anton eder gmbh - eder heizung · eder control-electronics: multicontrol basic circuit board, type...
TRANSCRIPT
Instruction manual
Modbus RTUfield bus module
ANTON EDER GMBHWeyerstraße 350
A-5733 Bramberg
www.eder-heizung.at
Ver.06/2020-en
Table of contents
Table of contents
1. General
1.1 Description
. Scope of delivery2
3. Bus module
3.1. Hardware ports, switches
3.1.1. Connector to Modbus network (1. interface)RTU RS
3.1.2. Connector supply voltage
3.1.3. Connector to multicontrol electronics (2. interface)RS
3.1.4. Power supply
3.2. indicator lightsLED
3.3. Switches
3.3.1. Termination (1. and 2. serial interface)
3.3.2. Rotary coding switches Modbus- , S4 (High) + S5 (Low)ID
3.3.3. Rotary coding switches S6 + S7 (serial interface to device)EDER
4. Mounting
5. Wiring diagram
5.1. Legend
5.2. Wiring diagram - connection of the bus module
6. Commissioning
6.1. Activation of the bus module in multicontrol device set-up
6.2. Configuration of the bus module
7. Data transfer
7.1. General
7.1.1. data transfer from the multicontrol device to the Modbus- masterRTU
7.1.2. data transfer from the Modbus master to the multicontrol deviceRTU
7.2. Data types
7.3. Bit significance
7.4. Bus module Modbus Output Register
7.5. Bus module Modbus Input Register
8. Notes
2
DisclaimerWe improve our products permanently and so we reserve the right to make modifications
anytime and without previous announcements. We do not assume any guarantee for the
correctness and completeness of this document.
Any claims, particularly claims for damages and loss of profit or financial losses must be
excluded!
1. General
1.1. Description
The Modbus field bus module (hereinafter called „bus module”) enables the connection ofRTUthe multicontrol resp. topcontrol series control electronics to a Modbus network.EDER RTU
In this application the bus module is a gateway and acts as Modbus Slave. It can be used withRTUevery Modbus Master which complies to the Modbus standard.RTU RTUThe connection between the multicontrol control electronics and the bus module is made via theRS PP232 interface of the multicontrol processor board ( ).
The Modbus interface of the bus module transfers data acc. to the Modbus protocol.RTU
The Modbus address of the bus module is set via two rotary coding switches (S4 / S5)
The usage resp. the implementation of the bus module presupposes that the user is familiar withthe commissioning and the programming of Modbus devices.The bus module acts as „ module”.IO
1. General
ECONECON
NOTE!
Figures in this document can vary due to model and configuration of the deliveredmulticontrol device.
i
ECON
INFORMATION!
This document refers to multicontrol and topcontrol series devices with software versionV1.26 of the processor board. Different software versions can lead to slight differences inoperation resp. the version of the device. To ensure an appropriate function of the busmodule, the software version of the processor board must be V1.22 or higher!
i
3
2. Scope of delivery
2. Scope of delivery
instruction manual
connection cable
cable gland PG13,5
ECONECON
NOTE!
The data transfer of the 232 interface of the multicontrol processor board is describedRSin chapters 7.4. and 7.5.Sending of the data from the 232 interface happens acc. to 7.4.RSReceiving of the data at the 232 interface happens acc. to 7.5.RSThis way of data transfer can also be used without a field bus module but with anappropriate 232 remote station or with suitable converters from 232 to the requiredRS RSphysical interface (e.g. with a converter 232 to 485).RS RS
i
Ver.04/2018-en
instruction manual
Modbus RTUfield bus module
ANTON EDER GMBHWeyerstraße 350
A-5733 Bramberg
www.eder-heizung.at
bus module bus module holding plate
incl. mounting screws
4
3. Bus module
3. Bus module
3.1. Hardware ports, switches
3.1.1. Connector to Modbus network (1. interface)RTU RS
The plug ”-X1” is available on the top side of the device. The 4-pin screw-type connector (-X1:terminal 4 ... 7) is used for connecting to the Modbus -network.RTU
The 3-pin screw-type connector (-X1: terminal 1 ... 3) is not used (internally necessary duringinitial configuration of the busmodule using it‘s config mode: S4 & S5 in position„ ”).FF
Pin assignement -X1 (3-pole + 4-pole screw-type plug connector)
plug -X1 (RS485 Modbus interface, terminal 4 ... 7)
plug -X2 (supply voltage)
rotary coding switchModbus-IDS4 (High) S5 (Low)
plug -X3 (RS232 interface)
Pin No. Name Function
1 Rx232 not required
2 Tx232 not required
3 AP GND- not required
4 Rx422+ (485+) Receive signal
5 Rx422- (485-) Receive signal
6 Tx 422+ (485+) Transmit signal
7 Tx 422- (485-) Transmit signal
5
3.1.2. Connector supply voltage
Pin assignment -X2 (4-pole screw-type plug connector; bottom side, back)
3.1.3. Connector to multicontrol electronics (2. interface)RS
The plug ”-X3" for the serial 232 interface (connection to the multicontrol/topcontrolRSprocessor board) is available on the bottom side of the device.
