Viking TotalPac2FireFlex Dual / 1230Viking TotalPac2FireFlex Dual / 1230
Systems Inc.Systems Inc.
www.fireflex.comwww.fireflex.com
Technical Presentation
ASPE
Cleveland, OH
March 10th, 2010
Technical Presentation
ASPE
Cleveland, OH
March 10th, 2010
History:History:
1990Power
Plants Unit
1990Power
Plants Unit
1991Light & Ordinary
Hazard
1991Light & Ordinary
Hazard
2002Second
Generation
2002Second
Generation
INTEGRATED SPRINKLER SYSTEMSINTEGRATED SPRINKLER SYSTEMS
Expanding the concept:Expanding the concept:
Extended range of configurations:Extended range of configurations:
Skid unitSkid unit Remote controlled unitRemote controlled unit Self-contained unitSelf-contained unit
INTEGRATED SPRINKLER SYSTEMSINTEGRATED SPRINKLER SYSTEMS
Description: Typical System LayoutDescription: Typical System Layout
Integrated CabinetIntegrated Cabinet
Foam TankFoam Tank
Air CylindersAir Cylinders
Distribution NozzlesDistribution Nozzles
Piping Network
ICAF SYSTEMICAF SYSTEM
(water tank also available)(water tank also available)
Description: Compressed Air Foam (CAF)Description: Compressed Air Foam (CAF)
CAF TECHNOLOGYCAF TECHNOLOGY
• Uniform & stable• High momentum• Excellent quality• 10:1 expansion
• Uniform & stable• High momentum• Excellent quality• 10:1 expansion
Integrated Clean Agent SystemsIntegrated Clean Agent Systems
• Clean Agent Integrated Fire Suppression Systems using 3M™ Novec™ 1230 Fire Protection Fluid
• Clean Agent Integrated Fire Suppression Systems using 3M™ Novec™ 1230 Fire Protection Fluid
• Combined Automatic Sprinkler and Clean Agent Integrated Fire Suppression Systems using 3M™ Novec™ 1230 Fire Protection Fluid
• Combined Automatic Sprinkler and Clean Agent Integrated Fire Suppression Systems using 3M™ Novec™ 1230 Fire Protection Fluid
fuelfuel
oxygen
heat
chainreaction
Extinguishing Mechanism
The Fire Tetrahedron Removing one of
the required components for fire
or disrupting the balance between them can cause a fire to extinguish
Novec 1230 Fluid extinguishes primarily
via cooling – removing heat from
the fire
Non-corrosive
Long term testing of compatibility with materials of construction (system hardware)
Compatability with plastics confirmed
30 year shelf life in properly maintained and installed systems
Compatible with fire system materials
3M NOVEC 12303M NOVEC 1230
Environmental Properties
Properties Novec 1230(FK-5-1-12)
Halon 1301 FM-200(HFC-227ea)
ECARO-25(HFC-125)
Ozone Depletion Potential
0 10 0 0
Global Warming Potential
1 6900 3220 3500
Atmospheric Lifetime (years)
0.014 65 29 33
EPA's SNAP Conformance
Yes N/A Yes Yes
3M NOVEC 12303M NOVEC 1230
Physical Properties
Properties Novec 1230(FK-5-1-12)
Halon 1301 FM-200(HFC-227ea)
ECARO-25(HFC-125)
Design % 4-6% 5 % 6.25-8.7 % 8-11.3 %
NOAEL % 10 5 9 7.5
Occupants Safety Margin %
67-150 % Nil 3-44 % Nil
(NOAEL) No Observable Adverse Effects Level for acute toxicity, including cardiac senisitization(NOAEL) No Observable Adverse Effects Level for acute toxicity, including cardiac senisitization
3M NOVEC 12303M NOVEC 1230
If Novec 1230 fluid is banned from or restricted in use as a fire protection agent due to ozone depletion potential or global warming potential, 3M will refund the purchase price of the fluid.
If Novec 1230 fluid is banned from or restricted in use as a fire protection agent due to ozone depletion potential or global warming potential, 3M will refund the purchase price of the fluid.
3M Novec 1230:3M Novec 1230:
Pre-Engineered Discharge Nozzles:
• Available: 1", 1½" & 2" dia.
• 180° or 360° discharge pattern
• 32' x 32' spacing – 16'-4" max. height
• No piping below 8,500 cu.ft. !
