ACHIBA PACKAGED COMPACT HORIZONTAL AIR / AIR
Models: 601 │ 741 │ 901 │
EDM_ACHIBA_601a901_207932_190102_EN
-
0
12.14 207470
lUNIDADES TIPO ROOF TOP –
INDEX
PRESENTATION ...................................................................................................................... 1
KEY POINTS ............................................................................................................................ 1
GENERAL SPECIFICATIONS ................................................................................................. 2
OPERATION LIMITS ................................................................................................................ 3
REFRIGERATION DIAGRAM .................................................................................................. 3
TECHNICAL DATA .................................................................................................................. 4
POWER SUPPLY ............................................................................................................... 5
DIMENSIONS ........................................................................................................................... 6
MODELS 601, 741 .............................................................................................................. 6
MODEL 901 ........................................................................................................................ 6
SOUND LEVELS ...................................................................................................................... 7
SOUND PRESSURE LEVEL .............................................................................................. 7
SOUND POWER LEVEL ..................................................................................................... 8
CAPACITIES ............................................................................................................................ 9
COOLING CAPACITY 601 .................................................................................................. 9
COOLING CAPACITY 741 ................................................................................................ 11
COOLING CAPACITY 901 ................................................................................................ 13
HEATING CAPACITY 601 ................................................................................................ 15
HEATING CAPACITY 741 ................................................................................................ 17
HEATING CAPACITY 901 ................................................................................................ 19
VENTILATION ........................................................................................................................ 21
INDOOR AIR FLOW 601 .................................................................................................. 21
INDOOR AIR FLOW 741 ................................................................................................... 21
INDOOR AIR FLOW 901 .................................................................................................. 22
OUTDOOR AIR FLOW 601 .............................................................................................. 22
OUTDOOR AIR FLOW 741 .............................................................................................. 23
OUTDOOR AIR FLOW 901 ............................................................................................... 23
CONTROL AND THERMOSTATS ......................................................................................... 24
OPTIONS ................................................................................................................................ 24
ACHIBA
-
1
EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR-AIR UNITS
AIRE-AIRE
PRESENTATION
- The ACHIBA air-air conditioners have been designed and optimized to meet the current requirements of energy efficiency
and environmental protection. The introduction of the green gas R410A DC inverter technology and expanded cooling
capacities together with an extensive list of accessories are examples of the improvements that have been carried out on
these equipments.
- The DC inverter technology adjuts the speed of the compressor so that it matches the actual requirements securing at the
same time the necessary energy consumption which reduces consumption drastically.
KEY POINTS
- Optimized design for an easier acces to the components.
- DC inverter technology : maximum saving and comfort
- Cooling capacities from 4 to 27kW
- Maximum adaptiblity to demand.
- Low sound level.
- High performance in the heat pump mode for low outdoor temperatures.
-
2 EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR AIR UNITS
GENERAL SPECIFICATIONS DESCRIPTION
The packaged inverter ACHIBA air conditioners comprise reversible horizontal and compact equipments. Their design enables integration to air distribution networks.
CABINET
Manufactured in galvanized steel, finished with polyester
resins, polymerized in the oven with an excellent
resistance to corrosion and weather conditions. The
whole unit is insulated with an inner thermo-acoustic
lining.
COMPRESSORS
Scroll type compressors.
Motor: BLDC. Number of poles: 6. Power supply: Three-
phase.
The Brushless motor comprises a stator and a rotor with
permanent magnets. The Brushless motor is more
efficient than an induction motor as there are no losses
by magnetizing currents in the rotor.
HEAT EXCHANGERS
Made of aluminium fins (1.8 mm fin slots) and
mechanically expanded 3/8’’ copper tubes of highly
efficient exchange performance.
EXPANSION DEVICE
All models are equipped with electronical expansion
valves.
AIR FILTER
Made of washable 10 mm reticulated polyurethane foam,
PPI-20 with a high filtration capacity.
FANS
Centrifugal.
Driven by a frequency converter:
Adjustable air flow in the condenser.
Three air flows in the evaporator (Low, Medium and High
speed).
The Available Pressure can be increased or decreased in
the Evaporator and the Condenser.
REFRIGERATION CIRCUIT
Made of special copper for cooling applications,
dehydrated, equipped with a filter-dryer and ball valves that
enable an easy access for control and charging. It
comprises a suction accumulator in the compressor suction
line to prevent a flood-back to the compressor.
- Revirsible valve for cycle reversing.
- One-way valves.
- The welding joints between the various parts are made
with copper-silver alloys.
CONTROL AND REGULATION DEVICES
All units are equipped with the following control and
security devices:
- 230 V. ambient thermostat (single phase).
- Protection thermal circuit breaker for the compressor,
fans and general control.
- Thermal protection for all the three-phase motors.
- Speed controller of the fan motor (outdoor side).
- High pressure switch.
- Pressure controlled antifrost System with time schedule.
- Reversing valve operated by a 230V Solenoid.
- ON-Off and COOL-HEAT remote connection.
- ALARM display.
OPTIONS
- Backup heating resistances for the antifrost operation.
- Hot water to air coil exchanger.
- Pre-treated coils to prevent corrosion.
- Insulation jacket for the compressor.
- Free-cooling:
Servomotor operated dampers to take advantage of the
outdoor air conditions for the indoor section air
conditioning.
- Weather conditions protection kit.
- Anti-frost resistance for condensate tray.
- Indoor air filters, high efficiency, G4, F6 and F7 class.
- Heavy duty motors. Available Pressure Increase in the
condenser and evaporator sections.
- Outdoor air filter
- Modbus
-
3
EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR-AIR UNITS
AIRE-AIRE
OPERATION LIMITS
COOLING CYCLE Outdoor Air Temperature Indoor Air Temperature
Dry Humid Dry Humid
Standard conditions 35 °C - 27 °C 19 °C
Minimum conditions -10 °C - 20 °C 15 °C
Maximum conditions 50 °C - 32 °C 23 °C
HEATING CYCLE Outdoor Air Temperature Indoor Air Temperature
Dry Humid Dry Humid
Standard conditions 7 °C 6 °C 20 °C -
Minimum conditions - 12 °C - 13 °C 15 °C -
Maximum conditions 24 °C 18 °C 26 °C -
REFRIGERATION DIAGRAM
1. Compressor
2. 4-way valve
3. Electronical expansion valve
4. Check valve
5. Filter
6. Suction accumulator
7. Solenoid valve
8. Outdoor coil
9. Outdoor fan
10. Indoor coil
11. Indoor fan
-
B1. Discharge temperature
B6. Suction pressure
B7. Discharge pressure
HP. High pressure switch
PT. Pressure transducer
TI. Indoor air temperature
TE. Outdoor air temperature
TAsp. Suction temperature
-
4 EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR AIR UNITS
TECHNICAL DATA
ACHIBA 601 741 901 CAPACITIES
Cooling Capacity (1) (20 - 80 - 120 Hz) kW 3,8 - 12,9 - 17,3 4,9 - 16,6 - 22,4 6,2 - 20,6 - 26,5
Heating Capacity (2) (20 - 80 - 120 Hz) kW 4,0 - 13,0 - 18,6 5,2 - 15,7 - 24,2 6,7 - 20,4 - 28,9
EER Coefficient (40 - 80 - 90 Hz) 2.87 - 2.51 - 2.40 2.83 - 2.53 - 2.27 2.93 - 2.42 - 2.22
Seasonal Energy Efficiency Ratio SEER / ηs,c 3,17 / 123,6 3,15 / 123,1 3,14 / 122,5
Coefficient of Performance COP (40 - 80 - 90 Hz) 2.92 - 2.52 - 2.47 2.91 - 2.64 - 2.50 2.83 - 2.35 - 2.17
Seasonal Coefficient of Performance SCOP / ηs,h(A) 3,0 / 117,1 2,98 / 116,2 2,96 / 115,2
Number of refrigeration circuits 1
REFRIGERANT
Type R-410A
Global Weather Potential (GWP) 2088
Charge kg 6,3 9,4
COMPRESSOR
Type SCROLL DC INVERTER
Number 1
Oil type FV50S (PVE)
Oil volume l 1,4 1,7 2,3
OUTDOOR EXCHANGER
Type Aluminium fin coils with copper pipes
Front area m2 0,605 0,900
Fin slots mm 1,8
Tube diameter " 3/8
OUTDOOR CIRCUIT FAN
Type CENTRIFUGAL DOUBLE SUCTION
Model 12/12 DD 12/12 SS
Voltage V 400/3/50
Motor power kW 1,1 1,5 2,2
Speed transmission Built-in motor Pulleys
Nominal Air flow m3/h 5.600 6.200 7.500
Available static pressure Pa 50
Maximum fan speed r.p.m. 847 970 1.058
INDOOR EXCHANGER
Type Aluminium fin coils with copper pipes
Front area m2 0,495 0,539 0,648
Fin slots mm 1,8
Tube diameter " 3/8
INDOOR CIRCUIT FAN
Type CENTRIFUGAL DOUBLE SUCTION
Model 12/9 SS 12/12 SS
Voltage V 400/3/50
Motor power kW 1,1 1,5
Speed transmission Pulleys
Air flow (Low / Medium / High) m3/h 2.300/2.800/3.600 3.000/3.600/4.600 3.700/4.400/5.500
Available static pressure Higher flow Pa 70 80 90
Maximum fan speed r.p.m. 841 986 1.000
(1) Nominal Cool: Compressor Frequency: 80Hz. Outdoor dry air Temperature: 35 °C. Indoor dry/humid Air Temperature: 27ºC / 19 °C. Indoor Air Flow: Low.
