range of pressure-independent control valves · the pressure-independent control valve r2...p...
Post on 30-May-2020
8 Views
Preview:
TRANSCRIPT
P. R2...P
Range of Pressure-Independent Control Valves
Two
havebecome
one
2
The pressure-independent control valve R2…P setsnew standards
The challenge
Energy savings with maximum convenienceand low installation prices are require-ments for the construction of new buil-dings and for renovations. Selecting thecorrect valves for the entire pipelinesystem and a professional hydraulicbalancing costs money. Valves are conventionally designed with a
valve authority of 0.5 and installed beforeeach consumer (e.g. air heater, heatexchanger, supply controls).However, pressure conditions vary depend-ing on the installation site of the consumer
and the load. In the case of consumers (# 1)that are placed near the main pump, the dif-ferential pressure between the supply/return pipes is much higher than at the endof the pipes (# n). With nominal volumetricflow, the necessary delivery height ∆pp100
of the main pump depends on the selec-ted pipe network (DN and pipe lengths)and on the minimum differential pressureat the last consumer (pressure drop at theconsumer and valve).
Pressure diagram at full load
The pressure difference ∆p #1 consists of the pressure drop at consumer T #1,valve V #1 and the balancing valve D #1.The valve V#1 is fully opened here. If valve#1
closes, the differential pressure canincrease up to ∆p #1, the valve authoritysinks markedly, and the flow quantityincreases disproportionately.
The solution
As a result of the consistent further deve-lopment of the tried-and-tested Belimocharacterized control valve, the valvedesign has been simplified with the newpressure-independent control valveR2...P. The flow rate is constant, evenwhen the valve closes and the differentialpressure increases. The valve authority is1, even with overdimensional valve sizes.
The advantages
Hydraulic balancing is no longer neces-sary. Equipping a building becomes simp-ler, and only one valve per consumer isneeded. Since no more balancing valvesare needed and the hydraulic balancing iseliminated, it is possible to save costs while –at the same time – increasing convenience.
# 1
# n
D
D
D
V
V
D V
D V
D VV
∆p p100 ∆p #1
T #1
V #1
D #1
T #n
V #n
∆p #n
0 100 %
100 %
VPv ≈ 0,3
Pv ≈ 0,5
Pv = 1
Example: Office building with several floors
30 Differential pressure 350 [kPa](effective pressure)
Flow
rat
e
Flow diagram R220P Only one valve is needed per consumer:
previously now
R2…P: the simplest way to control the flow rate
Pressure-reducing Control valvecontrol valve
Supplypressure
Valve authority Pv
Valve opening
Openingposition
100%90%80%70%60%50%40%
[l/s]0,8
0
3
Principle of operation
The characteristics
The pressure-independent control valveR2...P contains two valves: the self-regu-lating pressure-reducing valve [A] and thecontrol valve [AB] that works with equalpercentage. When the differential pressureincreases, the pressure-reducing valvecloses and ensures a constant pressureover the control valve. This is necessaryfor the flow rate to remain constant ±5 %(at a differential pressure of 30…350 kPa)with the current opening position of thecontrol valve.
The selection
The range of motorized, pressure-inde-pendent control valves comprises a practical spectrum. All valves are:
• 2-way valves in the most common nomi-nal widths (DN 15…50)
• Designed for a flow rate of 0.09l/s to 3.78 l/s
The corresponding drives
Optimum functionality of the Belimo pressure-independent control valve isensured by the corresponding motori-zation. Depending on the application, thepressure-independent control valves aresupplied with different rotary actuators.You can choose from the LR... and NR...rotary actuators. Depending on the type,they can be controlled by a modulating or3-point control system.
