  • 5/27/2018 APC715_V1.0_en

    1/62

    APC715 Pump Unit Controller

    USER MANUAL

    Smartgen Technology

  • 5/27/2018 APC715_V1.0_en

    2/62

    Chinese trademark

    English trademark

    Smartgenmake your generatorsmartSmartgen Technology Co., Ltd.

    No. 28 Jinsuo RoadZhengzhou

    Henan Province

    P. R. China

    Tel:+86-371-67988888/67981888

    +86-371-67991553/67992951

    +86-371-67981000(overseas)

    Fax:0086-371-67992952

    Web:http://www.smartgen.com.cn

    http://www.smartgen.cn

    Email:[email protected]

    All rights reserved. No part of this publication may be reproduced in any material form

    (including photocopying or storing in any medium by electronic means or other) without

    the written permission of the copyright holder.

    Smartgen Technology reserves the right to change the contents of this document

    without prior notice.

    http://www.smartgen.com.cn/http://www.smartgen.cn/mailto:[email protected]:[email protected]://www.smartgen.cn/http://www.smartgen.com.cn/
  • 5/27/2018 APC715_V1.0_en

    3/62

    Version

    Date Version Note

    2013-08-28 1.0 Original release.

    This manual is suitable for APC715 pump unit controller only.

    Clarification of notation used within this publication.

    SYMBOL INSTRUCTION

    NOTE

    Highlights an essential element of a procedure to ensure

    correctness.

    CAUTION!

    Indicates a procedure or practice, which, if not strictly observed,

    could result in damage or destruction of equipment.

    WARNING!

    Indicates a procedure or practice, which could result in injury to

    personnel or loss of life if not followed correctly.

  • 5/27/2018 APC715_V1.0_en

    4/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 4 of 62

    CONTENTS

    1 OVERVIEW........................................................................................ 62 PERFORMANCE AND CHARACTERISTICS .................................... 73 SPECIFICATION ................................................................................ 94 OPERATION .................................................................................... 10

    4.1 INDICATOR LIGHT ......................................................................................... 104.2 PUSHBUTTONS ............................................................................................. 114.3 LCD DISPLAY ................................................................................................. 12

    4.3.1 MAIN DISPLAY................................................................................... 124.3.2 USER MENU AND PARAMETERS SETTING MENU ........................ 13

    4.4 AUTO START/STOP OPERATION ................................................................. 164.5 MANUAL START/STOP OPERATION ............................................................ 174.6 ON-LOAD CONTROL PROCESS ................................................................... 184.7 ADJUST SPEED CONTROL .......................................................................... 19

    5 PROTECTION ................................................................................. 205.1 WARNINGS .................................................................................................... 205.2 SHUTDOWN ALARM ..................................................................................... 225.3 TRIP SHUTDOWN ......................................................................................... 245.4 FAULT IDLE .................................................................................................... 24

    6 CONNECTIONS .............................................................................. 257 DEFINITION AND RANGE OF PARAMETERS ................................ 28

    7.1 PARAMETER CONTENTS AND RANGE (TABLE 1) ...................................... 287.2 PROGRAMMABLE OUTPUT 1-5 (TABLE 2) .................................................. 37

    7.2.1 Custom Period Output ........................................................................ 417.2.2 Custom Combined Output .................................................................. 42

    7.3 DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS (ALL ACTIVEWHEN CONNECT TO GRAND (B-)) ...................................................................... 437.4 SELECTION OF SENSORS ........................................................................... 457.5 CONDITIONS OF CRANK DINSCONNECT SELECTION ............................. 46

    8 PARAMETERS SETTING ................................................................ 479 SENSOR SELECT ........................................................................... 4810 TYPICAL APPLICATION .................................................................. 4911 INSTALLATION ................................................................................ 5012 CONNECTIONS OF CONTROLLER WITH J1939 ENGINE ............ 51

    12.1CUMMINS ISB/ISBE ....................................................................................... 5112.2CUMMINS QSL9 ............................................................................................ 51

  • 5/27/2018 APC715_V1.0_en

    5/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 5 of 62

    12.3CUMMINS QSM11(IMPORT) ......................................................................... 5212.4CUMMINS QSX15-CM570 ............................................................................. 5212.5CUMMINS GCS-MODBUS ............................................................................. 5312.6

    CUMMINS QSM11 .......................................................................................... 53

    12.7CUMMINS QSZ13 .......................................................................................... 5412.8DETROIT DIESEL DDEC III / IV ..................................................................... 5412.9DEUTZ EMR2 ................................................................................................. 5512.10 JOHN DEERE .......................................................................................... 5512.11 MTU MDEC .............................................................................................. 5512.12 MTU ADEC(SMART MODULE) ................................................................ 5612.13 MTU ADEC(SAM MODULE) ..................................................................... 5612.14 PERKINS .................................................................................................. 5712.15 SCANIA .................................................................................................... 5712.16 VOLVO EDC3 ........................................................................................... 5812.17 VOLVO EDC4 ........................................................................................... 5812.18 VOLVO-EMS2 ........................................................................................... 5912.19 YUCHAI .................................................................................................... 5912.20 WEICHAI .................................................................................................. 60

    13 USB ................................................................................................. 6114 FAULT FINDING .............................................................................. 62

  • 5/27/2018 APC715_V1.0_en

    6/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 6 of 62

    1 OVERVIEW

    APC715 Pump Unit Controller is designed for pump systems which controlled by

    engine. It allows automatic start/stop, data measurement, alarm protection as well as

    remote control, remote measurement and remote communication function. It fit with

    LCD display, optional languages interface, and it is reliable and easy to use.

    Utilizing the GOV (Engine Speed Governor) control function, the controller is able to

    stabilize the outlet pressure via GOV.

    APC715 Pump Unit Controlleralso monitors the engine, indicating the operational

    status and fault conditions accurately. When abnormal condition occurs, it can protect

    the unit automatically; simultaneously the exact failure mode information is indicated

    by the LCD display on the front panel. SAE J1939 interface enables the controller to

    communicate with various ECU (ENGINE CONTROL UNIT) which fitted with J1939

    interface.

    APC715 Pump Unit Controlleradopt powerful 32-bit microprocessor technology with

    precision parameters measuring, fixed value adjustment, time setting and set value

    adjusting and etc. The majority of parameters can be configured from front panel and

    all the parameters can be set using PC (via USB port) and can be adjusted and

    monitored with the help of RS485 ports. It can be widely used in a number of pump

    control system with compact structure, simple connections and high reliability

  • 5/27/2018 APC715_V1.0_en

    7/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 7 of 62

    2 PERFORMANCE AND CHARACTERISTICS

    With ARM-based 32-bit SCM, highly integrated hardware, new reliability level.

    480x272 pixel, 4.3 inches LCD with backlight, multilingual interface (including

    English, Chinese or other languages) which can be chosen at the site, making

    commissioning convenient for factory personnel.

    Improved LCD wear-resistance and scratch resistance due to hard screen acrylic.

    Silicon panel and pushbuttons for better operation in high/low temperature

    environment

    RS485 communication port enabling remote control, remote measuring, remote

    communication via ModBus protocol.

    Equipped with CANBUS port and can communicate with J1939 genset. Not only

    can you monitoring frequently-used data (such as water temperature, oil pressure,

    engine speed, fuel consumption and so on) of ECU machine, but also control start,

    stop, raising speed and speed droop via CANBUS port.

    10 analog sensors; sensors can switch between resistor type and current type using

    jumper.

    More kinds of curves of temperature, oil pressure, fuel level can be used directly

    and users can define the sensor curves by themselves.

    Precision measure and display parameters about Engine and pump unit.

    Protection: automatic start/stop of the pump unit, perfect fault indication and

    protection function.

    All output ports are relay-out;

    Parameter setting: parameters can be modified and stored in internal FLASH

    memory and cannot be lost even in case of power outage; most of them can be

    adjusted using front panel of the controller and all of them can be modified using

    PC via USB or RS485 ports.

    Multiple crank disconnect conditions (speed sensor, oil pressure) are optional;

    Widely power supply range DC(8~35)V, suitable to different starting battery voltage

    environment;

    Event log, real-time clock, scheduled start & stop pump unit (can be set as start

    pump unit once a day/week/month whether with load or not);

    Accumulative total run time and total electric energy of A and B. Users can reset it

    as 0 and re-accumulative the value which make convenience to users to count the

  • 5/27/2018 APC715_V1.0_en

    8/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 8 of 62

    total value as their wish.

    Can control engine heater, cooler and fuel pump.

    With maintenance function. Actions (warning/shutdown) can be set when

    maintenance time out;

    All parameters used digital adjustment, instead of conventional analog modulation

    with normal potentiometer, more reliability and stability;

    Waterproof security level IP55 due to rubber seal installed between the controller

    enclosure and panel fascia;

    Metal fixing clips enable perfect performance in high temperature environment;

    Modular design, anti-flaming ABS plastic enclosure, pluggable connection terminals

    and embedded installation way; compact structure with easy mounting.

  • 5/27/2018 APC715_V1.0_en

    9/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 9 of 62

    3 SPECIFICATION

    Items Contents

    Working Voltage DC8. 0V to 35. 0V, Continuous Power Supply.

    Overall Consumption

  • 5/27/2018 APC715_V1.0_en

    10/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 10 of 62

    4 OPERATION

    4.1 INDICATOR LIGHT

    Note: Selected indicators description:

    Warning indicator and Alarm indicator:

    Alarm Type Warning Indicator Alarm Indicator

    Warning Slow flashing Slow flashing

    Shutdown Alarm Off Fast flashing

    Running indicator: illuminated from crank successful to ETS while off during other

    periods.