(2) Nominal Heating: Compressor Frequency: 80Hz. Outdoor dry/humid Air Temperature: 7ºC / 6 °C. Indoor dry air Temperature: 20 °C. Indoor Air Flow: Medium.
-
5
EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR-AIR UNITS
AIRE-AIRE
TECHNICAL DATA
ACHIBA 601 741 901
NOMINAL ELECTRICAL SPECIFICATIONS FOR STANDARD COOLING CONDITIONS (1)
Power supply 400/3/50 + N
Absorbed power Cooling kW 5,1 6,6 8,5
Absorbed current Cooling A 8,3 10,4 13,5
Indoor air flow m3/h 2.300 3.000 3.700
NOMINAL ELECTRICAL SPECIFICATIONS FOR STANDARD HEATING CONDITIONS (2)
Power Supply 400/3/50 + N
Absorbed power Heating kW 5,0 5,9 8,7
Absorbed current Heating A 7,9 9,5 14,3
Indoor air flow m3/h 2.800 3.600 4.400
MAXIMUM ELECTRICAL SPECIFICATIONS FOR STANDARD COOLING CONDITIONS (3)
Power Supply 400/3/50 + N
Absorbed power Cooling kW 8,7 11,8 14,8
Absorbed current Cooling A 13,4 18,2 22,3
Indoor air flow m3/h 2.800 3.600 4.400
MAXIMUM ELECTRICAL SPECIFICATIONS FOR STANDARD HEATING CONDITIONS (4)
Power Supply 400/3/50 + N
Absorbed power Heating kW 8,2 10,6 14,1
Absorbed current Heating A 12,7 16,9 21,7
Indoor air flow m3/h 3.600 4.600 5.500
DIMENSIONS AND WEIGHT
Length mm 1755 1998
Width mm 1697 1755
Height mm 640 672
Weight Kg 375 420 495
(1) Nominal Cooling: Compressor Frequency: 80Hz. Outdoor dry air Temperature: 35 °C. Indoor dry/humid Air Temperature: 27ºC / 19 °C. Indoor Air Flow: Low.
(2) Nominal Heating: Compressor Frequency: 80Hz. Outdoor dry/humid Air Temperature: 7ºC / 6 °C. Indoor dry air Temperature: 20 °C. Indoor Air Flow: Medium.
(3) Maximum Cooling: Compressor Frequency: 120Hz. . Outdoor dry air Temperature: 35 °C. Indoor dry/humid Air Temperature: 27ºC / 19 °C. Indoor Air Flow: Medium.
(4) Maximum Cooling: Compressor Frequency: 120Hz. Outdoor dry/humid Air Temperature: 7ºC / 6 °C. . Indoor dry air Temperature: 20 °C. Indoor Air Flow: High.
POWER SUPPLY
ACHIBA 601 741 901
Power supply (50Hz) 400V / 3 Phases + N + PE
Power supply TH-Tune Thermostat (50/60Hz) 230V / 1 Phase + N
Maximum operation current A 24 28 35
Nominal Minimum Maximum
Operating voltage 400 V 360 V 440 V
Unbalance between phases 0 V -12 V. (-3%) +12 V. (+3%)
Please contact Hitecsa for other power supply options.
-
6 EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR AIR UNITS
DIMENSIONS MODELS 601, 741
MODEL 901
Legend:
1. Electrical box
2. Interior coil
3. Exterior fan motor
4. Exterior fan
5. Air filter
6. Interior fan
7. Interior fan motor
8. Exterior coil
9. Compressor
10. Interior drain 3/4’’
11. Electrical power supply inlet
12. Main switch
13. Exterior drain 3/4’’
14. Compressor driver box
15. Fan driver box
1. Exterior fan 2. Exterior fan motor 3. Interior coil 4. Electrical box with compressor driver 5. External pressure plug 6. Compressor 7. Interior fan motor 8. Interior fan 9. Air filter
10. Interior drain 3/4’’
11. Exterior drain 3/4’’ 12. Electrical power supply inlet 13. Main switch 14. Electrical box with fan driver
-
7
EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR-AIR UNITS
AIRE-AIRE
SOUND LEVELS
SOUND PRESSURE LEVEL
ACHIBA 601 741 901
SOUND PRESSURE AT 5 M IN SEMISPHERE
Frequency Compressor (Hz) 120
65,2 68,1 70,0 Exterior Fan Frequency (Hz) 50
Interior Fan Speed HIGH
Frequency Compressor (Hz) 120
64,8 67,7 69,6 Exterior Fan Frequency (Hz) 50
Interior Fan Speed MEDIUM
Frequency Compressor (Hz) 120
64,7 67,6 69,5 Exterior Fan Frequency (Hz) 50
Interior Fan Speed LOW
Frequency Compressor (Hz) 80
63,7 66,6 68,5 Exterior Fan Frequency (Hz) 46
Interior Fan Speed HIGH
Frequency Compressor (Hz) 80
63,3 66,1 68,0 Exterior Fan Frequency (Hz) 46
Interior Fan Speed MEDIUM
Frequency Compressor (Hz) 80
63,1 65,9 67,8 Exterior Fan Frequency (Hz) 46
Interior Fan Speed LOW
Frequency Compressor (Hz) 45
57,7 60,3 62,0 Exterior Fan Frequency (Hz) 28
Interior Fan Speed HIGH
Frequency Compressor (Hz) 45
55,1 57,6 59,2 Exterior Fan Frequency (Hz) 28
Interior Fan Speed MEDIUM
Frequency Compressor (Hz) 45
53,5 55,9 57,5 Exterior Fan Frequency (Hz) 28
Interior Fan Speed LOW
Frequency Compressor (Hz) 25
56,6 59,1 60,8 Exterior Fan Frequency (Hz) 15
Interior Fan Speed HIGH
Frequency Compressor (Hz) 25
52,8 55,2 56,8 Exterior Fan Frequency (Hz) 15
Interior Fan Speed MEDIUM
Frequency Compressor (Hz) 25
49,1 51,3 52,8 Exterior Fan Frequency (Hz) 15
Interior Fan Speed LOW
-
8 EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR AIR UNITS
SOUND POWER LEVEL
DUCTED interior and exterior sides.