Identical mounting flange for allnominal widths, without lateralpressure on the stem
Stem with two 0-rings,blow-out proof
Chrome-plated ball
Teflon seat with O-ringensures leakage ratetight with low torquerequirement
Maintenance-freedifferential pressuremeasurement for thepressure-reducing valve
Vent window to prevent theaccumulation of condensation
Simple direct mounting of the rotary actuator usinga central screw, without shaft adapter
Flow direction
[AB]
[A]
Cross-section of the pressure-independent control valve R2…P
Thermal decoupling of rotary actuator andcontrol device
Belimo characterizing disk for equal-percentage flow characteristic
Pressure-reducing valve cone made of brass
Pressure-reducing cage made ofDelrin 500
Internal thread connection(BSP acc. to ISO 7/1)
Forged fitting, nickel-plated brass body
Pressure-regulating diaphragmmade of polyester-reinforcedsilicone
Stainless spring (not visible)supports the pressure-regulating diaphragm
4
0 ∆p
V
[l/s] [cl/s]4 400 R250P-378
R232P-151
R220P-066
R240P-157
R215P-009
30 50 100 150 200 250 300 350
0,3 0,5 1 1,5 2 2,5 3 3,5
1400 [kPa]
14 [bar]
➊ ➋ ∆ps
0,1 10
0,5 50
1 100
2 200
3 300
2,5 250
1,5 150
R225P-057
R215P-036 / R220P-036
R225P-098 R232P-101
R240P-252 / R250P-252
Closing pressure at which the rotary actuator isstill able to close the fitting tightly in relation tothe corresponding leakage rate.
Definition∆ps = 1400 kPa
Type designation
R220P–036
Flow rate in cl /s
Pressure-independent
DN in mm
Two-way control valve withinternal thread
Legend➊The differential pressure of 30...350 kPAshould be lower than the delivery pressure(delivery height) of the pump (HP) withnominal flow rate. If the delivery pressureof the pump (HP) is below the differentialpressure, the flow rate decreases
kvs [m3/h]
V100 [m3/h]
∆pv100 [bar]
V (R2…P) [l /s]
∆pv100 Differential pressure with fullyopened control valve
V100 Nominal flow rate with ∆pv100
➋If ∆p over the R2…P is greater than the dif-ferential pressure of 350 kPa, the maximumflow rate decreases (by approx. 25% inrelation to the given value).
∆pv100V100 = V(R2…P) x 6x
Differential pressure
— Type —
DesignIn the case of classic control valves, thevalves are selected kvs = in m3/h.
The decisive factor for the design of thepressure-independent control valve is theflow rate after the consumer or the heatexchanger.In the case of a maximum flow rate of < 2 m/s, the diameter of the pipe connectorat the heat exchanger can be set equal tothe diameter of R2...P (max. flow rate).
ExamplesThe flow rate through the pressure-inde-pendent control valve should be higherthan through the consumer or heatexchanger:
Example of an air cooler (throttling circuit)
V(valve) = V(exchanger)
0.36 l /s > 0.34 l/s
R220P-036 (Type)
Example of an air preheater (injection circuit with 2-way valve)
V(valve) = V(exchanger)
1.51 l /s > 1.25 l/s
R232P-151 (Type)
V100
∆pv100
HP
Q = 8.5 kW∆T = 6 KV(exchanger) = 0.34 l/s
HP
Q = 105 kW∆T = 20 KV(exchanger) = 1.25 l /s
Dimensioning
Dimensioning diagram for pressure-independent control valves R2…P
(scaling not linear)
5
Selection table
Technical data of the pressure-independent control valves R2…P
Rotary actuator LR... and NR... for pressure-independent control valves R2…P (modulating)
Nominal width DN [mm] 15...50 •Design 2-way: inlet A, outlet AB •Characteristic equal-percentage (A–AB) •Areas of application cold and warm water •Temperature of medium +5°C...+100°C (lower medium temperatures on request) •Material housing nickel-plated brass •
ball and spindle chrome-plated brass •Connections Internal thread BSP (ISO 7/1) •Rated pressure 41 bar [DN 15…32], 27 bar [DN 40…50] •Closing pressure ∆ps 14 bar •Differential pressure 30…350 kPa •
Type R2…P
Type LR24-SR NR24-SR NRY24-SR
Nominal voltage AC / DC 24V • • •Duration 140 s •
approx. 80…110 s •35 s •
Control modulating, DC 0…10V • • •Operating range DC 2…10V • • •Position feedback DC 2…10V • • •Manual override temporary • • •
permanent • •Connection cable 1 m • • •
Integrated screw terminals • •
Other versions and spring return actuators available on request
Rotary actuator NR... for pressure-independent control valves R2…P (3-point)
Type NR230-3 NR230-3-S NR24-3 NR24-3-S
Nominal voltage AC 24V • •AC 230V • •
Duration 140 s • • • •Control 3-point • • • •1 auxiliary switch adjustable, floating • •Manual override temporary • • • •
permanent • • • •Connection cable 1m • • • •
integrated screw terminals • • • •
Other versions and spring return actuators available on request
6
Ordering
Ordering example:
Technical data: Page 8
Designation: R225P-098+NR24-SR/Z
➀ Valve type:
Design 2-way pressure-independent control valveSize internal thread BSP 1”, DN 25Flow volume V = 0.98 l /s
➁ Assembling actuator fitted
➂ Actuator:
Nominal voltage rotary actuator AC/DC 24 VControl type modulatingRunning time 140 s
➃ Pipe connectors (option): 2 x ZR2325 separately (for prices, see current price list)
➀ ➁ ➂ ➃
2-way
LR rotary actuatorX NR rotary actuator
Actuator fittedX Supplied separately
➀ Valve
➁ Assembling
➂ Actuator types
The short price list is arranged as follows:
• 2-way pressure-independent controlvalve(for 2-way/3-way characterized controlvalves, see current price list)
The following data must be provided:
• Control modulating or 3-point• Nominal voltage AC / DC 24 V,
AC 24 V or AC 230 V
➃ Pipe connectorsseparately (option)
The valves and actuators can be suppliedas follows:
• Actuator fitted (+)• Valve/actuator separately ( / )• Separately at different times (on
request)
+
Separately
The pressure-independent control valvesare available as low-cost fittings with internal thread.