Pin assignment -X3 (3-pole screw-type plug connector)
3.1.4. Power supply
The bus module must be powered with 10-33 . The voltage supply is made through theVDC4-pole screw-plug connector -X2 at the bottom side of the device.Please note that the bus module must not be operated with voltage.AC
3.2. indicator lightsLED
The bus module features 8 s with the following significance:LED
Description Color Significance
LED (Bus) Power green Supply voltage 2. interfaceRS
LED (Bus) State red/green Interface state 2. interfaceRS
LED Power green Supply voltage
LED State red/green General error bus module
LED 1 / 2 / 4 / 8 (Error Nr / SelectID )
green The error number is displayed ( s flash,LEDonly important if the ”state”LEDsimultaneously lights red)
3. Bus module
Pin No. Name Function
1 UB (Pwr) 10..33 Volt supply voltage / DC
2 0 V (Pwr) 0 Volt supply voltage / DC
3 Rx Debug not required
4 Tx Debug not required
Pin No. Name Function
1 Rx 232 Receive signal
2 Tx 232 Transmit signal
3 AP GND- Application Ground
4 ... 7 RS RS422 ( 485) not required
6
3.3. Switches
The bus module features 8 switches (on its front side) with the following functions:
3.3.1. Termination (1. and 2. serial interface)
If the bus module is operated as the physically first or last device in a 485-bus or as 422, thereRSmust be a bus termination at this bus module. In order to do this the termination switch is set toposition . The resistor (150 ) integrated in the bus module is activated.ON �
In all other cases, the switch remains in position .OFF
3.3.2. Rotary coding switch Modbus- , S4 (High) + S5 (Low)ID
With these two switches the bus module‘s Modbus address is set in hexadecimal notation(01h...F7h).Setting of the Modbus address:The Modbus address is set in hexadecimal digits 01h…F7h (matches the Modbus addresses1 ... 247 decimal).
Example:Modbus- 26 decimal = 1A hexadecimalIDThe switch ”Modbus- High” must be set to 1 and the switch ”Modbus- Low” must be set toID IDA. If the rotary coding switch is set to a value between 1 and 247, the bus module uses thisModbus- (translation from decimal to hexadecimal see the following table).ID
3. Bus module
Name Description
Termination Rx422 (Application) Switchable Rx422-terminating resistor for 1. serialinterface (Modbus side)
Termination Tx422 (Application) Switchable Tx422- or 485-terminating resistor forRS1. serial interface (Modbus side)
Rotary coding switch S4 ID High for 1. serial interface (Modbus side)
Rotary coding switch S5 ID Low for 1. serial interface (Modbus side)
Rotary coding switch S6 ID High for 2. serial interface (not relevant)
Rotary coding switch S7 ID Low for 2. serial interface (not relevant)
Termination Rx422 (Fieldbus) Switchable Rx422-terminating resistor for 2. serialinterface
Termination Tx422 (Fieldbus) Switchable Tx422- or 485-terminating resistor forRS2. serial interface
7
Translation table from decimal to hexadecimal:
3.3.3. Rotary coding switches S6 + S7 (serial interface to device)EDER
The setting of these two switches is not relevant for the application which is explained in thisdocument. Ideally the switches should be left in position ”00” (both S6 and S7 in position ”0”).
3. Bus module
coding-switch„S4" (high)
coding-switch„S5" (low)
Adress „hex” Adress „dec”
0 1 01h 1
0 2 02h 2
... ... ... ...
0 9 09h 9
0 A 0Ah 10
0 B 0Bh 11
... ... ... ...
0 F 0Fh 15
1 0 10h 16
... ... ... ...
1 A 01A 26
... ... ... ...
7 D 7Dh 125
... ... ... ...
F 7 F7h 247
8
4. Mounting
Step 1Dismantle the cover - Open the 4 fasteners and lift the cover until it unhinges at the upper
hangers and pull it forward.
Step 2Disconnect power supply to multicontrol device.
CAUTION! It must be ensured that the disconnection of the power supply is allowed,depending on the actual operating situation of the multicontrol device. This is especiallyimportant if the device is already in operation and the bus module must be retrofitted.
Step 3Open the operating panel (release the 4 plastic screws (1) ) and replace the blind cap in the
bottom part of the operating panel with the delivered PG13,5 cable gland (2).
4. Mounting
fig.: multicontrol
fig.: picocontrol
1
1
2
3
1
1
2
fig.: multicontrol fig.: picocontrol
1
1
9
2
Step 4Plug the connection cable into the bus module and place the module into the bottom part of the
operating panel.
Attach the 232-plug of the connection cable (4-pole plug with coding pins) into the not usedRS
socket at the processor board (labelled with 232).RS
Insert the Modbus cable through the 13,5 cable gland (mounted in step 3) and plug it into thePG
4-pole plug X1 (Pin 04 .. 07) (connection see 3.1.3).
multi/topcontrol-devices:
4-pole plug (-X2)
3-pole plug (-X3)
4-pole connection to the multicontrolbasic circuit board (remains unchanged)
Modbus cableto Modbus RTUMaster (on site)
4. Mounting
bus module
holding plate
plug -X1 (Pin 04 .. 07)4-pole plug (RS232) bus module
connection cable
cable glandPG13,5
10
picocontrol-devices:
Step 5Reassemble the components in reverse order (cover operating panel (close the 4 plastic screws) ,
cover/plate) and supply the device with power again.
5. Wiring diagram
5.1. Legend
4-pole connection to the multicontrolbasic circuit board (remains unchanged)
drawn: 04.10.2016 Blassnig
reviewed:
approved:
size: A4 Revision: -
-A1
-A2
-A11 Modbus field bus moduleRTU
LEGEND
Wiring diagram - addition Modbus RTU
marking description
eder control-electronics: multicontrol basic circuit board, type 200331
eder control-electronics: processor board multi/topcontrol, type 10ABCO
4. mounting / 5. wiring diagram
4-pole plug (-X2)
3-pole plug (-X3)
bus module
holding plate
4-pole plug (RS232) bus module
connection cable
Modbus cableto Modbus RTUMaster (on site)
plug -X1 (Pin 04 .. 07)
cable glandPG13,5
11
5. Wiring diagram
5.2. Wiring diagram - connection of the bus module
12
6. Commissioning
6.1. Activation of the bus module in multicontrol device set-up
Go to user level 3.
