9 Active Action when input port 9 is active.
78~96 Reserved
97 Battery 2 High VoltsAction when battery 2 over voltage
warning alarm.
98 Battery 2 Low Volts
Action when battery 2 low voltage
warning alarm.
99 Emergency Stop Action when emergency stop alarm.
-
5/27/2018 APC715_V1.0_en
40/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 40 of 62
100 Failed To Start Action when failed start alarm.
101 Failed To Stop Action when failed stop alarm.
102 Under Speed Warn Action when under speed alarm.
103 Under Speed Shutdown Action when under speed shuts down.
104 Over Speed Warn Action when over speed warning.
105Over Speed Shutdown
Action when over speed shutdown
alarm.
106~138 Reserved
139 High Temp Warn Action when high temperature warning.
140 Low Temp Warn Action when low temperature warning.
141High Temp Shutdown
Action when hi-temperature Shutdown
alarm.
142 Reserved
143 Low OP Warn Action when low oil pressure warning.
144 Low OP Shutdown Action when low oil pressure shutdown.
145 OP Sensor OpenAction when oil pressure sensor is open
circuit.
146 Reserved
147 Low Level Warn Action when low oil level warning.
148 Over Flow Shutdown Action when low oil pressure shutdown.
149 Over Flow Warn Action when low oil pressure warning.
150 Config 1 High Warn
151 Config 1 Low Warn
152 Config 1 High Shut
153 Config 1 Low Shut
154 Config 2 High Warn
155 Config 2 Low Warn
156 Config 2 High Shut
157 Config 2 Low Shut
158 Config 3 High Warn
159 Config 3 Low Warn
160 Config 3 High Shut
161 Config 3 Low Shut
162 Config 4 High Warn
163 Config 4 Low Warn
164 Config 4 High Shut
165 Config 4 Low Shut
166 Config 5 High Warn
167 Config 5 Low Warn
168 Config 5 High Shut
169 Config 5 Low Shut
170 Config 6 High Warn
171 Config 6 Low Warn
-
5/27/2018 APC715_V1.0_en
41/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 41 of 62
172 Config 6 High Shut
173 Config 6 Low Shut
174 Outlet High Warn
175 Outlet Low Warn
176 Outlet High Shut
177 Outlet Low Shut
178~229 Reserved
230 Stop Mode Action in stop mode.
231 Manual Mode Action in Manual mode.
232 Reserved
233 Auto Mode Action in Auto mode.
234 Loading Status Indicate the system is on-load.
235~239 Reserved
7.2.1 Custom Period Output
Defined Period output is composed by 2 parts, period output S1 and condition output S2.
While S1 and S2 are TRUEsynchronously, OUTPUT;
While S1 or S2 isFALSE, NOT OUTPUT.
Period output S1, can set pump units one or more period output freely, can set the
delayed time and output time after enter into period.
Condition output S2; can set as any conditions in output ports.
NOTE:when delay time and output time both are 0 in period output S1, it is TRUE in
this period.
Example,
Output period: start
Delay output time: 2s
Output time: 3s
Condition output contents: output port 1 is active
Close when condition output active/inactive: close when active (disconnect when
inactive);
Output port 1 active, after enter starts time and delay 2s, this defined period output is
outputting, after 3s, stop outputting;
Output port 1 inactive, defined output period is not outputting.
-
5/27/2018 APC715_V1.0_en
42/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 42 of 62
7.2.2 Custom Combined Output
Defined combination output is composed by 3 parts, condition output S1 or S2 and
condition output S3.
S1 or S2 is TRUE, while S3 is TRUE, Defined combination output is outputting;
S1 and S2 are FALSE, or S3 is FALSE, Defined combination output is not outputting.
NOTE: S1, S2, S3 can be set as any contents except for defined combination
output in the output setting.
NOTE: 3 parts of defined combination output (S1, S2, S3) couldnt include or
recursively include themselves.
Example,
Contents of probably condition output S1: output port 1 is active;
Close when probably condition output S1 is active /inactive: close when active
(disconnect when inactive);
Contents of probably condition output S2, output port 2 is active;
Close when probably condition output S2 is active /inactive: close when active
(disconnect when inactive);
Contents of probably condition output S3: output port 3 is active;
Close when probably condition output S3 is active /inactive: close when active
(disconnect when inactive);
When input port 1 active or input port 2 active, if input port 3 is active, Defined
combination output is outputting; If input port 3 inactive, Defined combination output is
not outputting;
When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not,
Defined combination output is not outputting.
