andover controls - dcx 250 installation guide

29
Andover Controls Corporation i DCX 250 Installation Guide www.PDF-Zoo.com

Upload: jbhall55

Post on 01-Jan-2016

69 views

Category:

Documents


5 download

DESCRIPTION

Andover Controls - DCX 250 Installation Guide

TRANSCRIPT

Page 1: Andover Controls - DCX 250 Installation Guide

Andover Controls Corporation i

DCX 250Installation Guide

www.PDF-Zoo.com

Page 2: Andover Controls - DCX 250 Installation Guide

ii DCX 250 Installation Guide

Version F

Reproduction or distribution forbidden.

Copyright 1997 by Andover Controls.

Subject to change without notice.

Order No. 30-3001-196

Copyright 1997Andover Controls Corporation300 Brickstone SquareAndover, Massachusetts 01810All Rights Reserved.

Published by the Engineering Department at Andover Controls Corporation.

IMPORTANT NOTICE

This product is subject to change without notice. This document does not con-stitute any warranty, express or implied. Andover Controls Corporation re-serves the right to alter capabilities, performance, and presentation of this product at any time.

www.PDF-Zoo.com

Page 3: Andover Controls - DCX 250 Installation Guide

Andover Controls Corporation iii

Preface

The DCX 250 Installation Guide presents instructions for installingthe DCX 250 on Infinet. It first presents site preparation information and then step-by-step installation instructions.

This manual does not include programming information. For how to program the DCX 250, see the Andover Controls Infinity CXProgrammer’s Guide.

We recommend you read the Infinity Network Configuration Guide to plan your entire network before installing a single controller.

www.PDF-Zoo.com

Page 4: Andover Controls - DCX 250 Installation Guide

iv DCX 250 Installation Guide

www.PDF-Zoo.com

Page 5: Andover Controls - DCX 250 Installation Guide

Andover Controls Corporation v

Contents

Setting Up the DCX 250 Site/System Setup Requirements .............................................................2

Cabinet Dimensions and Weight ...................................................3 Power Requirements ......................................................................3 Cable Limitations ...........................................................................3 Lightning Protection ......................................................................4 Building Ground Requirements .....................................................4 Inspecting the Ground ....................................................................5 Environmental Requirements ........................................................5 Laying Out the Site Setup ..............................................................6

Installing the DCX 250 ............................................................................7 Unpacking ......................................................................................7 Parts Required ................................................................................7 Mounting ........................................................................................7 Connecting the AC Power Cable to the Power Supply ................. 9 Connecting the Infinet .................................................................11 Wiring the Infinet to the Infinity CX 9000 .................................. 13

Powering Up/Adjusting the Controller ..................................................14 Connecting the Battery ................................................................14 Powering Up ................................................................................14

www.PDF-Zoo.com

Page 6: Andover Controls - DCX 250 Installation Guide

vi DCX 250 Installation Guide

Checking That Controller Is Operating .......................................15 Reset Button .................................................................................16 Adjusting the LCD View Angle ..................................................16 Connecting the Andover Controls Service Tool ..........................18

www.PDF-Zoo.com

Page 7: Andover Controls - DCX 250 Installation Guide

Andover Controls Corporation vii

Figures

Figure 1. Tag That Identifies the Controller ...............................................6Figure 2. Dimensions of DCX 250 Cabinet, Top View..............................7Figure 3. Dimensions of DCX 250 Cabinet, Front View ........................8Figure 4. Location of AC Power Connection, Inside DCX 250 Cabinet ...10Figure 5. Metal Plate and Screw for Power Supply Wire .....................11Figure 6. Location of Infinet Connection, Inside DCX 250 Cabinet .......12Figure 7. Infinet Cable Wiring ..................................................................13Figure 8. Location of Battery, Indicator Lights, and Reset Button,

Inside, on Back of DCX 250 Display .......................................15Figure 9. Location of LCD View Angle Adjustment, Inside,

on Back of DCX 250 Display ...................................................17Figure 10. Location of Service Port, Inside DCX 250 Cabinet .................18

www.PDF-Zoo.com

Page 8: Andover Controls - DCX 250 Installation Guide

viii DCX 250 Installation Guide

www.PDF-Zoo.com

Page 9: Andover Controls - DCX 250 Installation Guide

DCX 250 Installation Guide 1

Sett ing U p the DCX 250

This manual covers the following:

• Site/System Setup Requirements

• Installing the DCX 250

• Powering Up/Adjusting the Controller

This manual does not include programming information. For how to program the DCX 250, see the Andover Controls Infinity ControllerProgrammer’s Guide.

