Wind Loading Calculator
USE ONLY FOR VIRIDIAN SOLAR PRODUCTS
PROJECT
Project numberProject NameClient
INPUTS
SiteBasic wind speed (from map) 23 m/s
Site altitude above sea level 10 m
Distance from the sea 10 km
Location type town
Installation
Roof height 5 m
Parapet > 200mm high YesRoof Zone EdgePanel tilt angle 10 degrees
The roof edge zone width is 0.1 x the longest roof dimension
RESULTS
Fixed System Free-standing System
Peak force on each bracket per panel
Number of 450 x 600 x 50mm concrete slabs per panel
V20E or PV20 V20E or PV20 5.8Fh max 145 N V30E or PV30 8.8Fv max 481 NFv min -296 N Dead load on roof per panel (including panel and ballast tray)
V30E or PV30 Load Uniformly Distributed
Fh max 217 N V20E or PV20 259 kg 113
Fv max 709 N V30E or PV30 376 kg 164Fv min -457 N
Example
Version 1.2
Edit the values above to reflect those of the project under consideration.
The calculation is based on BS6399-2:1997. Viridian Solar has added no additional loading factors to the result. The coefficient of friction is assumed to be 0.4 (rubber/steel), topography is assumed to be insignificant. If in doubt, consult a structural engineer.
(dynamic plus static loads, double the value for bracket between two panels)
kg/m2
kg/m2
For a free standing system of 10 solar panels in a single row, it is calculated that the required number of concrete slabs is 7.7 per panel. The total number of slabs is therefore 7.7 x 10 = 77. 10 panels require (n+1) = 11 ballast trays, so the number of slabs per ballast tray is calculated to be 77/11 = 7
www.viridiansolar.co.uk © Viridian Solar 2011
Wind Loading Pressure for Solar Panel on Open Framework
BS 6399-2:1997 Loading for Buildings Part 2 : Code of Practice for wind loads
From Inputs PageSite Altitude 10 m above sea levelLocation townDistance from sea 10 km
Building Height 5 m
Include Internal Pressure 0
Vb 23 m/s
Site Wind SpeedVs = Vb x Sa x Sd x Ss x Sp
Sd - site direction factor - set to 1 when the orientation of the building is unknownSs - seasonal factor - set to 1 when the building is permanentSp - probability factor - set to 1 for 50 year stormSa - Site altitude factor = 1 + 0.001 x altitude in m
Vs = 1.01 Vb
Effective Wind SpeedVe = Sb x Vs
Sb is based on height of building and whether it is in the country or town
In country or up to 2km into townBuilding Distance to sea (km)Height < 0.1 2 10 >100 1
5 1.65 1.62 1.57 1.45 2
10 1.78 1.78 1.73 1.62 3
15 1.85 1.85 1.82 1.71 4
In townBuilding Distance to sea (km)Height < 0.1 2 10 >100 1
5 1.5 1.45 1.36 2
10 1.73 1.69 1.58 3
15 1.85 1.82 1.71 4
Sb 1.45
Ve = 1.4645 Vb= 33.6835 m/s
Dynamic Pressure
695 Pa
qs = 0.613 Ve2
qs =
External Pressure
Ca = 1 for an element as small as a solar panel
Cp,net from lookup table
From BRE Digest 489, Wind loads on roof based PV systems
Table 4 Pressure coefficients Cp,net for PV modules based on open support structures
Roof zoneNo Parapet Parapet >200mm
Cp min Cp max Cp min Cp maxCorner -1.8 1.2 -1.5 1Edge -1.6 1.2 -1.2 1Central -0.6 0.6 -0.6 0.6
Table 5 Pressure coefficients Cp,net for PV modules based on enclosed support structures
Roof zoneNo Parapet Parapet >200mm
Cp min Cp max Cp min Cp maxCorner -1.7 0.5 -1.7 0.5Edge -1.6 0.5 -1.2 0.5Central -1.0 0.5 -1.0 0.5
NotesEdge zone is L/10 wide, where L is largest plan dimension of roof.
Conservatively consider location to be an edge
Parapet 2Central/Edge/Corner 1
Cp min from table 4 -1.2Cp max from table 4 1
Pe min -835 PaPe max 695 Pa
Pe = qs Cp,net Ca
Imposed Loads on Roof Due to Wind Load
V20/PV20
Positive Pressure 695 Pa Negative Pressure -835 Pa
FH FH
242 - 290 F FV F FV
1,391 1,370 - 1,669 - 1,644
W W510.12 510.12
459 N 481 N -271 N -296 N
NOTES:Loads shown are for each side of each solar panel.There is a horizontal force to react as well as the vertical force.
Area 2 Area
Angle θ 10 degrees _Theta
Panel and frame weight 510 N _W
m2
θ θ