ZXDU68 T451DC Power System
Product Description
Version: V4.1R02M02
ZTE CORPORATIONNO. 55, Hi-tech Road South, ShenZhen, P.R.ChinaPostcode: 518057Tel: +86-755-26771900Fax: +86-755-26770801URL: http://ensupport.zte.com.cnE-mail: support@zte.com.cn
LEGAL INFORMATIONCopyright © 2012 ZTE CORPORATION.
The contents of this document are protected by copyright laws and international treaties. Any reproduction or
distribution of this document or any portion of this document, in any form by any means, without the prior written
consent of ZTE CORPORATION is prohibited. Additionally, the contents of this document are protected by
contractual confidentiality obligations.
All company, brand and product names are trade or service marks, or registered trade or service marks, of ZTE
CORPORATION or of their respective owners.
This document is provided “as is”, and all express, implied, or statutory warranties, representations or conditions
are disclaimed, including without limitation any implied warranty of merchantability, fitness for a particular purpose,
title or non-infringement. ZTE CORPORATION and its licensors shall not be liable for damages resulting from the
use of or reliance on the information contained herein.
ZTE CORPORATION or its licensors may have current or pending intellectual property rights or applications
covering the subject matter of this document. Except as expressly provided in any written license between ZTE
CORPORATION and its licensee, the user of this document shall not acquire any license to the subject matter
herein.
ZTE CORPORATION reserves the right to upgrade or make technical change to this product without further notice.
Users may visit ZTE technical support website http://ensupport.zte.com.cn to inquire related information.
The ultimate right to interpret this product resides in ZTE CORPORATION.
Revision History
Revision No. Revision Date Revision Reason
R1.0 2011-03-03 First edition
R1.1 2011-04-20 A new section “Documentation Guide”
Serial Number: SJ-20110217090004-002
Publishing Date: 2011-04-20 (R1.1)
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
Safety PrecautionsThe table below describes the safety signs in this manual.
Safety Signs Meaning
DangerIndicates an imminently hazardous situation, which if not avoided, will
result in death or serious injury. This signal word should be limited to only
extreme situations.
WarningIndicates a potentially hazardous situation, which if not avoided, could
result in death or serious injury.
CautionIndicates a potentially hazardous situation, which if not avoided, could
result in minor or moderate injury. It may also be used to alert against
unsafe practices.
Electric shockThere is a risk of electric shock.
ElectrostaticThe device may be sensitive to static electricity.
Read the safety instructions before any operation of the equipment. The safety precautionsmentioned in this manual only serve as a supplement to the local safety codes.
Only trained professionals are allowed to install, operate and maintain the equipment. ZTEbears no liability to the consequences incurred by violation of the general safety operationrequirements, or violation of the safety standards for designing, manufacturing and usingthe equipment.
Take the following precautions when installing and operating the equipment.
High VoltageDirect contact or indirect contact with high voltage and mains through damp object willendanger the operator’s life.
l Observe the local safety codes during the equipment installation. The installationpersonnel must be qualified for high voltage and AC power operations.
l Never wear any conductive object, such as watch, bracelet or ring during the operationon the equipment.
l Prevent any moisture from entering the equipment during operations.
No Object With Harmful EffectsProtect the equipment against ingress of objects with harmful effects, such as conductiveobject and water. Otherwise, short circuit may occur and damage the equipment!
I
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
High Leakage Current
Earth connection is essential before connecting supply.
DC Short Circuit
Avoid short circuit during operation. ZXDU68 T451 system is a power supply product ofconstant DC voltage.
Connecting or Disconnecting Power Cable
Power cable operation with power ON will cause fatal danger to operation personnel anddamage to the equipment.
l Set all the breakers and switches to Off prior to connecting or disconnecting a powercable.
Setting all the breakers and switches to Off will cause power supply interruption to theloads connected. Do not shut down the system without permission. Or, switch theloads to another power supply system.
l Prior to connecting a cable, make sure that the cable and its label are in accordancewith the requirement.