  • 5/27/2018 APC715_V1.0_en

    11/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 11 of 62

    4.2 PUSHBUTTONS

    Stop

    Stop running pump unit in Auto/Manual mode;Reset alarm in stop mode; Lamp test (press atleast 3 seconds); During stopping process, pressthis button again to stop pump unit immediately.

    Start Start pump unit in Manual/Test mode.

    Manual ModePress this key and controller enters in Manualmode.

    Auto Mode Press this key and controller enters in Automode.

    MuteAlarming sound off; If there is alarm, pressing thebutton at least 3 seconds can reset this alarm.

    LoadCan control the clutch to switch on or off in manual

    mode.

    Adjust Speed Enter/Exit the speed adjust menu.

    Up/Increase1) Screen scroll; 2) Up cursor and increasevalue in setting menu.

    Down/Decrease1) Screen scroll; 2) Down cursor and decreasevalue in setting menu.

    Left1) Screen scroll; 2) Left move cursor in settingmenu.

    Right1) Screen scroll; 2) Right move cursor in settingmenu.

    Set/Confirm

    1. Enter intohelpinterface;2. Pressing and holding for more than 3 seconds

    enters parameter configuration menu;3. In settings menu confirms the set value.

    Exit1. Returns to the main menu;2. In settings menu returns to the previous menu.

    NOTE: In manual mode, pressing and simultaneously will force

    generator to crank. Successful start will not be judged according to crank disconnect

    conditions, operator will have to crank the starter motor manually; when operator

    decides that the engine has fired, he/she should release the button and start relay will

    be deactivated, safety on delay will start.

    WARNING: Default password is 00318, user can change it in case of others

    change the advanced parameters setting. Please clearly remember the password after

    changing. If you forget it, please contact Smartgen services and send all information in

    the controller page of ABOUTto us.

  • 5/27/2018 APC715_V1.0_en

    12/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 12 of 62

    4.3 LCD DISPLAY

    4.3.1 MAIN DISPLAY

    Main screen is divided into left and right separate viewing areas, use to select a

    viewing area; the selected area is marked with in its upper left corner. Both

    viewing areas show pages; use to scroll the pages and to scroll the

    screen.

    Engine, including as below,

    Engine status, engine temperature, engine oil pressure, fuel level, Configurable Sensor 1,

    battery voltage, charger voltage, accumulated run time, accumulated start times.

    NOTE:If connected with J1939 engine via CANBUS port, this page also includes:

    coolant pressure, coolant level, fuel temperature, fuel pressure, inlet temperature,exhaust temperature, turbo pressure, fuel consumption, total fuel consumption and so

    on. (Different engine with different parameters)

    Pump Unit

    Outlet pressure, pump flow, pump head, config. sensor 2~6 (can be set as

    temperature sensor, pressure sensor or level sensor)

    FormulaPump Head = ( Outlet pressure - Static Pressure)/0.0098.

    Alarm:

    Display all warnings, shutdown alarms, trip shutdown alarms and the corresponding

    information.

    NOTE:For ECU alarms and shutdown alarms, if the alarm information is displayed,

    check engine according to it, otherwise, please check the manual of generator according

    to SPN alarm code.

    Event log

    Records all start/stop events (shutdown alarm, trip shutdown alarm, manual/auto start or

    stop) and the real time when alarm occurs.

    Others, including,

    Time and Date, maintenance due time, input/output ports status.

    About,including,

    Issue time of software and hardware version, product PD number.

  • 5/27/2018 APC715_V1.0_en

    13/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 13 of 62

    Status, including as below,

    Engine speed, battery voltage 1, engine status

    Indicator Status

    Green Normal status; No alarm

    Yellow Warning or idle speed alarm occurs.

    Red Shutdown alarm occurs.

    Example:

    Engine Pump

    On load

    Manual Mode

    Normal Running

    Outlet Pressure

    1.0MPa 10Bar 145psi

    Config Sensor 2

    45 113Engine Temp.85 185 Config Sensor 3

    465kPa 4.65Bar 67.4psiOil Pressure

    465kPa 4.65Bar

    67.4psiConfig Sensor 4

    100%

    1500rpm 27.6V At Rest

    Engine Pump

    Fuel Level

    100%

    Config Sensor 5

    55 131

    Config Sensor 1

    85 185

    Config Sensor 6

    60 140

    Battery Voltage 1

    27.6V

    Pump Flow

    200m/h

    Battery Voltage 2

    27.6V

    Pump Head

    102m

    1500rpm 27.6V Emergency Stop

    4.3.2 USER MENU AND PARAMETERS SETTING MENU

    Press and hold for more than 3 seconds to enter into user menu;

    Parameter

    After entering the correct password (factory default password is 00318), you can enter

    into parameter settings interface.

    Language

    Selectable Chinese, English and others (default: Espanol)

  • 5/27/2018 APC715_V1.0_en

    14/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 14 of 62

    Commissioning

    On load, off load or custom commissioning can be chosen. Custom commissioning

    can configure on load or not during commissioning, when to commissioning and select

    the mode after commissioning (manual mode, auto mode and stop mode).

    Clear usersaccumulation

    Can clear User Acc. Run A, User Acc. Run B and Engine Acc. Run time.

    Parameter setting including as following,

    Timer settings

    Engine settings

    Analog sensor settings (Engine temperature, engine oil pressure, fuel level, config.

    1~6, outlet pressure)

    Input port settings

    output port settings

    GOV settings

    Pump settings

    Module settings

    Scheduling and maintenance settings

    Example,

    Return >Start Delay

    >Stop Delay

    >Preheat Delay

    >Cranking Time

    > Crank Rest Time

    > Safety On Time

    > Start Idle Time

    > Warming Up Time

    > Cooling Time

    > Stop Idle Time> ETS Hold Time

    Form1: Use to scroll settings,

    to enter settings (form2), to

    exit settings menu.

    Timers

    Engine

    Temp. Sensor

    OP Sensor

    Level Sensor

    Config Sensor 1

    Config Sensor 2

    Config Sensor 3

    Config Sensor 4Config Sensor 5

  • 5/27/2018 APC715_V1.0_en

    15/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 15 of 62

    Return Start Delay Form 2: Use to scroll

    settings, to enter settings (form3),

    to return to previous menu. (form

    1).

    Timers >Stop Delay

    >Preheat Delay

    >Cranking Time

    >Crank Rest Time

    >Safety On Time

    >Start Idle Time

    >Warming Up Time

    >Cooling Time

    >Stop Idle Time

    >ETS Hold Time

    Engine

    Temp. Sensor

    OP Sensor

    Level Sensor

    Config Sensor 1

    Config Sensor 2

    Config Sensor 3

    Config Sensor 4

    Config Sensor 5

    Return >Start Delay

    >Stop Delay

    >Preheat Delay

    Form 3: Use to scroll

    settings, to enter settings (form4),

    to return to previous menu. (form

    1).

    Timers

    Engine

    Temp. Sensor

    OP Sensor

    Level Sensor

    Config Sensor 1

    Config Sensor 2

    Config Sensor 3

    Config Sensor 4

    Config Sensor 5

    >Cranking Time

    >Crank Rest Time

    >Safety On Time

    >Start Idle Time

    >Warming Up Time

    >Cooling Time

    >Stop Idle Time

    >ETS Hold Time

    >Start Delay

    >Stop Delay

    >Preheat Delay

    Form 4Press to enter settings

    (form 5), to return to previous

    menu. (form 6).

    00008

    Cranking Time

    >Crank Rest Time

    >Safety On Time

    >Start Idle Time

    >Warming Up Time

    >Cooling Time

    >Stop Idle Time

    >ETS Hold Time

  • 5/27/2018 APC715_V1.0_en

    16/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 16 of 62

    >Start Delay

    >Stop Delay

    >Preheat Delay

    00008 Form5: Press to change cursor

    position, are used for

    changing cursor value, Confirm

    setting (form 4), exit setting (form

    4).

    Cranking Time

    >Crank Rest Time

    >Safety On Time

    >Start Idle Time

    > Warming Up Time

    >Cooling Time

    >Stop Idle Time

    >ETS Hold Time

    >Start Delay

    >Stop Delay

    >Preheat Delay

    00008

    Form 6: are used for

    changing the setting contents.

    Confirm setting (form 4), to return

    to previous menu. (form 1).

    Cranking Time

    >Crank Rest Time

    >Safety On Time

    >Start Idle Time

    > Warming Up Time

    >Cooling Time

    >Stop Idle Time

    >ETS Hold Time

    >Wait Stop Time

    NOTE:Pressing can exit setting directly during setting.

    4.4 AUTO START/STOP OPERATION

    Auto mode is selected by pressing the button; a LED besides the button will

    illuminate to confirm the operation.

    Automatic Start Sequence:

    1. When Remote Start is active, Start Delaytimer is initiated;2. When start delay is over, preheat relay energizes (if configured), preheat delay XX s

    information will be displayed on LCD;

    3. After the above delay, the Fuel Relay is energized, and then one second later, the

    Start Relay is engaged. The engine is cranked for a pre-set time. If the pump unit fails

    to fire during this cranking attempt then the fuel relay and start relay are disengaged

    for the pre-set rest period; crank rest time begins and wait for the next crank

    attempt.4. Should this start sequence continue beyond the set number of attempts, the start

  • 5/27/2018 APC715_V1.0_en

    17/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 17 of 62

    sequence will be terminated, the Fail to Start fault will be displayed on LCD.

    5. In case of successful crank attempt, the Safety On timer is activated, allowing Low

    Oil Pressure, High Temperature, Under speed and Charge Alternator Failure inputs

    to stabilize without triggering the fault. As soon as this delay is over, start idle delay

    is initiated (if configured).

    6. During start idle delay, under speed alarm is inhibited. When this delay is over,

    warming up delay is initiated (if configured).

    7. After the warming up delay, If engine speed has reached on-load requirements,

    then the pump close relay will be energized; pump uint will take load; pump unit will

    enter into Normal Running status.