Warranty RegistrationYour warranty is effective for 18 months starting on the date the system is shipped.

WarningBe sure wiring and installations comply with local, state, and national electrical codes.

www.PDF-Zoo.com

Page 10: Andover Controls - DCX 250 Installation Guide

Hardware Installation

2 DCX 250 Installation Guide

Site/System Set up RequirementsBefore you proceed to install the system, you should map out where you plan to install each controller, terminal/workstation, and modem. When planning the sites, be aware of any electrical interference that may oc-cur. You also need to be aware of cabinet dimensions, power requirements, cable limitations, and environmental requirements.

WarningThis equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions in this manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

NoteThis digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.

AvisLe présent appareil numérique n’émet pas de bruits radioélectriques dépassant les limites applicables aux appareils numériques de la class A prescrites dans le Règlement sur le brouillage radioélectrique édicté par le ministère des Communications du Canada.

www.PDF-Zoo.com

Page 11: Andover Controls - DCX 250 Installation Guide

Hardware Installation

DCX 250 Installation Guide 3

Cabinet Dimens ions and Weight

Each DCX 250 cabinet (if it has a cabinet) is approximately 8.1 × 8.1 × 3.5 in. and weighs 8.5 lbs.

Power Requirem ents

CautionIf the DCX 250 is in its own cabinet, it should receive power from its own independent, unswitched circuit.

The DCX 250 operates on 24 VAC +/–20% 50 or 60 Hz (for smoke con-trol applications, 24 VAC +10/–15%, 60 Hz). The DCX 250 consumes up to 18 VA of power.

Cable Limitations

The maximum cable length for Infinet is 4,000 ft at 19,200 baud (up to 32 Infinet controllers). You can extend Infinet beyond 4,000 ft or put more than 32 Infinet controllers on less than 4,000 ft by using the In-fiLink 200 amplification module.

Cables that form Infinet are 24-gauge, single-twisted-pair, tinned, shielded copper wire. Use the following cables1 or their equivalents:

NoteYou must use shielded cables for Infinet to ensure compliance with the Class A FCC limits and to communicate reliably.

• Brand Rex # H 9002 (single-pair)

• Anixter # 9J2401021 (single-pair plenum cable)

The cable should have a nominal impedance of 100 Ohms and anominal velocity of propagation of 78%.

1. You can also use any cables you may already have in place for ACNET or LBUS.

www.PDF-Zoo.com

Page 12: Andover Controls - DCX 250 Installation Guide

Hardware Installation

4 DCX 250 Installation Guide

Capacitance of Infinet cable should be nominal, below 12.5 pF/ft be-tween conductors and below 22 pF/ft between the conductor connected to ground and the next conductor.

Lightnin g Protec tion

WarningWhen running cables between buildings you must install lightning arresters for Infinet to prevent electromagnetic disturbances.

Use lightning arresters at each point where Infinet cable enters or exits a building. Use the following arrester:

Two pair gas tube arrester, Andover Controls # 01-2100-299.

Bui lding G round Requireme nts

WarningBe sure that all Infinity hardware products from Andover Controls Corporation are grounded to true earth ground. This kind of ground protects the equipment from voltage transients and other power surges in the area. We cannot guarantee that the controller system will operate as documented unless you properly ground all controllers.

WarningBe sure to have your grounds inspected before you begin the installation process to be sure your municipality follows the National Electrical Code. Many municipalities do not and may have substandard electrical grounds.

An example of a substandard ground is a galvanized steel cold water pipe. As the pipe corrodes, it does not act as a true ground. The corro-sion acts as an insulator, raising the potential of the pipe with respect to the ground.

www.PDF-Zoo.com

Page 13: Andover Controls - DCX 250 Installation Guide

Hardware Installation

DCX 250 Installation Guide 5

When lightning strikes in the area of the installation, it drastically changes the potential of the earth. Since properly grounded Andover Controls units respond to changes in potential more rapidly than poorly grounded electrical systems, a poorly grounded building tries to reach ground through the Andover Controls system. The surge of current can destroy electronic components on the controller board.

Surges of much lower potential than lightning also impact the reliability of Andover Controls equipment.

Inspec ting the Ground

You can check your ground as follows:

1. Check your ground by first inspecting the building power distribution panel for earth ground termination. If the ground termination is any of the following, it is not adequate and must be corrected:

• Does not exist.

• Is connected to a corroded or galvanized pipe.