Tools Safety
When operating high-voltage equipment, tools safety must be considered. Use InsulatedTools.
Electrostatic Damage
Electrostatic discharges generated by human body may damage components. Use wriststraps when handling the equipment. Insulate the uncovered metals to prevent shortcircuit.
Operation on Battery
l Before performing any operation on battery, read the safety precautions in the batterymanual.
l Connect the battery cables according to the instructions. Avoid short circuit andelectrolyte leakage.
II
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
Documentation GuideApplicable ProductThis guide and related documents apply to the ZXDU68 T451 (V4.1R02M02) DC powersystem.
Manual SuiteThe table below lists the manual suite of the system.
S.N. Document Description and Intended Audience
1 ZXDU68 T451 (V4.1R02M02)
DC Power System Product
Description
This document is intended for the use of all the users.
In this document, you will learn about:
l System structure and components
l System configuration
l System features and technical specifications
l Electrical connection diagram
l Term list
2 ZXDU68 T451 (V4.1R02M02) DC
Power System Quick Installation
& Commissioning Guide
This guide is intended for the use of engineers that
are authorized to install the equipment.
In this document, you will learn about:
l Equipment installation
l Cable connection
l System commissioning
3 ZXDU5868 CSU401 Monitoring
Software (V1.10J) Operation
Manual
This manual is intended for the use of maintenance
engineers.
In this document, you will learn about:
l Querying real-time running status
l Querying real-time alarms
l Query history alarms
l Setting Parameters
l Battery management
l Generator management
How to Get in TouchZTE welcomes your comments and suggestions on the quality and usefulness of thisdocument.
The following sections provide information on how to obtain support for the documentation.
If you have problems, questions, comments, or suggestions regarding your product,contact us by e-mail at 800@zte.com.cn. You can also call our customer support centerat (86) 755 26771900.
I
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
For further questions, comments, or suggestions on the documentation, you can fax yourcomments and suggestions to (86) 755 26770801. You can also browse our website at http://ensupport.zte.com.cn, which contains various interesting subjects like documentation,knowledge base, forum and service request.
II
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
ContentsSafety Precautions ......................................................................................... I
Documentation Guide .................................................................................... I
Chapter 1 Overview.................................................................................... 1-11.1 System Introduction............................................................................................ 1-1
1.2 Working Environment ......................................................................................... 1-1
Chapter 2 System Structure and Components........................................ 2-12.1 Overall System Structure .................................................................................... 2-1
2.2 Power Distribution Unit ....................................................................................... 2-2
2.3 ZXD2400 Rectifier .............................................................................................. 2-3
2.3.1 Rectifier Components ............................................................................... 2-3
2.3.2 Rectifier Indicators.................................................................................... 2-4
2.4 Monitoring Unit................................................................................................... 2-5
2.4.1 CSU Parts ............................................................................................... 2-5
2.4.2 CSU Indicators......................................................................................... 2-5
2.5 Slots Configuration ............................................................................................. 2-6
2.6 SIB Board Interfaces .......................................................................................... 2-6
2.7 Dimensions........................................................................................................ 2-7
Chapter 3 Monitoring Software ................................................................. 3-13.1 Software Version ................................................................................................ 3-1
3.2 Operation Interface............................................................................................. 3-1
3.3 Main Menu......................................................................................................... 3-2
Chapter 4 Characteristics and Specifications ......................................... 4-14.1 System Configuration ......................................................................................... 4-1
4.2 System Features ................................................................................................ 4-2
4.3 System Technical Specifications.......................................................................... 4-2
4.3.1 Environment Specifications ....................................................................... 4-2
4.3.2 AC Power Distribution Specifications ......................................................... 4-2
4.3.3 DC Power Distribution Specifications......................................................... 4-3
4.3.4 Rectifier Specifications ............................................................................. 4-3
4.3.5 CSU Specifications................................................................................... 4-4
4.3.6 Other Specifications ................................................................................. 4-4
4.4 Compliance Standards ....................................................................................... 4-5
I
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
Appendix A Signal Interface Definition ................................................... A-1
Appendix B Electrical Connection Diagram ........................................... B-1
Appendix C Term List................................................................................ C-1
II
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
Chapter 1OverviewTable of Contents
System Introduction....................................................................................................1-1Working Environment .................................................................................................1-1
1.1 System IntroductionZXDU68 T451 is an indoor power supply equipment. It can power mobile base stations,access network equipment, remote switch offices, transmission equipment, groundsatellite transceiver stations, and microwave communication devices.