    NOTE: In case of Remote Start (off Load), the procedure is the same, except for

    step NO. 7: the pump close relay will NOT be energised, generator will NOT accept load.

    Automatic Stop Sequence,

    1) When the Remote Start signal is deactivated while the Remote Stop signal is

    active, the Stop Delay is initiated.

    2) Once this stop delay has expired, the Pump Unit Breaker will open and the Cooling

    Delay is then initiated. Should the Remote Start signal be re-activated during the

    cooling down period, the unit will return running status. Once the Cooling Delay

    expires, the Stop Idle delay is initiated.

    3) During Stop Idle Delay (if configured), idle relay is energized.

    4) ETS Solenoid Hold begins, ETS relay is energized while fuel relay is

    de-energized and complete stop is detected automatically

    5) "Fail to Stop Delay" begins, complete stop is detected automatically.

    6) Pump unit is placed into its After stop timeafter its complete stop. Otherwise, fail

    to stop alarm is initiated and the corresponding alarm information is displayed on

    LCD (If pump unit stopped successfully after Failed to Stopalarm, it will enter

    After stop time and remove alarm).

    7) Pump unit is placed into its standby mode after its After stop time.

    4.5 MANUAL START/STOP OPERATION

    1 Manual Start: Manual mode is selected by pressing the button; a LED

    besides the button will illuminate to confirm the operation; then press

    button to start the unit; can automatically detect crank successful, and unitaccelerates to high-speed running automatically.

  • 5/27/2018 APC715_V1.0_en

    18/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 18 of 62

    When AfterUnload Idleis enabled, the unit is idle running when crank succeed;

    unit accelerates to high-speed running automatically and take load after press

    key by manual.

    With high temperature, low oil pressure and over speed during pump unit running,controller can protect it to stop quickly (please refer to No.2~7 of Auto start

    operation for detail procedures).

    2 MANUAL STOP: Press can stop the running pump unit. (please refer to

    No.2~7 of Auto stop operation for detail procedures).

    NOTE: In manual mode, users can control the pump unit on load or off load via

    Loadkey.

    4.6 ON-LOAD CONTROL PROCESS

    When controller is in Manual mode, manual control will be executed.

    Users can control the pump unit on load or off load by pressing key. The pump unit

    will unload automatically when it is stopped.

    If AfterUnload Idleis selected Disable

    Start the pump unit in manual mode and press key during the normal running

    process, then the generator will take load; press key again, the generator will

    unload.

    If AfterUnload Idleis selected Enable

    Start the pump unit in manual mode and it enters into idle running process. The pump

    unit will not enter into normal running status until key is pressed and it will take

    load as soon as the on-load requirements have reached.

    When the pump unit is normal running with load, press key once again will lead to

    the units offload (i.e. load relay deactivated); then the cooling delaywill be initiated.

    Once this has expired, the unit will enter into idle running status.

    When controller is in Auto mode, auto control will be executed.

    The pump unit will take load automatically when it is normal running and the on-load

    requirements have reached while unload automatically when it is stopped.

  • 5/27/2018 APC715_V1.0_en

    19/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 19 of 62

    4.7 ADJUST SPEED CONTROL

    Users can set the outlet pressure as the rated value simply by adjusting the engine

    speed. The Adjust Speed Controlwas divided into auto control and manual control.

    Manual Adjust Speed:Adjust Speed mode is selected by pressing the button; In

    this interface, users can adjust speed using navigational button: , manual adjust

    speed; , auto adjust speed; , manual raise speed; , manual drop speed. ,

    manual raise speedand , manual drop speedbuttons are active only when pump

    unit is normal running under Manual Adjust Speedmode.

    Auto Adjust Speed: Under this mode, during the unit is normal running, the

    controller will adjust the outlet pressure to rated speed and maintain its steady

    automatically according to the set value.

    The Auto Adjust Speedwas divided into relay adjust speed, GOV adjust speed and

    CAN adjust speed.

    Relay Adjust Speed: Control the engine servo motor simply by using speed raise relay

    and speed drop relay.

    GOV Adjust Speed: Control the electronic speed regulator simply by using GOV

    analog signal. Users should set parameters according to the actual situation as

    different regulators have different parameters.

    CAN Adjust Speed: Control the ECU engine speed simply by using CAN interface.

    Parameters setting and speed adjustment method are same as GOV. Some ECU

    engine has CAN adjust speed function, e.g. EMS2. Other engine types need the

    above two ways to adjust speed.

  • 5/27/2018 APC715_V1.0_en

    20/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 20 of 62

    5 PROTECTION

    5.1 WARNINGS

    Warnings are not shutdown alarms and do not affect the operation of the genset.

    Warning does not lead to shutdown, and when warning condition is no longer present,

    warning alarm will be cleared automatically. Warning types are as follows:

    No. Type Description

    1 Over Speed

    When the controller detects that the engine speed has

    exceeded the pre-set value, it will initiate a warning

    alarm.

    2 Under Speed

    When the controller detects that the engine speed has

    fallen below the pre-set value, it will initiate a warning

    alarm.

    3Loss of Speed

    Signal

    When the controller detects that the engine speed is 0

    and the action select Warn, it will initiate a warning

    alarm.

    4 Fail To StopAfter fail to stop delay, if unit is not stop completely, it

    will initiate a warning alarm.

    5 Charge Alt Fail

    When the controller detects that charger voltage has

    fallen below the pre-set value, it will initiate a warning

    alarm.

    6 Battery 1 OverVoltage

    When the controller detects that battery 1 voltage hasexceeded the pre-set value, it will initiate a warning

    alarm.

    7Battery 1 Under

    Voltage

    When the controller detects that battery 1 voltage has

    fallen below the pre-set value, it will initiate a warning

    alarm.

    8 Maintenance DueWhen maintenance countdown time is 0 and the action

    select Warn, it will initiate a warning alarm.

    9 ECU WarnIf an error message is received from ECU via J1939, it

    will initiate a warning alarm.

    10

    Temperature

    Sensor Open

    Circuit

    When the controller detects that the temperature

    sensor is open circuit and the action select Warn, it

    will initiate a warning alarm.

    11 High Temperature

    When the controller detects that engine temperature

    has exceeded the pre-set value, it will initiate a warning

    alarm.

    12 Low Temperature

    When the controller detects that engine temperature

    has fallen below the pre-set value, it will initiate a

    warning alarm.

    13Oil Pressure Open

    Circuit

    When the controller detects that the oil pressure sensor

    is open circuit and the action select Warn, it will

  • 5/27/2018 APC715_V1.0_en

    21/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 21 of 62

    No. Type Description

    initiate a warning alarm.

    14 Low Oil Pressure

    When the controller detects that the oil pressure has

    fallen below the pre-set value, it will initiate a warning

    alarm.

    15 Level Sensor Open

    When the controller detects that the level sensor is

    open circuit and the action select Warn, it will initiate a

    warning alarm.

    16 Low Fuel LevelWhen the controller detects that the fuel level has fallen

    below the pre-set value, it will initiate a warning alarm.

    17Flexible Sensor

    1~6 Open

    When the controller detects that the sensor is open

    circuit and the action select Warn, it will initiate a

    warning alarm.

    18

    Flexible Sensor

    1~6 High

    When the controller detects the sensor value is higher

    than the max. set value, it will initiate a warning alarm.

    19Flexible Sensor

    1~6 Low

    When the controller detects the sensor value is lower

    than the min. set value, it will initiate a warning alarm.

    20Digital Input 1~9

    Warn

    When the action of digital input port select Warnand

    active, it will initiate a warning alarm.

    21Battery 2 Over

    Voltage

    When the controller detects that battery 2 voltage has

    exceeded the pre-set value, it will initiate a warning

    alarm.

    22Battery 2 Under

    Voltage

    When the controller detects that battery 2 voltage has

    fallen below the pre-set value, it will initiate a warningalarm.

    23Outlet Pressure

    Sensor Open

    When the controller detects that the outlet pressure

    sensor is open circuit and the action select Warn, it

    will initiate a warning alarm.

    24Outlet Pressure

    Sensor High

    When the controller detects the sensor value is higher

    than the max. set value, it will initiate a warning alarm.

    25Outlet Pressure

    Sensor Low

    When the controller detects the sensor value is lower

    than the min. set value, it will initiate a warning alarm.

    26 Over Flow Warn When the controller detects the flow value is higherthan the max. set value, it will initiate a warning alarm.

    27Gearbox Over

    speed

    When the controller detects that the gearbox speed has

    exceeded the pre-set value, it will initiate a warning

    alarm.

    28Gearbox Under

    speed

    When the controller detects that the gearbox speed has

    fallen below the pre-set value, it will initiate a warning

    alarm.

    29End Of The

    Mandate

    When the mandate time has expired and the action

    select Warn, it will initiate a warning alarm.

  • 5/27/2018 APC715_V1.0_en

    22/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 22 of 62

    5.2 SHUTDOWN ALARM

    When controller detects shutdown alarm, it will send signal to open breaker and stop the

    unit. Shutdown alarm must be cleared manually and the fault removed to reset the

    module. Shutdown alarm types are as follows:

    NO. Type Description

    1 Emergency StopWhen the controller detects an emergency stop alarm

    signal, it will initiate a shutdown alarm.

    2 Over Speed

    When the controller detects that the generator speed

    has exceeded the pre-set value, it will initiate a

    shutdown alarm.

    3 Under Speed

    When the controller detects that the generator speed

    has fallen below the pre-set value, it will initiate a

    shutdown alarm.

    4Loss of Speed

    Signal

    When the controller detects that the engine speed is 0

    and the action select Warn, it will initiate a shutdown

    alarm.

    5 Maintenance DueWhen maintenance countdown time is 0 and the action

    select Shutdown, it will initiate a shutdown alarm.

