regional municipality of halton appleby zone 3...
Post on 06-Mar-2018
222 Views
Preview:
TRANSCRIPT
W-2134B-16 AUGUST 9, 2016 PAGE 1 OF 3 ADDENDUM NO. 2
Regional Municipality of Halton APPLEBY ZONE 3 BOOSTER PUMPING STATION
IN THE CITY OF BURLINGTON CONTRACT W-2134B-16
ADDENDUM NO. 2
Issue Date: Tuesday, August 9, 2016
This Addendum No. 2 forms part of the Plans and Contract Documents for the above noted contract and shall be read in conjunction therewith. This Addendum No. 2 shall take precedence over all requirements of the original plans and contract documents issued previously. The Tenderer must acknowledge receipt of this Addendum No. 2 on page 3 of the Form of Tender.
NO. OF ADDENDUM PAGES: 3 NO. OF REVISED CONTRACT DOCUMENT PAGES: NO. OF DRAWINGS (SKETCHES): 20 NO. OF NEW SPECIFICATION PAGES: 32 TOTAL NO. OF PAGES:
55
ISSUE 1: STEEL PIPE
Will AWWA C200 Steel Pipe be included as an equal alternate to CPP on this project?
Response: Please refer to attached Specification Section 02512 Alternative Watermain Material - Steel Pipe
ISSUE 2: FIBRE REINFORCED PLASTIC PIPE
Is it possible to bid that portion [750mm concrete pressure pipe] as an alternate such as FlowTite FRP piping?
Response: Please refer to attached Specification Section 02513 Alternative Watermain Material – Fibre Reinforced Plastic Pipe
ISSUE 3: GLASS BLOCKS
The cupola and high level pumping station windows, due to security concerns, shall be solid glass block.
W-2134B-16 AUGUST 9, 2016 PAGE 2 OF 3 ADDENDUM NO. 2
Response:
DELETE Section 04270 in its entirety and REPLACE WITH the revised Section 04270 dated August 2016 attached.
DELETE architectural drawings A-100 to A-117 in their entirety and REPLACE WITH the revised architectural drawings A-100 to A-117 attached.
ISSUE 4: ALTERNATIVE SUPPLIERS FOR AIR/VAPOUR MEMBRANE BARRIERS
We would like to request approval for alternate suppliers of air/vapour membrane barriers.
Response:
DELETE Section 07260 2.2.1:
Standard of acceptance: Blueskin SA is a self-adhering membrane consisting of an SBS rubberized asphalt compound which is integrally laminated to a blue cross-laminated polyethylene film designed to be self-adhered to a prepared substrate, providing an air/vapour/water barrier.
And REPLACE WITH:
Standard of acceptance: Membrane air/vapour barrier, 1.0 mm thick minimum, single-ply, self-adhering, self-sealing, rubberized asphalt, bonded to a cross-laminated high density polyethylene film.
And ADD Section 07260 2.2.2:
Acceptable manufacturers:
CCW 705 by Carlisle Coatings & Waterproofing Blueskin SA by Henry Company Canada Inc. Sopraseal Stick 1100 T by Soprema Exo-Air 110 by Tremco Air-Shield by W.R. Meadows Or Approved Equivalent
ISSUE 5: ALTERNATIVE SUPPLIERS FOR WATERPROOFING MEMBRANE AND DRAINAGE SYSTEM
We would like to request approval for alternate suppliers of waterproofing membranes and for drainage systems.
Response: Section 7100 2.1.1.2 and 2.1.2.2 already state "or approved equal". Alternative products will not be reviewed during the tender period. Approved product supply will be reviewed during the shop drawing process.
ISSUE 6: ALTERNATIVE SUPPLIERS FOR WASHROOM ACCESSORIES
Specification Section 10800 only lists one particular manufacturer for washroom accessories.
W-2134B-16 AUGUST 9, 2016 PAGE 3 OF 3 ADDENDUM NO. 2
Response: DELETE Section 10800 in its entirety and REPLACE WITH the revised Section 10800 dated August 2016 attached.
ISSUE 7: PLANTING OF TREES ON-SITE
Under the Region of Halton’s Tree-Canopy Replacement Policy on Regionally-Owned Lands, trees cut down or removed for public works shall be replaced.
Response: Under Division 2 – Site Work, Line Item “Landscaping” of the Form of Tender, the Contractor is to include the price of supplying and re-planting thirty (30) deciduous trees of varying species (50 to 75 DBH) in compliance with the Region of Halton’s Tree-Canopy Replacement Policy on Regionally Owned Lands. The location of the trees is to be confirmed with the Region in conjunction with topsoil and finish grading works on site. Please refer to Region Standard 100.04 Deciduous Tree Planting Detail attached.
ADD Region Standard 100.04 attached.
End of Addendum No. 2
SECTION 02512
ALTERNATIVE WATERMAIN MATERIAL - STEEL PIPE
i
PART 1 - GENERAL ...................................................................................................................1
1.1 DESCRIPTION ................................................................................................................................ 1 1.2 RELATED SPECIFICATION ......................................................................................................... 1 1.3 QUALITY ASSURANCE ............................................................................................................... 1 1.4 DEFINITIONS ................................................................................................................................. 2 1.5 MANUFACTURER QUALIFICATIONS ....................................................................................... 2 1.6 SHOP DRAWINGS ......................................................................................................................... 3 1.7 VERIFICATIONS AND TESTING................................................................................................. 3 1.8 HANDLING, STORAGE AND SHIPPING .................................................................................... 4 1.9 MARKINGS ..................................................................................................................................... 4
PART 2 - PRODUCTS ................................................................................................................5
2.1 PIPE DESIGN REQUIREMENTS .................................................................................................. 5 2.2 PIPE MATERIAL REQUIREMENTS ............................................................................................ 6 2.3 CATHODIC PROTECTION ........................................................................................................... 7 2.4 LAP WELD ...................................................................................................................................... 7 2.5 MECHANICAL COUPLINGS ........................................................................................................ 8 2.6 FLANGES ........................................................................................................................................ 8 2.7 BOLTS AND NUTS FOR FLANGES ............................................................................................. 8 2.8 LININGS AND COATINGS ........................................................................................................... 9
PART 3 - INSTALLATION ......................................................................................................10
3.1 PIPE INSTALLATION .................................................................................................................. 10 3.2 JOINTS ASSEMBLY .................................................................................................................... 10 3.3 FIELD TESTING AND COMMISSIONING ................................................................................ 11
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
1
02512
ALTERNATIVE WATERMAIN
MATERIAL - STEEL PIPE
SECTION 02512
ALTERNATIVE WATERMAIN MATERIAL - STEEL PIPE
PART 1 - GENERAL
1.1 DESCRIPTION
.1 This specification covers the construction of the 750 mm diameter Appleby
Zone 3 BPS watermain using steel pipe as an alternative material.
.2 All provisions and requirements of Section 02511 – Watermains and the
Contract Drawings shall also apply to the construction of the 750 mm
diameter watermain using steel pipe. In case of discrepancies between the
aforementioned Section 02511 and this current specification Section 02512
Alternative Watermain Material - Steel Pipe, this Section 02512 shall govern.