• Is connected using a small gauge wire (less than 14 AWG).

2. Be sure your Andover Controls cabinet is connected to the ground with a copper conductor that terminates at the distribution panel.

Environm ental Requi rements

The DCX 250 operates in rooms with temperatures ranging from 40 to 104°F and with humidity of between 30 and 85%, noncondensing.

The controller is designed to withstand the dust normally present in an equipment room, without any additional enclosures or filtering.

The cabinet that Andover Controls Corporation encloses the DCX 250 in is an Underwriter Laboratories listed enclosure.

www.PDF-Zoo.com

Page 14: Andover Controls - DCX 250 Installation Guide

Hardware Installation

6 DCX 250 Installation Guide

Laying Out the Site Setup

You may want to draw a map of where you plan to put each controller and store it in a notebook.

Find the tag attached to each controller that gives the number of the con-troller. Before you remove any tags, be sure the tag has all of the following information on it:

• Model number.

• Serial number.

• Location of the DCX 250 controller.

• Communications port the Infinet connects to on the Infinity CX 9000. (The DCX 250 installed inside the Infinity CX 9000 cabinet is automatically on COMM2.)

Figure 1 shows what the tag looks like.

Then collect the tags. You will need to know where your controllers are located when you later assign a name to each controller and each input and output.

Figure 1. Tag That Identi fies the Controller

Model DCX 250S/N 09878Volts 24 VAC 50/60 HzAmps .55 AOutput Contacts

Volts XXXXXAmps XXXXX Date XXX

S/N 09878Location Room 10DCX 250 Comm Port 2

ANDOVER CONTROLS

Andover Controls Corp. Andover, MA 01810 USA

Energy ManagementEquipment

TearHere

U L

You MayAdd asReminders

www.PDF-Zoo.com

Page 15: Andover Controls - DCX 250 Installation Guide

Hardware Installation

DCX 250 Installation Guide 7

Insta lling t he DCX 250Unpacking

Be careful when unpacking the unit to not damage the packaging material—you must reuse it if you ship the product back for repair.

Parts Required

To install a single controller you start with the following parts:

• DCX 250 Controller (in its own cabinet)

• AC Power Cable and Infinet Cable

• Infinity CX 9000 Controller

Mounti ng

Figure 2 gives dimensions for mounting a DCX 250 any of these ways:

• Fitting entire cabinet in wall cutout so it is flush with wall

• Screwing backplate of cabinet to wall

Figure 2. Dimens ions of DCX 250 Cabinet, Top View

2.40

3.70

www.PDF-Zoo.com

Page 16: Andover Controls - DCX 250 Installation Guide

Hardware Installation

8 DCX 250 Installation Guide

WarningNever drill holes in the DCX 250 cabinet or boards. A metal shaving could easily short circuit the electronics.

Figure 3 shows more dimensions for mounting the DCX 250. You should connect cables to the DCX 250 before you flush mount it.

Figure 3. Dimens ions of DCX 250 Cabinet, Front View

Mounting Hardware Providedfor Conventional WallboardMounting. Must NotchCutout for Hardware.

Mounting Holes For #8 Screws4 Places , (Optional)

3.081.00

1.50

6.71

8.08Min

Opening

1.50

5.08

8.08Min Opening

.08Typ

Mounting Holesfor #10 Screws4 Places (Optional)

www.PDF-Zoo.com

Page 17: Andover Controls - DCX 250 Installation Guide

Hardware Installation

DCX 250 Installation Guide 9

Connecting the AC Powe r Cableto the Po wer Supply

If you ordered the DCX 250 in its own cabinet (to be placed on the In-finet outside the Infinity CX 9000), the DCX 250 has its own power supply. So you need to connect the AC power cable.

WarningBe sure the AC power cable is not connected to an electrical power source while you are wiring the controller, or you could receive an electrical shock that is life-threatening.

NoteIf the installation requires the secondary of the 24 V transformer to be grounded, always connect the "neutral" to ground and only ground it at the transformer.

To connect the AC power cable, proceed as follows:

1. Lift off the front display panel on the DCX 250.

Figure 4 shows the inside of the DCX 250 controller.

Notice the board now directly in front of you is the power supply. Look to the upper left corner for the AC power connection. You must wire the AC power to the three screws on the upper left side of the power supply.