    6 ECU ShutdownIf shutdown alarm signal is received from ECU via

    J1939, it will initiate a shutdown alarm.

    7 ECU Fail

    If the module does not detect the J1939 data, it will

    initiate a shutdown alarm.

    8

    Temperature

    Sensor Open

    Circuit

    When the controller detects that the temperature

    sensor is open circuit and the action select Shutdown,

    it will initiate a shutdown alarm.

    9 High Temperature

    When the controller detects that engine temperature

    has exceeded the pre-set value, it will initiate a

    shutdown alarm.

    10Oil Pressure Open

    Circuit

    When the controller detects that the oil pressure sensor

    is open circuit and the action select Shutdown, it will

    initiate a shutdown alarm.

    11 Low Oil Pressure

    When the controller detects that the oil pressure has

    fallen below the pre-set value, it will initiate a shutdown

    alarm.

    12Level Sensor Open

    Circuit

    When the controller detects that the sensor is open

    circuit and the action select Shutdown, it will initiate a

    shutdown alarm.

    13Flexible Sensor

    1~6 Open

    When the controller detects that the sensor is open

    circuit and the action select Shutdown, it will initiate a

    shutdown alarm.

  • 5/27/2018 APC715_V1.0_en

    23/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 23 of 62

    NO. Type Description

    16Flexible Sensor

    1~6 High

    When the controller detects the sensor value is higher

    than the max. set value, it will initiate a shutdown

    alarm.

    17Flexible Sensor

    1~6 Low

    When the controller detects the sensor value is lower

    than the min. set value, it will initiate a shutdown alarm.

    18Digital Input 1~9

    Shutdown

    When the action of digital input port select Shutdown

    and active, it will initiate a shutdown alarm.

    19Outlet Pressure

    Sensor Open

    When the controller detects that the outlet pressure

    sensor is open circuit and the action select Shutdown,

    it will initiate a shutdown alarm.

    20Outlet Pressure

    Sensor High

    When the controller detects the sensor value is higher

    than the max. set value, it will initiate a shutdown

    alarm.

    21Outlet Pressure

    Sensor Low

    When the controller detects the sensor value is lower

    than the min. set value, it will initiate a shutdown alarm.

    22Over Flow

    Shutdown

    When the controller detects the flow value is higher

    than the max. set value, it will initiate a shutdown

    alarm.

    23Gearbox Over

    speed

    When the controller detects that the gearbox speed has

    exceeded the pre-set value, it will initiate a shutdown

    alarm.

    24Gearbox Under

    speed

    When the controller detects that the gearbox speed hasfallen below the pre-set value, it will initiate a shutdown

    alarm.

    25End Of The

    Mandate

    When the mandate time has expired and the action

    select Shutdown, it will initiate a shutdown alarm.

  • 5/27/2018 APC715_V1.0_en

    24/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 24 of 62

    5.3 TRIP SHUTDOWN

    On initiation of the trip shutdown condition the controller will de-energize the loadoutput

    to remove the load from the unit. Once this has occurred the controller will start the

    Cooling delay and allow the engine to cool before shutting down the engine. Trip

    shutdown alarm must be cleared manually and the fault removed to reset the module.

    Trip shutdown alarm types are as follows:

    NO. Types Description

    1 Maintenance Due

    When maintenance countdown time is 0 and the action

    select Trip Shutdown, it will initiate a trip shutdown

    alarm.

    2 Digital Input 1~9

    When the action of digital input port select Trip

    Shutdown and active, it will initiate a trip shutdown

    alarm.

    5.4 FAULT IDLE

    On initiation of the trip condition the controller will de-energize the loadoutput to remove

    the load from the unit. Once this has occurred the controller will start the Cooling delay

    and allow the engine to cool before idle running process. Fault idle alarm must be

    cleared by pressing Mutebutton more than 3s manually. Fault idle alarm types are as

    follows:

    No. Types Description

    1 Digital Input 1~9When the action of digital input port select Fault idle

    and active, it will initiate a trip shutdown alarm.

  • 5/27/2018 APC715_V1.0_en

    25/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 25 of 62

    6 CONNECTIONS

    APC715 controller back panel is shown below:

    Description of terminal connections:

    Pin FunctionCable

    SizeDescription

    1 B- 2.5mm2 Connected with negative of starter battery.

    2 B+ 2.5mm2

    Connected with positive of starter battery. If

    wire length is over 30m, better to double wires

    in parallel. Max. 20A fuse is recommended.

    3 Emergency Stop 2.5mm2Connected with B+ power supply via

    emergency stop button.

    4 Fuel Relay Output 1.5mm2

    B+ power is supplied by terminal 3, rated 16A

    5 Start Relay Output 1.5mm2B+ power is supplied by

    terminal 3, rated 16A

    Connected

    to starter

    coil

    6 Aux. Output 1 1.5mm2B+ power is supplied by

    terminal 2, rated 7A

    Details see

    form 2

    7 Aux. Output 2 1.5mm2B+ power is supplied by

    terminal 2, rated 7A

    8 Aux. Output 3 1.5mm2B+ power is supplied by

    terminal 2, rated 7A9 Aux. Output 4 1.5mm2

    B+ power is supplied by

    terminal 2, rated 7A

  • 5/27/2018 APC715_V1.0_en

    26/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 26 of 62

    Pin FunctionCable

    SizeDescription

    10 Aux. Output 5 1.5mm2B+ power is supplied by

    terminal 2, rated 7A

    11 Aux. Output 6 1.5mm2

    B+ power is supplied by

    terminal 2, rated 7A

    12 Charger(D+) 1.0mm2

    Connected with charger starters D+ (WL)

    terminals. Being hang up If there is no this

    terminal.

    13 Aux. Input 1 1.0mm2 Ground connected is active (B-)

    Details seeform 3

    14 Aux. Input 2 1.0mm2 Ground connected is active (B-)

    15 Aux. Input 3 1.0mm2 Ground connected is active (B-)

    16 Aux. Input 4 1.0mm2 Ground connected is active (B-)

    17 Aux. Input 5 1.0mm2 Ground connected is active (B-)

    18 Aux. Input 6 1.0mm2 Ground connected is active (B-)

    19 Aux. Input 7 1.0mm2 Ground connected is active (B-)

    20 Aux. Input 8 1.0mm2 Ground connected is active (B-)

    21 Aux. Input 9 1.0mm2 Ground connected is active (B-)

    22 Common GND(B-) 1.0mm2(B-) has already connected

    innerly.

    23Gearbox Magnetic

    Pickup 10.5mm2

    Connected with Gearbox Speed Sensor,

    shielding line is recommended. (B-) has

    already connected with speed sensor 2

    innerly.24

    Gearbox Magnetic

    Pickup 2

    25Magnetic Pickup

    GND

    (B-) has already connected with ground

    innerly.

    26Engine

    Magnetic Pickup 20.5mm2

    Connected with Engine Speed Sensor,

    shielding line is recommended. (B-) has

    already connected with speed sensor 2

    innerly.27

    Engine

    Magnetic Pickup 1

    28 Battery 2 Volt 1.0mm2 Connected with positive of battery 2.

    29

    Aux. Output 7 1.5mm2

    Normally close output, rated 7A

    Details see

    form 2

    30 Public points of relay31 Normally open output, rated 7A

    32

    Aux. Output 8 1.5mm2

    Normally close output, rated 7A

    33 Public points of relay

    34 Normally open output, rated 7A

    35

    Aux. Output 9 1.5mm2

    Normally close output, rated 7A

    36 Public points of relay

    37 Normally open output, rated 7A

    38

    Aux. Output 10 1.5mm2

    Normally close output, rated 7A

    39 Public points of relay40 Normally open output, rated 7A

  • 5/27/2018 APC715_V1.0_en

    27/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 27 of 62

    Pin FunctionCable

    SizeDescription

    41 GOV B2+ 0.5mm2120k resistance had been connected to

    GOV B+ innerly.

    42 GOV B1+ 0.5mm2 2-core shielding wire is recommended, its

    GOV end earthed.43 GOV A+ 0.5mm2

    44 ECU CAN L 0.5mm2Impedance-120 shielding wire is

    recommended, its single-end earthed.45 ECU CAN H 0.5mm2

    46 ECU CAN COM /

    47 NC Not connect.

    48Outlet Pressure

    Sensor1.0mm2 Connect to outlet pressure sensor

    49 Aux. sensor 6 1.0mm2Spare sensor of pump unit

    Details see

    form 4

    50 Aux. sensor 5 1.0mm2

    51 Sensor COM 3 1.0mm2Public terminal of sensor, (B-)

    has already connected.

    52 Aux. sensor 4 1.0mm2

    Spare sensor of pump unit53 Aux. sensor 3 1.0mm2

    54 Aux. sensor 2 1.0mm2

    55 Sensor COM 2 1.0mm2Public terminal of sensor, (B-)

    has already connected.

    56 Aux. sensor 1 1.0mm2 Spare sensor of engine

    57

    Oil pressure

    sensor 1.0mm

    2

    Connected to oil pressure sensor

    58Temperature

    sensor1.0mm2 Connected to temperature sensor

    59 Fuel level sensor 1.0mm2 Connected to fuel level sensor

    60 Sensor COM 11.0mm2 Public terminal of sensor, (B-) has already

    connected.

    61 RS485 /Impedance-120 shielding wire is

    recommended, its single-end earthed.62 RS485+ 0.5mm2

    63 RS485- 0.5mm2

    NOTE:USB ports in controller rear panel are programmable parameter ports, user

    can directly configure controller via PC in stop mode.

  • 5/27/2018 APC715_V1.0_en

    28/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 28 of 62

    7 DEFINITION AND RANGE OF PARAMETERS

    7.1 PARAMETER CONTENTS AND RANGE (TABLE 1)

    No. Items Parameter Default Description

    Timer Setting

    1 Start Delay (0-3600)s 1Time from remote start signal is

    active to start the pump unit.