In full configuration, the ZXDU68 T451 system is equipped with four ZXD2400 rectifiers,which form a power system with a maximum of 200 A output.
Figure 1-1 ZXDU68 T451
1.2 Working EnvironmentZXDU68 T451 is applied indoors. The requirements for the environment are as follows:
1. No conductive dusts or corrosive gases; no explosion hazard, no shake or jolt.2. In the AC power distribution box, a breaker should be available to power the ZXDU68
T451 system.
The AC input mode is three-phase five-wire (L1/L2/L3/N/PE).
3. The grounding busbar is available for the ZXDU68 T451 system and the groundingresistance meets the requirements in the engineering specifications.
1-1
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
ZXDU68 T451 Product Description
4. In the equipment room, the temperature, humidity and air pressure meet therequirements stated in Table 1-1.
Table 1-1 Requirements for Temperature, Humidity and Air Pressure
Item Requirement
Operating
temperature
-5 ℃ to +45 ℃; +15 ℃ to +25 ℃ recommended
l A low temperature affects the performance and charging efficiency
of the batteries; a high temperature shortens the service life of
the batteries.
l In case of over-temperature, improve the condition for heat
dissipation and turn on an air conditioner to lower the temperature.
Relative humidity 10% to 90% (non-condensing); 40% to 60% recommended
Air pressure 70 kPa to 106 kPa
1-2
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
Chapter 2System Structure andComponentsTable of Contents
Overall System Structure............................................................................................2-1Power Distribution Unit ...............................................................................................2-2ZXD2400 Rectifier ......................................................................................................2-3Monitoring Unit ...........................................................................................................2-5Slots Configuration .....................................................................................................2-6SIB Board Interfaces ..................................................................................................2-6Dimensions ................................................................................................................2-7
2.1 Overall System StructureThe structure of the ZXDU68 T451 cabinet is illustrated in Figure 2-1. Refer to Table 2-1for details concerning the individual components.
2-1
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
ZXDU68 T451 Product Description
Figure 2-1 Overall System Structure
1. Power distribution unit2. Rectifers
3. Monitoring unit4. DC meter
5. Signal Interface Board(SIB)
Table 2-1 ZXDU68 T451 Parts
Part Description
Power distribution unit Provides electrical distribution through AC and DC branches and
connection terminals (refer to “Power Distribution Unit” section of this
manual)
ZXD2400 Rectifiers Converts AC to stable DC power
Monitoring unit Provides management of the power distribution unit (AC and DC),
rectifiers and batteries
DC meter Provides accurate electrical measurements of the system
Signal Interface Board
(SIB)
Provides communication interface for the system
2.2 Power Distribution UnitThe power distribution unit is composed of AC and DC parts of the system and providesthe electrical connections and distribution. Figure 2-2 illustrates the distribution part of thesystem. Refer to Table 2-2 for the details on the individual components.
2-2
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
Chapter 2 System Structure and Components
Figure 2-2 Power Distribution Unit
1. Battery fuses2. DC output breakers
3. AC input breaker4. AC SPD
5. Rectifier breakers6. DC SPD
Table 2-2 ZXDU68 T451 Parts
Part Description
Battery fuses Provides battery connection to the system
DC output breakers Provides DC output power to load with overload protection
AC input breaker Turns on/off AC input
AC SPD Provides AC surge protection
Rectifier breakers Turns on/off rectifiers
DC SPD Provides DC surge protection
2.3 ZXD2400 Rectifier
2.3.1 Rectifier ComponentsThe ZXD2400 rectifier converts AC to DC.
For the appearance and structure of the ZXD2400 rectifier, see Figure 2-3.