Values in decibels A (dBA): Reference W0 = 10-12 Watts = 1pW
ACHIBA 601 741 901
OCTAVE BANDS (Hz) INT EXT SUR INT EXT SUR INT EXT SUR
125 49,9 67,1 65,3 53,4 64,3 68,7 54,3 67,2 70,2
250 58,2 71,4 72,6 59,1 70,1 74,5 61,3 72,3 76,8
500 64,8 77,0 79,1 66,5 76,0 81,6 68,3 78,0 83,6
1000 65,9 79,4 80,4 68,1 78,6 83,4 69,7 80,5 85,1
2000 65,9 79,7 80,4 67,7 79,4 83,2 69,5 81,1 85,0
4000 62,3 77,1 77,0 64,7 76,6 80,2 66,2 78,4 81,9
8000 57,8 68,7 71,9 56,9 68,6 72,4 60,0 70,2 75,4
Lw (dBA) 71,4 84,9 85,9 73,3 84,2 88,6 75,0 86,1 90,5
INT: Interior duct outlet
EXT: Exterior duct outlet
SUR: Surrounding
-
9
EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR-AIR UNITS
AIRE-AIRE
CAPACITIES The cooling and heating Net Capacities are stated in the following charts. They have been calculated by applying the corresponding correction factor according to the UNE-EN-14511 standard and the gross absorbed capacities values. The following color codes indicate the ventilator speed:
COOLING CAPACITY 601
Te Int.
Frequency (Hz)
601 DRY OUTDOOR TEMPERATURE (ºc)
25 30 35 40 45 50
21
ºC/1
5ºC
20
Sensible C.(w) 3.597 3.501 3.050 2.978 2.897 2.717
Absorbed C.(w) 1.228 1.320 1.256 1.356 1.442 1.679
TOTAL C. (w) 3.674 3.541 3.050 2.978 2.897 2.717
40
Sensible C.(w) 7.046 6.289 6.058 5.361 5.427 5.167
Absorbed C.(w) 2.509 2.371 2.522 2.567 2.730 3.095
TOTAL C. (w) 7.723 6.595 6.235 5.776 5.427 5.167
60
Sensible C.(w) 10.189 9.616 8.434 8.032 7.465 7.360
Absorbed C.(w) 3.554 3.820 3.728 4.014 4.113 4.633
TOTAL C. (w) 10.311 10.127 8.961 8.463 7.799 7.360
80
Sensible C.(w) 11.795 11.451 11.823 10.570 10.077 8.765
Absorbed C.(w) 4.739 5.048 5.466 5.915 6.073 5.920
TOTAL C. (w) 12.458 11.810 11.900 10.626 10.077 9.044
90
Sensible C.(w) 12.812 12.285 11.832 11.267 10.777 -
Absorbed C.(w) 5.392 5.827 6.197 6.664 7.334 -
TOTAL C. (w) 14.255 13.534 12.796 12.085 11.217 -
120
Sensible C.(w) 14.147 13.167 13.066 12.598 11.901 -
Absorbed C.(w) 7.586 8.182 8.789 9.461 10.281 -
TOTAL C. (w) 17.409 15.414 15.328 14.477 13.430 -
23
ºC/1
7ºC
20
Sensible C.(w) 3.806 3.653 3.526 3.372 3.199 3.005
Absorbed C.(w) 1.091 1.187 1.275 1.377 1.469 1.709
TOTAL C. (w) 3.806 3.653 3.526 3.372 3.199 3.005
40
Sensible C.(w) 6.658 6.328 5.584 5.272 5.952 5.617
Absorbed C.(w) 2.208 2.392 2.414 2.605 2.781 3.172
TOTAL C. (w) 7.305 6.981 6.588 6.241 5.952 5.617
60
Sensible C.(w) 10.343 8.811 8.365 7.898 6.919 7.468
Absorbed C.(w) 3.574 3.532 3.785 4.074 4.190 4.704
TOTAL C. (w) 10.650 10.034 9.653 9.143 8.553 8.020
80
Sensible C.(w) 11.974 11.522 11.804 8.827 8.390 9.291
Absorbed C.(w) 4.765 5.092 5.548 5.677 6.186 6.517
TOTAL C. (w) 13.101 12.500 12.521 11.316 11.051 10.259
90
Sensible C.(w) 13.006 12.360 11.736 10.650 8.870 -
Absorbed C.(w) 5.422 5.877 6.291 6.765 7.139 -
TOTAL C. (w) 14.991 14.325 13.783 13.056 12.126 -
120
Sensible C.(w) 14.362 13.248 12.959 12.236 11.533 -
Absorbed C.(w) 7.628 8.252 8.922 9.606 10.474 -
TOTAL C. (w) 18.307 16.316 16.511 15.640 14.728 -
25
ºC/1
7ºC
20
Sensible C.(w) 3.968 3.758 3.633 3.483 3.307 3.112
Absorbed C.(w) 1.128 1.213 1.280 1.373 1.450 1.691
TOTAL C. (w) 3.968 3.758 3.633 3.483 3.307 3.112
40
Sensible C.(w) 7.152 6.886 6.640 6.365 6.109 5.776
Absorbed C.(w) 2.135 2.295 2.422 2.599 2.743 3.138
TOTAL C. (w) 7.400 6.960 6.505 6.073 6.109 5.776
60
Sensible C.(w) 10.153 8.734 8.321 7.916 7.596 7.372
Absorbed C.(w) 3.367 3.459 3.649 3.917 4.133 4.650
TOTAL C. (w) 10.841 10.004 9.349 8.728 8.084 7.584
80
Sensible C.(w) 10.700 10.580 10.431 9.719 9.481 8.365
Absorbed C.(w) 4.283 4.623 5.238 5.663 6.103 6.233
TOTAL C. (w) 11.823 12.524 12.186 11.012 10.445 9.460
90
Sensible C.(w) 12.900 12.496 11.853 11.361 10.904 -
Absorbed C.(w) 5.608 5.704 5.981 6.419 7.042 -
TOTAL C. (w) 15.032 14.561 13.415 12.524 11.627 -
120
Sensible C.(w) 16.598 15.512 15.410 14.772 12.041 -
Absorbed C.(w) 7.890 8.429 8.952 9.582 10.007 -
TOTAL C. (w) 18.906 16.583 16.302 15.221 13.722 -
High Speed Medium Speed Low Speed
-
10 EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR AIR UNITS
COOLING CAPACITY 601
Te Int.
Frequency (Hz)
601 DRY OUTDOOR TEMPERATURE (ºc)
25 30 35 40 45 50
27
ºC/1
9ºC
20
Sensible C.(w) 4.150 4.032 3.828 3.677 3.494 3.315
Absorbed C.(w) 1.117 1.207 1.287 1.384 1.406 1.837
TOTAL C. (w) 4.150 4.032 3.828 3.677 3.494 3.315
40
Sensible C.(w) 7.072 6.805 6.571 6.360 6.442 6.135
Absorbed C.(w) 2.114 2.286 2.474 2.620 2.760 3.427
TOTAL C. (w) 7.935 7.469 7.111 6.754 6.442 6.135
60
Sensible C.(w) 10.039 9.475 9.150 8.753 8.405 7.431
Absorbed C.(w) 3.333 3.445 3.672 3.950 4.192 4.706
TOTAL C. (w) 11.625 10.735 10.066 9.396 8.728 8.194
80
Sensible C.(w) 11.622 11.321 10.965 9.784 9.472 -
Absorbed C.(w) 4.550 4.850 5.120 5.560 6.040 -
TOTAL C. (w) 14.300 13.440 12.870 11.630 11.060 -
90
Sensible C.(w) 12.624 12.146 11.730 11.221 10.014 -
Absorbed C.(w) 5.219 5.646 6.017 6.472 6.992 -
TOTAL C. (w) 16.363 15.402 14.443 13.485 12.137 -
120
Sensible C.(w) 16.413 13.018 12.952 12.392 11.058 -
Absorbed C.(w) 7.812 8.066 8.675 9.331 10.000 -
TOTAL C. (w) 20.272 17.542 17.302 16.153 14.530 -
29
ºC/2
1ºC
20
Sensible C.(w) 4.349 4.231 4.021 3.863 3.680 3.497
Absorbed C.(w) 1.120 1.212 1.297 1.393 1.405 1.835
TOTAL C. (w) 4.349 4.231 4.021 3.863 3.680 3.497
40
Sensible C.(w) 7.040 6.780 6.565 6.284 6.807 6.450
Absorbed C.(w) 2.120 2.294 2.455 2.637 2.778 3.443
TOTAL C. (w) 8.658 8.090 7.528 6.958 6.807 6.450
60
Sensible C.(w) 9.287 9.441 9.140 8.750 8.420 7.213
Absorbed C.(w) 3.193 3.457 3.699 3.975 4.510 4.766
TOTAL C. (w) 12.442 11.628 10.818 10.000 9.188 8.539
80
Sensible C.(w) 10.752 10.486 10.953 9.780 9.488 -
Absorbed C.(w) 4.412 4.717 5.158 5.596 6.090 -
TOTAL C. (w) 15.306 14.281 13.832 12.377 11.643 -
90
Sensible C.(w) 12.566 11.249 10.890 10.425 10.031 -
Absorbed C.(w) 5.234 5.515 5.909 6.360 7.049 -
TOTAL C. (w) 17.854 16.366 15.227 14.076 12.776 -
120
Sensible C.(w) 13.875 12.972 12.939 11.512 - -
Absorbed C.(w) 7.502 8.095 8.740 9.239 - -
TOTAL C. (w) 21.803 19.001 18.596 16.862 - -
High Speed Medium Speed Low Speed
-
11
EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR-AIR UNITS
AIRE-AIRE
COOLING CAPACITY 741
Te Int.