1.2 RELATED SPECIFICATION
.1 Section 02511 – Watermains
.2 Section 02513 – Alternative Watermain Material – FRP Pipe
.3 Section 01650 – Equipment Startup and Performance Testing
.4 Section 01660 – Commissioning
1.3 QUALITY ASSURANCE
.1 ANSI/AWS D1.1 Structural Welding Code- Steel
.2 ANSI/AWS B2.1 Specification for Welding Procedure and Performance
Qualification
.3 ANSI/AWWA C200 Steel Water Pipe—6 In. (150 mm) and Larger
.4 ANSI/AWWA C205 Cement-Mortar Protective Lining and Coating for Steel
Water Pipe – 4 In. (100 mm) and Larger- Shop Applied
.5 ANSI/AWWA C206 Field Welding of Steel Water Pipe
.6 ANSI/AWWA C207 Steel Pipe Flanges for Waterworks Service—Sizes 4 In.
Through 144 In. (100 mm through 3,600 mm)
.7 ANSI/AWWA C208 Dimensions for Fabricated Steel Water Pipe Fittings
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
2
02512
ALTERNATIVE WATERMAIN
MATERIAL - STEEL PIPE
.8 ANSI/AWWA C216 Heat-Shrinkable Cross-Linked Polyolefin Coatings for
the Exterior of Special Sections, Connections, and Fitting
.9 ANSI/AWWA C222 Polyurethane Coatings for the Interior and Exterior of
Steel Water Pipe and Fittings
.10 ANSI/AWWA C604-11 Installation of Buried Steel Water Pipe
.11 ASME Section IX International Boiler & Pressure Vessel Code: Welding and
Brazing Qualifications
.12 AWWA M11 Steel Water Pipe: A Guide for Design and Installation
.13 SSPC-PA 2 Systems and Specifications SSPC Painting Manual, Volume 2
Chapter 7: Measurement of Dry Coating Thickness with Magnetic Gages
.14 OPSS 1802 Material Specification for Smooth Walled Steel Pipe, November
2008
.15 OPSS 441 Construction Specification for Watermain Installation in Open Cut
.16 NSF/ANSI Standard 61 Drinking Water System Components – Health Effects
.17 ASTM A139 Standard Specification for Electric-Fusion (Arc)-Welded Steel
Pipe (NPS 4 and Over)
1.4 DEFINITIONS
.1 Dimension Ratio (DR): outside pipe diameter (mm) ÷ wall thickness (mm)
.2 Working Pressure (WP): maximum sustained operating pressure excluding
transient surge pressures
.3 Surge Pressure (Ps): transient surge pressure attributable to abrupt change in
flow
.4 Pressure Class (PC): numerical value assigned to standard manufactured pipe
sizes reflecting their structural capacity for sustaining working and surge
pressures with an appropriate factor of safety
1.5 MANUFACTURER QUALIFICATIONS
.1 Manufacturers who are fully experienced, reputable, and qualified in the
manufacture of the products to be furnished shall furnish all steel pipe and
fittings. The pipe and fittings shall be designed, constructed and installed in
accordance with the best practices and methods and shall comply with these
specifications as applicable.
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
3
02512
ALTERNATIVE WATERMAIN
MATERIAL - STEEL PIPE
.2 Pipe cylinders, lining, coating and fabrication of specials shall be the product
of one manufacturer that has not less than 5 years successful experience
manufacturing pipe of the particular type and size indicated. The pipe
manufacturer must have a certified quality assurance program. This certified
program shall be ISO 9001:2000 or other equivalent nationally recognized
program as approved by the Contract Administrator.
1.6 SHOP DRAWINGS
.1 All requirements of Section 01330 – Submittal Procedures and Section 02511
– Watermains for concrete pressure pipe watermain and precast concrete valve
chambers shall also apply to this section. Shop drawings shall be submitted to
the Contract Administrator for approval and shall include the following:
.1 Pipeline layout showing stations and elevations.
.2 Details of standard pipe, joints, specials and fittings.
.3 Calculations for pipe design and fittings reinforcement and/or test data.
.4 Details of joint bonding and field welded joint restraint calculations.
.2 Shop drawings shall be stamped and signed by a Professional Engineer
registered with Professional Engineers Ontario.
1.7 VERIFICATIONS AND TESTING
.1 All pipe shall be subject to inspection at the place of manufacture in
accordance with the provisions of AWWA C200 and AWWA coating and
lining standard as supplemented by the requirements herein.
.2 Except as modified herein, all materials used in the manufacture of the pipe
shall be tested in accordance with the requirements of AWWA C200 and
AWWA coating and lining standards.
.3 The Contractor shall perform required tests at no additional cost to the Owner.
The Contract Administrator shall have the right to witness all testing
conducted by the Contractor, provided that the Contractor’s schedule is not
delayed for the convenience of the Contract Administrator.
.4 All welding procedures used to fabricate pipe shall be qualified under the
provision of AWS B2.1 or ASME Section IX.
.5 All field installations shall use skilled welders, welding operators, and tackers
who have had adequate experience in the methods and materials to be used.
Welders shall maintain current qualifications under the provisions of AWS
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
4
02512
ALTERNATIVE WATERMAIN
MATERIAL - STEEL PIPE
B2.1 or ASME Section IX. Machines and electrodes similar to those in the
work shall be used in qualification tests. The Contractor shall furnish all
material and bear the expense of qualifying welders.
1.8 HANDLING, STORAGE AND SHIPPING
.1 Pipe shall be stulled as required to maintain roundness of +/- 1% during
shipping and handling.
.2 End caps shall be used at all times on all pipe sections during shipping,
storage and handling on site to prevent unwanted materials from entering the
pipe at all times except during jointing.
.3 Coated pipe shall be shipped on padded bunks with nylon belt tie-down straps
or padded banding located approximately over stulling.
.4 Coated pipe shall be stored on padded skids, sand or dirt berms, sand bags, old
tires or other suitable means so that coating will not be damaged.
.5 Coated pipe shall be handled with wide belt slings. Chains, cables or other
equipment likely to cause damage to the pipe or coating shall not be used.
.6 Prior to shipment, dialectically coated pipe shall be visually inspected for
damage to the coating by the following procedure.
.7 When visual inspection shows a dielectric coating system has sustained
physical damage, the area in question shall be subjected to an electrical
holiday test. Voltage shall be per AWWA C222.
.8 When the area is tested and there are no holidays, the area shall be noted
“OK” and shipped with no patching required.
.9 When the damaged area does show damage going clear to the steel from either
a visual inspection or a jeep from a holiday detector, the area shall be repaired
in accordance with Section 2.02 of these specifications and per manufacturer’s
recommendations.
1.9 MARKINGS
.1 The Contractor shall legibly mark all pipes and specials in accordance with
the laying schedule and marking diagram. Each pipe shall be numbered in
sequence and said number shall appear on the laying schedule and marking
diagram in its proper location for installation. All special pipe sections and
fittings shall be marked at each end with top field centerline. The word “top”
or other suitable markings shall be painted or marked on the outside top spigot
end of each pipe section.
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
5
02512
ALTERNATIVE WATERMAIN
MATERIAL - STEEL PIPE
PART 2 - PRODUCTS
2.1 PIPE DESIGN REQUIREMENTS
.1 Steel pipe shall conform to AWWA C200. Steel plate used in the manufacture
and fabrication of steel pipe shall meet the requirements of AWWA C200. All
longitudinal and girth seams, whether straight or spiral, shall be butt-welded
using an approved electric-fusion-weld process. All watermain and service
connection materials shall be in accordance with Contract Drawings and as
specified elsewhere in the Contract Documents.
.2 Pipe design is governed by the following criteria unless specifically noted
otherwise:
.1 Internal Working Pressure: 690 kPa
.2 Field Test Pressure: 1,050 kPa
.3 Water Hammer Allowance: 40%
.4 Trench Supported Full Vacuum: 100 kPa
.5 Live Load: HS-20
.6 Variable Depth of Earth Cover: as shown on drawings
.3 Pipe design shall be in accordance with AWWA M11.