• As an option, the types R2..P areavailable with individual pipe connec-tors supplied separately ( /Z).
/Z
Valve
The range includes the pressure-indepen-dent control valve as well as the characte-rized control valve and the open/closedball valve. Sizes: DN15 to 50mm.
Actuator types
For motorizing valves, there are two ratingclasses of actuators available that are sui-table for different power supplies andmethods of control.
Other versions and spring return actuatorsavailable on request.
Assembling
The prices quoted are per subassembly(valve and actuator).
A successful order willl need the followinginformation:
NEW: available as an option with indivi-dual pipe connectors supplied separa-tely.
BC
7
8
Data
Medium cold and pump water, water with50% volume of glycol
Temp. of medium +5°C…100°C, lower temp. on requestRated pressure 4140 kPa (R215P…R232P) / 2760 kPa (R240P…R250P)Flow characteristic equal percentage (following VDE 2173)Rangeability DN 15 Sv > 50
DN 20…50 Sv > 100Leakage rate air-bubble-tightPipe connector internal thread acc. to ISO 7/1Differential pressure 30…350 kPaClosing pressure ∆ps 1400 kPaAngle of rotation 90°Installation position standing to lying (in relation to the stem)Maintenance maintenance-freeMaterialFitting nickel-plated, hot-pressed brassBall chrom-plated brassSeal PTFEStem chrom-plated brassStem seal EPDM O-ringCharacterizing disk TEFZELValve cone stainless steelCage Delrin 500 AFDiaphragm polyester-reinforced siliconeSpring for valve cone stainless steel
Applications· Water-side control of air handling appa-
ratus in ventilation and air-conditioningplants
· Water-side control in heating plants
Mode of operationThe pressure-independent control valve ismotor-operated by a type LR or NR rotaryactuator. The actuators are controlled by astandard modulating or 3-point controlsystem and move the ball of the pressure-independent control valve, the throttlingelement, to the opening position dictatedby the control signal.
Product features
Equal-percentage characteristic of theflow ensured by the integrated characteri-zing disk.
Constant flow volume V with a differentialpressure of 30...350 kPa, thanks to theintegrated pressure-reducing valve. A valveauthority of 1 is attained, regardless of thedifferential pressure before and after thevalve.Even in the part-load range, the flow rateremains constant with each openingposition (angle of rotation) and ensures asteady control.
Manual operation by lever after disenga-ging the gearing latch on the type LR... orNR... rotary actuator.
The pressure-independent control valveR2... P is ordered together with the corre-sponding rotary actuator LR... or NR...