Frequency (Hz)
741 DRY OUTDOOR TEMPERATURE (ºc)
25 30 35 40 45 50
21
ºC/1
5ºC
20
Sensible C.(w) 5.000 4.867 4.240 4.140 4.027 3.777
Absorbed C.(w) 1.631 1.754 1.669 1.801 1.916 2.230
TOTAL C. (w) 5.107 4.923 4.240 4.140 4.027 3.777
40
Sensible C.(w) 9.242 8.248 7.945 7.032 7.118 6.777
Absorbed C.(w) 3.333 3.150 3.350 3.410 3.626 4.111
TOTAL C. (w) 10.129 8.650 8.178 7.576 7.118 6.777
60
Sensible C.(w) 13.270 12.524 10.985 10.461 9.722 9.586
Absorbed C.(w) 4.642 4.990 4.870 5.243 5.372 6.052
TOTAL C. (w) 13.429 13.190 11.671 11.022 10.158 9.586
80
Sensible C.(w) 15.256 14.811 15.292 13.671 13.033 11.337
Absorbed C.(w) 6.088 6.486 7.022 7.600 7.802 7.606
TOTAL C. (w) 16.113 15.275 15.392 13.743 13.033 11.698
90
Sensible C.(w) 16.596 15.913 15.327 14.595 13.960 -
Absorbed C.(w) 7.362 7.956 8.462 9.099 10.014 -
TOTAL C. (w) 18.465 17.531 16.575 15.654 14.530 -
120
Sensible C.(w) 18.353 17.081 16.950 16.343 15.439 -
Absorbed C.(w) 10.358 11.172 12.001 12.919 14.038 -
TOTAL C. (w) 22.584 19.996 19.885 18.781 17.423 -
23
ºC/1
7ºC
20
Sensible C.(w) 5.291 5.078 4.902 4.688 4.447 4.178
Absorbed C.(w) 1.449 1.577 1.694 1.829 1.952 2.270
TOTAL C. (w) 5.291 5.078 4.902 4.688 4.447 4.178
40
Sensible C.(w) 8.733 8.299 7.324 6.914 7.806 7.367
Absorbed C.(w) 2.933 3.177 3.207 3.461 3.694 4.214
TOTAL C. (w) 9.581 9.156 8.641 8.185 7.806 7.367
60
Sensible C.(w) 13.471 11.475 10.895 10.286 9.012 9.727
Absorbed C.(w) 4.668 4.614 4.944 5.322 5.473 6.144
TOTAL C. (w) 13.871 13.068 12.572 11.908 11.140 10.445
80
Sensible C.(w) 15.487 14.902 15.267 11.417 10.851 12.017
Absorbed C.(w) 6.122 6.542 7.128 7.294 7.948 8.373
TOTAL C. (w) 16.945 16.168 16.194 14.636 14.293 13.269
90
Sensible C.(w) 16.847 16.011 15.202 13.796 11.490 -
Absorbed C.(w) 7.404 8.025 8.590 9.237 9.748 -
TOTAL C. (w) 19.419 18.556 17.854 16.912 15.707 -
120
Sensible C.(w) 18.631 17.186 16.811 15.873 14.962 -
Absorbed C.(w) 10.416 11.268 12.182 13.116 14.302 -
TOTAL C. (w) 23.750 21.166 21.420 20.290 19.107 -
25
ºC/1
7ºC
20
Sensible C.(w) 5.516 5.224 5.051 4.842 4.598 4.326
Absorbed C.(w) 1.499 1.611 1.700 1.824 1.926 2.246
TOTAL C. (w) 5.516 5.224 5.051 4.842 4.598 4.326
40
Sensible C.(w) 9.381 9.032 8.709 8.348 8.013 7.576
Absorbed C.(w) 2.836 3.049 3.218 3.453 3.644 4.169
TOTAL C. (w) 9.705 9.129 8.532 7.965 8.013 7.576
60
Sensible C.(w) 13.223 11.375 10.837 10.310 9.893 9.602
Absorbed C.(w) 4.398 4.518 4.767 5.117 5.399 6.074
TOTAL C. (w) 14.119 13.029 12.176 11.367 10.529 9.877
80
Sensible C.(w) 13.839 13.684 13.491 12.570 12.263 10.819
Absorbed C.(w) 5.503 5.940 6.730 7.276 7.841 8.008
TOTAL C. (w) 15.292 16.199 15.761 14.243 13.509 12.235
90
Sensible C.(w) 16.710 16.186 15.353 14.716 14.125 -
Absorbed C.(w) 7.658 7.789 8.167 8.765 9.616 -
TOTAL C. (w) 19.472 18.861 17.377 16.223 15.061 -
120
Sensible C.(w) 21.533 20.124 19.991 19.164 15.621 -
Absorbed C.(w) 10.774 11.510 12.223 13.084 13.664 -
TOTAL C. (w) 24.526 21.513 21.149 19.746 17.801 -
High Speed Medium Speed Low Speed
-
12 EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR AIR UNITS
COOLING CAPACITY 741
Te Int.
Frequency (Hz)
741 DRY OUTDOOR TEMPERATURE (ºc)
25 30 35 40 45 50
27
ºC/1
9ºC
20
Sensible C.(w) 5.769 5.605 5.322 5.112 4.857 4.608
Absorbed C.(w) 1.484 1.604 1.710 1.839 1.868 2.440
TOTAL C. (w) 5.769 5.605 5.322 5.112 4.857 4.608
40
Sensible C.(w) 9.276 8.925 8.619 8.342 8.449 8.046
Absorbed C.(w) 2.808 3.037 3.287 3.481 3.667 4.553
TOTAL C. (w) 10.407 9.796 9.327 8.858 8.449 8.046
60
Sensible C.(w) 13.075 12.340 11.917 11.400 10.947 9.678
Absorbed C.(w) 4.354 4.500 4.796 5.159 5.476 6.147
TOTAL C. (w) 15.140 13.982 13.110 12.238 11.367 10.672
80
Sensible C.(w) 15.032 14.643 14.182 12.654 12.251 -
Absorbed C.(w) 5.846 6.231 6.578 7.143 7.760 -
TOTAL C. (w) 18.496 17.383 16.646 15.042 14.305 -
90
Sensible C.(w) 16.353 15.733 15.194 14.535 12.972 -
Absorbed C.(w) 7.127 7.710 8.216 8.837 9.547 -
TOTAL C. (w) 21.195 19.951 18.709 17.467 15.721 -
120
Sensible C.(w) 21.293 16.888 16.803 16.076 14.346 -
Absorbed C.(w) 10.667 11.014 11.846 12.741 13.654 -
TOTAL C. (w) 26.298 22.757 22.446 20.955 18.850 -
29
ºC/2
1ºC
20
Sensible C.(w) 6.046 5.882 5.590 5.371 5.116 4.861
Absorbed C.(w) 1.488 1.610 1.723 1.851 1.866 2.438
TOTAL C. (w) 6.046 5.882 5.590 5.371 5.116 4.861
40
Sensible C.(w) 9.233 8.893 8.610 8.242 8.928 8.459
Absorbed C.(w) 2.816 3.048 3.261 3.503 3.690 4.574
TOTAL C. (w) 11.355 10.611 9.873 9.126 8.928 8.459
60
Sensible C.(w) 12.096 12.296 11.904 11.396 10.966 9.395
Absorbed C.(w) 4.171 4.516 4.832 5.192 5.891 6.226
TOTAL C. (w) 16.205 15.145 14.090 13.024 11.966 11.122
80
Sensible C.(w) 13.907 13.562 14.167 12.649 12.272 -
Absorbed C.(w) 5.668 6.060 6.627 7.189 7.824 -
TOTAL C. (w) 19.797 18.471 17.890 16.008 15.059 -
90
Sensible C.(w) 16.277 14.571 14.106 13.504 12.994 -
Absorbed C.(w) 7.147 7.530 8.069 8.685 9.625 -
TOTAL C. (w) 23.127 21.200 19.724 18.233 16.549 -
120
Sensible C.(w) 18.000 16.828 16.785 14.935 - -
Absorbed C.(w) 10.244 11.054 11.934 12.616 - -
TOTAL C. (w) 28.285 24.650 24.124 21.875 - -
High Speed Medium Speed Low Speed
-
13
EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR-AIR UNITS
AIRE-AIRE
COOLING CAPACITY 901
Te Int.