.4 Pipe pressure class, wall thickness or dimension ratio shown on the Contract
Drawings or specified elsewhere in the Contract Documents take precedence
and may vary from those determined through the application of Design Guide
methodologies and procedures.
.5 This does not relieve the pipe supplier from responsibility for conducting an
independent analysis to confirm that dimensional information specified or
shown elsewhere satisfies the design criteria. In the event that Design Guide
procedures result in a wall section thicker than that shown or specified
elsewhere, use the larger of the two values.
.6 NSF/ANSI 61 compliant materials in contact with potable water.
.7 Referenced pipe sizes are nominal based on a conversion factor of 25 mm
equals 1 inch.
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
6
02512
ALTERNATIVE WATERMAIN
MATERIAL - STEEL PIPE
.8 Pipe shall be bedded and backfilled according to the drawings and
specifications and details or manufacturers recommendations utilizing an E’
value for design check per AWWA M11 Chapter 6.
.9 Pipe is to be furnished principally in 15 m net laying lengths with shorter
lengths, field trim pieces and closure pieces as required by Plan and profile for
location of elbows, tees, reducers and other in-line fittings. Or as required for
construction. The pipe fabricator shall prepare a pipe laying schedule showing
the location of each piece by mark number with station and invert elevation at
each bell end.
.10 Unless otherwise shown on the Plans, all specials and fittings shall conform to
the dimensions of AWWA C208. Pipe material used in fittings shall be of the
same material and pressure class as the adjoining pipe. The minimum radius
of elbows shall be 2 ½ times the pipe diameter and the maximum miter angle
on each section of the elbow shall not exceed 11 ¼-degrees (one cut elbow up
to 22 ½-degrees). If elbow radius is less than 2 ½ times the pipe diameter,
stresses shall be checked per AWWA M-11 and the pressure class increased if
necessary.
.11 Fittings shall be equal in pressure class design as the adjoining pipe. Specials
and fittings, unless otherwise shown on the Plans, shall be made of segmental
welded sections from hydrostatically tested pipe, with ends compatible with
the type of joint or coupling specified for the pipe. All welds made after
hydrostatic testing of the straight sections of pipe shall be tested per the
requirements of AWWA C200 Section 5.2.2.1.
2.2 PIPE MATERIAL REQUIREMENTS
.1 Steel Pipe - 750 mm diameter
.2 Spiral or straight seam full penetration butt-welded carbon steel pipe
fabrication to OPSS 1802 and AWWA C200.
.3 Fabricated fittings to AWWA C208.
.4 Mill certified steel sheet ASTM A139 Grade C 290 MPa (42,000 psi) or
higher.
.5 Minimum steel pipe wall thicknesses is based on the following design criteria
and including an allowance for location risk:
.1 50% yield stress under design working pressure
.2 75% yield stress under design working plus surge pressure
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
7
02512
ALTERNATIVE WATERMAIN
MATERIAL - STEEL PIPE
.3 Deflection due to handling: diameter ÷ 240
.4 Soil modulus E' : 6.9 MPa (1000 psi)
.5 Buoyancy factor: Rw 1.0
.6 Factor of safety for buckling: 2
.6 Conduct site specific analysis per AWWA M11 where criteria differ from
design criteria contained in this specification to confirm that stated wall
thicknesses are adequate.
.7 Minimum Pipe Wall Thickness
.1 For 750 mm diameter steel pipe: 6.35 mm (¼ inches)
.8 Manufacturer: Manufacturer of pipe and fittings shall employ product
technology used in the manufacture of steel pipe for a minimum of ten years
and the facility shall have at least 10 years of manufacturing experience
producing steel pipe.
.9 Acceptable manufacturers:
.1 Canadian Phoenix Steel Products (spiral-seam steel pipe to AWWA
C200)
.2 Ewing Fabricators (straight-seam steel pipe to AWWA C200)
.3 Northwest Pipe (spiral-seam steel pipe to AWWA C200)
2.3 CATHODIC PROTECTION
.1 Provide cathodic protection in compliance with Section 02510 Watermains for
the full length of the watermain construction.
2.4 LAP WELD
.1 Lap weld joints shall conform to AWWA C200 and as shown in Chapter 8 of
AWWA M11.
.2 Lap field welded joints shall be used where restrained joints are required or
indicated on the Plans. The standard bell shall provide for a 63 mm lap. The
minimum lap shall be 25 mm. The design maximum joint deflection or offset
shall be a 25 mm joint pull.
.3 Lap welded joints shall be welded either externally or internally. Holdbacks
for coating and linings shall be provided as shown on the reviewed shop
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
8
02512
ALTERNATIVE WATERMAIN
MATERIAL - STEEL PIPE
drawings. “Weld-after-backfill” of interior welds may be performed any time
after joint completion and backfilling has been completed.
.4 Unless otherwise shown on the Plans, all field joints shall be lap welded for
diameters 1980 mm and greater.
2.5 MECHANICAL COUPLINGS
.1 Mechanical couplings shall be in accordance with the Region’s Approved
Manufacturers Products List for Water Systems where applicable. Couplings
suitable for steel pipe shall be of the same manufacturer and coupling series
per the Region’s Approved Manufacturers Products List.
.2 Couplings for buried service shall have all metal parts painted with
polyurethane paint and conform to AWWA C222.
.3 Pipe ends for mechanical couplings shall conform to AWWA C200 and M11.
The shop applied outside coating shall be held back as required for field
assembly of the mechanical coupling or to the harness lugs or rings. Harness
lugs or rings and pipe ends shall be painted with one shop coat of
polyurethane conforming to AWWA C222.
.4 Pipe for use with sleeve-type couplings shall have plain ends at right angles to
the axis.
2.6 FLANGES
.1 Flanges shall be AWWA C207 Class E for operating pressures over 1035 KPa
to 1896 KPa or shall be AWWA C207 Class F for pressures to 2070 KPa
(drilling matches ANSI B 16.5 Class 250).
.2 Shop lining and coating shall be continuous to the end of the pipe or back of
the flange. Flange faces shall be shop coated with a soluble rust preventive
compound.
.3 Gaskets shall be full face, 3 mm thick, cloth-inserted rubber, Garlock 3000,
John Crane Co. Style 777 or equal.
2.7 BOLTS AND NUTS FOR FLANGES
.1 Bolts for flanges shall be carbon steel, ASTM A 307, Grade B for Class B and
D flanges and nuts shall be ASTM A 563, Grade A heavy hex. Bolts for Class
E and F flanges shall be ASTM A 193, Grade B7 and nuts shall be ASTM A
194, Grade 2H heavy hex.
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
9
02512
ALTERNATIVE WATERMAIN
MATERIAL - STEEL PIPE
.2 All unwelded pipe joints shall be bonded for electrical continuity in
accordance with the pipe manufacturer’s recommendations unless otherwise
specified in the Plans.
2.8 LININGS AND COATINGS
.1 Cement-mortar Lining
.1 Interior surface of all steel pipe, fittings and specials shall be lined in
the shop with cement-mortar lining applied centrifugally in conformity
with AWWA C205.
.2 Holdbacks shall be left bare and be provided as shown on the reviewed
shop drawings. Holdbacks shall be filled with cement mortar after
joint completion per AWWA C205.
.3 Defective linings as identified in AWWA C205 shall be removed from
the pipe wall and shall be replaced to the full thickness required.