User level 3 can be unlocked in menu “settings” - “code input”
code for user level 3:
User level 3 - menu structure:
user level 3 Grayed-out menu items already are accessible in lower user levels and described there
/))) actions/))) settings* /))) ...* .))) device set-up* /))) ...* .))) communication* /))) ...
* .))) Busmodule/Webmodul activate!�
/))) manual mode.))) code input
6.2. Configuration of the bus module
user level 3 Grayed-out menu items already are accessible in lower user levels and described there
/))) actions/))) settings* /))) ...* /))) Busmodule/Webmodul 1)
* * /))) enable receiving* * /))) enable device 2)
* * .))) ext. setpoint 2,3)
* .))) .../))) manual mode.))) code input
1) only if bus module is enabled
2) only if receiving is enabled
3) only in topcontrol
6. Commissioning
F1F1 F2F2
���� ����� �� �������������� ���� � ��� ��� ��� ��!
13
user level 3 settings Busmodule/Webmodul� � �
enable receiving „no” (default setting)
Data reception via the bus module is deactivated.
All data sent from Modbus to the multicontrol control via the bus
module are not considered.
„yes”Enables the data reception from Modbus. All data sent from Modbus
to the multicontrol control via the bus module are processed. This
will allow the execution of specified actions via the Modbus.
Details to the data reception see chapter 7.5. bus module Modbus
Input Register.
enable device „no” (default setting)
The enabling of the device via the bus module is deactivated.
„yes”The enabling of the device via the bus module is activated.
Thus the device function can be disabled resp. enabled via the bus
module.
General information on device enabling:If device enabling is locked, the multicontrol control electronics detects the external
deactivation and all components like pumps and valves are switched off. Though the
measurement of pressure, level, temperature as well as the output of all messages remain
activated. Among all other messages (e.g. analog signalling, binary signalling) the contacts
”warning” and ”fault” also remain functional.
The deactivation of the device function via device enabling can easily be recognized by the
green flashing (one-second intervals) at key 1. This allows to recognize immediately that theLED
device is even switched on via the key 1 but it is locked externally via the device enabling.
The following table shows the enabling of the device function depending on the possible
settings and status requests.
6. Commissioning
14
Table: Enabling of the device function
6. Commissioning
enable contactactivated(settings ->
device set-up ->enable contact)
[ is available /not available ]
enable contactstatus
(potential freecontact, Pin 82 at
basic circuit board)
[ On / Off ]
device enabling -bus activated
(settings ->busmodule ->enable device)
[ Yes / No ]
device enablingbus status
[ True / False ]
device functionenabled
[ Yes / No ]
not available Off No False Yes
not available Off No True Yes
not available Off Yes False No
not available Off Yes True Yes
not available On No False Yes
not available On No True Yes
not available On Yes False No
not available On Yes True Yes
available Off No False No
available Off No True No
available Off Yes False No
available Off Yes True No
available On No False Yes
available On No True Yes
available On Yes False No
available On Yes True Yes
ECON
INFORMATION!
The operation on the device with the keys 0 and 1 always has priority.If the device is deactivated with the key 0 and the red next to the key lights, theLEDdevice function is always deactivated, independent from the status of the enable contactor the bus.
i
15
ext. „no” (default setting)setpoint 1)
External setting of the setpoint of the upper working pressure via the
bus module is deactivated.
All setpoint values sent from the bus module are not considered by
the topcontrol control electronics.
„yes”External setting of the setpoint of the upper working pressure via the
bus module is activated.
All setpoint values sent from the bus module are considered by the
topcontrol control electronics and set for the upper working
pressure.
Details to the external setting of the setpoint see instruction manual
”topcontrol as a supplement to , -_1” - chapter 6 -TCM MCK MCM
external setpoint.
1) only in topcontrol
ECONECON
NOTE!
The external setting of the setpoint is only available in topcontrol series devices!
The external setting via the bus module has priority over the analog external setting ofthe setpoint. Independent from the analog external setting (device set-up ext.�
setpoint) the set value of the bus gets used as setpoint for the upper working pressure.
i
6. Commissioning
16
7. Data transfer
7.1. General
The bus module supports data transfer in both directions (sending and receiving).
Modbus telegrams of the on-site urgently necessary Modbus master get answered. The bus
module acts as a slave and is absolutely passive on the Modbus. It responds only on demand of
the master.
CAUTION!Simultaneous sending and receiving is not permitted. The period between the sequential
transfer cycles must be at least 1 second, independent from the direction. Otherwise problems
with the data processing and malfunctions of the multicontrol device can occur.
Modbus interface data:RTUphysical interface: 485Rs
baud rate: 9,6 kbit/s1)
1) The baud rate of the Modbus interface of the bus module is set to 9,6 kbit/s ex factory. If a different baud rateRTU
is desired in the course of project planning, the configuration of the bus module must be changed - changing of
the configuration only in consultation with the technical department.EDER
Possible baud rates of the interface: 9600, 19200, 38400, 57600, 115200.
7.1.1. Data transfer from the multicontrol device to the Modbus masterRTU 2)
The processor board of the multicontrol device sends data in one-second intervals via its 232RS
interface to the 232 interface of the bus module. This requires the activation of the dataRS
transfer (see 6.1. Activation of the bus module in multicontrol device set-up).