-
5/27/2018 APC715_V1.0_en
43/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 43 of 62
7.3 DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS(ALL ACTIVE WHEN CONNECT TO GRAND (B-))
No. Type Description
0 Users Configured
Including following functions,
Indication: indicate only, not warning or shutdown.Warning: warn only, not shutdown.
Shutdown: alarm and shutdown immediately
Never: input inactive.
Always: input is active all the time.
From crank: detecting as soon as start.
From safety on: detecting after safety on run delay.
1 Reserved
2 Alarm MuteCan prohibit Audible Alarm output when input is
active.
3 Reset Alarm Can reset shutdown alarm when input is active.
4 Reserved
5 Lamp TestAll LED indicators are illuminating when input is
active.
6 Panel Lock
All buttons in panel is inactive except
and there is in the left of first
row in LCD when input is active.
7 Reserved
8 Idle Control Mode Under speed protection is inactive.
9 Inhibit Auto Stop
In Auto mode, during pump unit normal running,
when input is active, inhibit pump unit shutdown
automatically.
10 Inhibit Auto StartIn Automode, inhibit pump unit start automatically
when input is active.
11 Inhibit ScheduledIn Auto mode, inhibit pump unit scheduled run
when input is active.
12 Reserved
13 Loading Status Connect to Aux. Points of clutch.
14 Load Inhibit Prohibit pump unit onload when input is active.
15 Reserved
16 Reserved
17 Reserved
18 Reserved
19 Reserved
20 Reserved
21 Inhibit Alarm Stop All shutdown alarms are prohibited exceptemergence stop.(Means battle mode)
22 Aux Instrument Mode All outputs are prohibited in this mode.
-
5/27/2018 APC715_V1.0_en
44/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 44 of 62
23 Reserved
24 Reset MaintenanceController will reset maintenance time and date as
default when input is active.
25 Reserved
26 Aux. High Temp Connect to sensor digital input.
27 Aux. Low OP Connect to sensor digital input.
28Remote Start
(On Load)
InAutomode, when the input is active, pump unit
can be started automatically and take load after
pump unit normal running.
29Remote Start
(Off Load)
In Auto mode, when the input is active, pump unit
can be started automatically and NOT take load
after pump unit normal running.
30 Aux. Manual Start
In Manual mode, when the input is active, pump
unit will start automatically; when input inactive,
pump unit will stop automatically.
31 Reserved
32 Remote Stop
InAutomode, when the input is active as well as
remote start signal is inactive, pump unit can be
stopped automatically.
33 Simulate Stop key An external button (not self-locking) can be
connected and pressed as simulate panel.34 Simulate Manual key
35 Reserved
36 Simulate Auto key An external button (not self-locking) can be
connected and pressed as simulate panel.37 Simulate Start key
38 Simulate Load key
39~5
1Reserved
52 Speed Raise Input An external button (not self-locking) can be
connected and control GOV manually.53 Speed Drop Input
-
5/27/2018 APC715_V1.0_en
45/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 45 of 62
7.4 SELECTION OF SENSORS
No. Description Remark
1Temperature
Sensor
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve3 VDO
4 CURTIS
5 VOLVO-EC
6 DATCON
7 SGX
8 SGD
9 SGH
10 PT100
11~15 Reserved
Defined resistances
range is (0~6)K,
default is SGX sensor.
2 Pressure Sensor
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 VDO 10Bar
4 CURTIS
5 VOLVO-EC
6 DATCON 10Bar
7 SGX
8 SGD
9 SGH10~15 Reserved
Defined resistances
range is (0~6)K,
default is SGX sensor.
3Fuel Level
Sensor
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 SGD
4 SGH
5~15 Reserved
Defined resistances
range is (0~6)K,
default is SGH sensor.
Note: User should take the controller apart to change the jumper hat from resistor
side to current side if your pump unit fitted with 4~20mA sensor.
