Substation Grounding- Sahadeo Latchmepersad, T&TEC 1

T&T SubsectionLocal IAS Chapter

GROUNDING-DESIGN AND CONSTRUCTIONSaturday 12th November 2005

Presented by

Eng. Sahadeo Latchmepersad, MIEEE, MAPETT, R. Eng.

Substation Grounding- Sahadeo Latchmepersad, T&TEC 2

ACKNOWLEDGEMENT

The Trinidad and Tobago Electricity Commission

Substation Grounding- Sahadeo Latchmepersad, T&TEC 3

Range of Large Industrial Customers

Rate D3- 4-25 MVA at 33, 66 or 132 kV

Rate E > 25 MVA at 66 or 132kV

Substation Grounding- Sahadeo Latchmepersad, T&TEC 4

Substation Grounding- Sahadeo Latchmepersad, T&TEC 5

Transmission

B.C/Union Estate Schematic

Substation Grounding- Sahadeo Latchmepersad, T&TEC 6

Objectives of Grounding

To provide means to carry electric currents to earth under normal and fault conductors without exceeding any operating and equipment limits or adversely affecting continuity of service.

Substation Grounding- Sahadeo Latchmepersad, T&TEC 7

Objectives of Grounding-

To ensure that a person in the vicinity of grounded facilities is not exposed to the danger of critical electric shock.

Substation Grounding- Sahadeo Latchmepersad, T&TEC 8

Basic Shock Situations

Substation Grounding- Sahadeo Latchmepersad, T&TEC 9

BRIGHTON 66kV SUBSTATION

Substation Grounding- Sahadeo Latchmepersad, T&TEC 10

Ventricular Fibrillation

The most dangerous consequence of electric current passing through the vital parts of a human body is a heart condition – ventricular fibrillation –immediate arrest of blood circulation.

Substation Grounding- Sahadeo Latchmepersad, T&TEC 11

Design Algorithm

Substation Grounding- Sahadeo Latchmepersad, T&TEC 12

Measuring Soil Resistivity

Procedure depends on the instrument

Substation Grounding- Sahadeo Latchmepersad, T&TEC 13

Substation Grounding- Sahadeo Latchmepersad, T&TEC 14

Soil Resistivity Calculation

ρ = 2 x Pi x a x RWhere R is Maximum measured Value

Substation Grounding- Sahadeo Latchmepersad, T&TEC 15

Tolerable Step Voltage

Step Voltage Limit 50 kgE Step 50 = (1000 + 6 Cs ρs) 0.116

√ts

E Step 70 = (1000 + 6 Cs ρs) 0.157√ts

Substation Grounding- Sahadeo Latchmepersad, T&TEC 16

Tolerable Touch Voltage Limit

E touch50 = (1000 + 1.5 Cs ρs) 0.116√ts

E touch70 = (1000 + 1.5 Cs ρs) 0.157√ts

Substation Grounding- Sahadeo Latchmepersad, T&TEC 17

Constants

Cs = 1 – [0.09 (1 - ρ/ ρ s)][2 hs + 0.09]

ρ = soil resitivityρ s = surface layer resistivityTs = duration of shock current in seconds including clearance time of circuit breaker plus relay

Substation Grounding- Sahadeo Latchmepersad, T&TEC 18

Conductor Sizing

I = Amm2 [TCAP.10-4] Ln Ko + Tm

[tc αr ρr] Ko + Ta

Substation Grounding- Sahadeo Latchmepersad, T&TEC 19

Grid Resistance

burial of depth theish conductor oflength total theis

/20111

2011

T

Tg

LyresistivitsoiltheisWhere

AhALR

ρ

ρ

+

++=

Substation Grounding- Sahadeo Latchmepersad, T&TEC 20

Substation Grounding- Sahadeo Latchmepersad, T&TEC 21

Calculated Step Voltage

Es = ρKs Ki IGLs

Ls = 0.75Lc + 0.85 LR

Substation Grounding- Sahadeo Latchmepersad, T&TEC 22

Calculated Mesh Voltage

Em = ρ Km Ki IG WhereLM

Lm = Lc + 1.55 +1.22 Lr LR

LX2 + Ly

2

LR = total length of ground rodsLc = length of conductor

Substation Grounding- Sahadeo Latchmepersad, T&TEC 23

Earthing Designs

Nitrogen 2000 66kV Substation

Substation Grounding- Sahadeo Latchmepersad, T&TEC 24

Output file

Nitrogen 2000 substation

Substation Grounding- Sahadeo Latchmepersad, T&TEC 25

Exothermic Joints

Step 1Position clean, dry cables in mold and close clamp.

Substation Grounding- Sahadeo Latchmepersad, T&TEC 26

Insert disk, insert pour weld metal and starter material into crucible, and ignite to

form the weld.

Substation Grounding- Sahadeo Latchmepersad, T&TEC 27

Remove finished connection. Clean mold

Substation Grounding- Sahadeo Latchmepersad, T&TEC 28

FENCE EARTHING

1. Inclusion of the fence within the ground grid area. Under this philosophy, the perimeter conductor of the grid will parallel the fence at a short distance of 1.0m outside. The crushed rock covering will also be required outside the fence.

Substation Grounding- Sahadeo Latchmepersad, T&TEC 29

FENCE EARTHING

2. Placement of the fence outside the ground grid area with close electric coupling between fence and adjacent earth along its length, but with no electrical tie between the fence and the main station grid

Substation Grounding- Sahadeo Latchmepersad, T&TEC 30

ANSI STANDARD 80-2000 Date: November 11, 2005Date:

Line-to-line Voltage V 66000 Volts Touch voltage limit E touch 70 1792 VoltsMaximum fault curent HV side 20000 Amps Step voltage limit E step 70 5678 VoltsMaximum Fault Current LV side 20000 AmpsSoil resistivity ρ 15 Ωm Touch voltage limit E touch 50 1324 VoltsSubstation Length L 34 metre Step voltage limit E step 50 4195 VoltsSubstation Width W 30 metreSpacing D 4 metre GPR = 4944 VoltsNumber of ground rods 28 Ea Em= 606 VoltsLength of ground rod 2.44 metres Es= 619 VoltsDepth of grid burial h 0.5 metresFault Duration tf 0.1 s Length of 4/0 Copper Required 574 metresCurrent Division Factor Sf 1 Size of Copper d = 0.01 metresX/R Ratio 7.20 No. of Copper Rods 28 EaCrushed Rock Resistivity ρs 2500 ΩmAmbient temp Ta 40 oC Grid Resistance 0.23 ΩThickness of crushed rock hs 0.102 metresGrid shape (Square=S, Rect.=R, L- shaped=L) rSubstation L-shape Length l 0 metreSubstation L-shape width w 0 metre

50kg Design O.K70kg Design O.K

INPUT DATA RESULTST&TEC Grounding Program

Substation Grounding- Sahadeo Latchmepersad, T&TEC 31

Development Program

Substation Grounding- Sahadeo Latchmepersad, T&TEC 32

AutoGrid Pro

Substation Grounding- Sahadeo Latchmepersad, T&TEC 33

Connection to Customer’s Substation

Fence eathingNumber of TailsIncreased area-lower RgIncreased amount of copper

Substation Grounding- Sahadeo Latchmepersad, T&TEC 34