Frequency (Hz)
901 DRY OUTDOOR TEMPERATURE (ºc)
25 30 35 40 45 50
21
ºC/1
5ºC
20
Sensible C.(w) 5.915 5.758 5.016 4.898 4.764 4.468
Absorbed C.(w) 1.899 2.042 1.943 2.097 2.230 2.596
TOTAL C. (w) 6.042 5.824 5.016 4.898 4.764 4.468
40
Sensible C.(w) 11.109 9.914 9.550 8.452 8.556 8.146
Absorbed C.(w) 3.880 3.667 3.900 3.970 4.221 4.786
TOTAL C. (w) 12.175 10.397 9.830 9.106 8.556 8.146
60
Sensible C.(w) 16.202 15.291 13.412 12.773 11.870 11.704
Absorbed C.(w) 5.705 6.132 5.985 6.443 6.602 7.437
TOTAL C. (w) 16.396 16.105 14.250 13.457 12.403 11.704
80
Sensible C.(w) 18.916 18.365 18.961 16.951 16.160 14.057
Absorbed C.(w) 7.876 8.391 9.084 9.832 10.093 9.840
TOTAL C. (w) 19.979 18.940 19.085 17.040 16.160 14.505
90
Sensible C.(w) 20.105 19.277 18.567 17.681 16.911 -
Absorbed C.(w) 9.148 9.886 10.515 11.306 12.443 -
TOTAL C. (w) 22.369 21.237 20.079 18.964 17.602 -
120
Sensible C.(w) 21.710 20.205 20.050 19.332 18.263 -
Absorbed C.(w) 12.871 13.882 14.913 16.053 17.444 -
TOTAL C. (w) 26.715 23.653 23.522 22.216 20.610 -
23
ºC/1
7ºC
20
Sensible C.(w) 6.259 6.007 5.799 5.546 5.261 4.943
Absorbed C.(w) 1.687 1.836 1.972 2.129 2.272 2.642
TOTAL C. (w) 6.259 6.007 5.799 5.546 5.261 4.943
40
Sensible C.(w) 10.497 9.975 8.803 8.311 9.383 8.855
Absorbed C.(w) 3.414 3.698 3.733 4.029 4.300 4.905
TOTAL C. (w) 11.516 11.005 10.386 9.838 9.383 8.855
60
Sensible C.(w) 16.448 14.011 13.302 12.559 11.003 11.876
Absorbed C.(w) 5.736 5.670 6.076 6.540 6.726 7.550
TOTAL C. (w) 16.936 15.956 15.350 14.539 13.602 12.753
80
Sensible C.(w) 19.203 18.478 18.930 14.156 13.455 14.900
Absorbed C.(w) 7.920 8.463 9.222 9.436 10.282 10.832
TOTAL C. (w) 21.011 20.047 20.080 18.148 17.722 16.453
90
Sensible C.(w) 20.409 19.396 18.416 16.713 13.919 -
Absorbed C.(w) 9.200 9.972 10.674 11.478 12.113 -
TOTAL C. (w) 23.525 22.479 21.629 20.488 19.028 -
120
Sensible C.(w) 22.039 20.329 19.886 18.776 17.699 -
Absorbed C.(w) 12.943 14.002 15.137 16.298 17.772 -
TOTAL C. (w) 28.094 25.037 25.338 24.001 22.602 -
25
ºC/1
7ºC
20
Sensible C.(w) 6.526 6.180 5.975 5.728 5.440 5.118
Absorbed C.(w) 1.745 1.875 1.979 2.123 2.242 2.615
TOTAL C. (w) 6.526 6.180 5.975 5.728 5.440 5.118
40
Sensible C.(w) 11.276 10.856 10.468 10.034 9.632 9.106
Absorbed C.(w) 3.301 3.549 3.746 4.020 4.242 4.853
TOTAL C. (w) 11.665 10.973 10.255 9.574 9.632 9.106
60
Sensible C.(w) 16.145 13.888 13.232 12.588 12.079 11.724
Absorbed C.(w) 5.405 5.552 5.858 6.288 6.635 7.464
TOTAL C. (w) 17.239 15.908 14.866 13.879 12.856 12.059
80
Sensible C.(w) 17.159 16.967 16.728 15.586 15.205 13.415
Absorbed C.(w) 7.119 7.685 8.707 9.413 10.144 10.360
TOTAL C. (w) 18.961 20.086 19.543 17.660 16.750 15.171
90
Sensible C.(w) 20.243 19.608 18.599 17.827 17.111 -
Absorbed C.(w) 9.516 9.679 10.148 10.891 11.949 -
TOTAL C. (w) 23.589 22.849 21.051 19.653 18.245 -
120
Sensible C.(w) 25.471 23.805 23.647 22.669 18.478 -
Absorbed C.(w) 13.388 14.302 15.188 16.258 16.979 -
TOTAL C. (w) 29.012 25.448 25.017 23.358 21.057 -
High Speed Medium Speed Low Speed
-
14 EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR AIR UNITS
COOLING CAPACITY 901
Te Int.
Frequency (Hz)
901 DRY OUTDOOR TEMPERATURE (ºc)
25 30 35 40 45 50
27
ºC/1
9ºC
20
Sensible C.(w) 6.825 6.631 6.296 6.048 5.746 5.451
Absorbed C.(w) 1.727 1.867 1.991 2.141 2.174 2.840
TOTAL C. (w) 6.825 6.631 6.296 6.048 5.746 5.451
40
Sensible C.(w) 11.150 10.728 10.360 10.027 10.156 9.671
Absorbed C.(w) 3.269 3.535 3.826 4.052 4.269 5.300
TOTAL C. (w) 12.509 11.775 11.211 10.647 10.156 9.671
60
Sensible C.(w) 15.964 15.067 14.550 13.919 13.366 11.817
Absorbed C.(w) 5.351 5.530 5.894 6.340 6.729 7.554
TOTAL C. (w) 18.485 17.072 16.007 14.942 13.879 13.030
80
Sensible C.(w) 18.639 18.156 17.585 15.690 15.190 -
Absorbed C.(w) 7.563 8.061 8.510 9.241 10.039 -
TOTAL C. (w) 22.934 21.554 20.640 18.651 17.737 -
90
Sensible C.(w) 19.810 19.059 18.406 17.608 15.715 -
Absorbed C.(w) 8.856 9.580 10.209 10.981 11.863 -
TOTAL C. (w) 25.676 24.169 22.664 21.160 19.045 -
120
Sensible C.(w) 25.187 19.977 19.876 19.016 16.970 -
Absorbed C.(w) 13.255 13.686 14.720 15.832 16.967 -
TOTAL C. (w) 31.108 26.919 26.551 24.788 22.298 -
29
ºC/2
1ºC
20
Sensible C.(w) 7.153 6.959 6.613 6.354 6.052 5.751
Absorbed C.(w) 1.732 1.874 2.006 2.155 2.172 2.838
TOTAL C. (w) 7.153 6.959 6.613 6.354 6.052 5.751
40
Sensible C.(w) 11.098 10.689 10.349 9.907 10.731 10.168
Absorbed C.(w) 3.278 3.548 3.796 4.078 4.295 5.324
TOTAL C. (w) 13.649 12.754 11.867 10.969 10.731 10.168
60
Sensible C.(w) 14.769 15.013 14.534 13.914 13.389 11.471
Absorbed C.(w) 5.126 5.550 5.938 6.380 7.239 7.651
TOTAL C. (w) 19.786 18.492 17.203 15.902 14.610 13.580
80
Sensible C.(w) 17.244 16.816 17.566 15.684 15.217 -
Absorbed C.(w) 7.333 7.840 8.573 9.300 10.122 -
TOTAL C. (w) 24.547 22.903 22.182 19.849 18.672 -
90
Sensible C.(w) 19.718 17.652 17.088 16.359 15.741 -
Absorbed C.(w) 8.881 9.357 10.027 10.792 11.960 -
TOTAL C. (w) 28.016 25.682 23.894 22.088 20.048 -
120
Sensible C.(w) 21.292 19.906 19.855 17.667 - -
Absorbed C.(w) 12.729 13.736 14.829 15.677 - -
TOTAL C. (w) 33.458 29.158 28.536 25.876 - -
High Speed Medium Speed Low Speed
-
15
EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR-AIR UNITS
AIRE-AIRE
HEATING CAPACITY 601
ºC Freq.
