analysis of voltage problems white
DESCRIPTION
masaya ka na sa kanyaTRANSCRIPT
VOLTAGE TERMINOLOGIESVOLTAGE TERMINOLOGIES
1. NOMINAL SYSTEM VOLTAGE1. NOMINAL SYSTEM VOLTAGEThe voltage by which a portion of the system is designated, and to which certain operating characteristics of the system are related. Each nominal system voltage pertains to a portion of the system bounded by transformers or utilization equipment.
2. SERVICE 2. SERVICE VOLTAGEVOLTAGEThe voltage at the point where the electrical
system of the supplier and the electrical system of the user are connected.
Taken from ANSI C84.1-1995 [Electric Power Systems and Equipment - Voltage Ratings (60 Hz)]
VOLTAGE TERMINOLOGIESVOLTAGE TERMINOLOGIESVOLTAGE TERMINOLOGIESVOLTAGE TERMINOLOGIES
3. UTILIZATION VOLTAGE3. UTILIZATION VOLTAGE
The voltage at the line terminals of utilization equipment.
4. NOMINAL UTILIZATION 4. NOMINAL UTILIZATION VOLTAGEVOLTAGEThe voltage rating of certain utilization
equipment used on the system.The voltage at which the operating and performance characteristics of equipment are referred.
Taken from ANSI C84.1-1995 [Electric Power Systems and Equipment - Voltage Ratings (60 Hz)]
NOMINAL SYSTEM
VOLTAGE
SERVICE VOLTAGE
UTILIZATIONVOLTAGE
A SIMPLE SECONDARY SYSTEM A SIMPLE SECONDARY SYSTEM INDICATING THE VOLTAGESINDICATING THE VOLTAGES
A SIMPLE SECONDARY SYSTEM A SIMPLE SECONDARY SYSTEM INDICATING THE VOLTAGESINDICATING THE VOLTAGES
NOMINAL UTILIZATION
VOLTAGE
VOLTAGE LIMITS ALLOWED US BY THE VOLTAGE LIMITS ALLOWED US BY THE DISTRIBUTION CODEDISTRIBUTION CODE
VOLTAGE LIMITS ALLOWED US BY THE VOLTAGE LIMITS ALLOWED US BY THE DISTRIBUTION CODEDISTRIBUTION CODE
± 10% from nominal measured at the Connection Point (Metering Point)
230 V 207 V 253 V
460 V 414 V 506 V
Nominal VoltageAllowable Limits
Minimum(-10%)
Maximum(+10%)
34.5 kV* 31.05 kV 37.95 kV
*For primary metered customers
VOLTAGE LIMITS ALLOWED US BY THE DISTRIBUTION CODE
VOLTAGE LIMITS ALLOWED US BY THE DISTRIBUTION CODE
FORMULA FOR COMPUTING VARIATION FROM NOMINAL VOLTAGE
FORMULA FOR COMPUTING VARIATION FROM NOMINAL VOLTAGE
% VAR. =
Measured/GivenVoltage
NominalVoltage
X 100%
NominalVoltage-
SAMPLE COMPUTATIONS OF VOLTAGE VARIATION
SAMPLE COMPUTATIONS OF VOLTAGE VARIATION
Given:
Vmin = 215V
Solution:
%Var.215 - 230
230= X 100% =
EXAMPLE 1:
Given:
Vmax = 250V
Solution:
%Var.250 - 230
230= X 100% =
EXAMPLE 2:
- 6.52%
+ 8.70%
COMMON VOLTAGE PROBLEMSCOMMON VOLTAGE PROBLEMSCOMMON VOLTAGE PROBLEMSCOMMON VOLTAGE PROBLEMS
1. . Undervoltage (Low Voltage)Undervoltage (Low Voltage)
2. . Overvoltage (High Voltage)Overvoltage (High Voltage)
3. . Voltage Unbalance (Imbalance)Voltage Unbalance (Imbalance)
4. . Voltage Sag (Dip)Voltage Sag (Dip)
5. . Voltage SwellVoltage Swell
6. . Voltage Fluctuation (Flicker)Voltage Fluctuation (Flicker)
Refers to a measured voltage having a value less than the nominal for a period of time greater than 1 minute. Typical values are 0.8 - 0.9 p.u.
