DESIGN AIR UNIVERSITY Customer Experience Majority of run 67% Majority of run 67% Delivers steady state cooling. Delivers steady state cooling. Eliminates temperature peaks & valleys from compressor cycling. Eliminates temperature peaks & valleys from compressor cycling. Better humidity control. Better humidity control. Majority of run 67% Majority of run 67% Delivers steady state cooling. Delivers steady state cooling. Eliminates temperature peaks & valleys from compressor cycling. Eliminates temperature peaks & valleys from compressor cycling. Better humidity control. Better humidity control.

TRANSCRIPT

Two-Stage Copeland Scroll Compressors

DESIGN AIR UNIVERSITY

External view• 1st stage = 67%• 2nd stage = 100%• Used in 17 SEER

AC.

DESIGN AIR UNIVERSITY

Customer Experience• Majority of run hours @ 67%• Delivers steady state cooling.• Eliminates temperature peaks

& valleys from compressor cycling.

• Better humidity control.

DESIGN AIR UNIVERSITY

How does it work?• Solenoid opens or closes a

port on the internal scrolls.• Valve is actually a ring that

rotates.• Ring opens or closes the

bypass port.

DESIGN AIR UNIVERSITY

Internal assembly

DESIGN AIR UNIVERSITY

1st Stage Position• Solenoid is NOT energized.• Port is OPEN.• Only 2/3 of scroll compresses

refrigerant.• The other 1/3 is bypassed thru

the open port.

DESIGN AIR UNIVERSITY

Solenoid: “unpowered”

DESIGN AIR UNIVERSITY

Port open

DESIGN AIR UNIVERSITY

Port open

DESIGN AIR UNIVERSITY

2nd Stage Position• Solenoid is energized w 24 volts dc.

• Ring rotates & closes the port.

• The entire scroll capacity is delivered.

DESIGN AIR UNIVERSITY

Scroll internals• Solenoid operates on DC voltage.• Initial inrush is 18 to 28 volts DC.• Holding voltage is less.

DESIGN AIR UNIVERSITY

Solenoid: “powered”

DESIGN AIR UNIVERSITY

Port closed

DESIGN AIR UNIVERSITY

Port closed

DESIGN AIR UNIVERSITY

Staging Control Wiring• Separate wiring to terminal

block on compressor shell.

• Connects integrated compressor control to internal solenoid.

DESIGN AIR UNIVERSITY

Checking Solenoid

Use your ohmmeter.

DESIGN AIR UNIVERSITY

Solenoid Molex Plug

DESIGN AIR UNIVERSITY

Molex unplugged

DESIGN AIR UNIVERSITY

Placement of probes

DESIGN AIR UNIVERSITY

“Good” Ohm reading

32 to 60 ohms.

DESIGN AIR UNIVERSITY

Ohm check on Molex plug

• If resistance is infinite, the solenoid is electrically “open”.

• Compressor never operates on 2nd stage.

• The fix? Replace the compressor.