Q: Does Partial Height Containment Work?

A: Yes.

Partial Height Containment Architecture

POLARGY WE KEEP THE CLOUD COOLTM

Partial Height CFD Analysis

BASE LINE 562 kW of heat load

164 racks

Slab floor

CRAH Galleries

18” Rack Top Baffles

POLARGY WE KEEP THE CLOUD COOLTM

CFD Test #1 No containment

RESULTS Hot spots

Recirculation over cabinets

16 non-compliant cabinets

Inlet temps > 89.6°F

POLARGY WE KEEP THE CLOUD COOLTM

CFD Test #2 Rack Top Baffles & No Doors

RESULTS

18” Rack Top Baffles

Significant improvement

Non-compliant cabinets reduced from 16 to 2

POLARGY WE KEEP THE CLOUD COOLTM

RESULTS

18” Rack Top Baffles

Aisle End Doors

100% compliance

CFD Test #3 Rack Top Baffles with Doors

POLARGY WE KEEP THE CLOUD COOLTM

CFD Conclusions

•  Partial height containment eliminated recirculation in the CFD modeling.

•  Today, the room is operating within the Service Level Agreement terms with no cabinets out of compliance.

Site’s Data Center Manager, “Just a side note - the baffles work great.”