Data transfer from the processor board to the bus module:interface type: 232Rs
transfer rate: 38,4 kbit/s
protocol: transparent, see 7.4. and 7.5.
start bit: 1
data bit: 8
stop bit: 1
parity: none
number of data bytes / transfer cycle: 192 Byte
7. Data transfer
17
The bus module transfers the data (192 Byte, received via the 232 interface and stored in aRS
buffer) on request to the Modbus master.RTU
The buffered data get updated (overwritten) if new data are sent by the processor board.
Deletion of the buffered data happens only in voltage-free state.
7.1.2. Data transfer from the Modbus master to the multicontrol deviceRTU 2)
The data transfer from the Modbus master to the bus module and subsequently to the
multicontrol processor board enables the execution of specified actions and the setting of
setpoint values. This requires the enabled receiving of the processor board (see 6.2.).
The data transfer to the bus modules must be projected on the Modbus masters side. During
project development it must be considered that exact 32 Bytes (acc. to the specifications of data
register 2) must be transfered per transfer cycle (see 7.5. Bus module Input Register). Time
interval between 2 cycles: at least 1 second!
It is recommended to send the currently desired data periodically from the Modbus master to the
bus module and to change the value of the "Byte 31: Send trigger" each time the data is sent.
Every change from byte 31 to the value sent before reliably triggers a transmission of the data
from the bus module to the multicontrol processor board. In the case of external setpoint
specification, it is also recommended that the Modbus master periodically compares the actual
setpoint received from the bus module with the setpoint sent by it, as these must be identical
after successful acceptance.
Actions (e.g. fault acknowledgement) are performed by changing the signal state from " " toOFF
" ". After the action has been performed, the signal status must be reset to " " (Keying:ON OFF
e.g. 2 s to ON and then again to OFF)
2 A Modbus master could be a Modbus compatible control system or a superior building management system.)This Modbus master is never in scope of delivery of - it always must be provided and projected on site.EDER
NOTE!
On Modbus side there must be intended 192 Byte for data receiving resp. 32 Byte fordata sending. Data sending is optional and accordingly also the related projectdevelopment.
Modbus control components are never in scope of delivery of EDER. These componentsmust be provided and projected on site.
i
7. Data transfer
18
7. Data transfer
7.2. Data types
Standardised data types:Register (16-Bit). According to the Modbus specification, for each register the High-Byte istransferred first, followed by the Low-Byte.Extended data bytes:32-Bit integer and 32-Bit float are transferred as 2 successive 16-Bit registers.
7.3. Bit significance
All multibyte data types are transferred as (Most Significant Byte).MSB
At compound data types ( 16, 16, 32) the first sent Byte is always classified as .SI UI UI MSB
Examples:Byte 0/1 (Register 0) ... binary signalling / binary status requests
... Byte 0 (High-Byte): 0 0 0 0 1 0 0 1 (bin), equivalent to 9 (dec) x 256 = 2304--> (warning existing & pump 1 is running)
... Byte 1 (Low-Byte): 0 0 0 0 0 0 1 0 (bin), equivalent to 2 (dec)--> (device function ext. enable contact status)
... Register 0 input value (dec): 2304 + 2 = 2306
Byte 6/7 (Register 3) ... current plant pressure [bar *100]
... Byte 6 (High-Byte): 0 0 0 0 1 1 0 0 (bin), equivalent to 12 (dec) x 256 = 3072
... Byte 7 (Low-Byte): 1 0 1 1 1 1 0 0 (bin), equivalent to 188 (dec)
... Register 3 input value (dec): 3072 + 188 = 3260 --> 32,6 bar
0 0 0 0 1 1 0 0
MSB LSB
msb lsb
SI 16 (e.g. Byte 6/7)
1 0 1 1 1 1 0 00 0 0 1 0 1 1 0 0 0 1 0 0 0 0 0Byte 5 Byte 6 Byte 7 Byte 8
......
CAUTION!
The multicontrol processor board doesn‘t check the sent resp. the received data. In caseof an incorrect Modbus project development, malfunction or breakdown of the datatransfer, malfunctions of the multicontrol device can occur. This is particularly relevant forthe external setpoint setting via Modbus.
19
7. Data transfer
20
7.4. Bus module Modbus Output RegisterRTU(data register 1)
The data register 1 shows the organisation of the data in the memory area of the
bus module which can be read via a read command (04H Read Input Registers) of
the Modbus- Master. All Multibyte data types are organised as (MostRTU MSB
Significant Byte).
Reg.Nr.
Byte // Bit
Descriptiondatatype
unit /status
Byte 0 binary signals UI 8
Bit 0warning existing1 = warning
ON OFF,
Bit 1fault existing1 = fault
ON OFF,
Bit 2makeup in operation1 = makeup ON
ON OFF,
Bit 3pump 1 in operation1 = pump 1 ON
ON OFF,
Bit 4pump 2 in operation1 = pump 2 ON
ON OFF,
Bit 5fast degassing1 = started
ON OFF,
Bit 6 -
Bit 7 -
Byte 1 binary status requests UI 8
Bit 0enable device via ext. enable contact1 = enabled
ON OFF,
Bit 1device operation status (ext. enable contact)1 = enabled (active)
ON OFF,
Bit 2enable device via activatedBUS1 = enabled
ON OFF,
Bit 3device operation status (bus)1 = enabled (active)
ON OFF,
0
Reg.Nr.