2. Thread the AC power cable through the cutout in the top of the DCX 250 cabinet.

CautionBe sure to connect all three wires, HOT, NEUTRAL, and GROUND. Otherwise, the controller could malfunction.

www.PDF-Zoo.com

Page 18: Andover Controls - DCX 250 Installation Guide

Hardware Installation

10 DCX 250 Installation Guide

3. The three screws are labeled GND NEUT HOT. The three wires at the end of your AC cable are black, white, and green.

4. Place the green wire under the metal plate behind the left screw, labeled GND.

Figure 4. Location of AC Power Connection ,Insid e DCX 250 Cabinet

GN

DN

EU

TH

OT

FRONT VIEW, CABINET OPEN

SIDE, TOP VIEW

AC PowerConnection

Power Supply

AC PowerCable EntersHere

Infinet CableEnters Here

www.PDF-Zoo.com

Page 19: Andover Controls - DCX 250 Installation Guide

Hardware Installation

DCX 250 Installation Guide 11

5. Tighten the screw with a flathead screw driver.

Figure 5 shows the position of the plate, where to place the wire, and how the screw fits on the plate. You can see how the screw holds the plate in place once you tighten it.

Figure 5. Metal Plate and Sc rew for Power Suppl y Wire

6. Place the white wire under the metal plate behind the middle screw, labeled NEUT.

7. Tighten the screw with a flathead screw driver.

8. Place the black wire under the metal plate behind the right screw, labeled HOT.

9. Tighten the screw with a flathead screw driver.

Connecti ng the Infin et

You wire the Infinet to the controller using the following procedure:

1. Lift off the front display panel on the DCX 250 controller cabinet.

Look at the board now directly in front of you.

Figure 6 shows the Infinet connection, a block terminal connector in the upper right corner. You must wire Infinet to that connector.

2. Thread the Infinet cable through the cutout in the top of the controller.

Insert Wire Here

Metal Plate

www.PDF-Zoo.com

Page 20: Andover Controls - DCX 250 Installation Guide

Hardware Installation

12 DCX 250 Installation Guide

Figure 6. Location of Infinet Connection,Insid e DCX 250 Cabinet

GN

DN

EU

TH

OT

FRONT VIEW, CABINET OPEN

SIDE, TOP VIEW

InfinetConnection

Power Supply

AC PowerCable EntersHere

Infinet CableEnters Here

www.PDF-Zoo.com

Page 21: Andover Controls - DCX 250 Installation Guide

Hardware Installation

DCX 250 Installation Guide 13

Figure 7 illustrates how to wire the Infinet cable to the block terminal connector.

Figure 7. Infinet Cable Wiring

3. Trim back the shield over the wires.

4. Slip the first wire from the incoming Infinet cable and the first wire from the outgoing Infinet cable into the hole beneath the screw labeled with a plus sign.

5. Tighten the screw down on it until the screw holds the wires in place.

6. Slip the second (usually black) wire from each Infinet cable under the screw labeled with a minus sign (middle) and tighten the screw down on them.

7. Slip the shields from the incoming and outgoing Infinet cables under the screw labeled SHLD and tighten the screw down on them.

Wiring the Infi net to the Infinity CX 9000

You connect the last piece of Infinet cabling to the Infinity CX 9000 as explained in the Andover Controls Infinity CX 9000 Hardware Installation Guide.

+

SHLD

Infinet Connection

WHITE WHITE

BLACK

BLACK

www.PDF-Zoo.com

Page 22: Andover Controls - DCX 250 Installation Guide

Hardware Installation

14 DCX 250 Installation Guide

Poweri ng Up/Adjusting the ControllerBoth the DCX 250 inside the Infinity CX 9000 and the DCX 250 in its own cabinet have a battery you need to connect.

Connecting the Battery

Lift off the front display panel on the DCX 250. Inside, on the back of

the display screen, find the AA battery on the upper left of the board.

Figure 8 shows the location of the battery. Remove the plastic tab below the clip on the battery to activate the battery.

The battery is a 850 mA-hr 3.6 V primary lithium battery that maintains RAM when AC power goes out.

Powerin g Up

The DCX 250 inside the Infinity CX 9000 runs off the power supply of the Infinity CX and begins operating when you connect AC power to the Infinity CX 9000.

For the DCX 250 in its own cabinet, you must check to be sure the fol-lowing are correct:

1. Be sure the AC power is wired properly. Check to be sure all three wires have been connected.

2. Be sure the controller has a true earth ground.

3. Be sure you have used the proper cables and correct lengths.

4. Be sure the battery is connected.

If you have completed all appropriate sections in this manual and in-stalled all Infinet controllers, you are now ready to power up the controller.

