vacuum contactor and starter...
Post on 28-Mar-2018
229 Views
Preview:
TRANSCRIPT
Technical Data
Vacuum Contactor and Starter SpecificationsBulletin Numbers 1102C, 1104C, 1109
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Topic Page
Specifications 2
1102C Approximate Dimensions 3…4
1104C Approximate Dimensions 5
1109 Approximate Dimensions 6…11
Resource Description
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other certification details.
2 Rockwell Automation Publication 1100-TD004A-EN-P
1102C, 1104C, 1109 Vacuum Contactors and Starters Specifications
200 A 400 A 600 A
Standards UL 508 CSA 22.2 1500V UL 508 CSA 22.2 1500V UL 508 CSA 22.2 1500V
Power Ratings
Insul. & Operating Voltage 200…1500V 200…1500V 200…1500V
Rated Fequency 50…400 Hz 50…400 Hz 50…400 Hz
Making Current Capacity 1600 A 3200 A 4800 A
Breaking Current Capacity 1600 A 3200 A 4800 A
Dielectric Strength 6Kv - 1 Min. Interrupter GAP 6Kv - 1 Min. Interrupter GAP 6Kv - 1 Min. Interrupter GAP
Interrupting Current (Max.) 2.2 kA 4.6 kA 6 kA
Short Circuit Withstand (Max.) 10 kA symmetrical amps @ 1500V AC 18 kA symmetrical amps @ 1500V AC 30 kA symmetrical amps @ 1500V AC
Mechanical Life 1 200 000 1 000 000 750 000
Elect. Life AC3 Duty 500 000 500 000 250 000
Switching Frequency(Mechanical)
1102C, 11091104C
600/hr (max.)6 s (full cycle)
600/hr (max.)6 s (full cycle)
600/hr (max.)6 s (full cycle)
Withstand current for 3 sec [kA] 3.2 6.0 6.5
Chop Current Max. 0.9 A 0.9 A 0.9 A
Control Ratings
Coil Voltage Operation -15% +10% -15% +10% -15% +10%
Inrush Power VA 1200VA 1100VA 1600VA
Sealed Power VA 12VA 12VA 14VA
Opening Time [ms] 120 160 160
Closing Time [ms] 20…40 20…40 30…40
Pick-Up Voltage 80% Cold 85% Hot 80% Cold 85% Hot 80% Cold 85% Hot
Drop-Out Voltage 70% or less 70% or less 70% or less
Application Ratings
Mounting Installation All planes All planes All planes
Altitude 6600 ft (2000 m) 6600 ft (2000 m) 6600 ft (2000 m)
Ambient Storage -65…+160 °F (-54…71 °C) -65…+160 °F (-54…71 °C) -65…+160 °F (-54…71 °C)
Operating Temperature -40…+135 °F (-40…57 °C) -40…+135 °F (-40…57 °C) -40…+135 °F (-40…57 °C)
Vibration/Shock 40 Hz: 2 G/30 G 40 Hz: 2 G/30 G 40 Hz: 2 G/30 G
3Rockwell Automation Publication 1100-TD004A-EN-P
Approximate Dimensions 1102C Vacuum Contactor
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1102C (200 A)
6.44(163.5)
5.3(134.5)
3.5 (89)0.9(22.7)
0.68(17.1)
Optional Aux.Contact Kit
1.0(25.1)
3.3(84.3)
7.5(190.6)
8.32(211.3)
(4) Mounting for 1/4 Screws0.34(8.5)0.32
(8.1)
5.93(150.6)
8.66(219.9)
4 Rockwell Automation Publication 1100-TD004A-EN-P
1102C Vacuum Contactor Approximate Dimensions
0.38 (9.7)
0.81 (20.5)
10.25(260.4)
0.38 (9.7)
0.6(15.2) R 0.19 (4.8)
(4) Mtg. Holes
Ø 0.4(10.2)
0.6(15.2)
0.88 (22.4)
0.88 (22.4)
0.6(15.2)
Ø 0.4(10.2)
0.38 (9.7)0.6
(15.2)
R 0.19 (4.8)(4) Mtg. Holes
400 A
600 A
8.0(203.2)
6.83(173.5)
8.25(209.5)
8.2(208.3)
9.25(234.9)
2.54(64.5)
9.1(231.1)
6.46(164.1)
4.77(121.2)
9.15(232.4)
8.0(203.2)
6.83(173.5)
8.25(209.5)
2.54(64.5)
9.1(231.1)
11.88(301.8)
6.46(164.1)
9.15(232.4)
2.87(72.9)
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1102C (400 A and 600 A)
5Rockwell Automation Publication 1100-TD004A-EN-P
Approximate Dimensions 1104C Reversing Vacuum Contactor
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1104C (200, 400, 600 A)
B
DA
E C
Contactor Size [A]A
HeightB
WidthC
DepthD
Mounting HeightE
Mounting Width
200 8.375(213)
14(358)
6.5(202)
7(210)
13(322)
400 9.25(235)
21(533)
7.10(232)
7.85(272)
19.5(495)
600 12(305)
21(533)
7.10(232)
10.82(280)
19.5(495)
6 Rockwell Automation Publication 1100-TD004A-EN-P
1109 Vacuum Starter Approximate Dimensions
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1109 (200 A)With E1 Plus Overload
0.50(12.7)
2.59(65.8)
RESET CL
0.37(9.5)
3 places
11.96(303.7)
RESET CL15.83(402)
14.88(377.8)
9.81(249.1)
1.52 (38.6)
4.75 (120.7)
8.44 (214.4)
6.8 (172.1)
4.92 (125.1)
3.28 (83.4)
5.79 (147.1)
4.98 (126.6)
7Rockwell Automation Publication 1100-TD004A-EN-P
Approximate Dimensions 1109 Vacuum Starter
CL
0.50(12.7)
1.78(45.1)
RESET CL
0.37(9.5)
3 places
5.79 (147.1)
4.98 (126.6)
15.83(402)
14.88(377.8)
9.81(249.1)
12.62(320.6)
RESET CL
1.52 (38.6)
4.75 (120.7)
8.44 (214.4)6.44 (163.4)
4.92 (125.1)
3.28 (83.4)
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1109 (200 A), ContinuedWith Eutectic Overload
8 Rockwell Automation Publication 1100-TD004A-EN-P
1109 Vacuum Starter Approximate Dimensions
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1109 (400 A)With E1 Plus Overload
9Rockwell Automation Publication 1100-TD004A-EN-P
Approximate Dimensions 1109 Vacuum Starter
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1109 (400 A), Continued
With Eutectic Overload
10 Rockwell Automation Publication 1100-TD004A-EN-P
1109 Vacuum Starter Approximate Dimensions
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1109 (600 A)
With E1 Plus Overload
11Rockwell Automation Publication 1100-TD004A-EN-P
Approximate Dimensions 1109 Vacuum Starter
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 1109 (600 A), Continued
With Eutectic Overload
Allen-Bradley, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1100-TD004A-EN-P - August 2014 Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
top related