    2 Stop Delay (0-3600)s 1Time from remote stop signal is

    deactivated to stop the pump unit.

    3Preheat

    Delay(0-3600)s 0

    Time of pre-powering heat plug

    before starter is powered up.

    4Cranking

    Time(3-60)s 8 Time of starter power up

    5 Crank RestTime

    (3-60)s 10 The waiting time before secondpower up when engine start fail.

    6Safety On

    Delay(0-3600)s 10

    Alarms for low oil pressure, high

    temperature, under speed, under

    frequency/voltage, charge fail are

    inactive.

    7Start Idle

    Time(0-3600)s 0

    Idle running time of the pump unit

    when starting.

    8

    Warming Up

    Time (0-3600)s 10

    Warming time between the pump

    unit take load and high speedrunning.

    9Cooling

    Time(0-3600)s 10

    Radiating time before stop the pump

    unit, after it unloads.

    10Stop Idle

    Time(0-3600)s 0

    Idle running time when pump unit

    stop.

    11

    ETS

    Solenoid

    Hold

    (0-3600)s 20Stop electromagnets power on time

    when pump unit is stopping.

    12Fail to Stop

    Delay(0-3600)s 0

    Time between ending of pump unitidle delay and stopped when ETS

    time is set as 0;

    Time between ending of ETS hold

    delay and stopped when ETS Hold

    output time is not 0.

    13After Stop

    Time(0-3600)s 0

    Time between pump unit stopped

    and standby.

    Engine Setting

    1 Engine Type (0-39) 0

    Default: Conventional genset (not

    J1939)

    When connected to J1939 engine,

  • 5/27/2018 APC715_V1.0_en

    29/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 29 of 62

    No. Items Parameter Default Description

    choose the corresponding type.

    2Flywheel

    Teeth

    (10-300) 118

    Tooth number of the engine, for

    judging of starter separation

    conditions and inspecting of engine

    speed. See the following Installation

    Instruction.

    3 Rated Speed (0-6000)RPM 1500Offer standard to judge

    over/under/loading speed.

    4Speed on

    Load(0-1000)% 90%

    Setting value is percentage of rated

    speed. Controller detects when it is

    ready to load. It wont enter into

    normal running process when speed

    is lower than loading speed.

    5Loss ofSpeed

    Signal

    (0-3600)s 5Time from detecting speed is 0 to

    confirm the action.

    6

    Loss of

    Speed

    Action

    (0-1) 0 0:Warn; 1:Shutdown

    7Over Speed

    Shutdown(0-1000)% 114%

    Setting value is percentage of rated

    speed and delay value can be set.8

    Under

    SpeedShutdown

    (0-1000)% 80%

    9Over Speed

    Warn(0-1000)% 110% Setting value is percentage of rated

    speed. Delay value and return value

    can be set.10Under

    Speed Warn(0-1000)% 86%

    11

    Battery 1

    Rated

    Voltage

    (0-60.0)V 24.0Standard for detecting over/under

    voltage of battery.

    12 Battery 1Over Volts

    (0-1000)% 120% Setting value is percentage of rated

    voltage of battery. Delay value &

    return value can be set.13Battery 1

    Under Volts(0-1000)% 85%

    14

    Battery 2

    Rated

    Voltage

    (0-60.0)V 24.0Standard for detecting over/under

    voltage of battery.

    15Battery 2

    Over Volts(0-1000)% 120% Setting value is percentage of rated

    voltage of battery. Delay value &

    return value can be set.16 Battery 2Under Volts

    (0-1000)% 85%

    17 Charge Alt (0-60.0)V 8.0 In normal running, when charger

  • 5/27/2018 APC715_V1.0_en

    30/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 30 of 62

    No. Items Parameter Default Description

    Fail D+(WL) voltage under this value,

    charge failure alarms.

    18Start

    Attempts

    (1-10) times 3

    Max. Crank times of crank attempts.

    When reach this number, controller

    will send start failure signal.

    19Crank

    Disconnect(0-2) 2

    See form 5.

    There are 3 conditions of

    disconnecting starter with engine.

    Each condition can be used alone

    and simultaneously to separating the

    start motor and genset as soon as

    possible.

    20DisconnectEngine

    Speed

    (0-1000)% 24%

    Setting value is percentage of rated

    speed. When engine speed is higherthan the set value, starter will be

    disconnected. See the following

    Installation Instruction.

    21Disconnect

    Oil Pressure(0-1000)kPa 200

    When generator oil pressure is

    higher than the set value, starter will

    be disconnected. See the following

    Installation Instruction.

    22 After UnloadIdle

    (0-1) 0

    0: Disable1: Enable Active when

    system is in manual mode. After startthe unit, it is enter into idle running

    when the unit is not on-load.

    Module Setting

    1Power on

    Mode(0-2) 0

    0: Stop mode 1: Manual mode 2:

    Auto mode

    2Module

    Address(1-254) 1

    Controllers address during remote

    sensing.

    3 Stop Bits (0-1) 0 0: 2 stop bits; 1: 1 stop bit

    4 Language (0-2) 0 0: Simplified Chinese 1: English2: Others

    5 Password (0-65535) 00318For entering advanced parameters

    setting.

    Scheduling And Maintenance Setting

    1Scheduled

    Run(0-1) 0 0: Disable1: Enable

    2Scheduled

    Not Run(0-1) 0 0: Disable1: Enable

    3 Maintenance (0-1) 0 0: Disable

    1: EnableAnalog Sensors Setting

    Temperature Sensor

  • 5/27/2018 APC715_V1.0_en

    31/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 31 of 62

    No. Items Parameter Default Description

    1 Curve Type (0-15) 7 SGX. See form 5.

    2Open Circuit

    Action(0-2) 0 0: Warn; 1: Shutdown; 2: No action

    3High Temp.

    Shutdown(0~300)C 98

    Shutdown when external sensor

    temperature is higher than this

    value. Detecting only after safety

    delay is over. The delay value can

    be set.

    4High Temp.

    Warn(0~300)C 95

    Warn when external sensor

    temperature is higher than this

    value. Detecting only after safety

    delay is over. The delay value and

    return value can be set.

    5 Low Temp.Warn

    (0-1) 0 0: Disable1: Enable

    6Custom

    Curve

    Users should set the corresponding

    curve when select resistor curve

    type or current curve type.

    Oil Pressure Sensor

    1 Curve Type (0-15) 7 SGX. See form 5.

    2Open Circuit

    Action(0-2) 0 0: Warn; 1: Shutdown; 2: No action

    3Low OP

    Shutdown(0-1000)kPa 103

    Shutdown when external oilpressure is lower than this value.

    Detecting only after safety delay is

    over. The delay value can be set.

    4Low OP

    Warn(0-1000)kPa 124

    Warn when external oil pressure is

    higher than this value. Detecting

    only after safety delay is over. The

    delay value and return value can be

    set.

    5Custom

    Curve

    Users should set the correspondingcurve when select resistor curve

    type or current curve type.

    Liquid Level Sensor

    1 Curve Type (0-15) 4 SGH. See form 5.

    2Open Circuit

    Action(0-2) 0 0:Warn; 1:Shutdown; 2:No action

    3Low Level

    Warn

    (0-1000)% 10

    Warn when external level is lower

    than this value. It is detecting all the

    time. The delay value and returnvalue can be set.

    4 Custom Users should set the corresponding

  • 5/27/2018 APC715_V1.0_en

    32/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 32 of 62

    No. Items Parameter Default Description

    Curve curve when select resistor curve

    type or current curve type.

    Flexible Sensor 1~6

    1

    Flexible

    Sensor

    Setting

    (0-1) 0

    0: Disable1: Enable (can be set as

    temperature/oil pressure/liquid lever

    sensor)

    2 Curve Type Depends on sensor type.

    3Open Circuit

    Action(0-2) 0 0:Warn; 1:Shutdown; 2:No action

    4High

    Shutdown(0-9000) 100

    Shutdown when external sensor

    value is higher than this value. The

    delay value and warn enable can

    be set.

    5Low

    Shutdown(0-9000) 10

    Shutdown when external sensor

    value is lower than this value. The

    delay value and warn enable can

    be set.

    6 High Warn (0-9000) 90

    Warn when external sensor value is

    higher than this value. The delay

    value, warn enable and return

    value can be set.

    7 Low Warn (0-9000) 20

    Warn when external sensor value is

    lower than this value. The delayvalue, warn enable and return

    value can be set.

    8Custom

    Curve

    Users should set the corresponding

    curve when select resistor curve

    type or current curve type.

    Outlet Pressure Sensor

    1 Curve Type (0-15) 2

    2Open Circuit

    Action

    (0-2) 1 0:Warn; 1:Shutdown; 2:No action

    3High

    Shutdown(0-9000)% 120

    Shutdown when external sensor

    value is higher than this value. The

    delay value and warn enable can

    be set.

    4Low

    Shutdown(0-9000)% 10

    Shutdown when external sensor

    value is lower than this value. The

    delay value and warn enable can

    be set.

    5 High Warn (0-9000)% 110Warn when external sensor value ishigher than this value. The delay

    value, warn enable and return

  • 5/27/2018 APC715_V1.0_en

    33/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 33 of 62

    No. Items Parameter Default Description

    value can be set.

    6 Low Warn (0-9000)% 20

    Warn when external sensor value is

    lower than this value. The delay

    value, warn enable and return

    value can be set.

    7Custom

    Curve

    Users should set the corresponding

    curve when select resistor curve

    type or current curve type.

    8Rated Outlet

    Pressure(0-9000)kPa 1000

    Set the outlet ports rated working

    pressure of pump unit.