601 Outdoor Temperature (°C): BS (BH)
(Hz) -11 (-12) -7 (-8) 2 (1) 7 (6) 10 (9) 15/14 20/19
16
ºC
20 Absorbed C.(w) - - - 1.435 1.166 819 760
TOTAL C. (w) - - - 4.113 4.453 5.024 5.755
40 Absorbed C.(w) - - 3.000 2.610 2.091 1.657 1.526
TOTAL C. (w) - - 6.770 7.770 8.463 9.490 10.665
60 Absorbed C.(w) 3.987 4.017 4.137 3.752 3.025 2.651 2.612
TOTAL C. (w) 6.153 6.972 9.332 10.645 11.463 12.733 14.219
80 Absorbed C.(w) 4.949 5.060 5.349 5.055 4.583 4.184 3.984
TOTAL C. (w) 7.606 8.739 11.536 13.072 14.193 16.030 17.442
90 Absorbed C.(w) 5.018 5.155 5.562 5.748 4.998 4.649 4.632
TOTAL C. (w) 8.520 9.741 12.955 14.817 15.927 17.683 19.173
120 Absorbed C.(w) 7.249 7.539 8.202 8.744 7.395 7.478 7.343
TOTAL C. (w) 10.968 12.435 16.363 18.893 20.258 22.792 24.787
18
ºC
20 Absorbed C.(w) - - - 1.472 1.458 1.370 1.199
TOTAL C. (w) - - - 4.075 4.143 4.560 5.321
40 Absorbed C.(w) - 3.561 3.069 2.687 2.660 2.498 2.219
TOTAL C. (w) - 5.076 6.697 7.688 7.817 8.603 9.151
60 Absorbed C.(w) 4.071 4.102 4.232 3.855 3.816 3.605 3.305
TOTAL C. (w) 6.105 6.906 9.232 10.532 10.709 11.252 13.230
80 Absorbed C.(w) 5.073 5.186 5.490 5.257 5.205 4.889 4.318
TOTAL C. (w) 7.554 8.671 11.427 13.108 13.328 14.668 17.400
90 Absorbed C.(w) 5.155 5.297 5.712 5.906 5.847 5.614 4.919
TOTAL C. (w) 8.481 9.681 12.847 14.682 14.929 16.794 19.598
120 Absorbed C.(w) 7.487 7.779 8.444 8.986 8.898 8.358 7.323
TOTAL C. (w) 10.968 12.410 16.273 18.761 19.076 20.993 24.499
20
ºC
20 Absorbed C.(w) - - - 1.508 1.497 1.433 1.311
TOTAL C. (w) - - - 4.037 4.101 4.491 5.204
40 Absorbed C.(w) 3.630 3.622 3.138 2.765 2.745 2.627 2.436
TOTAL C. (w) 4.454 5.028 6.621 7.603 7.724 8.459 8.932
60 Absorbed C.(w) 4.156 4.191 4.328 3.960 3.955 3.784 3.623
TOTAL C. (w) 6.058 6.843 9.134 10.417 10.102 11.064 12.917
80 Absorbed C.(w) 5.201 5.317 5.712 5.402 5.364 5.133 4.733
TOTAL C. (w) 7.515 8.607 11.440 12.980 13.186 14.441 17.008
90 Absorbed C.(w) 5.301 5.440 5.861 6.374 6.329 6.056 5.540
TOTAL C. (w) 8.446 9.620 12.735 14.760 14.994 16.422 19.026
120 Absorbed C.(w) 7.734 7.948 8.846 9.239 9.175 7.147 6.537
TOTAL C. (w) 10.977 12.417 16.343 18.639 18.935 20.737 24.026
High Speed Medium Speed Low Speed
-
16 EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR AIR UNITS
HEATING CAPACITY 601
ºC Freq.
601 Outdoor Temperature (°C): BS (BH)
(Hz) -11 (-12) -7 (-8) 2 (1) 7 (6) 10 (9) 15/14 20/19
16
ºC
20 Absorbed C.(w) - - - 1.544 1.538 1.500 1.431
TOTAL C. (w) - - - 3.996 4.055 4.391 5.082
40 Absorbed C.(w) 3.691 3.733 2.892 2.951 2.940 2.906 2.773
TOTAL C. (w) 4.414 4.979 6.501 7.517 7.628 7.528 8.713
60 Absorbed C.(w) 4.244 4.326 4.071 4.337 4.225 4.410 4.207
TOTAL C. (w) 6.012 6.779 8.972 10.419 10.574 11.536 13.351
80 Absorbed C.(w) 5.334 5.498 5.997 5.701 5.679 5.583 5.326
TOTAL C. (w) 7.471 8.542 11.329 12.853 13.045 14.359 16.617
90 Absorbed C.(w) 5.448 5.631 6.146 6.241 6.217 6.064 5.785
TOTAL C. (w) 8.414 9.564 12.627 14.476 14.692 15.909 18.412
120 Absorbed C.(w) 7.936 8.244 9.234 9.686 9.647 9.410 8.977
TOTAL C. (w) 10.975 12.398 16.245 18.512 18.788 20.345 23.544
18
ºC
20 Absorbed C.(w) - - - 1.665 1.665 1.657 1.665
TOTAL C. (w) - - - 3.956 3.986 4.322 4.340
40 Absorbed C.(w) 3.753 3.797 2.962 3.026 3.029 3.053 3.034
TOTAL C. (w) 4.374 4.934 6.427 7.428 7.483 7.395 8.491
60 Absorbed C.(w) 4.337 4.419 4.315 4.035 4.038 4.204 4.177
TOTAL C. (w) 5.969 6.718 8.962 10.204 10.281 11.231 12.896
80 Absorbed C.(w) 5.472 5.636 6.140 6.257 6.311 6.278 6.237
TOTAL C. (w) 7.430 8.479 11.219 12.906 13.218 14.332 16.456
90 Absorbed C.(w) 5.600 5.855 6.650 6.401 6.406 6.371 6.330
TOTAL C. (w) 8.385 9.561 12.670 14.344 14.453 15.669 17.992
120 Absorbed C.(w) 8.194 8.500 9.481 9.960 9.968 9.915 9.850
TOTAL C. (w) 10.992 12.376 16.164 18.451 18.589 20.156 23.142
High Speed Medium Speed Low Speed
-
17
EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR-AIR UNITS
AIRE-AIRE
HEATING CAPACITY 741
ºC Freq.