12---

www.PDF-Zoo.com

Page 23: Andover Controls - DCX 250 Installation Guide

Hardware Installation

DCX 250 Installation Guide 15

To start the controller, turn on the AC power source (or close the power connection) and the controller starts automatically.

Figure 8. Location o f Battery, Indicator Li ghts, and Reset Button, Insid e, on Back of DCX 250 Disp lay

Checkin g That Controll er Is Operating

Lift off the front display panel on the DCX 250. Inside, on the back of the display, are the indicator lights.

The illustration above shows the RD (green) and TD (yellow) lights to the far left middle and the green CPU light near the center. The small red square to the upper right of the CPU light is the RESET button.

Once the controller starts, the following occurs (and also occurs if you press RESET):

1. The CPU light begins flashing and flashes every .2 sec.

2. The TD light immediately starts flashing after you let go of the button to show data is being transmitted.

3.6 V LithiumBattery

RD Light

TD LightResetButton

CPU Light

LCD ViewAngle ADJ

TestPins

- +

www.PDF-Zoo.com

Page 24: Andover Controls - DCX 250 Installation Guide

Hardware Installation

16 DCX 250 Installation Guide

3. The RD light begins flashing only if data is being received from other controllers on the network. This may not happen immediately.

4. If the CPU light flashes every .1 sec, the CPU has failed an internal test.

For help with troubleshooting, contact the Andover Controls Technical Services Department.

Reset Butto n

The RESET button is the red square button to the upper right of the CPU light on the controller board (see Figure 8). You press it to initiate a warm start. The same process that occurs when you power up AC power occurs when you press RESET.

Adj usting the LCD View Angle

The LCD view angle adjustment knob is about 1 in. to the left of the lower right corner of the board.

Figure 9 shows the location of the knob. You turn the knob to adjust the angle of the display.

The contrast changes at different viewing angles. Adjust it to your needs.

www.PDF-Zoo.com

Page 25: Andover Controls - DCX 250 Installation Guide

Hardware Installation

DCX 250 Installation Guide 17

Figure 9. Location of LCD View Angle Adjustment, Inside, on Back of DCX 250 Display

3.6 V LithiumBattery

RD Light

TD LightResetButton

CPU Light

LCD ViewAngle ADJ

TestPins

- +

www.PDF-Zoo.com

Page 26: Andover Controls - DCX 250 Installation Guide

Hardware Installation

18 DCX 250 Installation Guide

Connecti ng the Andov er Control s Servi ce Tool

The SERVICE PORT is an RJ 11 (phone) connector on the upper rightside of the power supply, left of the Infinet connection (see Figure 10).

You connect the Andover Controls Service Tool to the DCX 250. The service tool accesses all DCX 250s and other Infinet controllers on the same network. For information on availability of the Andover Controls Service Tool, contact your Andover Controls representative.

Figure 10. Locatio n of Service Port, Inside DCX 250 Cabinet

GN

DN

EU

TH

OT

FRONT VIEW, CABINET OPEN

SIDE, TOP VIEW

Service Port

Power Supply

AC PowerCable EntersHere

Infinet CableEnters Here

www.PDF-Zoo.com

Page 27: Andover Controls - DCX 250 Installation Guide

DCX 250 Installation Guide Index-1

Index

AAC power

wiring 9

Bbattery

location of 14

Ccabinet

dimensions 3cable

for Infinet 3for lightning protection 4

circuit requirements for power 3

Ddimensions

cabinet 3for mounting 7, 8

Gground

correcting 5inspecting 5requirements 4

Iindicator lights

understanding 15Infinet

connecting 11lightning arrester for 4

Infinet cable numbers 3

LLCD knob

location of 16lightning arrester

for Infinet 4

M

mountingdimensions for 7, 8

P

partsrequirements 7

power requirementscircuit 3

power surgespreventing 4

powering upprocedure to prepare for 14

R

repairpackaging required to ship for 7

requirementsparts 7power 3

RESET buttonlocation of 16

S

service portpurpose of 18

Service Toolwhere to connect 18

T

temperaturesfor operating 5

W

wiringAC power 9correct wire gauge for ground 5Infinet connection 11

www.PDF-Zoo.com

Page 28: Andover Controls - DCX 250 Installation Guide

Index-2 DCX 250 Installation Guide

www.PDF-Zoo.com

Page 29: Andover Controls - DCX 250 Installation Guide

30-3001-196 DCX 250 Installation Guide Rev F

www.PDF-Zoo.com