UNDERVOLTAGEUNDERVOLTAGE
UNDERVOLTAGEUNDERVOLTAGE
Overextended secondary lines
Undersized/overloaded secondary lines, transformer lead wires or service drop Loose connections
Overloaded transformer
Poor/loose grounding or cut system neutral
Wrong tapping of dual voltage transformers in wye-wye banks (120/240V instead of 139/277V) Low transformer tap-setting
Low primary voltage
Causes:Causes:
Causes Of Low Primary Supply VoltageCauses Of Low Primary Supply Voltage
Loose connections on the primary
Overextended primary lines Undersized primary conductors Low substation bus voltage
De-energized substation/line capacitor banks
Disabled or defective OLTC of substation power transformer
Defective substation/line AVRs
UNDERVOLTAGEUNDERVOLTAGE
Equipment malfunction
Dropout of motor controllers
Heating losses and speed changes in induction motors
Shutdown of electronic and computer eqpt.
Reduced output of capacitor banks
Effects:Effects:
UNDERVOLTAGEUNDERVOLTAGE
Load shifting or load splitting
Reconductoring
Correction of loose connections
Raising of transformer tapping
Installation of line capacitors and AVRs
Typical Solutions:Typical Solutions:
Upgrading of source transformer
Refers to a measured voltage having a value greater than the nominal for a period of time greater than 1 minute. Typical values are 1.1 - 1.2 p.u.
OVERVOLTAGEOVERVOLTAGE
OVERVOLTAGEOVERVOLTAGE
High tap-setting of distribution transformer
High primary voltage
Loose or isolated system neutral/grounding
Wrong transformer connection, polarity or tapping
Single-phasing of open-wye, open-delta bank
Causes:Causes:
Failure of electronic devices
Shortened equipment life
Unwanted operation in some relays
Damage to capacitors
Effects:Effects:
OVERVOLTAGEOVERVOLTAGE
Lowering of transformer tap-setting
Automatic or manual switching of capacitor banks during off-peak periods
Installation of additional pole grounding
Typical Solutions:Typical Solutions:
OVERVOLTAGEOVERVOLTAGE
The maximum deviation from the average of the three phase voltages, divided by the average of the three phase voltages, expressed in percent.
UNBALANCED VOLTAGEUNBALANCED VOLTAGE
FORMULA FOR COMPUTING VOLTAGE FORMULA FOR COMPUTING VOLTAGE UNBALANCE ON THREE PHASE SYSTEMSUNBALANCE ON THREE PHASE SYSTEMS
FORMULA FOR COMPUTING VOLTAGE FORMULA FOR COMPUTING VOLTAGE UNBALANCE ON THREE PHASE SYSTEMSUNBALANCE ON THREE PHASE SYSTEMS
% VOLTAGE UNBALANCE =
Maximum Deviationfrom the Average
Average VoltageX 100%
The Distribution Code prescribes an limit of 2.5% at the Connection Point during normal operating conditions.
SAMPLE COMPUTATION OF VOLTAGE UNBALANCE
SAMPLE COMPUTATION OF VOLTAGE UNBALANCE
% Unb.8.33V
228.33V= X 100% = 3.65%
Given:
Va = 220V, Vb = 230V, Vc = 235V
Required:
% Voltage Unbalance
Solution:
Vave220 + 230 + 235
3= = 228.33V
Maximum Deviation = 220 - 228.33 = 8.33V
Unbalanced secondary load
Loose connections
Loose neutral or insufficient grounding
Non-uniform transformer taps
Large difference in transformer impedances
One-phase out
De-energized capacitor units
Single-phasing of open-wye, open-delta bank
Unbalanced loading of the primary line
Defective AVR
Causes:Causes:UNBALANCED VOLTAGEUNBALANCED VOLTAGE
UNBALANCED VOLTAGEUNBALANCED VOLTAGE
Overheating of three-phase motors
Effects:Effects:
Shutdown of equipment due to operation of unbalanced voltage (zero-sequence) relay
Load balancing
Typical Typical Solutions:Solutions:
Correction of loose connections
Installation of additional pole grounding
Installation of AVRs
MOTOR DERATING FACTOR DUE TO UNBALANCED VOLTAGE
MOTOR DERATING FACTOR DUE TO UNBALANCED VOLTAGE
Der
atin
g F
acto
r
0 1 432 5
1.0
0.9
0.8
0.7
Percent Voltage Unbalance
Taken from 14.35 of NEMA MG 1 - 1993
RMS voltage variation between 0.1 to 0.9 of the nominal voltage for less than 1 minute.