Byte // Bit
Descriptiondatatype
unit /status
Byte 1 binary status requests UI 8
Bit 4from V1.26: busmodule/webmodule: receivingdisabled1 = disabled
Bit 5
from V1.26: : external setpoint: activatedTCand invalid (hence replaced by substitutevalue)1 = activated and invalid
Bit 6 -
Bit 7 -
Byte 2 to : breakdown send data byte 0MC BMS UI 8
Bit 0reset faults1 = faults has been reset
ON OFF,
Bit 1reset warnings1 = warnings has been reset
ON OFF,
Bit 2makeup : reset amountMCF1 = makeup amount has been reset
ON OFF,
Bit 3makeup : one-time fillingMCF1 = one-time filling has been started
ON OFF,
Bit 4degassing: start fast degassing1 = fast degassing has been started
ON OFF,
Bit 5 -
Bit 6 -
Bit 7 -
Byte 3
Bit 0 … 3 = on-site handle--> 0 = main display--> 1 = message level--> 2 = display level--> 3 = user levelBit 4 … 7 = current user level--> 0 = user level 2--> 1 = user level 3--> 2 = user level 4--> 3 = user level 5
UI 8
1
0
7. Data transfer
21
TC ... only with topcontrol
7. Data transfer
22
TC ... only with topcontrol
Reg.Nr.
Byte // Bit
Descriptiondatatype
unit /status
13 Byte 26
TC: external setpoint: upper working pressure:source0 = no ext. setpoint1 = ext. setpoint: analog input (4-20 mA)2 = ext. Setpoint from busmodule
UI 8
13 Byte 27
TC:operating mode valves0 = redundancy mode1 = valve Y3 only2 = valve Y4 only3 = staggered mode4 = parallel mode
UI 8
14 Byte 28/29current pressure vessel 1 bottom 1uPLvalue range: -300 … + 1300
SI 16 mbar
15 Byte 30/31current pressure vessel 1 top 1oPLvalue range: -300 … + 1300
SI 16 mbar
16 Byte 32/33current pressure vessel 2 bottom 2uPLvalue range: -300 … + 1300
SI 16 mbar
17 Byte 34/35current pressure vessel 2 top 2oPLvalue range: -300 … + 1300
SI 16 mbar
18 Byte 36/37current temperature of the multicontrolprocessor board
SI 16 °C (*100)
19 Byte 38/39maximum temperature of the multicontrolprocessor board
SI 16 °C (*100)
20 Byte 40/41minimum temperature of the multicontrolprocessor board
SI 16 °C (*100)
21 Byte 42/43software versione.g.: 126 = version 1.26
SI 16
22 Byte 44
language pack0 = lang. pack a1 = lang. pack b2 = lang. Pack c…
UI 8
7. Data transfer
23
TC ... only with topcontrol
Reg.Nr.
Byte // Bit
Descriptiondatatype
unit /status
22 Byte 45
device type0 = -SMCK1 = -D (-twin)MCK2 = -M (-twin)MCK3 = -S1MCM4 = -D1 (-twin)MCM5 = -M1 (-twin)MCM6 = -S2-S9MCM7 = -D2-D9 (-twin)MCM8 = -M2-M9 (-twin)MCM9 = -S-xx-xMCM10 = -D-xx-x (-twin)MCM11 = -M-xx-x (-twin)MCM12 = -S2-12-2TCM13 = -D2-12-2TCM14 = -M2-12-2TCM15 = -D2-12-2-twinTCM16 = -M2-12-2-twinTCM17 = -S3-23-6TCM18 = -D3-23-6TCM19 = -M3-23-6TCM20 = -D3-23-6-twinTCM21 = -M3-23-6-twinTCM22 = -S7-13-5TCM23 = -D7-13-5TCM24 = -M7-13-5TCM25 = -D7-13-5-twinTCM26 = -M7-13-5-twinTCM27 = -S9-24-0TCM28 = -D9-24-0TCM29 = -M9-24-0TCM30 = -D9-24-0-twinTCM31 = -M9-24-0-twinTCM32 = -Sxx-xTCM33 = -Dxx-xTCM34 = -Mxx-xTCM35 = -Dxx-x-twinTCM36 = -Mxx-x-twinTCM37 = -SMCA38 = -S1MCC39 = -D1 (-twin)MCC40 = -M1 (-twin)MCC41 = -SPCK
UI 8
7. Data transfer
24
7. Data transfer
25
TC ... only with topcontrol
Reg.Nr.
Byte // Bit
Descriptiondatatype
unit /status
23/24 Byte 46...49pump 1 operating hoursCAUTION: displayed in seconds!
UI 32 s
25/26 Byte 50...53pump 2 operating hoursCAUTION: displayed in seconds!
UI 32 s
27 Byte 54/55 -
28 Byte 56/57level L1value range: 0 … 100
SI 16 %
29 Byte 58/59level L2value range: 0 … 100
SI 16 %
Byte 60
operating mode pumps0 = redundancy mode1 = pump M1 only2 = pump M2 only3 = staggered mode4 = parallel mode
UI 8
Byte 61current priority pump0 = pump 1; 1 = pump 2
UI 8
Byte 62
operating mode level0 = automatic change1 = level L1 only2 = level L2 only
UI 8
Byte 63
operating mode makeup0 = amount-controlled1 = uncontrolled2 = time-controlled
UI 8
Byte 64
degassing: current operating stage0 = locked1 = pressure build-up2 = degassing3 = break4 = open valve5 = overpressure
UI 8
Byte 65TC: current preferred valve0 = valve Y31 = valve Y4
UI 8
30
31
32
Reg.Nr.