Defective linings shall be cut back to a square shoulder in order to
avoid feather edged joints. Cracks shall be repaired as identified in
AWWA C205.
.4 Fittings shall be cement-mortar lined per AWWA C205. Pipe and
fittings too small to cement-mortar line may be lined with AWWA
C210 epoxy or AWWA C222 polyurethane.
.5 Cement-mortar lining shall be kept moist during storage and shipping.
The Contractor shall provide a polyethylene or other suitable bulkhead
on the ends of the pipe and on all special openings to prevent drying
out the lining. All bulkheads shall be substantial enough to remain
intact during shipping and storage until the pipe is installed.
.2 Polyurethane Coating
.1 Polyurethane coating shall be per AWWA C222 to a minimum
thickness of 25 mils, measured in accordance with SSPC-PA 2.
Coating shall be continuous to the ends of the pipe except where field
welding is indicated. Exterior field joints shall be completed utilizing
heat-shrink sleeves per AWWA C216. Coatings shall be coloured blue
to reflect potable water.
.2 Coating repairs shall be per AWWA C222 and paint manufacturer’s
recommendations.
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
10
02512
ALTERNATIVE WATERMAIN
MATERIAL - STEEL PIPE
PART 3 - INSTALLATION
3.1 PIPE INSTALLATION
.1 Pipe installation shall be in accordance with AWWA C604-11. The
Contractor shall provide and install all required piping and accessories in
accordance with the contract documents and manufacturer’s
recommendations. The Contractor shall provide for visits to the site by the
manufacturers’ representative to review installation and repair procedures.
Pipe installation as specified in this section supplements AWWA M11.
.2 Steel pipe shall be concrete encased per the attached detail drawing from
Station 1+151 to Station 1+212 for a distance of 61 metres. Concrete
encasement to include 15M reinforcing bars @ 300 mm EW with 75mm
cover. Provide 50 mm polystyrene insulation.
.3 Installing Buried Piping
.1 Handle pipe in a manner to avoid any damage to the pipe. Do not drop
or roll pipe into trenches under any circumstances.
.2 Inspect each pipe and fitting before lowering into the trench. Inspect
the interior and exterior protective coatings. Repair damaged areas in
the field in accordance with AWWA M11 Section 2.02. Clean ends of
pipe thoroughly. Remove foreign matter and dirt from inside of pipe
and keep clean during and after laying.
.3 Grade the bottom of the trench and place a 100 mm minimum layer of
select or scarified material under the pipe. Before laying each section
the pipe, check the grade and correct any irregularities found. The
trench bottom shall form a uniform bearing and support for the pipe.
.4 At the location of each joint, dig bell (joint) holes in the bottom of the
trench and at the sides to permit completion and visual inspection of
the entire joint.
.5 Keep the trench in a dewatered condition during pipe laying.
.6 When the pipe laying is not in progress, including the noon hours,
close the open ends of the pipe. Do not permit trench water, animals,
or foreign objects to enter the pipe.
3.2 JOINTS ASSEMBLY
.1 Lap Field Welded Joints
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
11
02512
ALTERNATIVE WATERMAIN
MATERIAL - STEEL PIPE
.1 Clean exposed end of joint surfaces.
.2 Provide a minimum overlap of 25 mm at any location around the joint
circumference.
.3 Field welders and field weld procedures shall be certified in
accordance with AWS D1.
.4 At the Contractor’s option, provide a full fillet weld per AWWA C206
either on the inside or outside of the pipe. Inside welding may be
performed after backfilling in accordance with manufacturer’s
recommendations.
.5 Testing of field welds shall be in accordance with AWWA C206.
.6 Grout the interior of the joints with cement-mortar per AWWA C205.
Complete the exterior of the joints with heat-shrink sleeve per AWWA
C216 and manufacturer’s recommendations.
.2 Flanged Joints
.1 Bolt holes of flanges shall straddle the horizontal and vertical
centerlines of the pipe. Clean flanges by wire brushing before
installing flanged fittings. Clean flange bolts and nuts by wire
brushing; lubricate bolts with graphite or oil.
.2 Insert the nuts and bolts (or studs), finger tighten, and progressively
tighten diametrically opposite bolts uniformly around the flange to the
proper tension.
.3 Execute care when tightening joints to prevent undue strain upon
valves, pumps and other equipment.
.4 If flanges leak under pressure testing, loosen or remove the nuts and
bolts, reset or replace the gasket, reinstall or re-tighten the bolts and
nuts, and retest the joints.
3.3 FIELD TESTING AND COMMISSIONING
.1 Test and commission in accordance with the Region’s procedures and as
specified in Section 01650 - Equipment Startup and Performance Testing,
Section 01660 - Commissioning and on the contract drawings. Perform
hydrostatic pressure test to 1050 KPa.
.2 Provide all necessary piping and valves between section being tested and the
water supply, together with all required materials and equipment.
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
12
02512
ALTERNATIVE WATERMAIN
MATERIAL - STEEL PIPE
.3 Provide dished heads, blind flange or bulkheads as necessary to isolate and
test pipeline as shown on the contract drawings.
END OF SECTION
SECTION 02513
ALTERNATIVE WATERMAIN MATERIAL – FIBRE REINFORCED PLASTIC
PIPE
i
PART 1 - GENERAL ...................................................................................................................1
1.1 DESCRIPTION ................................................................................................................................ 1 1.2 RELATED SPECIFICATION ......................................................................................................... 1 1.3 REFERENCES ................................................................................................................................. 1
PART 2 - PRODUCTS ................................................................................................................2
2.1 MATERIALS ................................................................................................................................... 2 2.2 PIPE DESIGN REQUIREMENTS .................................................................................................. 3 2.3 MANUFACTURING AND PRODUCT CONSTRUCTION .......................................................... 4 2.4 DIMENSIONS ................................................................................................................................. 5 2.5 SHOP DRAWINGS ......................................................................................................................... 5 2.6 VERIFICATIONS AND TESTING................................................................................................. 6 2.7 CUSTOMER INSPECTION ............................................................................................................ 6 2.8 PACKAGING, HANDLING AND SHIPPING ............................................................................... 7 2.9 MARKINGS ..................................................................................................................................... 7
PART 3 - EXECUTION ..............................................................................................................7
3.1 INSTALLATION ............................................................................................................................. 7
PART 4 - FIELD TESTING AND COMMISSIONING ..........................................................8
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
1
02513
ALTERNATIVE WATERMAIN
MATERIAL – FIBRE REINFORCED
PLASTIC PIPE
SECTION 02513
ALTERNATIVE WATERMAIN MATERIAL - FIBRE REINFORCED PLASTIC
PIPE
PART 1 - GENERAL
1.1 DESCRIPTION
.1 This specification covers the construction of the 750 mm diameter Appleby
Zone 3 BPS watermain using fibre reinforced plastic (FRP) pipe as an
alternative material.
.2 This specification designates the manufacturing, design and installation
requirements of glass-fibre-reinforced plastic pipe for the Appleby Zone 3
BPS watermain.
.3 All provisions and requirements of Section 02511 – Watermains, and the
Contract Drawings shall also apply to the construction of the 750 mm
diameter watermain using FRP pipe. In case of discrepancies between the
aforementioned Section 02511 and this current specification Section 02513
Alternative Watermain Material – FRP Pipe, this Section 02513 shall govern.
1.2 RELATED SPECIFICATION
.1 Section 02511 – Watermains
.2 Section 02512 – Alternative Watermain Material – Steel Pipe
.3 Section 01650 – Equipment Startup and Performance Testing
.4 Section 01660 – Commissioning
1.3 REFERENCES
.1 AWWA C950 Standard specification Fiberglass Pressure Pipe.