741 Outdoor Temperature (°C): BS (BH)
(Hz) -11 (-12) -7 (-8) 2 (1) 7 (6) 10 (9) 15/14 20/19
16
ºC
20 Absorbed C.(w) - - - 1.802 1.464 1028 955
TOTAL C. (w) - - - 5.049 5.466 6.168 7.065
40 Absorbed C.(w) - - 3.725 3.241 2.597 2.058 1.895
TOTAL C. (w) - - 8.266 9.488 10.334 11.588 13.022
60 Absorbed C.(w) 4.801 4.838 4.982 4.519 3.643 3.192 3.145
TOTAL C. (w) 7.473 8.468 11.334 12.929 13.922 15.464 17.269
80 Absorbed C.(w) 5.786 5.915 6.253 5.909 5.358 4.891 4.657
TOTAL C. (w) 9.189 10.558 13.936 15.792 17.147 19.366 21.072
90 Absorbed C.(w) 6.209 6.378 6.881 7.112 6.184 5.752 5.731
TOTAL C. (w) 10.475 11.976 15.928 18.217 19.582 21.740 23.572
120 Absorbed C.(w) 8.969 9.327 10.148 10.818 9.149 9.252 9.085
TOTAL C. (w) 14.240 16.144 21.244 24.529 26.302 29.592 32.182
18
ºC
20 Absorbed C.(w) - - - 1.848 1.830 1.707 1.562
TOTAL C. (w) - - - 5.003 5.087 5.598 6.533
40 Absorbed C.(w) - 4.422 3.811 3.337 3.327 3.266 2.756
TOTAL C. (w) - 6.198 8.177 9.387 9.544 10.503 11.172
60 Absorbed C.(w) 4.902 4.940 5.096 4.642 4.597 4.341 3.981
TOTAL C. (w) 7.415 8.388 11.213 12.791 13.005 13.663 16.066
80 Absorbed C.(w) 5.930 6.062 6.418 6.145 6.084 5.715 5.047
TOTAL C. (w) 9.126 10.475 13.805 15.836 16.101 17.720 21.022
90 Absorbed C.(w) 6.378 6.554 7.067 7.307 7.235 6.947 6.086
TOTAL C. (w) 10.427 11.902 15.795 18.051 18.353 20.647 24.095
120 Absorbed C.(w) 9.263 9.625 10.447 11.118 11.682 10.973 9.614
TOTAL C. (w) 14.240 16.112 21.127 24.358 24.767 27.257 31.808
20
ºC
20 Absorbed C.(w) - - - 1.894 1.880 1.799 1.646
TOTAL C. (w) - - - 4.956 5.035 5.514 6.388
40 Absorbed C.(w) 4.507 4.498 3.896 3.433 3.410 3.262 3.024
TOTAL C. (w) 5.438 6.139 8.085 9.283 9.430 10.328 10.906
60 Absorbed C.(w) 5.005 5.047 5.212 4.769 4.762 4.557 4.362
TOTAL C. (w) 7.357 8.311 11.093 12.652 12.270 13.439 15.687
80 Absorbed C.(w) 6.080 6.216 6.677 6.315 6.271 6.001 5.533
TOTAL C. (w) 9.079 10.398 13.821 15.681 15.929 17.446 20.548
90 Absorbed C.(w) 6.558 6.731 7.251 7.886 7.831 7.493 6.854
TOTAL C. (w) 10.384 11.827 15.657 18.147 18.434 20.190 23.391
120 Absorbed C.(w) 9.569 9.833 10.944 11.431 11.351 10.868 10.240
TOTAL C. (w) 14.252 16.121 21.219 24.200 24.583 26.924 31.194
High Speed Medium Speed Low Speed
-
18 EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR AIR UNITS
HEATING CAPACITY 741
ºC Freq.
741 Outdoor Temperature (°C): BS (BH)
(Hz) -11 (-12) -7 (-8) 2 (1) 7 (6) 10 (9) 15/14 20/19
22
ºC
20 Absorbed C.(w) - - - 1.939 1.932 1.884 2.283
TOTAL C. (w) - - - 4.906 4.979 5.392 6.240
40 Absorbed C.(w) 4.583 4.635 3.591 3.664 3.650 3.608 3.442
TOTAL C. (w) 5.390 6.080 7.938 9.178 9.315 9.193 10.639
60 Absorbed C.(w) 5.111 5.210 4.902 5.223 5.125 5.311 5.066
TOTAL C. (w) 7.302 8.233 10.897 12.654 12.842 14.012 16.601
80 Absorbed C.(w) 6.236 6.427 7.010 6.664 6.638 6.526 6.226
TOTAL C. (w) 9.026 10.319 13.687 15.528 15.759 17.347 20.076
90 Absorbed C.(w) 6.740 6.967 7.604 7.721 7.690 7.501 7.156
TOTAL C. (w) 10.345 11.758 15.524 17.797 18.062 19.560 22.636
120 Absorbed C.(w) 9.819 10.200 11.424 11.984 11.936 11.643 11.107
TOTAL C. (w) 14.249 16.097 21.091 24.034 24.392 27.012 30.567
24
ºC
20 Absorbed C.(w) - - - 2.091 2.092 2.082 2.091
TOTAL C. (w) - - - 4.856 4.893 5.304 5.328
40 Absorbed C.(w) 4.660 4.715 3.678 3.758 3.760 3.791 3.767
TOTAL C. (w) 5.341 6.024 7.848 9.070 9.138 9.031 10.368
60 Absorbed C.(w) 5.223 5.322 5.197 4.859 4.863 5.062 5.030
TOTAL C. (w) 7.249 8.159 10.884 12.393 12.486 13.640 15.661
80 Absorbed C.(w) 6.397 6.588 7.178 7.314 7.377 7.339 7.290
TOTAL C. (w) 8.976 10.243 13.554 15.592 15.969 17.314 19.880
90 Absorbed C.(w) 6.929 7.244 8.228 7.919 7.925 7.883 7.832
TOTAL C. (w) 10.309 11.755 15.577 17.635 17.767 19.264 22.120
120 Absorbed C.(w) 10.138 10.516 11.730 12.323 12.330 12.266 12.186
TOTAL C. (w) 14.271 16.068 20.986 23.955 24.135 26.169 30.046
High Speed Medium Speed Low Speed
-
19
EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR-AIR UNITS
AIRE-AIRE
HEATING CAPACITY 901
ºC Freq.
901 Outdoor Temperature (°C): BS (BH)
(Hz) -11 (-12) -7 (-8) 2 (1) 7 (6) 10 (9) 15/14 20/19
16
ºC
20 Absorbed C.(w) - - - 2.438 1.981 1391 1292
TOTAL C. (w) - - - 6.825 7.389 8.338 9.550
40 Absorbed C.(w) - - 5.039 4.384 3.513 2.784 2.564
TOTAL C. (w) - - 11.037 12.668 13.798 15.472 17.387
60 Absorbed C.(w) 6.691 6.743 6.944 6.298 5.077 4.449 4.383
TOTAL C. (w) 9.854 11.166 14.945 17.048 18.358 20.391 22.771
80 Absorbed C.(w) 8.301 8.486 8.971 8.478 7.687 7.017 6.681
TOTAL C. (w) 11.964 13.747 18.145 20.562 22.326 25.215 27.436
90 Absorbed C.(w) 8.867 9.108 9.827 10.157 8.831 8.214 8.184
TOTAL C. (w) 13.357 15.271 20.310 23.228 24.969 27.721 30.057
120 Absorbed C.(w) 11.755 12.224 13.300 14.178 11.991 12.126 11.907
TOTAL C. (w) 17.007 19.281 25.372 29.296 31.413 35.343 38.436
18
ºC
20 Absorbed C.(w) - - - 2.500 2.476 2.326 2.038
TOTAL C. (w) - - - 6.763 6.876 7.567 8.831
40 Absorbed C.(w) - 5.982 5.156 4.514 4.469 4.198 3.727
TOTAL C. (w) - 8.276 10.918 12.533 12.743 14.025 14.916
60 Absorbed C.(w) 6.832 6.885 7.103 6.470 6.406 6.051 5.549
TOTAL C. (w) 9.777 11.060 14.786 16.866 17.148 18.018 21.185
80 Absorbed C.(w) 8.508 8.697 9.208 8.816 8.729 8.199 7.241
TOTAL C. (w) 11.882 13.639 17.974 20.619 20.965 23.073 27.371
90 Absorbed C.(w) 9.108 9.360 10.092 10.435 10.332 9.920 8.692
TOTAL C. (w) 13.295 15.176 20.140 23.017 23.403 26.328 30.725
120 Absorbed C.(w) 12.140 12.615 13.692 14.572 14.428 13.553 11.874
TOTAL C. (w) 17.007 19.243 25.233 29.092 29.579 32.553 37.989
20
ºC
20 Absorbed C.(w) - - - 2.562 2.544 2.435 2.227
TOTAL C. (w) - - - 6.699 6.805 7.453 8.635
40 Absorbed C.(w) 6.097 6.085 5.271 4.644 4.612 4.412 4.091
TOTAL C. (w) 7.261 8.197 10.795 12.395 12.592 13.790 14.561
60 Absorbed C.(w) 6.976 7.034 7.264 6.647 6.637 6.351 6.080
TOTAL C. (w) 9.701 10.959 14.627 16.683 16.179 17.720 20.686
80 Absorbed C.(w) 8.723 8.918 9.579 9.060 8.996 8.609 7.937
TOTAL C. (w) 11.821 13.538 17.995 20.417 20.740 22.715 26.753
90 Absorbed C.(w) 9.365 9.612 10.355 11.262 11.183 10.701 9.788
TOTAL C. (w) 13.241 15.081 19.964 23.139 23.505 25.744 29.827
120 Absorbed C.(w) 12.541 12.887 14.343 14.982 14.878 11.588 13.047
TOTAL C. (w) 17.022 19.254 25.343 28.903 29.361 32.157 37.257
High Speed Medium Speed Low Speed
-
20 EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR AIR UNITS
HEATING CAPACITY 901
ºC Freq.