VOLTAGE SAG (DIP)VOLTAGE SAG (DIP)
VOLTAGE SAG (DIP)VOLTAGE SAG (DIP)
Line-to-ground faults
Starting of large loads (such as motors, ACU and arc furnaces)
Loose connections
Causes:Causes:
Shutdown of sensitive loads
Effects:Effects:
Flickering or turning off of lights
VOLTAGE SAG (DIP)VOLTAGE SAG (DIP)
Increasing the size of conductor and transformers feeding loads with high inrush current Reduced-voltage motor starters
Use of UPS or constant voltage transformers (CVTs) for sensitive electronic loads
Typical Typical Solutions:Solutions:
RMS voltage variation exceeding 1.1 p.u. for less than 1 minute.
VOLTAGE SWELLVOLTAGE SWELL
VOLTAGE SWELLVOLTAGE SWELL
Line-to-ground faults
Switching-on of capacitor bank Dropping of large loads
Causes:Causes:
Failure of of electronic and computer devices
Shortened equipment life
Unwanted operation in some relays
Effects:Effects:
Damage to capacitors
VOLTAGE SWELLVOLTAGE SWELL
Ensure of system neutral
Scheduling of capacitor switching
Typical Typical Solutions:Solutions: Eliminate causes of faults
Series of random voltage changes. The changes normally are between 95% to 105%.
VOLTAGE FLUCTUATIONVOLTAGE FLUCTUATION
VOLTAGE FLUCTUATIONVOLTAGE FLUCTUATION
Loads with significant current variations such as arc furnaces, sawmills and arc welders. Loose connections
Causes:Causes:
Effects:Effects: Annoying variation in light output (flicker)
from incandescent and discharge light sources Video output distortion
VOLTAGE FLUCTUATIONVOLTAGE FLUCTUATION
Correction of loose connections
Reconductoring
Typical Solutions:Typical Solutions:
Provision of separate source for the loads causing the problem
MISCELLANEOUSMISCELLANEOUS
TOPICSTOPICS
A. Voltage MismatchA. Voltage Mismatch
B. Power Factor Correction CapacitorsB. Power Factor Correction CapacitorsC. Improper Setting of Over- and
Under-voltage ProtectionC. Improper Setting of Over- and
Under-voltage Protection
D. Deficiencies in the Customer’s Distribution System
D. Deficiencies in the Customer’s Distribution System
COMMON PROBLEMS AT THE CUSTOMER SIDE
COMMON PROBLEMS AT THE CUSTOMER SIDE
A.A. Voltage Mismatch Voltage MismatchSome customer equipment, usually motors, are rated either 220 volts or 440 volts. The motors can successfully operate in supply voltages of up ±10% of their rating (198V to 242V for 220-volt motors and 396V to 484V for 440-volt motors). Our 230- and 460-volts supply voltage, meanwhile, could reach 253V and 506V, respectively, which although still within the ERB limits, are already above the operating range of the motors.
Solutions at the Customer Side:
1. Install a special transformer or voltage regulator for the equipment.
Solutions at the Utility Side:
1. Adjust the tap setting of the source transformer after careful evaluation of the customer’s existing supply voltage.
COMMON PROBLEMS AT THE CUSTOMER SIDE
COMMON PROBLEMS AT THE CUSTOMER SIDE
B.B. Power Factor Correction Power Factor Correction CapacitorsCapacitors
Most industrial and commercial customers install capacitors to improve the power factor of their system. However, capacitors also raise the system’s voltage and could cause overvoltages during light load/off-peak periods when switched-on permanently .