2-3
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
ZXDU68 T451 Product Description
Figure 2-3 ZXD2400 Rectifier
1. Indicators2. Shutter3. Handle
4. Stop Pin5. Input/Output Integrated
Socket
6. Air Vent
2.3.2 Rectifier IndicatorsFor the indicators of the rectifier, see Figure 2-4.
Figure 2-4 Rectifier Indicators
Note:l Normally, only the IN and OUT indicators are lit. When the rectifier is in sleep mode,
only the IN indicator is lit.l In case of current limit, the CL indicator is lit.l In case of any alarm, the ALM indicator is lit.
The aforementioned indicators signify the working state of the rectifier. Refer to Table 2-3for a description.
Table 2-3 Indicators Description
Designation Description Status Indication
IN Input Lit (green) The AC input is normal
OUT Output Lit (green) The DC output is normal
CL Current limit Lit (yellow) Current limit occurs (The rectifier output
current has reached the current limit)
ALM Alarm Lit (red) Alarm occurs
2-4
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
Chapter 2 System Structure and Components
2.4 Monitoring Unit
2.4.1 CSU PartsSee Figure 2-5 for the pictures of the Centralized Supervision Unit (CSU).
Figure 2-5 Centralized Supervision Unit
1. LCD2. Indicators3. Buttons
4. Captive Screw5. Handle6. Reset Button (RST)
7. Input/Output Interface
Note:
Press the RST button to restart the CSU.
2.4.2 CSU IndicatorsFor the CSU indicators, see Figure 2-6.
Figure 2-6 CSU Indicators
For a description of the indicators and the working status they signify, refer to Table 2-4.
Table 2-4 CSU Indicators
Indicator Status Indication
PWRPower
Lit (green) The CSU is powered on
RUNRun
Flashing (green) The CSU is working normally
2-5
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
ZXDU68 T451 Product Description
Indicator Status Indication
EQUEqualized charge
Lit (green) The battery equalized charge is in the process
COMMCommunication
Flashing (green) The CSU is communicating with the background PC
ALMAlarm
Flashing (red) An alarm or a fault occurs
2.5 Slots ConfigurationThe number of rectifiers for each of the phases should be basically identical in order tomaintain phase balance and favor a good radiation. The distribution of the slots and phasesof the rectifiers are shown in Figure 2-7.
Figure 2-7 Slots Configuration
2.6 SIB Board InterfacesThe Signal Interface Board (SIB) provides external communication interfaces andmonitoring unit signals interfaces. The SIB board is shown in Figure 2-8. Refer to Table2-5 for the interfaces description.
Note:
The communication ports of the monitoring unit are X19, X20, X21 and X22. X21 and X22are optional.
l X19 and X21 are used in RS232 communication mode. X20 and X22 (optional) areused in RS485 communication mode.
l Use X21 when using Modem communication mode.l X19 and X20 should not be used at the same time.l Use X19 when downloading programs or downloading font in RS232.
