DESCRIPTION

SCADAPack 314, Low-cost, high-performance programmable logic controller. Features: High-performance 32-bit processor, Two serial ports (RS-232/485), USB 2.0 peripheral port, Optional integrated 900MHz or 2.4GHz spread-spectrum radio, I/O: 16 digital inputs, 10 digital outputs; 8 configurable analog inputs; 3 counter inputs, Low power consumption, user configurable power-saving modes, Relay Ladder Logic, IEC 61131-3, and C/C++ programmable. Visit SCADAPack RTUs and PLCs for more info.

TRANSCRIPT

Product Data Sheet

SCADAPack 314Low-cost, high-performance programmable logic controllerFeaturesn High-performance32-bitprocessorn Twoserialports(RS-232/485),USB2.0peripheralportn Optionalintegrated900MHzor2.4GHzspread-spectrumradion I/O:16digitalinputs,10digitaloutputs;8configurableanalog

inputs;3counterinputsn Lowpowerconsumption,userconfigurablepower-savingmodesn RelayLadderLogic,IEC61131-3,andC/C++programmablen CCSAUSClass1,Division2HazardousAreaRatingn CSAcertifiedtoUL508standardsn Three-yearpartsandlabourwarranty

BuiltontheprovenSCADAPack300-seriesplatform,theSCADAPack314featureshigh-performance32-bitprocessing,high-speedserialcommunication,integratedpowersupply,advancedpower-management,andawiderangeofdigitalandanalogI/Oinacost-effective,compactcontroller.Featuringindustry-standardModbusandDNP3serialprotocolsandachoiceofflexibleprogramminglanguages,theSCADAPack314iseasytointegrateanddeploy.EnhancedIntegrationwithControlMicrosystems’ClearSCADASCADAhostsoftwareprovidesevengreaterremoteconfiguration,monitoring,andcontrolfeatures.Applicationsincluderemotesensorlocations,solarpoweredinstallations,processcontrol,liftandpumpstations,damcontrolsystems,andenvironmentalmonitoringsolutions.Powerful ProcessorTheheartoftheSCADAPack314isapowerful32-bitmicroprocessorforresponsiveapplicationperformance.A16MBflashROMand4MBCMOSRAMprovideamplespaceforuseinfirmwareandapplicationprogramming.Flexible ProgrammingSCADAPack314supportsprogramminginRelayLadderLogic,theIEC61131-3familyoflanguages,andC++.Upto32independentC++applicationscanbesimultaneouslyloaded,executed,anddeletedinparallelwithstandardcontrollerlogictoprovidemaximumflexibilityandperformance.

advancedDNP3protocolfunctionalitylikereport-by-exception,store-and-forwardmessaging,maintenance,polling,unsolicitedmessaging,anddata-backfilling.Compact ChassisAsmallfootprintandlow-profilechassisenablestheSCADAPack314tousecompactmountingenclosuresandfitintodenseequipmentracksforapplicationswherespaceisatapremium.Built for Durability, Reliability, and SafetySCADAPack314hasconformalcoatings,zinc-platedsteelsystemcomponents,andiscertifiedtoClass1,Division2HazardousAreaRating,CSAcertifiedtoUL508Standards,andATEXII3G/IECExcertified(solidstaterelaytypes,24VDIversiononly)forperformanceinhazardousenvironments.Enhanced Integration with Control Microsystems SCADA ProductsControlMicrosystemsoffersacomprehensiveSensortoEnterpriseproductportfolio.SCADAPackcontrollersfeaturepre-defineddeviceprofilesandconfigurationtemplateswithinControlMicrosystems’SCADAhostmanagementsoftware,ClearSCADA,toofferconfigurationandmonitoringattheclickofabutton.Remoteconfiguration,firmwareupgrades,clock-synchronization,anddatalogretrievaldirectlytothehosthistorianaresomeoftheadvancedfeaturesofferedbyEnhancedIntegrationthatmakeiteasiertomanageyourSCADAsystem.Industry-leading Three-Year WarrantyAllControlMicrosystemsproductsaremanufacturedtoexactingstandardsandarebackedbyanindustry-leadingthree-yearpartsandlabourwarranty.