Solutions at the Customer Side:
1. Manually de-energize the capacitors during off-peak periods.
2. Install a controlling device (voltage or power factor based) that would energize only the needed capacitor units during certain periods of the day.
COMMON PROBLEMS AT THE CUSTOMER SIDE
COMMON PROBLEMS AT THE CUSTOMER SIDE
C.C. Improper Setting of Under- and Over-Improper Setting of Under- and Over-voltage voltage ProtectionProtection
Under- and over-voltage relays in customer installations are sometimes set at very narrow voltage ranges resulting in unnecessary trippings.
Solutions at the Customer Side:
1. Adjust the relay settings to correspond to the actual operating range of the equipment being protected
COMMON PROBLEMS AT THE CUSTOMER SIDE
COMMON PROBLEMS AT THE CUSTOMER SIDE
D.D. Deficiencies in the Customer’s Deficiencies in the Customer’s DistributionDistribution SystemSystem
In some instances, the voltage problem is caused by problems on the customer’s electrical facilities, such as:
1. Loose connections2. Undersized, overloaded or overextended conductors3. Unbalanced distribution of single-phase loads
Solutions at the Customer Side:
1. Correct the problem(s) and seek the services of an electrical consultant, if necessary.
COMMON PROBLEMS AT THE CUSTOMER SIDE
COMMON PROBLEMS AT THE CUSTOMER SIDE
HOW DO SUPPLY PROBLEMS CAUSE MOTOR FAILURE?
HOW DO SUPPLY PROBLEMS CAUSE MOTOR FAILURE?
1. Undervoltage1. UndervoltageA motor running at less than nameplate voltage tolerance will run hotter than when it has the correct voltage. This is because the motor tries to maintain torque and will draw more current as the voltage decreases. Lower voltage also means a slower rotation, which means less movement of cooling air.
2. Overvoltage2. OvervoltageA slight increase in voltage causes the actual current draw to decrease. However, the motor’s impedance is not a fixed value and can change markedly when voltages are outside design parameters. So when the impedance starts to drop (due to the effects of the increased voltage), current goes up (per Ohm’s Law). If the voltage continues to increase, the current will also increase, causing excessive heat buildup.
3. Unbalanced Voltage3. Unbalanced VoltageUnbalanced supply voltage causes overheating of both the rotor and stator windings of three-phase induction motors. The relationship between voltage unbalance and overheating is exponential, not linear. A small amount of heat produces a large amount of excess heat.
The effect of unbalanced voltage on polyphase induction motors is equivalent to the introduction of a “negative sequence voltage” having a rotation opposite to that occurring with balanced voltages. This negative-sequence voltage produces an air gap flux rotating against the rotation of the rotor, tending to produce high currents.
HOW DO SUPPLY PROBLEMS CAUSE MOTOR FAILURE?
HOW DO SUPPLY PROBLEMS CAUSE MOTOR FAILURE?
This graph indicates the
percent temperature
rise vs. percent voltage
unbalance. To calculate the percentage of temperature rise, double
the square of the voltage unbalance
percentage.
Taken from the Sept. 1999 Power Quality Advisor (Supplement of EC&M Magazine)
4. Phase Loss4. Phase LossThis is the most severe level of unbalance. When phase loss occurs while a motor is running at full load, the winding temperature soars as the motor attempts to maintain it torque. It’s likely the motor will stall, subjecting the windings to locked rotor currents. (A motor in locked rotor conditions acts like a low impedance load, drawing high currents.) Unless the motor is disconnected from the the supply, it will most certainly fail.
5. Phase Sequence Reversal5. Phase Sequence ReversalInterchanging any two supply conductors will reverse the direction of rotation of a polyphase motor. For some process configurations, reversal in direction could severely damage connected equipment -- or worse, fatally injure people.
HOW DO SUPPLY PROBLEMS CAUSE MOTOR FAILURE?
ESTIMATING VOLTAGE INCREASE OR DECREASE WHEN CHANGING
TRANSFORMER TAPS
ESTIMATING VOLTAGE INCREASE OR DECREASE WHEN CHANGING
TRANSFORMER TAPS
TAP CHANGING OF TRANSFORMERS WITH FIVE (5) 2.5% TAPS
TAP CHANGING OF TRANSFORMERS WITH FIVE (5) 2.5% TAPS
A. Raising of Tap-setting
Number ofSteps
Multiply ExistingVoltage by
1 1.025
Note: No. of steps refer to the number of tap changes from the original to the new tap position. For example, there are 3 steps from Tap 2 to Tap 5.
