© ABB Group – Version 2.1 (2010-03)Technical Guides
AC500Fast counterAdvanced module
Scalable PLC AC500
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast Counter Content
The fast counters in AC500 - overview
The fast counter in S500 - I/O - modules
The fast counter in DC551-CS31 module
The fast counter and interrupt functions in DC541-CM module
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast Counter Coming up
The fast counters in AC500 - overview
The fast counter in S500 - I/O - modules
The fast counter in DC551-CS31 module
The fast counter and interrupt functions in DC541-CM module
© ABB Group – Version 1.0 (2009-02)Technical Guides
Input signal of a fast counter
Inputs signals up to 300 kHz Fast counter operates independent of the cycle time. Fast counter functionality is provided by:
Digital input modules connected via I/O bus to PM5xx CPU up to 50kHzDC551 – CS31 module up to 50kHzCI592 – CS31 module up to 50kHzDC541 – CM module up to 50 kHzCD522 module (up to 300 KHz)PM55x, PM56x CPU up to 30kHz
taskexecution I O I OO I II I I IO O O
Fast Counter Purpose
cycle time
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterIn AC500 (1)
Central extension: Fast counters available
De-central extension CS31:
CS31 Interface DC551 or CI592: Fast counter availableI/O bus: Up to 2 modules
CD522 only!
Central extension:
Fast counters are available in up to 10 modules on I/O bus and in up to 4 multifunction modules mounted in terminal base left to the CPU.
CS31 field bus
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterIn AC500 (2)
Master‘s central extension: Fast counters availableSlave’s central extension: Fast counters available
De-central extension FBP, AC500 (as slave)
Central extension: Fast counters available
De-central extension FBP, S500:
PROFIBUS: up to 4 modulesCANopen: up to 2 modulesDeviceNet: up to 2 modulesCD522 only!
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterModules with Fast Counter (1)
Central extension
Multifunction moduleDC541–CM
or
I/Os
interrupt module fast counter
I/Os
S500 I/O module
DC522, DC523,DC532, DI524
DX522
Central extension
fast counter
CPUPM55x, PM56x
fast counter
CPU I/Os
Central extension
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterModules with Fast Counter (2)
Encoder + PWM ModuleCD522
fast counter I/Os
Central extensionDe-central extension
(PROFIBUS, CANopen,DeviceNet, CS31 bus)
DC551-CS31
or
CI592-CS31
fast counter
Connection to CS31 bus
I/Os
De-central extension
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterData Exchange
The counter function is performed within a module containing the fast counter. The data exchange between the counter and the user program is performed by using the input and output operands.
Fast counter I/O operands are created automatically during set-up.
The fast counter library is included automatically into project if fast counter is configured.
CPU Module with fast counter
Image memory
%QD, %QB
%IW, %IB
Counting functionSet parameters
Actual counter parameters
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterSet-up procedure
Counter Settings
The fast counter is activated and set by a parameter of the module.
Counter settings are to be made in the project software “Resources” \ “PLC Configuration”.
The amount of parameters depends on the module type.
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterSet up procedure
Settings to be done:
Counter operation mode
Symbolic names for counter I/O operands
Setting parameters like:Start value
End value
Up/down …etc.
according to the module typeand operation mode
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast Counter Coming up
The fast counters in AC500 - overview
The fast counter in S500 - I/O - modules
The fast counter in DC551-CS31 module
The fast counter and interrupt functions in DC541-CM module
© ABB Group – Version 1.0 (2009-02)Technical Guides
Here you are able to select the operation mode of the fast counter
Select “Resources” \ “PLC Configuration” \ “AC500” \ “I/O Bus” \“DC532” \ “Fast Counter”
Fast CounterExample: Module DC532 (1)
© ABB Group – Version 1.0 (2009-02)Technical Guides
PLC configuration: Symbolic variables (not necessary but easier to read )
Fast CounterExample: Module DC532 (2)
© ABB Group – Version 1.0 (2009-02)Technical Guides
Global variables: Byte to bit reduction for BOOL signals
Control byteStatus byte
Fast CounterExample: Module DC532 (3)
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast Counter Coming up
The fast counters in AC500 - overview
The fast counter in S500 - I/O - modules
The fast counter in DC551-CS31 module
The fast counter and interrupt functions in DC541-CM module
© ABB Group – Version 1.0 (2009-02)Technical Guides
1. Right click “COM1-CS31-Bus“ and select “Append Subelement“
Fast CounterExample: Module DC551 (1)
PLC configuration DC551: 2. Select the DC551-CS31..+2FC
FC = Fast Counter
© ABB Group – Version 1.0 (2009-02)Technical Guides
Address switchfor fast counteron DC551- CS31:(70 + 1 =) 71 (70 + module address)PLC configuration:
Select the operation mode of the fast counterand set the addresses like shown
has to be in accordancewith this setup
Fast CounterExample: Module DC551 (2)
© ABB Group – Version 1.0 (2009-02)Technical Guides
PLC configuration: Symbolic variables (not necessary but easier to read )
Fast CounterExample: Module DC551 (3)
© ABB Group – Version 1.0 (2009-02)Technical Guides
Global variables: Byte to bit reduction for bool signals
Control byteStatus byte
Fast CounterExample: Module DC551 (4)
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterFeatures (S500 Digital I/O Modules, DC551 and CI592)
Maximum counting frequency 50 kHz respectively depends on operating mode.
If using DC modules each counting input has to be externally circuited in series with a resistor of 470 / 1W (to avoid influences from deactivated module output).
The positive edge signals are counted if not noted differently.
When the counter reaches programmed end value the output CF = TRUE is generated permanently. CF is reset to FALSE by setting the counter again (set value) .
