ZonePRO™ Modulating Thermostats
Technical TrainingJuly 10, 2006
2
Models and Features
• Models with 1 output- TB6980A1007 (Floating)
- TB7980A1006 (Analog 0-10V or 2-10V)
• Models with 3 outputs- TB6980B1006 (1st output is floating)
- TB7980B1005 (1st output is analog 0-10V or 2-10V)
- 2nd output can be configured for: Analog 0-10V Analog 2-10V 24V
- 3rd output is 24V only
• Features for all models- Automatic changeover (duct sensor required)
- Manual changeover (remote switch or relay required)
- Night setback
- Min and Max temperature setpoint stops
3
Applications and Accessories
• Hydronic and pressure dependent VAV with or without reheat
• Non-programmable• Up to three outputs depending on model• Can be used for:
- Floating or Analog damper/valve actuator control
- Damper/valve actuator with duct reheat and aux heat (B models)
- Hydronic systems (room control, perimeter heating and cooling)
• Compatible accessories- R841 family of electromechanical relays
- 50014156-002 remote room sensor
- 50014157-001 duct temperature sensor
- 32004800-001 bare thermistor
4
Terminal Connections
Terminal Description
12
24 VACCOM
Power supply
34
AN1COM Output 1
TB7980 models
34
OPENCLOSED
TB6980 models
56
T2/AN2T2/COM
Output 2 (TB6980B and TB7980B models)WARNING: Make sure SW6 is set to the proper setting (Triac or Analog)
78
T3T3
Output 3 (TB6980B and TB7980B models)
910
COMSENSOR
External sensor input. (For applications requiring an external sensor)
911
COMC-Over
Mode Changeover input (N.O contact).
912
COMNSB
Night Setback activation input (N.O. contact)
5
Typical Applications
Damper control with electric reheat and auxiliary hot-water heating
TB6980B
Relay
24 VAC not COM
6
Typical Applications
Damper control with electric reheat and auxiliary baseboard heating
TB7980B
Relay
Relay
7
Typical Applications
Damper control with automatic changeover, electric reheat and central cooling
TB7980B
50014157-001
Relay
8
Typical Applications
Temperature control of fresh air supply
TB6980B
Relay
50014157-001
9
Typical Applications
Changeover and NSB inputs sharing the same 24-Vac transformer
TB7980B TB7980B TB7980B
10
Modèle 1A2T
Application Default mode & output 1 type
Output 2 type Output 3 type Output 3 activation
NSB value Output 1 min.
opening
Maximum setpoint
Minimum setpoint
0 Internal sensor 0 Cool / 0-10V 0 Not used 0 Not used 0 100% 1 1°C (2°F) 0 0%
Can be set between 35°C (95°F) and "minimum setpoint + 1“
Default value is 35°C (95°F)
Can be set between 10°C (50°F) and “maximum setpoint -1“
Default value is 10°C (50°F)
1 Room 1 Heat / 0-10V 1 SSR 24 VAC
1 SSR 24 VAC 1 10% 2 2°C (4°F) 1 10%
2 Return 2 Cool / 2-10V 2 N.C. Valve 2 N.C. Valve 2 20% 3 3°C (6°F) 2 20%
3 Supply 3 Heat / 2-10 V 3 N.O. Valve 3 N.O. Valve 3 30% 4 4°C (8°F) 3 30%
4 Auto changeover
4 Mech. relay
4 Mech. Relay 4 40% 5 5°C (10°F) 4 40%
5 Limited cooling 5 SSR 3-32V 5 Contact 5 50% 6 6°C (12°F) 5 50%
6 SCR 0-10V 6 60% 7 7°C (14°F)
7 Act. 0-10V 7 70% 8 8°C (16°F)
8 Act. / 2-10V
8 80% 9 9°C (18°F)
9 90%
Default configuration
Configuration – TB7980B1005
11
Modèle 1F2T
Application Default Mode Output 2 type Output 3 type Output 3 activation
NSB value Output 1 min.