Ordering examples: (with NR24-SR)
a) R240P-252 with NR24-SR – rotary actuator fitted– order code: R240P-252+NR24-SR
b) R240P-252 with NR24-SR– rotary actuator supplied separately– order code: R240P-252/NR24-SR
2-way pressure-inde-pendent control valveDN 15...50
For the modulatingcontrol of cold and hotwater
Equal-percentage characteristic
Selection R2...P pressure-independent control valve
Technical data R2...P pressure-independent control valve
V[l /s]
DN
[mm] [inches]Type
Suitable rotary actuatormodulating DC 0…10V
Suitable rotaryactuator 3-point
151520202525323240405050
R215P-009R215P-036R220P-036R220P-066R225P-057R225P-098R232P-101R232P-151R240P-157R240P-252R250P-252R250P-378
0.090.360.360.660.570.981.011.511.572.522.523.78
1⁄2”1⁄2”3⁄4”3⁄4”1”1”
11⁄4”11⁄4”11⁄2”11⁄2”2”2”
LR24-SR(AC/DC 24V)
Emergency control function (rotary actuators with spring) on request
NR24-3(-S)(AC 24V)
NR230-3(-S)(AC 230 V)
NR(Y)24-SR(AC/DC 24V)
9
Dimensions
A
B
C
D
Dimensions Max. threadDN [mm] G Thread screwing depth
[mm] [inches] A B C D E [kg] Rp [mm]15 1⁄2” 122 116 101 58 57 0.4 1⁄2” 1320 3⁄4” 134 128 106 59 57 0.4 3⁄4” 1325 1” 179 179 122 75 82 0.65 1” 1732 1 1⁄4” 179 179 122 75 82 0.65 1 1⁄4” 1940 1 1⁄2” 204 204 144 93 78 0.75 1 1⁄2” 1950 2” 216 216 150 93 78 0.95 2” 22
E
Sizes R2...P pressure-independent control valve
10
Installation and dimensions with rotary actuators LR…
LR... rotary actuators
The compact LR... rotary actuator is speci-ally designed for the motorization needs ofpressure-independent control valves up toDN 32. In particular, it has the followingadvantageous characteristics:
• Modulating control • Temporary disengagement allows
manual operation• Central fixing bolt for simple mounting• Clear indication of position• Installation possible in 4 positions• Low space requirements due to
compact dimensions• 1 m long, pre-fitted connecting lead
The pressure-independent control valve R2…Pwith LR... rotary actuator
A-AB=100%
AB
A
4x90°
CCW
10
CCW
A
Installation of R2...P and rotary actuator LR...
Dimensions of complete actuator set R2...P and LR...
664018 min. 70
134
H83
59
min
. 200
42
LR...
Rp
EA
F
B
C
DimensionsDN Thread [mm]
[mm] [inches] Rp A B C E F H15 1⁄2” 1⁄2” 122 116 101 57 41 4520 3⁄4” 3⁄4” 134 128 106 57 48 4825 1” 1” 179 179 122 82 63 4832 1 1⁄4” 1 1⁄4” 179 179 122 82 63 48
11
Installation and dimensions with rotary actuators NR…
NR... rotary actuators
The powerful NR... rotary actuator is suitable for the reliable motorization ofpressure-independent control valves up toDN 50. It offers the following applicationadvantages:
• Modulating or 3-point control• Temporary and permanent dis-
engagement allows manual operation• Central fixing bolt for simple mounting• Clear indication of position• Installation possible in 4 positions• Low space requirements due to com-
pact dimensions• 1 m long, pre-fitted connecting lead• If desired, with auxiliary switch,
adjustable, floating
A-AB=100%
AB
A
CCW
10
CCW
A
Installation of R2...P and rotary actuator NR...
Dimensions of complete actuator set R2...P and NR...
80
3393
H
114.
5
min
. 250NR...
42
min. 70
Rp
EA
F
B
C
DimensionsDN Thread [mm]
[mm] [inches] Rp A B C E F H
15 1⁄2” 1⁄2” 122 116 101 57 41 4520 3⁄4” 3⁄4” 134 128 106 57 48 4825 1” 1” 179 179 122 82 63 4832 1 1⁄4” 1 1⁄4” 179 179 122 82 63 4840 1 1⁄2” 1 1⁄2” 204 204 144 78 65 5150 2” 2” 216 216 150 78 69 57
The pressure-independent control valve R2…Pwith NR... rotary actuator
EN
G –
03.
04 –
pd
f .
KS
. S
ubje
ct t
o te
chni
cal m
odifi
catio
ns
Belimo is represented in over 60 countries throughout the world.Visit our website www.belimo.ch for the addresses.
Air applications Water applications
Innovation, Quality and Consultancy:A partnership for motorizing HVAC actuators
Standard actuators andspring-return actuatorsfor air control dampersin HVAC systems
Safety actuators formotorizing fire andsmoke extractiondampers
VAV systems for indivi-dual room air control
Mixing actuators andmotorized ball valves forHVAC water circuits
Globe valves and intel-ligent linear actuators –also for leading makesof valve
top related