-
5/27/2018 APC715_V1.0_en
46/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 46 of 62
7.5 CONDITIONS OF CRANK DINSCONNECT SELECTION
No. Setting description
0 Oil pressure
1 Engine Speed
2 Oil pressure + Engine SpeedNOTE:
1. There are 3 conditions to make starter disconnected with engine. Engine speed and
oil pressure both can be used separately. We recommend that oil pressure should
be using with engine speed together, in order to make the starter motor is separated
with engine immediately and can check crank disconnect exactly.
2. Engine speed is the magnetic equipment which be installed in starter for detecting
flywheel teeth.3. When set as engine speed, must ensure that the number of flywheel teeth is as same
as setting, otherwise, over speed shutdown or under speed shutdown may be
caused.
4. If pump unit without engine speed sensor, please dont select corresponding items,
otherwise, start fail or loss speed signal maybe caused.
5. If genset without oil pressure sensor, please dont select corresponding items.
-
5/27/2018 APC715_V1.0_en
47/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 47 of 62
8 PARAMETERS SETTING
1. Please change the controller parameters when generator is in standby mode only
(e. g. Crank disconnect conditions selection, digital input, digital output, various
delay), otherwise, shutdown and other abnormal conditions may occurs.
2. Maximum set value must over minimum set value in case that the condition of too
high as well as too low will happen.
3. When setting the warning alarm, please set the correct return value; otherwise,
maybe there is abnormal alarm. When setting the maximum value, the return value
must less than set value; When setting the minimum value, the return value must
over than set value.
4. Digital input could not be set as same items; otherwise, there are abnormal
functions. However, the digital output can be set as same items.
-
5/27/2018 APC715_V1.0_en
48/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 48 of 62
9 SENSOR SELECT
1) When reselect sensors, the sensor curve will be transferred into the standard value.
For example, if temperature sensor is SGX (120C resistor type), its sensor curve
is SGX (120C resistor type); if select the SGD (120C resistor type), the
temperature sensor curve is SGD curve.
2) When there is difference between standard sensor curves and using sensor, user
can adjust it in curve type.
3) When input the sensor curve, X value (resistor) must be input from small to large,
otherwise, mistake occurs.
4) If select sensor type as None, sensor curve is not working and LCD does not
display the sensor information.
5) If there is alarm switch only for the select sensor, user must set the sensor as
None, otherwise, maybe shutdown or warning occurs.
6) The headmost or backmost values in the vertical coordinates can be set as same
as below,
Common unitconversion table
N/m2 (pa) kgf/cm2 bar (p/in2.psi)
1Pa 1 1.02x105 1x10
5 1.45x104
1kgf/cm2 9.8x104 1 0.98 14.2
1bar 1x105 1.02 1 14.5
1psi 6.89x103 7.03x102 6.89x10
2 1
-
5/27/2018 APC715_V1.0_en
49/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 49 of 62
10 TYPICAL APPLICATION
-
5/27/2018 APC715_V1.0_en
50/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 50 of 62
11 INSTALLATION
Controller is panel built-in design; it is fixed by clips when installed.
1) Battery Voltage Input
NOTE: APC715 controller can suit for widely range of battery voltage
DC(8~35)V. Negative of battery must be connected with the engine shell soundly.
The diameter of wire which from power supply to battery must be over 2.5mm 2. If
floating charge configured, please firstly connect output wires of charger to
batterys positive and negative directly, then, connect wires from batterys positive
and negative to controllers corresponding input ports in order to prevent charge
disturbing the controllers normal working.2) Speed Sensor Input
NOTE: Speed sensor is the magnetic equipment which be installed in starter
and for detecting flywheel teeth. Its connection wires to controller should apply for
2 cores shielding line. The shielding layer should connect to shielding GND
terminal in controller while another side is hanging in air. The else two signal wires
are connected to MP1 and MP2 terminals, moreover, MP2 has already connected
to B- innerly. The output voltage of speed sensor should be within AC(1~24)V
(effective value) during the full speed. AC12V is recommended (in rated speed).
When install the speed sensor, let the sensor is spun to contacting flywheel first,
then, port out 1/3 lap, and lock the nuts of sensor at last.