2-6
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
Chapter 2 System Structure and Components
Figure 2-8 SIB Board Interface
Table 2-5 SIB Board Interfaces Description
Interface Designation Interface Designation
X2 Battery 1 Temperature X14 Monitoring Unit Fault Detect
X3 Battery 2 Temperature X15 Output Relays 1, 2
X4 Battery 3 Temperature X16 Output Relays 3, 4
X5 Battery 4 Temperature X17 Output Relays 5, 6
X6 Environment Temperature X18 Output Relays 7, 8
X7 Flood Alarm X19 COM1 (RS232)
X8 Smoke Alarm X20 COM1 (RS485)
X9 Glass Broken Alarm X21 COM3 (RS232)
X10 Intrusion Alarm X22 COM2 (RS485)
X11 Door Magnet Alarm X23 Environment Humidity
X12 Input Relays 1, 2 X24 48V Power Input
X13 Input Relays 3, 4 - -
2.7 DimensionsThe dimensions of the ZXDU68 T451 cabinet are shown in Figure 2-9. The cabinetspecifications are as follows:
l Dimensions: 600 mm x 600 mm x 400 mm (H x W x D)l Cabinet weight: about 70 kg (including rectifiers and monitoring unit)l Monitoring unit: 2.2 kg/pcl ZXD2400 rectifier: 3.8 kg/pc, 4 sets
2-7
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
ZXDU68 T451 Product Description
Figure 2-9 Cabinet Dimensions
2-8
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
Chapter 3Monitoring SoftwareTable of Contents
Software Version ........................................................................................................3-1Operation Interface.....................................................................................................3-1Main Menu .................................................................................................................3-2
3.1 Software VersionUsers can query the software version of the CSU (monitoring unit) by accessing Msg >Version.
Figure 3-1 Software Version
1. Product model 2. Software version
3.2 Operation InterfaceFigure 3-2 shows the front panel of the Centralized Supervision Unit (CSU).
Figure 3-2 Operation Interface
1. LCD 2. Buttons
Table 3-1 describes the buttons of the CSU.
3-1
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
ZXDU68 T451 Product Description
Table 3-1 Buttons of the CSU
Button Function
▲l Turns pages upwards
l Increases values
▼l Turns pages downwards
l Decreases values
Moves the cursor to the right
Moves the cursor to the left
Esc Exits and returns to the upper-level interface
Entl Enters the lower-level interface
l Confirms the current menu item
l Saves the current parameter setting
<▲ + Ent> Displays help information
3.3 Main MenuAfter the CSU is powered on, it performs self-check and initialization. Then the main menuinterface appears, as shown in Figure 3-3.
Note:
When the screen saver is displayed, press Esc or Ent to enter the main menu interface.
Figure 3-3 Main Menu
Table 3-2 describes the main interface.
Table 3-2 Description of Main Interface
Interface Description
Used to query real-time running information
Used to query real-time alarm information
Used to set parameters, such as system parameters, alarm attributes, and so on
Used to query history records, such as history alarms, event records, and so on
3-2
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
Chapter 4Characteristics andSpecificationsTable of Contents
System Configuration .................................................................................................4-1System Features ........................................................................................................4-2System Technical Specifications.................................................................................4-2Compliance Standards ...............................................................................................4-5
4.1 System ConfigurationTable 4-1 describes the system configuration.
Table 4-1 System Configuration
Item Configuration
AC input l Three-phase five-wire (L1/L2/L3/N/PE)
l 63A/3P MCB
Rectifier ZXD2400 (V4.3) rectifiers (4 units)
Monitoring unit Configured
AC surge arrester Class C SPD, with discharging current ≤40 kA
Battery input 2*400 A fuses
DC output
l 200 A DC output current
l LLVD1: 5 MCBs (10A/16A/32A/63A)
l LLVD2: 2 MCBs (16A/32A)
The DC output can be configured to meet user requirements
DC surge arrester Configured
Other components l LLVD1 & LLVD2 contactors
l Two battery temperature sensors and cables
l IP or SNMP board (optional)
• The customized product may be different from this table.• MCB: Miniature Circuit Breaker• LLVD: Load Low Voltage Disconnect
4-1
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
ZXDU68 T451 Product Description
4.2 System FeaturesThe ZXDU68 T451 system has the following features:
l A wide range of input phase voltage (wire voltage: 80 VAC - 300 VAC) makes thesystem suitable for areas with unstable voltage.
l The ZXDU68 T451 cabinet contains the AC distribution unit, DC distribution unit,rectifiers and monitoring unit.