    9Static

    Pressure(0-9000)kPa 0

    Set the outlet ports static pressure

    of pump unit.

    10

    Flow

    Function (0-1) 0 0: Disable

    1: Enable

    11 Rated Flow (0-10000)m/h 1000 Pump units rated working pressure.

    12Over Flow

    Warn(0-1000)% 110

    During normal running process, it

    will initiated a warning alarm signal

    when flow value has exceed the set

    value. The delay value, warn

    enable and return value can be set.

    13Over Flow

    Shut (0-1000)% 120

    During normal running process, it

    will initiate a shutdown alarm signal

    when flow value has exceeded theset value. The warn enable and

    delay value can be set.

    14 Flow CurveDifferent outlet pressures

    correspond to different flow value.

    Flexible Input Ports

    Flexible Input Port 1

    1Contents

    Setting(0-53) 28 Remote start (on load). See form 3.

    2 Active Type (0-1) 0 0: Closed to active 1: Open toactive

    Flexible Input Port 2

    1Contents

    Setting(0-53) 26

    High temperature shutdown.

    See form 3.

    2 Active Type (0-1) 00: Closed to active 1: Open to

    active

    Flexible Input Port 3

    1Contents

    Setting

    (0-53) 27Low oil pressure shutdown.

    See form 3.

    2 Active Type (0-1) 00: Closed to active 1: Open to

    active

  • 5/27/2018 APC715_V1.0_en

    34/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 34 of 62

    No. Items Parameter Default Description

    Flexible Input Port 4

    1Contents

    Setting(0-53) 0

    User defined.

    See form 3.

    2 Active Type (0-1) 0

    0: Closed to active 1: Open to

    active

    3 Arming (0-3) 20: From safety on 1: From starting

    2: Always 3:Never

    4Active

    Actions(0-4) 0

    0: Warn; 1: Shutdown; 2: Trip

    Shutdown 3: Fault Idle 4: Indication

    5 Active Delay (0-20.0)s 2.0Time from detecting active to

    confirm.

    6 Description User defined.

    Flexible Input Port 5

    1Contents

    Setting(0-53) 0

    User defined.

    See form 3.

    2 Active Type (0-1) 00: Closed to active 1: Open to

    active

    3 Arming (0-3) 20: From safety on 1: From starting

    2: Always 3:Never

    4Active

    Actions(0-4) 0

    0: Warn; 1: Shutdown; 2: Trip

    Shutdown 3: Fault Idle 4: Indication

    5 Active Delay (0-20.0)s 2.0

    Time from detecting active to

    confirm.6 Description User defined.

    Flexible Input Port 6

    1Contents

    Setting(0-53) 0 User defined. See form 3.

    2 Active Type (0-1) 00: Closed to active 1: Open to

    active

    3 Arming (0-3) 20: From safety on 1: From starting

    2: Always 3:Never

    4 ActiveActions

    (0-4) 1 0: Warn; 1: Shutdown; 2: TripShutdown 3: Fault Idle 4: Indication

    5 Active Delay (0-20.0)s 2.0Time from detecting active to

    confirm.

    6 Description User defined.

    Flexible Input Port 7

    1Contents

    Setting(0-53) 5 Lamp Test. See form 3.

    2 Active Type (0-1) 00: Closed to active 1: Open to

    activeFlexible Input Port 8~9

  • 5/27/2018 APC715_V1.0_en

    35/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 35 of 62

    No. Items Parameter Default Description

    1Contents

    Setting(0-53) 0 User defined. See form 3.

    2 Active Type (0-1) 00: Closed to active 1: Open to

    active

    3 Arming (0-3) 00: From safety on 1: From starting

    2: Always 3:Never

    4Active

    Actions(0-4) 0

    0: Warn; 1: Shutdown; 2: Trip

    Shutdown 3: Fault Idle 4: Indication

    5 Active Delay (0-20.0)s 2.0Time from detecting active to

    confirm.

    6 Description User defined.

    Flexible Output Ports

    Flexible Output Port 1

    1Contents

    Setting(0-239) 1

    User defined period output (default

    output is in preheating) See form 4.

    2 Active Type (0-1) 00:Normally open; 1:Normally

    close

    Flexible Output Port 2

    1Contents

    Setting(0-239) 35 Idle speed control. See form 4.

    2 Active Type (0-1) 0 0:Normally open; 1:Normally close

    Flexible Output Port 3

    1ContentsSetting

    (0-239) 29 On-load control. See form 4.

    2 Active Type (0-1) 0 0:Normally open; 1:Normally close

    Flexible Output Port 4

    1Contents

    Setting(0-239) 31 Reserved. See form 4.

    2 Active Type (0-1) 0 0:Normally open; 1:Normally close

    Flexible Output Port 5

    1

    Contents

    Setting (0-239) 38 ETS solenoid hold. See form 4.2 Active Type (0-1) 0 0:Normally open; 1:Normally close

    Flexible Output Port 6

    1Contents

    Setting(0-239) 48 Common alarm. See form 4.

    2 Active Type (0-1) 0 0:Normally open; 1:Normally close

    Flexible Output Port 7~10

    1Contents

    Setting(0-239) 0 Not used. See form 4.

    2 Active Type (0-1) 0 0:Normally open; 1:Normally closeGOV Setting

  • 5/27/2018 APC715_V1.0_en

    36/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 36 of 62

    No. Items Parameter Default Description

    1Adjust

    Speed Type(0-2) 2

    0Not Used; 1Relay Adjust Speed

    2GOV Adjust Speed

    2GOV Output

    Reverse(0-1) 0 0Disable1Enable.

    3GOV Center

    Voltage SW1(0-10.0) 0 Default central voltage: 0V

    4GOV Voltage

    Range SW2(0-10.0) 2.0 Default volt. range: (-2.5~+2.5)V

    5 GOV Gain (0-100) 20 GOV gain control

    6GOV

    Stability(0-100) 20 GOV stability control

    7

    Relay Adjust

    Speed Dead

    Band

    (0-10.0)% 1.0

    GOV relay control8

    GOV Relay

    Gain(0-100)% 10

    9GOV Relay

    Stability(0.05-1.60)s 0.10

    10GOV Relay

    Response(0.25-4.00) 0.5

    Pump Unit Setting

    1Speed

    Enabled(0-1) 0 0Disable1Enable.

    2Flywheel

    Teeth(1-300) 118 Tooth number of the engine.

    3 Rated Speed (0-6000)RPM 500Offer standard to judge over/under

    speed.

    4Over Speed

    Shut(0-1000)% 114%

    Setting value is percentage of rated

    speed and delay value can be set.5

    Under

    Speed Shut(0-1000)% 80%

    6 Over SpeedWarn

    (0-1000)% 110% Setting value is percentage of rated

    speed. Delay value and return value

    can be set.7Under

    Speed Warn(0-1000)% 86%

  • 5/27/2018 APC715_V1.0_en

    37/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 37 of 62

    7.2 PROGRAMMABLE OUTPUT 1-5 (TABLE 2)

    No. Type Description

    0 Not Used

    1 Custom Period 1

    Details of function description please

    see the following.

    2 Custom Period 23 Custom Period 3

    4 Custom Period 4

    5 Custom Period 5

    6 Custom Period 6

    7 Custom Combined 1

    8 Custom Combined 2

    9 Custom Combined 3

    10 Custom Combined 4

    11 Custom Combined 512 Custom Combined 6

    13 Reserved

    14 Reserved

    15 Reserved

    16 Reserved

    17 Air Flap

    Action when over speed shutdown and

    emergence stop. It can close the air

    inflow to stop the engine as soon as

    possible.

    18 Audible Alarm

    Action when warning or shutdown

    occurs. Can be connected annunciator

    externally. When alarm muteinput port

    is active, the alarm will be prohibit.

    19 Louver ControlAction in genset starting and disconnect

    when genset stopped completely.

    20 Fuel Pump ControlIt is controlled by fuel pump of level

    sensors limited threshold.

    21 Heater Control It is controlled by heating of temperaturesensors limited threshold.

    22 Cooler ControlIt is controlled by cooler of temperature

    sensors limited threshold.

    23Oil Pre-supply Actions in period of cranking to safety

    run.

    24 Reserved

    25 Pre-LubricateActions in period of pre-heating to safety

    run.

    26 Remote PC Output This port is controlled by RS485communication (PC).

    27 Reserved

  • 5/27/2018 APC715_V1.0_en

    38/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 38 of 62

    28 Reserved

    29 On-load OutputControl generator to take load or off

    load.

    30 Reserved

    31 Reserved

    32 Reserved

    33 Crank RelayAction when genset is starting and

    disconnect when crank successful.

    34 Fuel RelayAction when genset is starting and

    disconnect when stop is completed.

    35 Idle Control

    Used for engine which has idles. Close

    before starting and open in warming up

    delay; Close during stopping idle

    process and open when stop is

    completed.

    36 Raise Speed

    Action in warming up delay and be

    controlled by GOV in normal running

    process.

    37 Drop Speed

    Action between the period from stop

    idleto failed to stopand be controlled

    by GOV in normal running process.

    38 ETS Control

    Used for engines with ETS

    electromagnet. Close when stop idle is

    over and open when pre-set ETSdelayis over.

    39 Pulse Drop speed

    Active 0.1s when controller enter into

    stop idle, used for control part of ECU

    dropping to idle speed (temporary

    reserved).

    40 ECU StopSuitable for engines which fitted with

    ECU; used for control ECU stop.

    41 ECU Power Supply

    Suitable for engines which fitted with

    ECU; used for control ECU powersupply.

    42 Pulse raise speed

    Active 0.1s when controller enter into

    warming up delay; used for control part

    of ECU raising to normal speed

    (temporary reserved).

    43 Crank SuccessClose when detects a successful start

    signal.