.2 ASTM D4161 Standard specification for “fibreglass” pipe joints using
flexible elastomeric seals.
.3 ASTM D2412 Standard Test Method for Determination of External Loading
Characteristics of Plastic Pipe by Parallel-Plate Loading.
.4 ASTM D2290 Standard Test Method for Apparent Hoop Tensile Strength of
Plastic or Reinforced Plastic Pipe by Split Disk Method.
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
2
02513
ALTERNATIVE WATERMAIN
MATERIAL – FIBRE REINFORCED
PLASTIC PIPE
.5 ASTM D2992 Practice of Obtaining Hydrostatic or Pressure Design Basis for
“Fiberglass” (Glass-Fiber-Reinforced Thermosetting-Resin) Pipe and Fittings.
.6 ASTM D638 Standard Test Method for Tensile Properties of Plastics.
.7 ASTM D695 Standard Test Method for Compressive Properties of Rigid
Plastics.
.8 ASTM F 477 Specification for elastomeric seals (gaskets) for joining plastic
pipe.
.9 ISO 7432 Glass-reinforced thermosetting plastics (GRP) pipe and fittings –
Test method to prover the design of locked socket-and-spigot joints, including
double-socket joints with elastomeric seals.
.10 OPSS 441 Construction Specification for Watermain Installation in Open Cut.
.11 NSF/ANSI Standard 61 Drinking Water System Components – Health
Effects.
PART 2 - PRODUCTS
2.1 MATERIALS
.1 Resin: The manufacturer shall use only polyester or vinyl ester resin systems
designed for the service intended.
.2 Filler: Sand shall be at least 95% silica sand and have a maximum moisture
content of 0.2%.
.3 Additives: Resin additives, such as curing agents, pigments, dyes, fillers and
thixotropic agents, when used, shall not be detrimental to the pipe.
.4 Elastomeric Gaskets: Gaskets shall be EPDM rubber and suitable for the
service intended. All gaskets shall meet the requirement of ASTM F 477.
.5 Glass Reinforcement: Continuous filaments and chop rovings shall be of the
highest commercial grade E-glass fibres with a finish compatible with the
resin.
.6 All materials in contact with potable water shall be NSF/ANSI 61 compliant.
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
3
02513
ALTERNATIVE WATERMAIN
MATERIAL – FIBRE REINFORCED
PLASTIC PIPE
2.2 PIPE DESIGN REQUIREMENTS
.1 Pipe: The pipe shall be manufactured in accordance with AWWA C950. The
pipe shall meet the following cell limits of AWWA C950: Type 1, Liner C,
Grade 4. The pipe shall be field connected with glass reinforced sleeve
couplings that utilize elastomeric sealing gaskets as the sole means to
maintain joint water tightness. The couplings shall be manufactured using the
same process as the pipe. The joints shall utilize elastomeric sealing gaskets
meeting the performance requirements of ASTM D4161.
.2 The pipe shall be manufactured using a filament wound mandrel process
utilizing continuous glass fibre reinforcements in the circumferential
direction. Both continuous glass fibre rovings and chopped roving will be
incorporated for high hoop strength and axial reinforcement. A sand fortifier
shall be used to provide increased stiffness with placement near the neutral
axis in the core.
.3 Pipe design is governed by the following criteria unless specifically noted
otherwise:
.1 Internal Working Pressure: 690 kPa
.2 Field Test Pressure: 1,050 kPa
.3 Water Hammer Allowance: 40%
.4 Trench Supported Full Vacuum: 100 kPa
.5 Live Load: HS-20
.6 Variable Depth of Earth Cover: as shown on drawings
.4 Pipe pressure class, wall thickness or dimension ratio shown on the Contract
Drawings or specified elsewhere in the Contract Documents take precedence
and may vary from those determined through the application of Design Guide
methodologies and procedures.
.5 This does not relieve the pipe supplier from responsibility for conducting an
independent analysis to confirm that dimensional information specified or
shown elsewhere satisfies the design criteria. In the event that Design Guide
procedures result in a wall section thicker than that shown or specified
elsewhere, use the larger of the two values.
.6 NSF/ANSI 61 compliant materials in contact with potable water.
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
4
02513
ALTERNATIVE WATERMAIN
MATERIAL – FIBRE REINFORCED
PLASTIC PIPE
.7 Referenced pipe sizes are nominal based on a conversion factor of 25 mm
equals 1 inch.
.8 Pipe material used in fittings shall be of the same material and pressure class
as the adjoining pipe. The minimum radius of elbows shall be 2 ½ times the
pipe diameter and the maximum miter angle on each section of the elbow
shall not exceed 11 ¼-degrees (one cut elbow up to 22 ½-degrees). If elbow
radius is less than 2 ½ times the pipe diameter, stresses shall be checked and
the pressure class increased if necessary.
.9 Specials and fittings, unless otherwise shown on the Contract Drawings, shall
be made of segmental sections from hydrostatically tested pipe, with ends
compatible with the type of joint or coupling specified for the pipe.
2.3 MANUFACTURING AND PRODUCT CONSTRUCTION
.1 Pipe: The pipe shall be manufactured in accordance with AWWA C950. The
pipe shall meet the following cell limits of AWWA C950: Type 1, Liner C,
Grade 4. The pipe shall be field connected with glass reinforced sleeve
couplings that utilize elastomeric sealing gaskets as the sole means to
maintain joint water tightness. The couplings shall be manufactured using the
same process as the pipe. The joints shall utilize elastomeric sealing gaskets
meeting the performance requirements of ASTM D4161.
.2 The pipe shall be manufactured using a filament wound mandrel process
utilizing continuous glass fibre reinforcements in the circumferential
direction. Both continuous glass fibre rovings and chopped roving will be
incorporated for high hoop strength and axial reinforcement. A sand fortifier
shall be used to provide increased stiffness with placement near the neutral
axis in the core.
.3 Restrained Joints: The pipe may be connected with a fibreglass reinforced
sleeve/coupling subject to approval by the Engineer utilizing a double bell
with elastomeric sealing gaskets as the sole means to maintain joint water-
tightness and locking rods to transfer axial thrust from one pipe section to
another. On each side, the coupling bell shall have a standard rubber gasket
and a rod-groove system, through which the load is transferred via
compressive and shear action. The pipe spigot shall have a matching rod-
groove. The joint shall meet the performance requirements of ISO 7432.
.4 Laminated Joints: The pipe may be field connected with a fibreglass laminate
subject to approval by the Engineer as the sole means to maintain joint water
tightness and to transfer axial loads. The joints shall meet the performance
requirements of ASTM D4161.
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
5
02513
ALTERNATIVE WATERMAIN
MATERIAL – FIBRE REINFORCED
PLASTIC PIPE
.5 Fittings: Elbows, reducers, tees, wyes, laterals and other fittings shall be of
the same structural design as adjoining pipe. Fittings shall be manufactured
with mitered sections of pipe and joined by fibreglass overlay. Biaxial fitting
with restrained joints shall be required when thrust blocking is not an
acceptable means of restraining the fittings.
.6 Manufacturer: Manufacturer of pipe and fittings shall employ product
technology used in the manufacture of fibreglass pipe for a minimum of 10
years and the facility shall have at least 10 years of manufacturing experience
producing fibreglass pipe.
.7 Acceptable manufacturer: Glass reinforced polymer (GRP) pipe by Thompson
Pipe Group – Flowtite.