Customizable Power Saving ModesWithpowerconsumptionaslowas15mWinSleepMode,SCADAPack314featuresuser-customizablepowerconfigurationswhichcanbeconfiguredremotelyorbythecontrollerapplicationitself.Insolarpoweredapplications,theSCADAPack314’spower-savingdesignallowssmallersolarpanelsandbatteriestobeusedtofurtherreducecosts.Versatile Analog and Digital I/OSCADAPack314includesawealthofI/Otomeetthedemandsofyourapplicationwith16digitalinputs,10digitaloutputs,8analoginputs,2optionalanalogoutputs,3counterinputs,andinternalpowersupplyvoltagemonitoringinputforsolarpoweredapplications.SCADAPack314iscompatiblewithselectControlMicrosystems5000-se-riesI/OExpansionModulestoincreasethecontroller’sI/Ocapacityandversatility.Flexible CommunicationsSCADAPack314offersawiderangeofconnectivityandcommunicationoptions.TwoRS-232/485serialcommunicationportssupportModbusRTU,ModbusASCII,andDNP3communicationprotocols.Ahigh-speedUSBperipheralportallowsforlocalconfiguration.Forremoteapplications,SCADAPack314canbeconfiguredwithoptionalintegrated,license-free,spreadspectrum900MHzand2.4GHzwirelessmodules,externalradios,ordial-upmodem.Modbus and DNP3 Protocol Support for Easy IntegrationSCADAPack314supportsopenModbusandDNP3protocolstoensureinteroperabilityandcompatibilitywithawiderangeofSCADAequipmentfromthird-partyvendors.SCADAPack314supportsbothModbusmasterandslaveconfigurationsand

is becoming

ControlMicrosystems

SCADAPack 314 Product Data Sheet

Specifications (P314: 5212 controller board and integrated 56O7 I/O board)Controller

Processors CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimerMicrocontrollerco-processor,20MHzclock

Memory 4MBSRAM,16MBflashROM

Non-Volatile CMOSSRAMwithlithiumbatteryretainscontentsfor2-yearswithnopower

Datalog Capacity 465kwords

I/OAnalog Inputs 8softwareconfigurable:0-20/4-20mA/0-5/0-10V(15-bit)

3internal:measureincomingpowersupplyvoltageforsolarapplications,batteryvoltage,andcontrollertemperature

Analog Outputs Standard:None2withoptional5305on5607I/Oboard:0-20/4-20mA(12-bit)

Digital I/O 16digitalinputs:12/24V,48V,115/125V,240V10relayoutputs:drycontactorDCsolid-state

Counter Inputs 1drycontact:0-10Hzor0-5kHz2turbineordrycontact:0-10kHz

CommunicationsSerial Port COM1 RS-232port,8-pinmodularRJ45jack,fullorhalf-duplex,or

RS-485port,2-wire,half-duplex

Serial Port COM2 RS-232port,8-pinmodularRJ45jack,fullorhalf-duplex,orRS-485port,2-wire,half-duplex

Baud Rates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200

Serial Protocols ModbusRTU,ModbusASCII,DNP3,DF1

Serial Protocol Modes Slave,Master,Master/Slave,StoreandForward

USB Peripheral Port USB2.0compliantB-typereceptacle

Wireless1 Spread-spectrumradioat900MHz2and2.4GHz2

GeneralI/O Terminations 5,6,and9-poleremovableterminalblocks,12to22AWG,15Acontacts

Dimensions 5.65inch(144mm)wide,6.50inch(165mm)high,2.80inch(72mm)deep

Packaging Corrosionresistant,zinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%,non-condensing,–40°F(–40°C)to158°F(70°C)