l Convenient cable connections.l Hot-pluggable rectifiers.l Intelligent monitoring unit.l High reliability with MTBF ≥ 2 × 105 h.l The ZXDU68 T451 system supports multiple networking modes, such as RS232, and
RS485
4.3 System Technical Specifications
4.3.1 Environment SpecificationsThe specifications for the environment of the equipment are described in Table 4-2.
Table 4-2 Environment Specifications
Item Specification
Operating temperature -5 ℃ to +45 ℃
Storage temperature -40℃ to +70℃
Relative humidity 10% to 90% (non-condensing); 40% to 60% recommended
Air pressure 70 kPa to 106 kPa
Other requirements l No conductive objective or water falling into the chassis
l No conductive dusts or corrosive gases
l No explosion hazard, no shake or jolt
l Ground slope is no more than 5°
4.3.2 AC Power Distribution SpecificationsThe specifications for the AC power distribution of the system are described in Table 4-3.
Table 4-3 AC Power Distribution Specifications
Item Specification
AC input l Three-phase five-wire (L1/L2/L3/N/PE)
l 63A/3P MCB
AC input voltage 80 VAC - 300 VAC
(Input voltage variation affects the output power of the rectifier)
4-2
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
Chapter 4 Characteristics and Specifications
Item Specification
AC input frequency 50/60 Hz
AC input power factor ≥ 0.99 (with full load)
AC urge protection Class C SPD, with discharging current ≤40 kA
• MCB: Miniature Circuit Breaker
4.3.3 DC Power Distribution SpecificationsThe specifications for the DC power distribution of the system are described in Table 4-4.
Table 4-4 DC Power Distribution Specifications
Item Specification
DC output voltage l Rated output voltage: -53.5 VDC
l Range: -42 VDC to -58 VDC
Rated DC output current 200 A (full configuration)
Rated DC output power 9600 W (full configuration)
Maximum DC output power 12780 W (full configuration)
DC output l LLVD1: 5 MCBs (10A/16A/32A/63A)
l LLVD2: 2 MCBs (16A/32A)
Battery input fuses 2*400 A fuses
Source effect ≤ 0.1%
Load effect ≤ 0.5%
Regulated voltage precision ≤ 0.6%
Weighted noise voltage < 1 mV
Peak-peak noise voltage ≤ 100 mV
Broad frequency noise voltage ≤ 30 mV (3.4 kHz~150 kHz)
≤ 20 mV (0.15 MHz~30 MHz)
Discrete frequency noise voltage ≤ 5 mV (3.4 kHz~150 kHz)
≤ 3 mV (150 kHz~200 kHz)
≤ 2 mV (200 kHz~500 kHz)
≤ 1 mV (0.5 MHz~30 MHz)
DC voltage drop < 500 mV
• MCB: Miniature Circuit Breaker• LLVD: Load Low Voltage Disconnect
4.3.4 Rectifier SpecificationsFor the ZXD2400 specifications description, refer to Table 4-5.
4-3
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
ZXDU68 T451 Product Description
Table 4-5 ZXD2400 Rectifier Specifications
Item Specification
AC input mode Single-phase three-wire (L/N/PE)
AC input voltage 80 V to 300 V
Input voltage variation affects the output power of the rectifier
DC output voltage Rated output voltage: 53.5 V, range: 42 V to 58 V
4.3.5 CSU SpecificationsFor a description of the CSU specifications, refer to Table 4-6.
Table 4-6 CSU Specifications
Item Specifications
Power mode DC power
Operation interface LCD and buttons
Precision of AC voltage ±1%
Precision of the battery current and the output current of the system ±1%
Precision of the battery voltage and the output voltage of the system ±0.5%
Temperature precision ±5.4 ℉ (±3 ℃)