901 Outdoor Temperature (°C): BS (BH)
(Hz) -11 (-12) -7 (-8) 2 (1) 7 (6) 10 (9) 15/14 20/19
22
ºC
20 Absorbed C.(w) - - - 2.623 2.612 2.548 2.431
TOTAL C. (w) - - - 6.632 6.731 7.289 8.435
40 Absorbed C.(w) 6.200 6.270 4.858 4.957 4.938 4.882 4.657
TOTAL C. (w) 7.197 8.118 10.599 12.254 12.436 12.274 14.204
60 Absorbed C.(w) 7.123 7.261 6.832 7.280 7.150 7.402 7.061
TOTAL C. (w) 9.628 10.856 14.369 16.686 16.935 18.477 21.382
80 Absorbed C.(w) 8.947 9.221 10.057 9.561 9.524 9.363 8.932
TOTAL C. (w) 11.752 13.436 17.821 20.218 20.519 22.587 26.139
90 Absorbed C.(w) 9.625 9.949 10.859 11.026 10.983 10.712 10.219
TOTAL C. (w) 13.191 14.993 19.795 22.693 23.031 24.940 28.861
120 Absorbed C.(w) 12.869 13.368 14.973 15.707 15.645 15.260 14.557
TOTAL C. (w) 17.018 19.225 25.190 28.705 29.098 31.509 36.464
24
ºC
20 Absorbed C.(w) - - - 2.829 2.832 2.817 2.830
TOTAL C. (w) - - - 6.564 6.613 7.170 7.201
40 Absorbed C.(w) 6.304 6.379 4.976 5.084 5.086 5.129 5.095
TOTAL C. (w) 7.131 8.043 10.479 12.110 12.200 12.057 13.843
60 Absorbed C.(w) 7.280 7.418 7.243 6.772 6.776 7.056 7.010
TOTAL C. (w) 9.559 10.759 14.352 16.342 16.465 17.986 20.653
80 Absorbed C.(w) 9.178 9.452 10.298 10.493 10.584 10.529 10.460
TOTAL C. (w) 11.687 13.337 17.648 20.301 20.791 22.544 25.884
90 Absorbed C.(w) 9.895 10.345 11.750 11.309 11.316 11.257 11.184
TOTAL C. (w) 13.145 14.989 19.862 22.486 22.655 24.564 28.205
120 Absorbed C.(w) 13.287 13.783 15.374 16.151 16.162 16.078 15.972
TOTAL C. (w) 17.044 19.191 25.064 28.610 28.824 32.396 35.885
High Speed Medium Speed Low Speed
-
21
EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR-AIR UNITS
AIRE-AIRE
VENTILATION
INDOOR AIR FLOW 601
INDOOR AIR FLOW 741
0
0,5
1
1,5
2
2,5
0
20
40
60
80
100
120
140
1500 2000 2500 3000 3500 4000
Cu
rren
t (A
)
Ava
ilab
le P
ress
ure
(P
a)
Flow (m3/h)
Alta
Media
Baja
Intensidad Alta
Intensidad Media
Intensidad Baja
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
0
50
100
150
200
250
2000 2500 3000 3500 4000 4500 5000 5500
Cu
rren
t (A
)
Ava
ilab
le P
ress
ure
(P
a)
Flow (m3/h)
Alta
Media
Baja
Intensidad Alta
Intensidad Media
Intensidad Baja
-
22 EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR AIR UNITS
VENTILATION INDOOR AIR FLOW 901
OUTDOOR AIR FLOW 601
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
0
50
100
150
200
250
300
3000 3500 4000 4500 5000 5500 6000
Cu
rren
t (A
)
Ava
ilab
le P
ress
ure
(P
a)
Flow (m3/h)
Alta
Media
Baja
Intensidad Alta
Intensidad Media
Intensidad Baja
0
1
2
3
4
5
0
50
100
150
200
250
2000 2500 3000 3500 4000 4500 5000 5500
Cu
rren
t (A
)
Ava
ilab
le P
ress
ure
(P
a)
Flow (m3/h)
100%
70%
Presión delconductoIntensidad 100%
Intensidad 70%
Q= 5600 m3/h
High
Medium
Low
High current
Medium current
Low current
100% 70% Duct pressure 100% current 70% current
-
23
EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR-AIR UNITS
AIRE-AIRE
VENTILATION
OUTDOOR AIR FLOW 741
OUTDOOR AIR FLOW 901
0
1
2
3
4
5
0
50
100
150
200
250
1400 1900 2400 2900 3400 3900 4400 4900 5400 5900 6400
Cu
rren
t (
A)
Ava
ilab
le P
ress
ure
(P
a)
Flow (m3/h)
100%
70%
Presión delconductoIntensidad 100%
Intensidad 70%
Q= 6200 m3/h
0
2
4
6
8
10
12
0
50
100
150
200
250
300
350
400
4300 4800 5300 5800 6300 6800 7300 7800
Cu
rren
t (A
)
Ava
ilab
le P
ress
ure
(P
a)
Air flow (m3/h)
100%
70%
Presión delconductoIntensidad 100%
Intensidad 70%
Q= 7500 m3/h
100% 70% Duct pressure 100% current 70% current
100% 70% Duct pressure 100% current 70% current
-
24 EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR AIR UNITS
CONTROL AND THERMOSTATS The TH-Tune controller is available for the whole DC Inverter range (compact and split equipments).
It displays:
- Cooling/Heating mode.
- Control temperature (room / return)
- Outdoor temperature
- Alarm codes
Icons and symbols show the operation state of the compressor and the outdoor fan. The indoor fan speed can be defined by
the user (high, medium or low). However it is advisable to chose the automatic mode. The controller will display instruction
codes in case of alarms or required maintenance.
WALL PROBE
Temperature is controlled thanks to a wall room temperature probe.
It provides a more stable control of the temperature by measuring the value of the control zone. Generally speaking we
do recommend to install the wall probe close to the TH-Tune controller.
OPTIONS
BACK-UP HEATING RESISTANCES FOR THE ANTIFROST OPERATION
One stage coils that comprise nickel-chrome wire resistances fitted in a frame provided with separators. They are made
of galvanized and bichromate steel plates and include a thermal protector. A contactor and a connection terminal box are
included.
DIMENSIONS (mm)
MODEL A B C D
601-741 370 330 353 395
901 370 330 398 440
Legend:
1. Contactor
2. Connection terminal plugs
3. Thermal protector
-
25
EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR-AIR UNITS
AIRE-AIRE
OPTIONS FREE COOLING
The Free-Cooling is available as an option and enables the equipment to use the outdoor air to enhance air condition with
Energy savings.
8 possible combinations are available for the 601, 741, 901 models.
The standard air outlet (facing the free cooling) is not recommended for the 3, 5 and 7 combinations.
-
26 EDM_ACHIBA_601a901_207932_190102_EN
ACHIBA PACKAGED COMPACT HORIZONTAL AIR AIR UNITS
Subject to modifications without prior notice.
top related