Pre-Engineered Discharge Nozzles:
• Available: 1", 1½" & 2" dia.
• 180° or 360° discharge pattern
• 32' x 32' spacing – 16'-4" max. height
• No piping below 8,500 cu.ft. !
CLEAN AGENTCLEAN AGENT
FIREFLEX 1230FIREFLEX 1230
Engineered Systems:
• Larger or multiple room hazards or volumes
• Need some calculations/software required
• Re-use existing Halon 1301 piping at 500psi
Engineered Systems:
• Larger or multiple room hazards or volumes
• Need some calculations/software required
• Re-use existing Halon 1301 piping at 500psi
3M Novec 1230:3M Novec 1230:
Engineered Discharge Nozzles:
• Available: ½", 1", 1½", 2" & 2½" dia.
• 180° or 360° discharge pattern
• 32' x 32' spacing – 16'-4" max. height
• Re-use existing Halon 1301 piping at 500psi
Engineered Discharge Nozzles:
• Available: ½", 1", 1½", 2" & 2½" dia.
• 180° or 360° discharge pattern
• 32' x 32' spacing – 16'-4" max. height
• Re-use existing Halon 1301 piping at 500psi
CLEAN AGENTCLEAN AGENT
Product Description:Product Description:
• Fully Integrated
• Clean Agent System Only
• Factory Built & Tested
• Fully Integrated
• Clean Agent System Only
• Factory Built & Tested
FIREFLEX 1230FIREFLEX 1230
Product Description:Product Description:
• Sturdy Cabinet with Lock
• Competitively Priced
• Eliminates Site Coordination Issues
• Sturdy Cabinet with Lock
• Competitively Priced
• Eliminates Site Coordination Issues
FIREFLEX 1230FIREFLEX 1230
Product Description:Product Description:Integrated Potter PFC-4410 RC Releasing panel
Integrated Potter PFC-4410 RC Releasing panel
Clean Agent Cylinder from 40 to 601 lbs cap.
Clean Agent Cylinder from 40 to 601 lbs cap.
Sturdy CabinetSturdy Cabinet
Detailed Instructions & Unit Serial NumberDetailed Instructions & Unit Serial Number
FIREFLEX 1230FIREFLEX 1230
Available Configurations:Available Configurations:
• Clean Agent Only – No Sprinklers
• Self-contained or Remote Controlled (no panel)
• Master-Salve Cylinders Available
• Main-Reserve Arrangement Available
• Pre-Engineered or Engineered Piping System
• Clean Agent Only – No Sprinklers
• Self-contained or Remote Controlled (no panel)
• Master-Salve Cylinders Available
• Main-Reserve Arrangement Available
• Pre-Engineered or Engineered Piping System
FIREFLEX 1230FIREFLEX 1230
FIREFLEX 1230FIREFLEX 1230System dimensions and Capacity Table:System dimensions and Capacity Table:
FireFlex® 1230 Cabinets Capacity (# of cylinders) & dimensions
Cylinder Size (lbs) Dimensions
Cabinet Size 40 76 164 322 601 A B C
24" 1 1 1 1 -- 23" 25" 77⅛"
36" 2 2 2 -- 1 35¾" 25" 77⅛"
48" -- -- -- 2 2 46" 25" 77⅛"
FIREFLEX DUALFIREFLEX DUALProduct Description:Product Description:
• Fully Integrated System
• Combines Preaction & Clean Agent
• Factory Built & Tested
•Serialized
• Fully Integrated System
• Combines Preaction & Clean Agent
• Factory Built & Tested
•Serialized
Product Description:Product Description:
• Sturdy Cabinet with Lock
• Competitively Priced
• Eliminates Site Coordination Issues
• Sturdy Cabinet with Lock
• Competitively Priced
• Eliminates Site Coordination Issues
FIREFLEX DUALFIREFLEX DUAL
Product Description:Product Description:
Air CompressorAir Compressor
Optional Common Integrated Potter PFC 4410RC Releasing Panel
Optional Common Integrated Potter PFC 4410RC Releasing Panel
Viking Preaction 2” & 3” Viking Preaction 2” & 3”
Clean Agent CylinderClean Agent Cylinder
Detailed Instructions & Unit Serial NumberDetailed Instructions & Unit Serial Number
FIREFLEX DUALFIREFLEX DUAL