Byte // Bit
Descriptiondatatype
unit /status
33 Byte 66/67level start makeupvalue range: 0 … 100
SI 16 %
34 Byte 68/69level stop makeupvalue range: 0 … 100
SI 16 %
35/36 Byte 70...73 entire makeup amount up to now 32 lUI
37 Byte 74/75 makeup: remaining amount 16 lSI
38/39 Byte 76...79 makeup: remaining time 32 sUI
40/41 Byte 80...83 water treatment: remaining capacity 32 lUI
42/43 Byte 84...87degassing: remaining time of the currentoperating phasedisplayed in seconds
UI 32 s
44/45 Byte 88...91degassing: operating hoursdisplayed in seconds
UI 32 s
46 Byte 92/93P1min: set limitset value in menu "monitoring"value range: 0 … 4000
SI 16 bar (*100)
47 Byte 94/95P1max: set limitset value in menu "monitoring"value range: 0 … 4000
SI 16 bar (*100)
48 Byte 96/97Lmin: set limitset value in menu "monitoring"value range: 0 … 100
SI 16 %
Byte 98 UI 8
Bit 0P1min: current state ( , Alert)OK1 = Alert
OK, Alert
Bit 1P1max: current state ( , Alert)OK1 = Alert
OK, Alert
Bit 2L1min: current state ( , Alert)OK1 = Alert
OK, Alert
Bit 3 -
Bit 4 -
Bit 5 -
Bit 6 -
Bit 7 -
49
7. Data transfer
26
Reg.Nr.
Byte // Bit
Descriptiondatatype
unit /status
Byte 99 UI 8
Bit 0 -
Bit 1 -
Bit 2 -
Bit 3 -
Bit 4 -
Bit 5 -
Bit 6 -
Bit 7 -
50 Byte 100/101Lmax: set limitSetting value in the "monitoring" menuvalue range: 0 … 100
SI 16 %
51 Byte 102/103T1min: set limitSetting value in the "monitoring" menuvalue range: -500 … +1200
SI 16 °C (*10)
52 Byte 104/105T1max: set limitSetting value in the "monitoring" menuvalue range: -500 … +1200
SI 16 °C (*10)
Byte 106 UI 8
Bit 0Lmax: current state ( , Alert)OK1 = Alert
OK, Alert
Bit 1T1min: current state ( , Alert)OK1 = Alert
OK, Alert
Bit 2T1max: current state ( , Alert)OK1 = Alert
OK, Alert
Bit 3 -
Bit 4 -
Bit 5 -
Bit 6 -
Bit 7 -
49
53
7. Data transfer
27
Reg.Nr.
Byte // Bit
Descriptiondatatype
unit /status
Byte 107 UI 8
Bit 0 -
Bit 1 -
Bit 2 -
Bit 3 -
Bit 4 -
Bit 5 -
Bit 6 -
Bit 7 -
54 Byte 108/109T2min: set limitSetting value in the "monitoring" menuvalue range: -500 … +1200
SI 16 °C (*10)
55 Byte 110/111T2max: set limitSetting value in the "monitoring" menuvalue range: -500 … +1200
SI 16 °C (*10)
Byte 112 UI 8
Bit 0T2min: current state ( , Alert)OK1 = Alert
OK, Alert
Bit 1T2max: current state ( , Alert)OK1 = Alert
OK, Alert
Bit 2 -
Bit 3 -
Bit 4 -
Bit 5 -
Bit 6 -
Bit 7 -
Byte 113 UI 8
Bit 0 -
Bit 1 -
Bit 2 -
Bit 3 -
Bit 4 -
Bit 5 -
Bit 6 -
Bit 7 -
56
53
7. Data transfer
28
Reg.Nr.
Byte // Bit
Descriptiondatatype
unit /status
Byte 114 UI 8
Bit 0TC: overflow valve 1 coupling0 = output „Off“ valves close mechanically
ON OFF,
Bit 1TC: overflow valve 1 open1 = overflow valve opens
ON OFF,
Bit 2TC: overflow valve 1 close1 = overflow valve closes
ON OFF,
Bit 3TC: overflow valve 2 coupling0 = output „Off“ valves close mechanically
ON OFF,
Bit 4TC: overflow valve 2 open1 = overflow valve opens
ON OFF,
Bit 5TC: overflow valve 2 close1 = overflow valve closes
ON OFF,
Bit 6 -
Bit 7 -
Byte 115 UI 8
Bit 0MCA: switching valve open1 = switching valve opens
ON OFF,
Bit 1MCA: switching valve close1 = switching valve closes
ON OFF,
Bit 2 -
Bit 3 -
Bit 4 -
Bit 5 -
Bit 6 -
Bit 7 -
Byte 116MCA: operating mode0 = contact controlled1 = press.controlled
UI 8
Byte 117
from V1.26: : current operating stageMCA0 = off1 = makeup2 = circulation3 = pause circulation4 = locked5 = diverter valve Y5: open6 = diverter valve Y5: close
UI 8
58
57
57
7. Data transfer
29
TC MCA... only with topcontrol / ... only with multicontrol autofill
Reg.Nr.