2.4 DIMENSIONS
.1 Diameters: The outside diameter of pipe shall be per the AWWA C950-Table
4.
.2 Lengths: Pipe shall be supplied in nominal lengths of 3.0 metres to 12.0
metres. Actual lay length shall be nominal ±1 inch. Special short lengths may
be used where surface geography or installation conditions require shorter
lengths.
.3 Wall Thickness: The average wall thickness of the pipe shall not be less than
the nominal wall thickness published in the manufacturer’s literature, and the
minimum wall thickness at any point shall not be less than 87.5% of the
nominal wall thickness.
.4 End Squareness: All points around each end of a pipe unit shall fall within
6.35 mm or 0.5% of the nominal diameter of the pipe, whichever is greater, to
a plane perpendicular to the longitudinal axis of the pipe.
2.5 SHOP DRAWINGS
.1 All requirements of Section 01330 – Submittal Procedures and Section 02511
– Watermains for concrete pressure pipe watermain and precast concrete valve
chambers shall also apply to this section. Shop drawings shall be submitted to
the Contract Administrator for approval and shall include the following:
.1 Pipeline layout showing stations and elevations.
.2 Details of standard pipe, joints, specials and fittings.
.3 Calculations for pipe design and fittings reinforcement and/or test data.
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
6
02513
ALTERNATIVE WATERMAIN
MATERIAL – FIBRE REINFORCED
PLASTIC PIPE
.4 Details of joint bonding and field joint restraint calculations.
.2 Shop drawings shall be stamped and signed by a Professional Engineer
registered with Professional Engineers Ontario.
2.6 VERIFICATIONS AND TESTING
.1 Pipes: Pipe shall be manufactured in accordance with AWWA C950.
.2 Joints: Joints shall meet the requirements of ASTM D4161.
.3 Stiffness: Each pipe shall have sufficient strength to exhibit the minimum
pipe stiffness at 5% deflection as required by the Engineer. Stiffness shall be
tested in accordance with the test method of ASTM D2412. One pipe shall be
tested every 50 lengths of each type, grade, and size pipe produced.
.4 Hydrostatic Leak Test: All pipes and couplings produced shall be
hydrostatically tested at two times the pressure rating of the pipe in
accordance with AWWA C950 at the manufacturing facility prior to
shipment.
.5 Hoop Tensile Strength: Pipe shall meet or exceed the hoop-tensile strength
shown in AWWA C950, Tables 9 & 10 when tested in accordance with
ASTM D638 or ASTM D2290. One pipe shall be tested every 50 lengths of
each type, grade, and size pipe produced.
.6 Longitudinal Beam Strength: Pipe shall meet or exceed the requirements of
AWWA C950.
.7 Longitudinal Tensile Strength: Pipe shall meet or exceed the requirements of
AWWA C950 when tested in accordance with ASTM D638.
.8 Longitudinal Compressive Strength: Pipe shall meet or exceed the
requirements of AWWA C950 when tested in accordance with ASTM D695.
.9 Chemical Resistance: Pipe shall meet or exceed the requirements of AWWA
C950 when tested in accordance with ASTM D3681.
2.7 CUSTOMER INSPECTION
.1 The Region or other designated representative shall be entitled to inspect
pipes and witness the manufacturing process.
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
7
02513
ALTERNATIVE WATERMAIN
MATERIAL – FIBRE REINFORCED
PLASTIC PIPE
2.8 PACKAGING, HANDLING AND SHIPPING
.1 Packaging, handling and shipping shall be performed in accordance with the
Manufacturer’s instructions.
.2 End caps shall be used at all times on all pipe sections during shipping,
storage and handling on site to prevent unwanted materials from entering the
pipe at all times except during jointing.
2.9 MARKINGS
.1 The Contractor shall legibly mark all pipes and specials in accordance with
the laying schedule and marking diagram. Each pipe shall be numbered in
sequence and said number shall appear on the laying schedule and marking
diagram in its proper location for installation. All special pipe sections and
fittings shall be marked at each end with top field centerline. The word “top”
or other suitable markings shall be painted or marked on the outside top spigot
end of each pipe section.
PART 3 - EXECUTION
3.1 INSTALLATION
.1 Installation: The installation of pipe and fittings shall be in accordance with
the Contract Drawings, Section 2511 - Watermains and the manufacturer’s
recommended practices. The Contractor shall provide for visits to the site by
the manufacturers’ representative to review installation and repair procedures.
.2 FRP watermain pipe shall be insulated for a distance of 65 metres as shown in
Contract Drawing G-202.
.3 Installing Buried Piping:
.1 Handle pipe in a manner to avoid any damage to the pipe. Textile
slings devices or other suitable materials and/or a forklift are
recommended. Do not drop or roll pipe into trenches under any
circumstances.
.2 Inspect each pipe and fitting before lowering into the trench. Repair
damaged areas as required per AWWA C905. Clean ends of pipe
thoroughly. Remove foreign matter and dirt from inside of pipe and
keep clean during and after laying.
APPLEBY ZONE 3 BOOSTER
PUMPING STATION
August 2016
8
02513
ALTERNATIVE WATERMAIN
MATERIAL – FIBRE REINFORCED
PLASTIC PIPE
.3 Grade the bottom of the trench and place a 100 mm minimum layer of
select or scarified material under the pipe. Before laying each section
the pipe, check the grade and correct any irregularities found. The
trench bottom shall form a uniform bearing and support for the pipe.
.4 At the location of each joint, dig bell (joint) holes in the bottom of the
trench and at the sides to permit completion and visual inspection of
the entire joint.
.5 Keep the trench in a dewatered condition during pipe laying.
.6 When the pipe laying is not in progress, including the noon hours,
close the open ends of the pipe. Do not permit trench water, animals,
or foreign objects to enter the pipe.
.4 Jointing:
.1 Pipe end, gasket and sealing surfaces shall be inspected for damage
and cleaned of all debris.
.2 Apply joint lubricant to the sleeve coupling interior and the
elastomeric gasket. Use only lubricants approved by the pipe
manufacturer.
.3 Use suitable equipment and end protection to push the pipes together.
.4 Do not exceed joining or pushing forces recommended by the
manufacturer.
PART 4 - FIELD TESTING AND COMMISSIONING
.1 Test and commission in accordance with the Region’s procedures and as
specified in Section 01650 - Equipment Startup and Performance Testing,
Section 01660 - Commissioning and on the Contract Drawings.
.2 Provide all necessary piping and valves between section being tested and the
water supply, together with all required materials and equipment.
.3 Provide dished heads, blind flange or bulkheads as necessary to isolate and
test watermain as shown on the Contract Drawings.
.4 Perform field hydrostatic pressure test to 1050 KPa.
END OF SECTION
SECTION 04270 GLASS UNIT MASONRY
i
1 PART 1 – GENERAL ....................................................................................................................1
1.1 RELATED WORK ..................................................................................................................... 1 1.2 RELATED WORK SPECIFIED ELSEWHERE.......................................................................... 1 1.3 QUALITY ASSURANCE: ......................................................................................................... 1 1.4 JOB CONDITIONS: ................................................................................................................... 1
2 PART 2 – PRODUCTS ..................................................................................................................1
2.1 MATERIALS: ............................................................................................................................ 1
3 PART 3 – EXECUTION ...............................................................................................................3
3.1 EXAMINATION: ....................................................................................................................... 3 3.2 PREPARATION: ........................................................................................................................ 3 3.3 INSTALLATION: ...................................................................................................................... 3
APPLEBY ZONE 3 BOOSTER PUMPING STATION AUGUST 2016
1 04270
GLASS UNIT MASONRY
SECTION 04270 GLASS UNIT MASONRY
1 PART 1 – GENERAL
1.1 RELATED WORK
.1 Furnish all labour and materials to install all glass blocks where shown on the drawings or specified herein. This shall include the furnishing and installation of all expansion strips, packing, panel reinforcing, panel anchors, caulking, asphalt emulsion, and other labour and materials necessary for a complete installation. This contract does include the coordination with the structure to receive the glass block panels, such as chases, stiffeners, etc., except as hereinafter specified.
