np-series - valve regulated lead acid battery€¦ · the battery shop uk ltd unit 20 orbit centre...

Post on 19-Aug-2020

2 Views

Category:

Documents

0 Downloads

Preview:

Click to see full reader

TRANSCRIPT

NP7-12

Nominal voltage 12 V20-hr rate Capacity to 1.75VPC at 20°C 7 Ah10-hr rate Capacity to 1.75VPC at 20°C 6.4 Ah

Length 151 (±1) mmWidth 65 (±1) mmHeight mm(height over terminals) 97.5 (±2) mmMass (typical) 2.65 kg

FASTON (Quickfit / release) 4.75 mm

Storage ChargeDischarge LAYOUT

Capacity loss per month at 20°C (approx) 3 %

Standard OptionFlame retardant option (FR)

13.65 (±1%) V2.275 (±1%) V/cell

Float Charge voltage temperature correction factor (for variations from the standard 20°C)

-3 mV/cell/°C

14.5 (±3%) V2.42 (±3%) V/cell

Cyclic Charge voltage temperature correction factor (for variations from the standard 20°C)

-4 mV/cell/°C

Float charge current limit No limit ACyclic (or Boost) charge current limit 1.75 A

1 second 210 A1 minute 48 A

3RD PARTY CERTIFICATIONSInternal resistance N/A mΩ ISO 9001 - Quality Management SystemsShort-Circuit current N/A A ISO 14001 - Environmental Management Systems

EN 18001 - OHSAS Management SystemsMeasured at 1 kHz 45 mΩ UNDERWRITERS LABORATORIES Inc.

VdS (Germany) - VdS No: G189099Refer to the technical manual NP

STANDARDSEUROBAT Classification: Standard Commercial 3 to 5 years IEC61056

Yuasa design life @ 20°C up to 5 years

ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICEIssue No.: V.2 / Issue Date: March 2011

NP-Series - Valve Regulated Lead Acid Battery

-20°C to +60°C

ABS (UL.94:HB)ABS (UL94:V0)

SPECIFICATIONS

DIMENSIONS

TERMINAL TYPE

OPERATING TEMPERATURE RANGE

STORAGE

CASE MATERIAL

CHARGE VOLTAGE

-20°C to +60°C-15°C to +50°C

SAFETY

Float charge voltage at 20°C

Cyclic (or Boost) charge at 20°C

CHARGE CURRENT

MAXIMUM DISCHARGE CURRENT

InstallationCan be installed and operated in any orientation except permanently invertedHandles

SHORT-CIRCUIT CURRENT & INTERNAL RESISTANCE(according to EN IEC 60896-21)

IMPEDANCE

DESIGN LIFE

PERFORMANCE & CHARACTERISTICS

VRLA Batteries release hydrogen gas which can form explosive mixtures in air. Do not place inside a sealed container

The Battery Shop UK Ltd Unit 20 Orbit Centre Ashworth Road Swindon SN5 7YG 01793 421509 www.thebatteryshop.co.uk

RecyclingYUASA's VRLA batteries must be recycled at the end of life in accordance with local and national laws and regulations

Batteries must not be suspended by their handles (where fitted)Vent valvesEach cell is fitted with a low pressure release valve to allow gasses to escape and then reseal.Gas Release