opening
Output 1 opening
time
Maximum
setpoint
Minimum
setpoint
0 Internal sensor 0 Cool 0 Not used 0 Not used 0 100% 1 1°C (2°F) 0 0% 0 80
Can be set between 35°C (95°F) and “min setpoint + 1“
Default value is 35°C (95°F)
Can be set between 10°C (50°F) and “max setpoint -1“
Default value is 10°C (50°F)
1 Room 1 Heat 1 SSR 24 VAC
1 SSR 24 VAC
1 10% 2 2°C (4°F) 1 10% 1 90
2 Return 2 N.C. Valve 2 N.C. Valve 2 20% 3 3°C (6°F) 2 20% 2 100
3 Supply 3 N.O. Valve 3 N.O. Valve 3 30% 4 4°C (8°F) 3 30% 3 110
4 Auto changeover
4 Mech. relay 4 Mech. Relay
4 40% 5 5°C (10°F)
4 40% 4 120
5 Limited cooling 5 SSR 3-32V 5 Contact 5 50% 6 6°C (12°F)
5 50% 5 130
6 SCR 0-10V 6 60% 7 7°C (14°F)
6 140
7 Act. 0-10V 7 70% 8 8°C (16°F)
7 150
8 Act. / 2-10V 8 80% 9 9°C (18°F)
8 160
9 90%
Default configuration
Configuration – TB6980B1006
12
Configuration menu TB6980B
output 1 default mode
Output 1 Activation
13
Configuration menu TB6980BOutput 1 Modes
Menu setting TB7980 models TB6980 models
0 Cool / 0-10 V analog (max. of 10 min. refresh)
Cool(24 V tri-state floating)
1 Heat / 0-10 V analog (max. of 10 min. refresh)
Heat(24 V tri-state floating)
2 Cool / 2-10V analog (max. of 10 min. refresh)
3 Heat / 2-10 V analog (max. of 10 min. refresh)
14
Configuration menu TB6980B
output 1 default mode Output 1 jumps at 100% if there is an instant 5°F difference
Output 2 Activation
15
Configuration menu TB6980BOutput 2 Modes
Menu setting Description
0 Not used
1 24 VAC pulsed (triac) 1 sec. Cycle
2 24 VAC pulsed (triac) / 10 min. cycle / direct action (e.g., N.C. thermal valve)
3 24 VAC pulsed (triac) / 10 min. cycle / reverse action (e.g., N.O. thermal valve)
4 24 VAC pulsed (triac) / 15 min. cycle (e.g., mechanical relay such as R841)
5 0-10 V pulsed / 1 sec. Cycle
6 0-10 V analog / 1 sec. Refresh (e.g., SCR controlled device such as re-heater)
7 0-10 V analog / max. of 10 min. refresh (e.g., valve)
8 2-10 V analog / max. of 10 min. refresh (e.g., damper)
16
Configuration menu TB6980BOutput 3 Activation
output 1 default modeOutput 1 jumps at 100% if there is an instant 5°F difference
Output 2 jumps at 100% if there is an instant 11°F difference
17
Configuration menu TB6980BOutput 3 Modes
Menu setting Description
0 Not used
1 24 VAC pulsed (triac) 1 sec. Cycle
2 24 VAC pulsed (triac) / 10 min. cycle / direct action (e.g., N.C. thermal valve)
3 24 VAC pulsed (triac) / 10 min. cycle / reverse action (e.g., N.O. thermal valve)
4 24 VAC pulsed (triac) / 15 min. cycle (e.g., mechanical relay such as R841)
5 N.O. contact (The contact closes when output 1 reaches or exceeds set percentage)
18
Configuration menu TB6980BOutput 3 Activation “Contact Mode”
output 1 default mode
19
Configuration and Operation
• Configuration- Dip switches
Temperature display, F or C (SW1) Access mode (SW2) Output 2 type (SW6)
• This sets output 2 type (analog or triac)
• Operation- Backlight (on for 12 seconds)
- Temperature setting by 1° increments (2°F in changeover)
- Output display (Hold Override for 4 seconds)
20
Operation (continued)
• Operation- Changeover
Manual changeover (contact) Automatic changeover (9°F differential between duct and room) Night setback
• Override (2 hours)
• Error codes- E1 (internal sensor defective)
- E2 (internal sensor shorted)
- E3 (external temperature sensor defective or not connected)
- E4 (external temperature sensor shorted)
21
System Components
OS # Dimensions Compatible Valves and Actuators Sensors and Accessories Replaces
TB6980A1007
2.7 x 4.6 x 1.0 in. (69 x 118 x
27 mm)
VC6930, VC6934, VC6936, ML6984A1006, ML6420, ML6161B2024, MN6105A1011
R841 Series of electromechanical relays, 50014157-001 air duct sensor, 50014156-002 space sensor, ST6008A1003 and
ST7009A1003 time clocks, 209651A wall plate
T6984A1059
TB6980B1006
T6984D1046, T6984E1043
TB7980A1006 VC7930, VC7934, VC7936, ML7984A4009,
ML7420, ML7161A2008, MN7505A2001
T7984A1057, T7984A1065
TB7980B1005
T7984B1055, T7984C1053
ML6984
ZonePRO
MN7505
VC7930ST7009
22
Literature and Point of Purchase Materials
TECHNICAL LITERATURE
62-0238 Installation Instructions
63-4370 Guide Specification
63-8563 Actuator Cross Reference
SALES LITERATURE
63-9555 Brochure
n/a Flyer
All ZonePRO sales, technical and PowerPoint materials can be downloaded at customer.honeywell.com/buildings
www.honeywell.com
top related