1.2 RELATED WORK SPECIFIED ELSEWHERE
.1 Thermal Insulation: Section 7200
1.3 QUALITY ASSURANCE:
.1 Samples:
.1 Submit two (2) glass block units of each type specified showing size, colour, design and pattern of faces.
.2 Submit representative samples of panel reinforcing, panel anchors, expansion strips and sealant.
1.4 JOB CONDITIONS:
.1 Store unopened cartons of glass block in a dry area.
.2 Do not install glass block units when air temperature is less than 4°C.
2 PART 2 – PRODUCTS
2.1 MATERIALS:
.1 Glass block units shall be solid masonry units made of clear, colourless glass without a highly reflective oxide surface coating, by WECK (thru Thames Valley Brick &Tile, Burlington 1-800-567-5800) Pittsburgh Corning Corporation or equivalent. The glass block unit types shall be as follows: 190 mm x 190 mm x 100 mm Metric Series Fortress Extra Heavy Glass Block from WECK or Vistabrik Solid Glass Block by Pittsburgh Corning Corporation or other approved equal glass block manufacturer. Blocks to meet requirements for security applications and to minimize vandalism.
APPLEBY ZONE 3 BOOSTER PUMPING STATION AUGUST 2016
2 04270
GLASS UNIT MASONRY
.2 Edge Coating – glass blocks shall have a polyvinyl butyral edge coating to provide for better bonding and to provide for an expansion/contraction mechanism for each block.
.3 Mortar shall be 1 part Portland Cement, 1/2 part lime, and sand equal to between 21/2 and 3 times the amount of cementitious material (cement plus lime), all measures by volume. Admixtures in the form of setting accelerators and anti-freeze compounds shall not be used.
.1 An optimum mortar mix recommendation is 1 part Portland Cement, 1/2 part lime and 4 parts sand.
.2 Any combinations of the above mortar mixture shall fall within Type S mortar as specified by ASTM 270.
.3 Mix all mortar components to a consistency as stiff as will permit good working. Mortar shall be drier than mortar for ordinary masonry. Retempering the mortar after it has taken its initial set shall not be permitted.
.4 Mortar shall consist of the following:
.1 Portland Cement – shall be Type 1 conforming to the Standard Specifications for Portland Cement, ASTM Designation C 150.
.2 Lime – shall be a high-calcium lime, or a pressure-hydrated dolomitic lime, provided that not less than 92% of all the active ingredients are completely hydrated, conforming to ASTM C 207, Type S.
.3 Sand – shall conform to “Std. Spec. for Aggregate for Masonry Mortar,” ASTM C 144 for thin joints. A clean, white, quartize type, essentially free of iron compounds, is recommended.
.4 Expansion Strips – shall be polyethylene foam as furnished by WECK, Pittsburgh Corning Corporation or approved equal. Colour to be white and thickness to be 10 mm.
.5 Panel Reinforcing – shall be Panel Reinforcing as furnished by WECK, Pittsburgh Corning Corporation or approved equal and shall be of galvanized steel double-wire mesh formed of two parallel 9-gauge wires 50 mm on centre with electrically welded cross wires at regular intervals, placed every 2 vertical glass block courses.
.6 Panel Anchors – where shown on drawings or required, Panel Anchors shall be furnished by WECK, Pittsburgh Corning Corporation or equivalent and shall be No. 20-gauge perforated steel strips 600 mm long by 42 mm wide galvanized
APPLEBY ZONE 3 BOOSTER PUMPING STATION AUGUST 2016
3 04270
GLASS UNIT MASONRY
after perforating. Embed at every 2 block courses vertically, and at tops of glass block panels as recommended by manufacturer.
.7 Asphalt Emulsion - where shown or required, shall be a water-based asphalt emulsion (Karnak 100 by Karnak Chemical Corporation, Clark N.J. or equal).
.8 Packing (Backer Rods) – where indicated on drawings or required as a lateral cushioning for Glass Block panels at jambs, heads, and intermediate supports, shall be polyethylene foam, neoprene or equal filler approved by the sealant manufacturer.
.9 Sealant – shall be a non-staining, waterproof mastic, silicone type.
.10 Structural Channels – see Division 5, Metals.
3 PART 3 – EXECUTION
3.1 EXAMINATION:
.1 Do not commence operations without examining existing related works for any conflict with work done under this Division.
3.2 PREPARATION:
.1 Verify that channels have been provided at head, jambs, and intermediate locations for the purpose of providing panel support. Bolt or weld channels to surrounding structure. Verify that intermediate stiffeners or supports are adequate to provide required wind load or load bearing resistance.
.2 Mix all mortar components to a consistency that is drier than mortar for ordinary masonry. Retempering the mortar after it has taken its initial set shall not be permitted. Do not use antifreeze compounds or accelerators.
3.3 INSTALLATION:
.1 Apply heavy coat of Asphalt Emulsion to sill area. Allow emulsion to dry before placing mortar.
.2 Adhere Expansion Strips to jambs and head with gobs of asphalt emulsion. Make certain expansion strip extends to sill.
.3 Set a full mortar bed joint, applied to sill.
.4 Set the lower course of block. All mortar joints must be full and not furrowed. Steel tools must not be used to tap blocks into position.
.5 Install Panel Reinforcing in horizontal joints. Reinforcing shall be installed every 2 blocks vertically and in joints immediately above and below all openings within
APPLEBY ZONE 3 BOOSTER PUMPING STATION AUGUST 2016
4 04270
GLASS UNIT MASONRY
panels. Reinforcing shall run continuously from end to end of panels and shall be lapped not less than 150 mm whenever it is necessary to use more than one length. Do not bridge expansion joints with reinforcing.
.6 Install reinforcing as follows:
.1 Place lower half of mortar in bed joint. Do not furrow.
.2 Press panel reinforcing into place.
.3 Cover panel reinforcing with upper half of mortar bed and trowel smooth. Do not furrow.
.7 Place full mortar bed for joints not requiring panel reinforcing – do not furrow.
.8 Set succeeding course of blocks.
.9 Strike joints smooth when mortar is thumb print hard. At this time rake out all spaces requiring sealant to a depth equal to the width of the spaces. Remove surplus mortar from faces of glass blocks and wipe dry. Tool joints smooth and concave, before mortar takes final set.
.10 After final mortar has set (approx. 24 hours), install packing tightly between glass block panel and jamb and head construction. Leave space for sealing.
.11 Apply sealant evenly to the full depth of recesses as indicated on the drawings and in accordance with the manufacturer’s application manual and instructions.
.12 Surplus mortar shall be removed and the faces of the blocks wiped dry at the time joints are tolled. Cleaning is facilitated by the use of an ordinary household scrub brush having stiff bristles. Final cleaning shall be done by others after mortar has attained final set but before becoming dry on the block surfaces. Do not use abrasive cleaners (steel wool, wire brush) in conjunction with removing mortar or dirt from the faces of glass block. Remove mortar with damp cloth before final set occurs.