    44 Reserved

    45 Reserved46 Reserved

    47 Start Battery Cycle During cranking process, start battery

  • 5/27/2018 APC715_V1.0_en

    39/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 39 of 62

    will be switchover circularly if multiple

    crank is needed.

    48 Common AlarmAction when pump unit common

    warning, common shutdown alarm.

    49 Common Trip Action when common trip alarm.

    50 Common Shutdown Action when common shutdown alarm.

    51 Common Fault Idle Alarm Action when fault idle alarm.

    52 Common Warn Alarm Action when common warning alarm.

    53 Reserved

    54 Battery 1 High VoltsAction when battery 1 over voltage

    warning alarm.

    55 Battery 1 Low VoltsAction when battery 1 low voltage

    warning alarm.

    56

    Charge Alt Fail Action when charge failure warning

    alarms.

    57 Reserved

    58 Reserved

    59 Reserved

    60 ECU Warn Indicate ECU sends a warning signal.

    61 ECU Shutdown Indicate ECU sends a shutdown signal.

    62 ECU COM FailIndicate controller cannot communicate

    with ECU.

    63 Reserved

    64 Reserved

    65 Reserved

    66 Reserved

    67 Reserved

    68 Reserved

    69 Aux Input 1 Active Action when input port 1 is active.

    70 Aux Input 2 Active Action when input port 2 is active.

    71 Aux Input 3 Active Action when input port 3 is active.

    72 Aux Input 4 Active Action when input port 4 is active.

    73 Aux Input 5 Active Action when input port 5 is active.

    74 Aux Input 6 Active Action when input port 6 is active.

    75 Aux Input 7 Active Action when input port 7 is active.

    76 Aux Input 8 Active Action when input port 8 is active.

    77 Aux Input 9 Active Action when input port 9 is active.

    78~96 Reserved

    97 Battery 2 High VoltsAction when battery 2 over voltage

    warning alarm.

    98 Battery 2 Low Volts

    Action when battery 2 low voltage

    warning alarm.

    99 Emergency Stop Action when emergency stop alarm.

  • 5/27/2018 APC715_V1.0_en

    40/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 40 of 62

    100 Failed To Start Action when failed start alarm.

    101 Failed To Stop Action when failed stop alarm.

    102 Under Speed Warn Action when under speed alarm.

    103 Under Speed Shutdown Action when under speed shuts down.

    104 Over Speed Warn Action when over speed warning.

    105Over Speed Shutdown

    Action when over speed shutdown

    alarm.

    106~138 Reserved

    139 High Temp Warn Action when high temperature warning.

    140 Low Temp Warn Action when low temperature warning.

    141High Temp Shutdown

    Action when hi-temperature Shutdown

    alarm.

    142 Reserved

    143 Low OP Warn Action when low oil pressure warning.

    144 Low OP Shutdown Action when low oil pressure shutdown.

    145 OP Sensor OpenAction when oil pressure sensor is open

    circuit.

    146 Reserved

    147 Low Level Warn Action when low oil level warning.

    148 Over Flow Shutdown Action when low oil pressure shutdown.

    149 Over Flow Warn Action when low oil pressure warning.

    150 Config 1 High Warn

    151 Config 1 Low Warn

    152 Config 1 High Shut

    153 Config 1 Low Shut

    154 Config 2 High Warn

    155 Config 2 Low Warn

    156 Config 2 High Shut

    157 Config 2 Low Shut

    158 Config 3 High Warn

    159 Config 3 Low Warn

    160 Config 3 High Shut

    161 Config 3 Low Shut

    162 Config 4 High Warn

    163 Config 4 Low Warn

    164 Config 4 High Shut

    165 Config 4 Low Shut

    166 Config 5 High Warn

    167 Config 5 Low Warn

    168 Config 5 High Shut

    169 Config 5 Low Shut

    170 Config 6 High Warn

    171 Config 6 Low Warn

  • 5/27/2018 APC715_V1.0_en

    41/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 41 of 62

    172 Config 6 High Shut

    173 Config 6 Low Shut

    174 Outlet High Warn

    175 Outlet Low Warn

    176 Outlet High Shut

    177 Outlet Low Shut

    178~229 Reserved

    230 Stop Mode Action in stop mode.

    231 Manual Mode Action in Manual mode.

    232 Reserved

    233 Auto Mode Action in Auto mode.

    234 Loading Status Indicate the system is on-load.

    235~239 Reserved

    7.2.1 Custom Period Output

    Defined Period output is composed by 2 parts, period output S1 and condition output S2.

    While S1 and S2 are TRUEsynchronously, OUTPUT;

    While S1 or S2 isFALSE, NOT OUTPUT.

    Period output S1, can set pump units one or more period output freely, can set the

    delayed time and output time after enter into period.

    Condition output S2; can set as any conditions in output ports.

    NOTE:when delay time and output time both are 0 in period output S1, it is TRUE in

    this period.

    Example,

    Output period: start

    Delay output time: 2s

    Output time: 3s

    Condition output contents: output port 1 is active

    Close when condition output active/inactive: close when active (disconnect when

    inactive);

    Output port 1 active, after enter starts time and delay 2s, this defined period output is

    outputting, after 3s, stop outputting;

    Output port 1 inactive, defined output period is not outputting.

  • 5/27/2018 APC715_V1.0_en

    42/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 42 of 62

    7.2.2 Custom Combined Output

    Defined combination output is composed by 3 parts, condition output S1 or S2 and

    condition output S3.

    S1 or S2 is TRUE, while S3 is TRUE, Defined combination output is outputting;

    S1 and S2 are FALSE, or S3 is FALSE, Defined combination output is not outputting.

    NOTE: S1, S2, S3 can be set as any contents except for defined combination

    output in the output setting.

    NOTE: 3 parts of defined combination output (S1, S2, S3) couldnt include or

    recursively include themselves.

    Example,

    Contents of probably condition output S1: output port 1 is active;

    Close when probably condition output S1 is active /inactive: close when active

    (disconnect when inactive);

    Contents of probably condition output S2, output port 2 is active;

    Close when probably condition output S2 is active /inactive: close when active

    (disconnect when inactive);

    Contents of probably condition output S3: output port 3 is active;

    Close when probably condition output S3 is active /inactive: close when active

    (disconnect when inactive);

    When input port 1 active or input port 2 active, if input port 3 is active, Defined

    combination output is outputting; If input port 3 inactive, Defined combination output is

    not outputting;

    When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not,

    Defined combination output is not outputting.

  • 5/27/2018 APC715_V1.0_en

    43/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 43 of 62

    7.3 DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS(ALL ACTIVE WHEN CONNECT TO GRAND (B-))

    No. Type Description

    0 Users Configured

    Including following functions,

    Indication: indicate only, not warning or shutdown.Warning: warn only, not shutdown.

    Shutdown: alarm and shutdown immediately

    Never: input inactive.

    Always: input is active all the time.

    From crank: detecting as soon as start.

    From safety on: detecting after safety on run delay.

    1 Reserved

    2 Alarm MuteCan prohibit Audible Alarm output when input is

    active.

    3 Reset Alarm Can reset shutdown alarm when input is active.

    4 Reserved

    5 Lamp TestAll LED indicators are illuminating when input is

    active.

    6 Panel Lock

    All buttons in panel is inactive except

    and there is in the left of first

    row in LCD when input is active.

    7 Reserved

    8 Idle Control Mode Under speed protection is inactive.

    9 Inhibit Auto Stop

    In Auto mode, during pump unit normal running,

    when input is active, inhibit pump unit shutdown

    automatically.

    10 Inhibit Auto StartIn Automode, inhibit pump unit start automatically

    when input is active.

    11 Inhibit ScheduledIn Auto mode, inhibit pump unit scheduled run

    when input is active.

    12 Reserved

    13 Loading Status Connect to Aux. Points of clutch.

    14 Load Inhibit Prohibit pump unit onload when input is active.

    15 Reserved

    16 Reserved

    17 Reserved

    18 Reserved

    19 Reserved

    20 Reserved

    21 Inhibit Alarm Stop All shutdown alarms are prohibited exceptemergence stop.(Means battle mode)

    22 Aux Instrument Mode All outputs are prohibited in this mode.

  • 5/27/2018 APC715_V1.0_en

    44/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 44 of 62

    23 Reserved

    24 Reset MaintenanceController will reset maintenance time and date as

    default when input is active.

    25 Reserved

    26 Aux. High Temp Connect to sensor digital input.

    27 Aux. Low OP Connect to sensor digital input.

    28Remote Start

    (On Load)

    InAutomode, when the input is active, pump unit

    can be started automatically and take load after

    pump unit normal running.

    29Remote Start

    (Off Load)

    In Auto mode, when the input is active, pump unit

    can be started automatically and NOT take load

    after pump unit normal running.

    30 Aux. Manual Start

    In Manual mode, when the input is active, pump

    unit will start automatically; when input inactive,

    pump unit will stop automatically.

    31 Reserved

    32 Remote Stop

    InAutomode, when the input is active as well as

    remote start signal is inactive, pump unit can be

    stopped automatically.

    33 Simulate Stop key An external button (not self-locking) can be

    connected and pressed as simulate panel.34 Simulate Manual key

    35 Reserved

    36 Simulate Auto key An external button (not self-locking) can be

    connected and pressed as simulate panel.37 Simulate Start key

    38 Simulate Load key

    39~5

    1Reserved

    52 Speed Raise Input An external button (not self-locking) can be

    connected and control GOV manually.53 Speed Drop Input

  • 5/27/2018 APC715_V1.0_en

    45/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 45 of 62

    7.4 SELECTION OF SENSORS

    No. Description Remark

    1Temperature

    Sensor

    0 Not used

    1 Custom Res Curve

    2 Custom 4-20mA curve3 VDO

    4 CURTIS

    5 VOLVO-EC

    6 DATCON

    7 SGX

    8 SGD

    9 SGH

    10 PT100

    11~15 Reserved

    Defined resistances

    range is (0~6)K,

    default is SGX sensor.