Power: 5212 Controller Board11-30VDC,15mWat12Vduringsleepmode.(Note:ThepowerconsumptionduringsleepmodeisaffectedbythenumberofserialportsconnectedtotheRS-232devices.Thereisa2.4mWincreaseperconnectedport,foramaximumof4.8mWwithbothportsconnected.)500mWat12Vduringnormaloperation.32MHz,LEDsoff,noexpansion,andUSBdisabled300mWat12Vduringreducedpowermodeoperation.2MHz,LEDsoff,noexpansion,USBdisabled5607 I/O Module•Add190mWwhenenablingtheUSBport•Add30to90mWwhenenablingtheLEDs8.5Wat24Vmaximum,5Vsupplyfully-loaded11-30VDC,10.3mAplusanalogoutputs325mA(max.)at5Vrequiredfrom5212controllerboard

Warranty 3-yearsonpartsandlabor

1 Availableonlywithoptionalintegratedwirelessmodulesorstand-alonewirelessmodules.2 Notapplicableinallcountries.

SCADAPack 314 Product Data Sheet

Model Code P314-1A00-AB00representsasamplecodeforaSCADAPack314,5607I/OboardandModbusprotocolemulation

Model Select: ControllerP314 SCADAPack314,withModel5607I/Oboard,includes8AI,16DI,10DOand3counterinputs

Code Select: Communication Ports1 3communicationports:2RS-232/485(RJ45),1USBPeripheral(B-Type)

Code Select: Gas Flow Run-Time OptionA None

G 2-rungasflow

F 4-rungasflow

Code Select: Protocol Option0 Modbusprotocolemulation

1 ModbusandDF1protocolemulation

2 ModbusandDNP3.0(Level2)protocolemulation

3 Modbus,DF1andDNP3.0(Level2)protocolemulation

Code Select: Programming Environment0 TelePACELadderLogicandCLanguagefirmwareloaded-IECenabled(programmingtoolssoldseparately)

1 IEC61131-3andCLanguagefirmwareloaded-TelePACEenabled(programmingtoolssoldseparately)

Code Select: Analog InputsA 8selectableas0-20,4-20mA,0-5Vor0-10V

Code Select: Digital Inputs/OutputsB 16DI(12/24V)and10drycontactrelays

C 16DI(48V)and10drycontactrelays

D 16DI(120V)and10drycontactrelays

E 16DI(240V)and10drycontactrelays

F 16DI(12/24V)and10DCsolid-staterelays,ATEXandIECExcertification

G 16DI(48V)and10solid-staterelays

H 16DI(120V)and10solid-staterelays

I 16DI(240V)and10solid-staterelays

Code Select: Analog Outputs0 None

1 2-channelanalogoutputoption,0-20mA

Code Select: Integrated Communication Interfaces0 None

FreeWave & MDS Radios (requires one RS-232 port on controller)1 900MhzFreeWavespread-spectrumradioConsult CMI for availability in your market area

2 2.4GHzFreeWavespread-spectrumradioConsult CMI for availability in your market area

A 900MHzMDSspread-spectrumradioConsult CMI for availability in your market area

Integrated SCADAWave Radio (requires one RS-232 port on controller)B 900MHzSCADAWavespread-spectrumradiowithencryption,902-928MHz(FCC/IC)

C 900MHzSCADAWavespread-spectrumradiowithencryption,915-928MHz(AUS)

D 900MHzSCADAWavespread-spectrumradio915-928MHz(BRAZIL)

E 900MHzSCADAWavespread-spectrumradio921-928MHz(NZ)

J 2.4GHzSCADAWavespread-spectrumradio,ETSI/100mW,ATEX(EUROPE)(approvalpending)

K 2.4GHzSCADAWavespread-spectrumradiowithEncryption,500mW(CANADA,USA&AUSTRALIA)

L 2.4GHzSCADAWavespread-spectrumradio,500mW(OUTSIDEOFEUROPE,CANADA,USA&AUSTRALIA)

CONTROL MICROSYSTEMS www.controlmicrosystems.com

W ithinNor thA merica:(888) 267-2232 n OutsideNor thA merica:(613) 591-1943 n O t tawan Calgar yn Denver n Hous tonn Melbournen LeidenControlMicrosystemsreservestherighttochangeproductspecificationswithoutnotice. PrintedinCanadanV011nM01011-77

SCADAPack 314 Product Data Sheet

is becoming

ControlMicrosystems

top related