END OF SECTION
SECTION 10800 WASHROOM ACCESSORIES
i
PART 1 - GENERAL...................................................................................................................1
1.1 GENERAL REQUIREMENTS........................................................................................................ 1 1.2 SCOPE OF WORK .......................................................................................................................... 1 1.3 RELATED WORK........................................................................................................................... 1 1.4 QUALITY ASSURANCE ............................................................................................................... 1 1.5 SUBMITTALS ................................................................................................................................. 1 1.6 DELIVERY, STORAGE AND HANDLING .................................................................................. 2 1.7 CO-ORDINATION .......................................................................................................................... 2
PART 2 - ACCESSORIES ..........................................................................................................2
2.1 TOILET TISSUE DISPENSERS ..................................................................................................... 2 2.2 HAND DRYER ................................................................................................................................ 2 2.3 SURFACE MOUNTED PAPER TOWEL DISPENSER & WASTE RECEPTACLE ................... 2 2.4 MIRRORS - TYPE “A” ................................................................................................................... 3 2.5 COAT HOOK................................................................................................................................... 3 2.6 WASHROOM SHELF ..................................................................................................................... 3 2.7 FABRICATION ............................................................................................................................... 3
PART 3 - EXECUTION ..............................................................................................................4
3.1 INSPECTION ................................................................................................................................... 4 3.2 INSTALLATION ............................................................................................................................. 4 3.3 ADJUSTING AND CLEANING ..................................................................................................... 4
APPLEBY ZONE 3 BOOSTER PUMPING STATION AUGUST 2016
1
10800 WASHROOM ACCESSORIES
SECTION 10800 WASHROOM ACCESSORIES
PART 1 - GENERAL
1.1 GENERAL REQUIREMENTS
.1 Conform to the requirements stated in the General Conditions, Supplementary General Conditions of this Specification and all addenda.
1.2 SCOPE OF WORK
.1 Furnish all labour, materials, and equipment necessary to supply and install washroom accessories as shown on drawings and specified herein.
1.3 RELATED WORK
.1 Unit Masonry- Section 04200
1.4 QUALITY ASSURANCE
.1 Toilet and bath accessories to be installed by fully experienced workmen in strict accordance with the manufacturer's instructions and reviewed shop drawings.
.2 Products specified herein are based on Bobrick washroom accessories. The Consultant will determine the specific equivalence of any proposed alternate product.
.3 Manufacturer’s or brand names on the face of units is not acceptable.
.4 Electric hand dryers must be warranted for a period of ten (10) years, other products to be warranted per manufacturer’s standard warranty.
.5 Mounting heights to be at recommended standard practice and to Ontario Building Code, where required, to meet Barrier-Free requirements.
.6 Tamper proof screws, bolts, etc. must be used for all fastenings.
1.5 SUBMITTALS
.1 Submit shop drawings or catalogue illustrations in quadruplicate for review by the Consultant. Clearly indicate size and description of components, base materials, surface finish inside and out, hardware and locks, attachment devices, description of rough-in-frames and building-in details of anchors for grab bars.
APPLEBY ZONE 3 BOOSTER PUMPING STATION AUGUST 2016
2
10800 WASHROOM ACCESSORIES
1.6 DELIVERY, STORAGE AND HANDLING
.1 Co-ordinate delivery of toilet and bath accessories to the site in order to avoid unnecessary delays in construction and to avoid damage due to excessive storage periods.
.2 Store materials in weathertight enclosures and take all necessary precautions to protect finishes from damage.
1.7 CO-ORDINATION
.1 Co-ordinate location of toilet and bath accessories with all other pertinent trades to ensure the installation of adequate back-up blocking or reinforcing.
PART 2 - ACCESSORIES
2.1 TOILET TISSUE DISPENSERS
.1 Bobrick B-265 or approved equivalent, surface-mounted multi-roll dispenser, heavy-gauge steel with bright polished chrome finish with concealed locking device, controlled delivery.
.2 Location and quantity: one required in new washroom.
2.2 HAND DRYER
.1 Model A hand dryer shall be manufactured by World Dryer or approved equivalent to include 6.35 mm thick cast iron cover. Cover to be finished with porcelain enamel. Motor shall be of the universal type, 1/10 HP at 7500 RPM. Dryer shall deliver 7300 linear feet of air per minute (LFM). Hand Dryer shall be activated by means of a push button control device. Hand dryer shall be listed by ULC and certified by CSA.
.2 Location and quantity: one required in new washroom.
2.3 SURFACE MOUNTED PAPER TOWEL DISPENSER & WASTE RECEPTACLE
.1 Bobrick B-3699 or approved equivalent, surface mounted, Type 304, 0.8 mm stainless steel welded construction. Door has full-length stainless steel piano-hinge. Removable waste container.
.2 Location and quantity: one required in new washroom.
APPLEBY ZONE 3 BOOSTER PUMPING STATION AUGUST 2016
3
10800 WASHROOM ACCESSORIES
2.4 MIRRORS - TYPE “A”
.1 Bobrick B-2936 or approved equivalent, size 457 x 762 mm, tilt mirror, surface mounted, Type 304 satin finish stainless steel frame with polished stainless steel mirror.
.2 Location and quantity: one in new washroom.
2.5 COAT HOOK
.1 Bobrick B-233 or approved equivalent, type 304 stainless steel, satin finish, with a 32 x 32 mm hook and a projection of 29 mm.
.2 Location and quantity: one required in new washroom.
2.6 WASHROOM SHELF
.1 Bobrick B-296 or approved equivalent, surface mounted stainless steel shelf, satin finish, 610 mm long, 152 mm deep.
.2 Locate above water closet in new washroom.
2.7 FABRICATION
.1 Weld and grind joints of fabricated components flush and smooth. Use mechanical fasteners only where approved.
.2 Wherever possible form exposed surfaces from one sheet of stock, free of joints.
.3 Brake form sheet metal work with 1.5 mm radius bends.
.4 Form surfaces flat without distortion. Maintain flat surfaces without scratches or dents.
.5 Back paint components where contact is made with building finishes to prevent electrolysis.
.6 Hot dip galvanized concealed ferrous metal anchors and fastening devices.
.7 Shop assemble components and package complete with anchors and fittings.
.8 Deliver inserts and rough-in frames to job-site at appropriate time for building-in. Provide templates, details, and instructions for building in anchors and inserts.
.9 Provide steel anchor plates and components for installation on studding and building framing.
APPLEBY ZONE 3 BOOSTER PUMPING STATION AUGUST 2016
4
10800 WASHROOM ACCESSORIES
PART 3 - EXECUTION
3.1 INSPECTION
.1 Prior to installation of toilet and bath accessories, carefully inspect the installed work of all other trades and verify that all such work is complete to the point where this installation may properly commence.
3.2 INSTALLATION
.1 Refer to washroom layouts for general location of accessories. Exact location and mounting heights of all accessories are to be directed on site by Consultant and in accordance with OBC.
.2 Install all washroom accessories in strict accordance with manufacturer's recommendations and as specified herein.
.3 Install and secure accessories rigidly in place as follows:
.1 Hollow masonry units or drywall: use toggle bolts drilled into cell/wall cavity.
.4 Use tamper proof screws/bolts for fasteners.
.5 Fill units with necessary supplies shortly before final acceptance of building.
3.3 ADJUSTING AND CLEANING
.1 Make good all wall finishes after accessory installation, to the satisfaction of the Consultant.
.2 At completion of installation, clean up and remove all debris caused by this construction.
END OF SECTION
top related