    2 Pressure Sensor

    0 Not used

    1 Custom Res Curve

    2 Custom 4-20mA curve

    3 VDO 10Bar

    4 CURTIS

    5 VOLVO-EC

    6 DATCON 10Bar

    7 SGX

    8 SGD

    9 SGH10~15 Reserved

    Defined resistances

    range is (0~6)K,

    default is SGX sensor.

    3Fuel Level

    Sensor

    0 Not used

    1 Custom Res Curve

    2 Custom 4-20mA curve

    3 SGD

    4 SGH

    5~15 Reserved

    Defined resistances

    range is (0~6)K,

    default is SGH sensor.

    Note: User should take the controller apart to change the jumper hat from resistor

    side to current side if your pump unit fitted with 4~20mA sensor.

  • 5/27/2018 APC715_V1.0_en

    46/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 46 of 62

    7.5 CONDITIONS OF CRANK DINSCONNECT SELECTION

    No. Setting description

    0 Oil pressure

    1 Engine Speed

    2 Oil pressure + Engine SpeedNOTE:

    1. There are 3 conditions to make starter disconnected with engine. Engine speed and

    oil pressure both can be used separately. We recommend that oil pressure should

    be using with engine speed together, in order to make the starter motor is separated

    with engine immediately and can check crank disconnect exactly.

    2. Engine speed is the magnetic equipment which be installed in starter for detecting

    flywheel teeth.3. When set as engine speed, must ensure that the number of flywheel teeth is as same

    as setting, otherwise, over speed shutdown or under speed shutdown may be

    caused.

    4. If pump unit without engine speed sensor, please dont select corresponding items,

    otherwise, start fail or loss speed signal maybe caused.

    5. If genset without oil pressure sensor, please dont select corresponding items.

  • 5/27/2018 APC715_V1.0_en

    47/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 47 of 62

    8 PARAMETERS SETTING

    1. Please change the controller parameters when generator is in standby mode only

    (e. g. Crank disconnect conditions selection, digital input, digital output, various

    delay), otherwise, shutdown and other abnormal conditions may occurs.

    2. Maximum set value must over minimum set value in case that the condition of too

    high as well as too low will happen.

    3. When setting the warning alarm, please set the correct return value; otherwise,

    maybe there is abnormal alarm. When setting the maximum value, the return value

    must less than set value; When setting the minimum value, the return value must

    over than set value.

    4. Digital input could not be set as same items; otherwise, there are abnormal

    functions. However, the digital output can be set as same items.

  • 5/27/2018 APC715_V1.0_en

    48/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 48 of 62

    9 SENSOR SELECT

    1) When reselect sensors, the sensor curve will be transferred into the standard value.

    For example, if temperature sensor is SGX (120C resistor type), its sensor curve

    is SGX (120C resistor type); if select the SGD (120C resistor type), the

    temperature sensor curve is SGD curve.

    2) When there is difference between standard sensor curves and using sensor, user

    can adjust it in curve type.

    3) When input the sensor curve, X value (resistor) must be input from small to large,

    otherwise, mistake occurs.

    4) If select sensor type as None, sensor curve is not working and LCD does not

    display the sensor information.

    5) If there is alarm switch only for the select sensor, user must set the sensor as

    None, otherwise, maybe shutdown or warning occurs.

    6) The headmost or backmost values in the vertical coordinates can be set as same

    as below,

    Common unitconversion table

    N/m2 (pa) kgf/cm2 bar (p/in2.psi)

    1Pa 1 1.02x105 1x10

    5 1.45x104

    1kgf/cm2 9.8x104 1 0.98 14.2

    1bar 1x105 1.02 1 14.5

    1psi 6.89x103 7.03x102 6.89x10

    2 1

  • 5/27/2018 APC715_V1.0_en

    49/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 49 of 62

    10 TYPICAL APPLICATION

  • 5/27/2018 APC715_V1.0_en

    50/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 50 of 62

    11 INSTALLATION

    Controller is panel built-in design; it is fixed by clips when installed.

    1) Battery Voltage Input

    NOTE: APC715 controller can suit for widely range of battery voltage

    DC(8~35)V. Negative of battery must be connected with the engine shell soundly.

    The diameter of wire which from power supply to battery must be over 2.5mm 2. If

    floating charge configured, please firstly connect output wires of charger to

    batterys positive and negative directly, then, connect wires from batterys positive

    and negative to controllers corresponding input ports in order to prevent charge

    disturbing the controllers normal working.2) Speed Sensor Input

    NOTE: Speed sensor is the magnetic equipment which be installed in starter

    and for detecting flywheel teeth. Its connection wires to controller should apply for

    2 cores shielding line. The shielding layer should connect to shielding GND

    terminal in controller while another side is hanging in air. The else two signal wires

    are connected to MP1 and MP2 terminals, moreover, MP2 has already connected

    to B- innerly. The output voltage of speed sensor should be within AC(1~24)V

    (effective value) during the full speed. AC12V is recommended (in rated speed).

    When install the speed sensor, let the sensor is spun to contacting flywheel first,

    then, port out 1/3 lap, and lock the nuts of sensor at last.

    3) Output And Expansion Relay

    NOTE: All outputs of controller are relay contact output type. If need to expand

    the relays, please add freewheel diode to both ends of expand relays coils (when

    coils of relay has DC current) or, add resistance-capacitance return circuit (when

    coils of relay has AC current), in order to prevent disturbance to controller or

    others equipment.

  • 5/27/2018 APC715_V1.0_en

    51/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 51 of 62

    12 CONNECTIONS OF CONTROLLER WITH J1939 ENGINE

    12.1 CUMMINS ISB/ISBE

    Terminals of controller Connector B Remark

    Fuel relay output 39

    Start relay output -Connect with starter coil

    directly

    Auxiliary output port

    1

    Expand 30A relay, battery

    voltage of 01,07,12,13 is

    supplied by relay

    ECU power

    Set Auxiliary output 1 as ECU

    power

    Terminals of controller 9 pins connector Remark

    CAN GND SAE J1939 shield

    CAN communication shielding

    line(connect with ECU terminalonly)

    CAN(H) SAE J1939 signalImpedance 120 connecting

    line is recommended.

    CAN(L) SAE J1939 returnImpedance 120 connecting

    line is recommended.

    Engine type:Cummins ISB

    12.2 CUMMINS QSL9

    Suitable for CM850 engine control modeTerminals of controller 50 pins connector Remark

    Fuel relay output 39

    Start relay output - Connect to starter coil directly

    Terminals of controller 9 pins connector Remark

    CAN GND SAE J1939 shield-E

    CAN communication shielding

    line(connect with ECU terminal

    only)

    CAN(H) SAE J1939 signal-CImpedance 120 connecting

    line is recommended.

    CAN(L) SAE J1939 return-DImpedance 120 connecting

    line is recommended.

    Engine type: Cummins-CM850

  • 5/27/2018 APC715_V1.0_en

    52/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 52 of 62

    12.3 CUMMINS QSM11(IMPORT)

    It is suitable for CM570 engine control module. Engine type is QSM11 G1, QSM11 G2.

    Terminals of controller C1 connector Remark

    Fuel relay output 5&8

    Outside expand relay, when

    fuel output, making port 5 andport 8 of C1 be connected

    Start relay output - Connect to starter coil directly

    Terminals of controller 3 pins data link connector Remark

    CAN GND C

    CAN communication shielding

    line(connect with ECU

    terminal only)

    CAN(H) A

    Impedance 120 connecting

    line is recommended.

    CAN(L) BImpedance 120 connecting

    line is recommended.

    Engine type: Cummins ISB

    12.4 CUMMINS QSX15-CM570

    It is suitable for CM570 engine control module. Engine type is QSX15.

    Terminals of controller 50 pins connector Remark

    Fuel relay output 38 Oil spout switch

    Start relay output - Connect to starter coil directly

    Terminals of controller 9 pins connector Remark

    CAN GND SAE J1939 shield-E

    CAN communication shielding

    line(connect with ECU

    terminal only)

    CAN(H) SAE J1939 signal-CImpedance 120 connecting

    line is recommended.

    CAN(L) SAE J1939 return-D

    Impedance 120 connecting

    line is recommended.

    Engine type: Cummins QSX15-CM570

  • 5/27/2018 APC715_V1.0_en

    53/62

    APC715 Pump Unit Controller

    APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 53 of 62

    12.5 CUMMINS GCS-MODBUS

    It is suitable for GCS engine control module. Use RS485-MODBUS to read information

    of engine. Engine types are QSX15, QST30, QSK23 / 45/60/78 and so on.

    Terminals of controller D-SUB connector 06 Remark

    Fuel relay output 5&8

    Outside expand relay, whenfuel output, making port 05

    and 08 of the connector 06 be

    connected.

    Start relay output - Connect to starter coil directly

    Terminals of controller D-SUB connector 06 Remark

    RS485 GND 20

    CAN communication shielding

    line(connect with ECU

    terminal only)

    RS485+ 21Impedance 120 connecting

    line is recommended.

    RS485- 18Impedance 120 connecting

    line is recommended.

    Engine type: Cummins QSK-MODBUS, Cummins QST-MODBUS, Cummins

    QSX-MODBUS

    12.6 CUMMINS QSM11

    Terminals of controller OEM connector of engine RemarkFuel relay output 38

    Start relay output - Connect with starter coil

    directly

    CAN GND - CAN communication shielding

    line(connect with controllers

    this terminal only)

    CAN(H) 46 Impedance 120 connecting

    line is recommended.

    CAN(L) 37 Impedance 120 connectingline is recommended.

    Engine type: com