Byte // Bit
Descriptiondatatype
unit /status
59/60 Byte 118..121electronics: operating hoursdisplayed in seconds
UI 32 s
61 Byte 122/123 vessel code 16SI
Byte 124 UI 8
Bit 0makeup available1 = Yes
YES NO,
Bit 1sensor T2 available1 = Yes
YES NO,
Bit 2level measurement L2 available1 = Yes
YES NO,
Bit 3 -
Bit 4 -
Bit 5 -
Bit 6 -
Bit 7 -
62 Byte 125
water treatment: configuration0 = not available1 = softening 6MWE2 = softening 12MWE3 = desalination 2MVE4 = desalination 4MVE
UI 8
Byte 126
degassing: operating mode0 = off1 = as per timer progr.2 = always enabled
UI 8
Byte 127
from V1.23: degassing device set-up0 = not available1 = pump degassing2 = degassing module
UI 8
63
62
62
7. Data transfer
30
Reg.Nr.
Byte // Bit
Descriptiondatatype
unit /status
64 Byte 128/129blocking temp.T1Setting value in the "degassing" menuvalue range: -500 … +400
SI 16 °C (*10)
65 Byte 130/131temperat. Limit T1Setting value in the "degassing" menuvalue range: -500 … +950
SI 16 °C (*10)
66 Byte 132/133blocking temp.T2Setting value in the "degassing" menuvalue range: -500 … +400
SI 16 °C (*10)
67 Byte 134/135temperat. Limit T2Setting value in the "degassing" menuvalue range: -500 … +950
SI 16 °C (*10)
Byte 136 free 8UI
Byte 137 free 8UI
Byte 138 free 8UI
Byte 139 free 8UI
Byte 140 free 8UI
Byte 141 free 8UI
Byte 142 free 8UI
Byte 143 free 8UI
68
69
70
71
7. Data transfer
31
Reg.Nr.
Byte // Bit
Descriptiondatatype
unit /status
Byte 144 UI 8
Bit 0 W11: time changed due to daylight saving , AlertOK
Bit 1 E1: data link error to basic circuit board , AlertOK
Bit 2 E7: write error I2C basic circuit board , AlertOK
Bit 3 E20: write error I2C module: binary signalling , AlertOK
Bit 4 E18: write error I2C module: analog sign. , AlertOK
Bit 5 E4: read error I2C basic circuit board , AlertOK
Bit 6 E19: read error I2C module: binary signalling , AlertOK
Bit 7 E17: read error I2C module analog sign. , AlertOK
Byte 145 UI 8
Bit 0 E13: transmitter 1o meas. signal too low , AlertPL OK
Bit 1 E12: transmitter 1o meas. signal too high , AlertPL OK
Bit 2 E15: transmitter 1u meas. signal too low , AlertPL OK
Bit 3 E14: transmitter 1u meas. signal too high , AlertPL OK
Bit 4 E11: transmitter P1 meas. signal too low , AlertOK
Bit 5 E10: transmitter P1 meas. signal too high , AlertOK
Bit 6 E8: temperature sensor T1 short circuit , AlertOK
Bit 7 E9: temperature sensor T1 break , AlertOK
Byte 146 UI 8
Bit 0 E21: temperature sensor T2 short circuit , AlertOK
Bit 1 E22: temperature sensor T2 break , AlertOK
Bit 2 E2: pump M1 start failed , AlertOK
Bit 3 E3: pump M1 stop failed , AlertOK
Bit 4 E23: pump M2 start failed , AlertOK
Bit 5 E24: pump M2 stop failed , AlertOK
Bit 6 E26: makeup amount exceeded , AlertMCF OK
Bit 7 W16: makeup remain. amount <20% , AlertMCF OK
Byte 147 UI 8
Bit 0 W17: softening remain. capacity <20% , AlertMWE OK
Bit 1 E28: softening change cartridge , AlertMWE OK
Bit 2 W4: temperature limit sensor T1 exceeded , AlertOK
Bit 3 W13: temperature limit sensor T2 exceeded , AlertOK
Bit 4 W2: manual mode at least 1 output , AlertOK
Bit 5 E16: dry run protection has been activated , AlertOK
Bit 6 E30: transmitter 2o meas. signal too low , AlertPL OK
Bit 7 E29: transmitter 2o meas. signal too high , AlertPL OK
72
73
7. Data transfer
32
Reg.Nr.
Byte // Bit
Descriptiondatatype
unit /status
Byte 148 UI 8
Bit 0 E32: transmitter 2u meas. signal too low , AlertPL OK
Bit 1 E31: transmitter 2u meas. signal too high , AlertPL OK
Bit 2 E0: device is disabled , AlertOK
Bit 3 E34: sms-module: pin code wrong , AlertOK
Bit 4 E35: sms-module: sim card error , AlertOK
Bit 5 E33: sms-module: no response , AlertOK
Bit 6 W19: sms-module: no network , AlertOK
Bit 7 W8: monitoring: P1min under-run , AlertOK
Byte 149 UI 8
Bit 0 W7: monitoring: P1max over-run , AlertOK
Bit 1 W6: monitoring: Lmin under-run , AlertOK
Bit 2 W5: monitoring: Lmax over-run , AlertOK
Bit 3 W10: monitoring: T1min under-run , AlertOK
Bit 4 W9: monitoring: T1max over-run , AlertOK
Bit 5 W15: monitoring: T2min under-run , AlertOK
Bit 6 W14: monitoring: T2max over-run , AlertOK
Bit 7 E5: max. run-time pump M1 exceeded , AlertOK
Byte 150 UI 8
Bit 0 E25: max. run-time pump M2 exceeded , AlertOK
Bit 1 E6: too many pump requests per period , AlertOK
Bit 2 E27: makeup: max. run-time exceeded , AlertOK
Bit 3 W3: accomplish periodic maintenance , AlertOK
Bit 4 W12: underpressure in vessel 1 ( 1o) , AlertPL OK
Bit 5 W18: underpressure in vessel 2 ( 2o) , AlertPL OK
Bit 6 E36: pump M1 error , AlertOK
Bit 7 E37: pump M2 error , AlertOK
Byte 151 UI 8
Bit 0 E38: write error analog module: 0 , AlertAO OK
Bit 1 E39: read error analog module: 0 , AlertAO OK
Bit 2 E40: external setpoint meas.signal too low , AlertOK
Bit 3 E41: external setpoint meas.signal too high , AlertOK
Bit 4 W20: demineral. remaMVE in.capacity <20% , AlertOK
Bit 5 E42: demineral. change cartridge , AlertMVE OK
Bit 6 W21: blocking temp. T1 sensor T1 below , AlertOK
Bit 7 W22: blocking temp. T2 sensor T2 below , AlertOK
74
75
7. Data transfer
33
Reg.Nr.