3) Output And Expansion Relay
NOTE: All outputs of controller are relay contact output type. If need to expand
the relays, please add freewheel diode to both ends of expand relays coils (when
coils of relay has DC current) or, add resistance-capacitance return circuit (when
coils of relay has AC current), in order to prevent disturbance to controller or
others equipment.
-
5/27/2018 APC715_V1.0_en
51/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 51 of 62
12 CONNECTIONS OF CONTROLLER WITH J1939 ENGINE
12.1 CUMMINS ISB/ISBE
Terminals of controller Connector B Remark
Fuel relay output 39
Start relay output -Connect with starter coil
directly
Auxiliary output port
1
Expand 30A relay, battery
voltage of 01,07,12,13 is
supplied by relay
ECU power
Set Auxiliary output 1 as ECU
power
Terminals of controller 9 pins connector Remark
CAN GND SAE J1939 shield
CAN communication shielding
line(connect with ECU terminalonly)
CAN(H) SAE J1939 signalImpedance 120 connecting
line is recommended.
CAN(L) SAE J1939 returnImpedance 120 connecting
line is recommended.
Engine type:Cummins ISB
12.2 CUMMINS QSL9
Suitable for CM850 engine control modeTerminals of controller 50 pins connector Remark
Fuel relay output 39
Start relay output - Connect to starter coil directly
Terminals of controller 9 pins connector Remark
CAN GND SAE J1939 shield-E
CAN communication shielding
line(connect with ECU terminal
only)
CAN(H) SAE J1939 signal-CImpedance 120 connecting
line is recommended.
CAN(L) SAE J1939 return-DImpedance 120 connecting
line is recommended.
Engine type: Cummins-CM850
-
5/27/2018 APC715_V1.0_en
52/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 52 of 62
12.3 CUMMINS QSM11(IMPORT)
It is suitable for CM570 engine control module. Engine type is QSM11 G1, QSM11 G2.
Terminals of controller C1 connector Remark
Fuel relay output 5&8
Outside expand relay, when
fuel output, making port 5 andport 8 of C1 be connected
Start relay output - Connect to starter coil directly
Terminals of controller 3 pins data link connector Remark
CAN GND C
CAN communication shielding
line(connect with ECU
terminal only)
CAN(H) A
Impedance 120 connecting
line is recommended.
CAN(L) BImpedance 120 connecting
line is recommended.
Engine type: Cummins ISB
12.4 CUMMINS QSX15-CM570
It is suitable for CM570 engine control module. Engine type is QSX15.
Terminals of controller 50 pins connector Remark
Fuel relay output 38 Oil spout switch
Start relay output - Connect to starter coil directly
Terminals of controller 9 pins connector Remark
CAN GND SAE J1939 shield-E
CAN communication shielding
line(connect with ECU
terminal only)
CAN(H) SAE J1939 signal-CImpedance 120 connecting
line is recommended.
CAN(L) SAE J1939 return-D
Impedance 120 connecting
line is recommended.
Engine type: Cummins QSX15-CM570
-
5/27/2018 APC715_V1.0_en
53/62
APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 53 of 62
12.5 CUMMINS GCS-MODBUS
It is suitable for GCS engine control module. Use RS485-MODBUS to read information
of engine. Engine types are QSX15, QST30, QSK23 / 45/60/78 and so on.
Terminals of controller D-SUB connector 06 Remark
Fuel relay output 5&8
Outside expand relay, whenfuel output, making port 05
and 08 of the connector 06 be
connected.
Start relay output - Connect to starter coil directly
Terminals of controller D-SUB connector 06 Remark
RS485 GND 20
CAN communication shielding
line(connect with ECU
terminal only)
RS485+ 21Impedance 120 connecting
line is recommended.
RS485- 18Impedance 120 connecting
line is recommended.
Engine type: Cummins QSK-MODBUS, Cummins QST-MODBUS, Cummins
QSX-MODBUS
12.6 CUMMINS QSM11
Terminals of controller OEM connector of engine RemarkFuel relay output 38
Start relay output - Connect with starter coil
directly
CAN GND - CAN communication shielding
line(connect with controllers
this terminal only)
CAN(H) 46 Impedance 120 connecting
line is recommended.
CAN(L) 37 Impedance 120 connectingline is recommended.
Engine type: com