2 1.050
3 1.075
4 1.100
SCHEMATIC WIRING DIAGRAM OF DUAL VOLTAGE TRANFORMERS
SCHEMATIC WIRING DIAGRAM OF DUAL VOLTAGE TRANFORMERS
PRIMARY WINDING
SECONDARY WINDING
120/240 V
TERMINALBLOCK
JUMPER
TAPCHANGER
THESE TAPS ARE USED BOTH FOR
TAP A & TAP B SETTINGS
139/277 V
H1
H2
12345
B A
X1 X3 X2 X4
B. Lowering of Tap-setting
Number ofSteps
Multiply ExistingVoltage by
1 0.975
Note: No. of steps refer to the number of tap changes from the original to the new tap position. For example, there are 4 steps from Tap 5 to Tap 1.
2 0.950
3 0.925
4 0.900
TAP CHANGING OF TRANSFORMERS WITH FIVE (5) 2.5% TAPS
TAP CHANGING OF TRANSFORMERS WITH FIVE (5) 2.5% TAPS
Vp = Vs x --------240
18,920
TAP NO.
1
2
3
4
5
VOLTAGE RATING
20,420
19,920
19,420
18,920
18,430
TRANSFORMATION RATIO
a1=20,420/240
a2=19,920/240
a3=19,420/240
a4=18,920/240
a5=18,430/240
1. Assume the transformer is at Tap 4
a4 = ------Vs
Vp
Vs
Vp
240
18,920------ = -----
2. Assume the tapping is lowered to Tap 2
Vsnew= ----a2 = -----Vsnew
Vp
a2
Vp
Vsnew= ------------
Vs x --------240
18,920
--------240
19,920
Vsnew = Vs x --------19,920
18,920
Vsnew = Vs x 0.95
SAMPLE DERIVATION OF THE MULTIPLYING FACTORS
Tap No. Rating
1 34.4
2 33.3
3 31.6
Voltage Rating For Each Tap
TMC 1 Bank No. 1
Fuij Denki Seizo4 MVA
34.4 kV - 13.8kVDelta-Wye
Tap No. Rating
1 37.088
2 36.225
3 35.363
4 34.500
5 33.638
* 2.5% per tap
Voltage Rating For Each Tap
Tanza Bank No. 1
Elin5 MVA
34.5 kV - 13.8kVWye-Delta
SAMPLE NAMEPLATE RATING OF POWER TRANSFORMERS
SAMPLE NAMEPLATE RATING OF POWER TRANSFORMERS
BF-Parañaque Bank No.1
EFACEC
50/66.7/83.33 MVA
100 kV-34.5kV-13.8kV
Wye-Wye-Delta
6 114.125
7 112.750
8 111.375
9 110.00
10 108.625
11 107.250
12 105.875
13 104.500
14 103.125
15 101.750
16 100.375
17 99.000
* 1.25% per tap
Tap No. Rating
Tap No. Rating
1 121.000
2 119.625
3 118.250
4 116.875
5 115.500
On-Load-Tap-Changer (OLTC)
SAMPLE NAMEPLATE RATING OF POWER TRANSFORMERS
SAMPLE NAMEPLATE RATING OF POWER TRANSFORMERS
Baliwag Bank No. 1Takaoka10 MVA
69 kV - 13.8kVDelta-Wye
Tap No. Rating
1 72.45
2 70.73
3 69.00
4 67.28
5 65.55
* 2.5% per tap
HV Tap Changer
SAMPLE NAMEPLATE RATING OF POWER TRANSFORMERS
SAMPLE NAMEPLATE RATING OF POWER TRANSFORMERS
1 12.420
2 12.590
: :
7 13.460
8 13.630
9 13.800
10 13.970
11 14.150
: :
16 15.010
17 15.180
* 1.23% per tap
Tap No. Rating
LV OLTC