Byte // Bit
Descriptiondatatype
unit /status
Byte 152 UI 8
Bit 0 E43: ext. fault via digital input ! , AlertOK
Bit 1 W23: ext.warning via digital input ! , AlertOK
Bit 2 message 67 , AlertOK
Bit 3 message 68 , AlertOK
Bit 4 message 69 , AlertOK
Bit 5 message 70 , AlertOK
Bit 6 message 71 , AlertOK
Bit 7 message 72 , AlertOK
Byte 153 UI 8
Bit 0 message 73 , AlertOK
Bit 1 message 74 , AlertOK
Bit 2 message 75 , AlertOK
Bit 3 message 76 , AlertOK
Bit 4 message 77 , AlertOK
Bit 5 message 78 , AlertOK
Bit 6 message 79 , AlertOK
Bit 7 message 80 , AlertOK
Byte 154 UI 8
Bit 0 message 81 , AlertOK
Bit 1 message 82 , AlertOK
Bit 2 message 83 , AlertOK
Bit 3 message 84 , AlertOK
Bit 4 message 85 , AlertOK
Bit 5 message 86 , AlertOK
Bit 6 message 87 , AlertOK
Bit 7 message 88 , AlertOK
Byte 155 UI 8
Bit 0 message 89 , AlertOK
Bit 1 message 90 , AlertOK
Bit 2 message 91 , AlertOK
Bit 3 message 92 , AlertOK
Bit 4 message 93 , AlertOK
Bit 5 message 94 , AlertOK
Bit 6 message 95 , AlertOK
Bit 7 message 96 , AlertOK
76
77
7. Data transfer
34
Reg.Nr.
Byte // Bit
Descriptiondatatype
unit /status
Byte 156 free 8UI
Byte 157 free 8UI
Byte 158 free 8UI
Byte 159 free 8UI
Byte 160 free 8UI
Byte 161 free 8UI
Byte 162 free 8UI
Byte 163 free 8UI
Byte 164 free 8UI
Byte 165 free 8UI
Byte 166 free 8UI
Byte 167 free 8UI
Byte 168 free 8UI
Byte 169 free 8UI
Byte 170 free 8UI
Byte 171 free 8UI
Byte 172 free 8UI
Byte 173 free 8UI
Byte 174 free 8UI
Byte 175 free 8UI
Byte 176 free 8UI
Byte 177 free 8UI
Byte 178 free 8UI
Byte 179 free 8UI
Byte 180 free 8UI
Byte 181 free 8UI
Byte 182 free 8UI
Byte 183 free 8UI
Byte 184 free 8UI
Byte 185 free 8UI
Byte 186 free 8UI
Byte 187 free 8UI
Byte 188 free 8UI
Byte 189 free 8UI
Byte 190 free 8UI
Byte 191 free 8UI95
86
87
88
89
90
91
92
93
94
85
78
79
80
81
82
83
84
7. Data transfer
35
7. Data transfer
36
7.5. Bus module Modbus Input Register(data register 2)
The data register 2 shows the organisation of the data in the memory area of the bus
module which can be sent via a write command (10H Write Multiple Registers) from the
Modbus master to the bus module. All Multibyte data types are organised asRTU MSB
(Most Significant Byte).
Reg.Nr.
Byte // Bit
Descriptiondatatype
unit /status
Byte 0 binary remote acknowledgement UI 8
Bit 0reset fault messages1 = fault messages get reset
ON OFF,
Bit 1reset warning messages1 = warning messages get reset
ON OFF,
Bit 2makeup : reset amountMCF1 = makeup amount gets reset
ON OFF,
Bit 3makeup : one-time fillingMCF1 = one-time filling gets executed
ON OFF,
Bit 4degassing: start fast degassing1 = fast degassing gets started
ON OFF,
Bit 5 -
Bit 6 -
Bit 7 -
Byte 1 UI 8
Bit 0
device function enabling via bus: Off-On1 = device enabling via bus is active.Note: only effective, if "device functionenabling via bus enabled" ist set.
ON OFF,
Bit 1
Bit 2 -
Bit 3 -
Bit 4 -
Bit 5 -
Bit 6 -
Bit 7 -
Byte 2 free 8UI
Byte 3 free 8UI
0
1
7. Data transfer
37
TC ... only with topcontrol
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Notes
8. Notes
38
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Notes
8. Notes
39
ANTON EDER GMBHA-9909 Leisach 52Tel.: +43 (0) 4852 644 77Fax: +43 (0) 4852 644 77-20
Branch office A-5733 Bramberg | Weyerstraße 350 | Tel.: +43 (0) 6566 7366Branch office A-1230 Wien | Gorskistraße 15 | Tel.: +43 (0) 1 985 37 30