Humidity precision ±5%
Boolean value precision 100%
4.3.6 Other SpecificationsOther specifications are described in Table 4-7.
Table 4-7 Other Specifications
Item Specification
Chassis dimensions 600 mm × 600 mm × 600 mm (H × W × D)
Chassis weight Approximately 70 kg (including rectifiers and the monitoring unit)
Rectifier weight 3.8 kg/set
Monitoring unit weight 2.2 kg
Cable connection Front
Installation mode Floor mounted
Noise ≤ 55 dB(A)
4-4
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
Chapter 4 Characteristics and Specifications
Item Specification
Mean Time Between Failures
(MTBF)
≥ 2.2 × 105 h
Safety standard IEC 60950
EMC standard EN55022; IEC61000
Conductive disturbance and
radioactive disturbance
EN55022 level A
4.4 Compliance StandardsEMC Standards
The ZXDU68 T451 system is in compliance with the following ElectromagneticCompatibility (EMC) standards:
l EN55022l IEC61000-3-3; IEC61000-3-2; IEC61000-4-2; IEC61000-4-3; IEC61000-4-4;
IEC61000-4-6; IEC61000-4-8; and IEC61000-4-11
Safety Standards
The ZXDU68 T451 system is in compliance with the UL/IEC/EN 60950 safety standards.
Other Standards
The ZXDU68 T451 system is also in compliance with the following standards:
l The Restriction of Hazardous Substances (RoHS) directive (2002/95/EC) of theEuropean Union.
l This device complies with Part 15 of the FCC Rules. Operation is subject to thefollowing two conditions: (1) this device may not cause harmful interference, and (2)this device must accept any interference received, including interference that maycause undesired operations.
4-5
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
ZXDU68 T451 Product Description
This page intentionally left blank.
4-6
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
Appendix ASignal Interface DefinitionThe Signal Interface Board (SIB) provides external communication interfaces andmonitoring unit signals interfaces. Refer to Table A-1 for the SIB interfaces description.
Table A-1 SIB Board Interfaces Description
Interface Designation PinNo.
SignalDefinition
Signal Description
1 T1 Battery 1 temperature signalX2
Battery 1 Temperature 2 +12V1 +12 V power supply
1 T2 Battery 2 temperature signalX3
Battery 2 Temperature 2 +12V1 +12 V power supply
1 T3 Battery 3 temperature signalX4
Battery 3 Temperature 2 +12V1 +12 V power supply
1 T4 Battery 4 temperature signalX5
Battery 4 Temperature 2 +12V1 +12 V power supply
1 TEMP Environment temperature signalX6
Environment Temperature 2 +12V1 +12 V power supply
1 VCC_W Flood sensor signal 1
2 +12V1 +12 V power supply
3 AGND Analog ground
X7
Flood Alarm
4 WATER_IN Flood sensor signal 2
1 +12V1 +12 V power supplyX8
Smoke Alarm 2 SMOKE_IN Smoke sensor signal
1 +12V1 +12 V power supply
2 AGND Analog ground
3 GLASS_IN Glass broken signal
X9
Glass Broken Alarm
4 AGND Analog ground
1 +12V1 +12 V power supply
2 AGND Analog ground
X10
Intrusion Alarm
3 DOOR_IN Intrusion signal
A-1
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
ZXDU68 T451 Product Description
Interface Designation PinNo.