Available Configurations:Available Configurations:
• Preaction Single or Double Interlock
• 2" or 3" dia. Sprinkler Valve
• Self-contained or Remote Controlled (no panel)
• Pre-engineered or Engineered Piping System
• Preaction Single or Double Interlock
• 2" or 3" dia. Sprinkler Valve
• Self-contained or Remote Controlled (no panel)
• Pre-engineered or Engineered Piping System
FIREFLEX DUALFIREFLEX DUAL
FIREFLEX DUALFIREFLEX DUAL
FireFlex® DUAL Cabinets Capacity (# of cylinders) & dimensions
Cylinder Size (lbs) Dimensions
Cabinet Size 40 76 164 322 601 A B C
36" 1 1 -- -- -- 35¾" 25" 77⅛"
48" -- -- 1 1 1 46" 25" 77⅛"
System dimensions and Capacity Table:System dimensions and Capacity Table:
NFPA 2001 Standard on Clean Agent Fire Protection Systems
ISO 14520 Standard on Gaseous Media Fire Extinguishing Systems
UL Listed FM Approved
VdS Approved LPCB Approved
IMO Recognized
Lloyds Approved
Standards, Approvals and Listings for Novec 1230 Fluid
U.S EPA SNAP approved as alternative to halon in occupied spaces
DNV Approved
Bureau Veritas Approved
CNPP Approved
LISTINGS & APPROVALSLISTINGS & APPROVALSClean Agent(Sevo Equipment):Clean Agent(Sevo Equipment):
UL & ULC Listed:
• 360 psi Pre-engineered Systems
• Engineered Systems by Mid-2010
FM Approved:
• 500 psi Pre-Engineered Systems
• Engineered Systems early 2010
UL & ULC Listed:
• 360 psi Pre-engineered Systems
• Engineered Systems by Mid-2010
FM Approved:
• 500 psi Pre-Engineered Systems
• Engineered Systems early 2010
Potter Releasing Panel & Viking Preaction System:Potter Releasing Panel & Viking Preaction System:
• UL & ULC Listed
• FM Approved
• CSFM Approved
• NYC Accepted
• UL & ULC Listed
• FM Approved
• CSFM Approved
• NYC Accepted
LISTINGS & APPROVALSLISTINGS & APPROVALS
FIREFLEX DUAL & 1230
(Assembled Units):
FIREFLEX DUAL & 1230
(Assembled Units):
• Pre-engineered System: c-UL-us (early 2010)
• FM Approved 500 psi
• Engineered System: c-UL-us & FM (early 2010)
• CSFM & NYC (early 2010)
• Pre-engineered System: c-UL-us (early 2010)
• FM Approved 500 psi
• Engineered System: c-UL-us & FM (early 2010)
• CSFM & NYC (early 2010)
LISTINGS & APPROVALSLISTINGS & APPROVALS
• Cable racks
• Clean Rooms
• Clinical / Diagnostic equipment
• Control Rooms
• Data Centers
• Electric Utility facilities
• Generator & turbine enclosures
• Cable racks
• Clean Rooms
• Clinical / Diagnostic equipment
• Control Rooms
• Data Centers
• Electric Utility facilities
• Generator & turbine enclosures
APPLICATIONSAPPLICATIONS
• IT Systems
• Mix rooms
• Pump Stations
• Switch Rooms & UPS
• Telecommunications
• Testing / Imaging equipment
• Transformer Vaults
• Etc…
• IT Systems
• Mix rooms
• Pump Stations
• Switch Rooms & UPS
• Telecommunications
• Testing / Imaging equipment
• Transformer Vaults
• Etc…
Information required for designInformation required for design• Obtain specifications
• Approvals required, AHJ
• Determine if a reserve is required
• Identify hazard normal ambient temperature
• Obtain location altitude
• Obtain drawings, sketches of dimensions
• Qualify room size when quoting a job
• Obtain hazard areas, length, width, ceiling height
• Determine system location
• Obtain specifications
• Approvals required, AHJ
• Determine if a reserve is required
• Identify hazard normal ambient temperature
• Obtain location altitude
• Obtain drawings, sketches of dimensions
• Qualify room size when quoting a job
• Obtain hazard areas, length, width, ceiling height
• Determine system location