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterOperating Modes–S500 I/O Modules, DC551 and CI592 (1)
Up counter
Counter disabled
0(1)
Counting input A
End value reached Output (if existing)
1
As (1) with
Enabling input B
2
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterOperating Modes–S500 I/O Modules, DC551 and CI592 (2)
Up / down counter
As (3)
Inverted counting input of B
4
(4)
Counting input
With dynamic HWset input 5 (0-1 edge)
5
As (4)
Dynamic set input(1-0 edge)
6
(3) Two independentcounters
Counting input A, B
3
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterOperating Modes–S500 I/O Modules, DC551 and CI592 (3)
Up / down counter for incremental encoder
(7)
Counting input A
Counting input B
Counting frequency 35 kHz
7
Reserved
8
As (7) but
X2 puls multiplication:counting A0-1 , 1-0edges
Counting frequency 30 kHz
9
As (7) but
X4 puls multiplication:counting A and B0-1 , 1-0edges
Counting frequency 15 kHz
10
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast Counter Coming up
The fast counters in AC500 - overview
The fast counter in S500 - I/O - modules
The fast counter in DC551-CS31 module
The fast counter and interrupt functions in DC541-CM module
© ABB Group – Version 1.0 (2009-02)Technical Guides
The digital input/output module contains 8channels: C0 – C7Up to 4 DC541 can be operated by a PM57x, PM58x or PM59x CPU
Fast CounterModule DC541-CM: Fast Counter (1)
The counter module DC541 can be used alternatively in one of two operating modes:
fast counting device Interrupt input / output device
© ABB Group – Version 1.0 (2009-02)Technical Guides
The module functionality in both operating modes is independent of the program cycle.
The implementation of the module function is performed by function blocks. The library is loaded automatically into the project.
Visualizations are available.
Fast CounterModule DC541-CM: Fast Counter (2)
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterDC541-CM – Counting Mode
DC541-CMPWM
8 channels
10 kHz
DC541_PWM
Input/output
DC541_IO
Incremental encoder
Tracks A, B, Zero
Touch trigger
50 kHz
1 channel
Remaining channels are usable for other modes
DC541_32BIT_CNT
Frequency output
8 channels
2.5 kHz max
Endless definednumber of pulses
DC 541_FREQ_OUT
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterDC541-CM (2)
DC541-CMUp counter Up / down counter
endless counting
1 channel
Remaining channels are usable for other modes
DC541_FWD_CNT
50 kHz
2 channels
Remaining channels are usable for other modes
DC 541_32BIT_CNT
5 kHz
4 channels
Remaining channels are usable for other modes
DC 541_32BIT_CNT
2.5 kHz
8 channelsDC 541_32Bit_CNT
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterDC541-CM (3)
DC541-CM
Time and frequency measurement
8 channels
Resolution 100 s
DC541_FREQ
Resolution 1 s (1 channel only)
DC541_FREQ_FAST
1 channel
Limit values display of counters on channels 0-3
DC541_LIMIT
© ABB Group – Version 1.0 (2009-02)Technical Guides
1. Insert the moduleDC541 in the configuration of the PLC (one of thecoupler slots)
2. Right click at the DC541 line
3. Select “AppendSubelement”and after that select the mode
Fast CounterExample: DC541_FWD_CNT(1)
© ABB Group – Version 1.0 (2009-02)Technical Guides
4. Left click at this line
5. Select the counter:In this case C0 is the input for the counter pulses
Fast CounterExample: DC541_FWD_CNT (2)
© ABB Group – Version 1.0 (2009-02)Technical Guides
3. Select the function
1. Left click here(Visualization)
2. Draw this square(drag and draw)
Fast CounterExample: DC541_FWD_CNT (3)
The function block DC541_FD_CNT can be visualized by an appropriate visualization object.
© ABB Group – Version 1.0 (2009-02)Technical Guides
4. Right click here
5. Click at “configure”
Fast CounterExample: DC541_FWD_CNT (4)
© ABB Group – Version 1.0 (2009-02)Technical Guides
6. Click at “placeholder”
7. Left click here and click F2
Fast CounterExample: DC541_FWD_CNT (5)
© ABB Group – Version 1.0 (2009-02)Technical Guides
8. Select the counterinstance
Fast CounterExample: DC541_FWD_CNT (6)
© ABB Group – Version 1.0 (2009-02)Technical Guides
The digital input/output module contains 8channels: C0 – C7Up to 4 DC541 can be operated by a PM5xxCPU
Fast CounterModule DC541-CM: Interrupt Mode (1)
The counter module DC541 can be used alternatively in one of two operating modes:
Fast counting device Interrupt input / output device
© ABB Group – Version 1.0 (2009-02)Technical Guides
Interrupt input/output device
Interrupt, interrupt-start with jitter < 100 µs
Digital input and output
Reaction time maximum 500 µsec this means time between read interrupt-input and write interrupt-output. Also if input and output are on two different DC541 of the CPU
Fast CounterModule DC541-CM: Interrupt Mode (2)
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterExample: DC541_INT (1)
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterExample: DC541_INT (2)
It is possible to start one interrupt task per module.There are different types of interrupt tasks:
Ext_CouplerX_InputAny Ext_CouplerX_InputAny_high_prio
Task triggered by any interrupt Task triggered by any interruptfrom module with specific priority from module with highest priority.
The task execution time must not exceed approximately 400 µs
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterExample: DC541_INT(3)
© ABB Group – Version 1.0 (2009-02)Technical Guides
Fast CounterExample: DC541_INT_IN
© ABB Group – Version 1.0 (2009-02)Technical Guides