SignalDefinition
Signal Description
1 DOOR1 Door magnet signalX11
Door Magnet Alarm 2 AGND Analog ground
1 INRLY1 Input relay 1
2 INRLY2 Input relay 2
X12
Input Relays 1, 2
3 AGND Analog ground
1 INRLY3 Input relay 3
2 INRLY4 Input relay 4
X13
Input Relays 3, 4
3 AGND Analog ground
1 FAULT-NO Monitoring unit fault-NO
2 FAULT-COM Monitoring unit fault-Common end
X14
Monitoring Unit Fault Detect
3 FAULT-NC Monitoring unit fault-NC
1 RO1-NO Relay output 1– NO
2 RO1-COM Relay output 1– Common end
3 RO1-NC Relay output 1– NC
4 RO2-NO Relay output 2– NO
5 RO2-COM Relay output 2– Common end
X15
Output Relays 1, 2
6 RO2-NC Relay output 2– NC
1 RO3-NO Relay output 3– NO
2 RO3-COM Relay output 3– Common end
3 RO3-NC Relay output 3– NC
4 RO4-NO Relay output 4– NO
5 RO4-COM Relay output 4– Common end
X16
Output Relays 3, 4
6 RO4-NC Relay output 4– NC
1 RO5-NO Relay output 5– NO
2 RO5-COM Relay output 5– Common end
3 RO5-NC Relay output 5– NC
4 RO6-NO Relay output 6– NO
5 RO6-COM Relay output 6– Common end
X17
Output Relays 5, 6
6 RO6-NC Relay output 6– NC
A-2
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
Appendix A Signal Interface Definition
Interface Designation PinNo.
SignalDefinition
Signal Description
1 RO7-NO Relay output 7– NO
2 RO7-COM Relay output 7– Common end
3 RO7-NC Relay output 7– NC
4 RO8-NO Relay output 8– NO
5 RO8-COM Relay output 8– Common end
X18
Output Relays 7, 8
6 RO8-NC Relay output 8– NC
1 - Not used
2 RXD_1 Receive Data
3 TXD_1 Transmit Data
4 - Not used
5 GND_1 Ground
6 - Not used
7 - Not used
8 - Not used
9 - Not used
10 GNDP Protection ground
X19
COM1 (RS232)
11 GNDP Protection ground
1 485A1 RS485 signal AX20
COM1 (RS485) 2 485B1 RS485 signal B
1 DCD Data Carrier Detect
2 RXD_2 Receive Data
3 TXD_2 Transmit Data
4 DTR Data Terminal Ready
5 GND_2 Ground
6 DSR Data Set Ready
7 RTS Request To Send
8 CTS Request To Clear
10 GNDP Protection ground
X21
COM3 (RS232)
11 GNDP Protection ground
1 485A0 RS485 signal AX22
COM2 (RS485) 2 485B0 RS485 signal B
A-3
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
ZXDU68 T451 Product Description
Interface Designation PinNo.
SignalDefinition
Signal Description
1 VCC Digital power supply
2 HUM_IN Humidity signal
X23
Environment Humidity
3 GND Digital ground
1 48V+ +48V input power
2 - Not used
X24
48V Power Input
3 48V- –48V input power
A-4
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
Appendix BElectrical ConnectionDiagramThe electrical connection diagram of the ZXDU68 T451 system is shown in Figure B-1.
Figure B-1 Electrical Connection Diagram
B-1
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
ZXDU68 T451 Product Description
This page intentionally left blank.
B-2
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
Appendix CTerm ListRefer to Table C-1 for the details of acronyms that are used in this manual.
Table C-1 Term List
Abbreviation Full Name
AC Alternating Current
ACDP AC Distribution Panel
ACDR AC Distribution Rack
ACMU AC Monitoring Unit
ALM Alarm
BLVD Battery Low Voltage Disconnect
CL Current Limit
CSU Centralized Supervision Unit
DC Direct Current
DCDP DC Distribution Panel
DCDR DC Distribution Rack
EMC Electromagnetic Compatibility
LCD Liquid Crystal Display
LED Light Emitting Diode
LLVD Load Low Voltage Disconnect
LVD Low Voltage Disconnect
MCB Miniature Circuit Breaker
MCCB Moulded Case Circuit Breaker
MODEM Modulator-Demodulator
NC Normally Closed
NO Normally Open
PE Protection Earth
PFC Power Factor Correction
PWR Power
RECR Rectifier Rack
C-1
SJ-20110217090004-002|2011-04-20 (R1.1) ZTE Proprietary and Confidential
ZXDU68 T451 Product Description
Abbreviation Full Name
RLY Relay
SIB Signal Interface Board
SMR Switching Mode Rectifier
C-2