FD-1
FD
FD
TD
HD
FD
HD
HD
HD
HD
HD
FD
HD
TD-1
HD
HD
HD
HD
HD
HD
HD
HD
HD
FD
FD
20 UP TO TRAPPRIMERS
EXISTING STORM SEWER
TO REMAIN.
REMOVE INSULATED & HEAT TRACED LINE
EXISTING 4"
EXISTING 8"SANITARY LINE
REMOVE PVC LINE ANDINSULATED SERVINGVENTED FLOOR.
EXISTING 4"
EXISTING STUB UP LINE
FOR PRODUCE MISTING.
EXISTING 6"
PRODUCE MISTING LINE
TO BE REMOVED ORABANDONED (TYPICAL)
EXISTING 4"REFRIGERATION LINE
TO BE REMOVED ORABANDONED(TYPICAL)
PRODUCE MISTING LINETO BE REMOVED OR
ABANDONED (TYPICAL)
REFRIGERATION LINE
TO BE REMOVED ORABANDONED(TYPICAL)
REFRIGERATION LINE
TO BE REMOVED ORABANDONED(TYPICAL)
REFRIGERATION LINE
TO BE REMOVED ORABANDONED(TYPICAL)
REFRIGERATION LINETO BE REMOVED OR
ABANDONED(TYPICAL)
REFRIGERATION LINE
TO BE REMOVED ORABANDONED(TYPICAL)
EXISTING STORMSYSTEM TO REMAIN
REFRIGERATION LINETO BE REMOVED OR
ABANDONED(TYPICAL)
EXISTING 3"
HD
HD
HD
HD
2-54 Adelaide Street Winnipeg Manit aob R3A 0V7
P 204 947 3775 F 204 947 3789 www.nejmark.mb.ca
N E J M A R KA R C H I T E C T
PROJECT TITLE:
SHEET TITLE:
COMMISSION NUMBER: SHEET NUMBER:
SOBEYS VARSITY COMMONS
1550- 8 St. E, SASKATOON,
SASKATCHEWAN
Drawings and specifications, as instruments of service are the property of the architect, the
copyright in the same being reserved to them. No reproduction may be made without the
permission of the architects, and when made, must bear their names. All prints to be returned.
The contractor is to verify dimensions and date noted herein with conditions on the site and is
held responsible for reporting discrepancy to the architects for adjustment.
DRAWN BY:
PRINTING DATE:
STAMP
No. ISSUED FOR DATE BY
1607
PSG2016.03.09
PERMIT AND TENDER1
JA
2016.03.09
2-472 STRADBROOK AVENUE
W I N N I P E G , M B R 3 L 0 J 9
( 2 0 4 ) 2 7 2 - 3 2 5 5
J O B :
FOUNDATION PLAN -
DEMOLITION
M1.1
SCALE:M1.1N
FOUNDATION PLAN - PLUMBING DEMOLITION1/8"=1'-0"
1
GENERAL NOTES - FOUNDATIONPLAN DEMOLITION
1. MECHANICAL DESIGN IS BASED ON INFORMATION AVAILABLE FROMRECORD DRAWINGS AND PRELIMINARY SITE VISIT. EXACT
LOCATIONS OF DRAINS AND ROUTING OF PIPING TO BE CONFIRMEDON SITE. MODIFY SYSTEM DESIGN AS REQUIRED TO SUIT SITE
CONDITIONS.
2. GENERAL CONTRACTOR TO REMOVE GREASE INTERCEPTORS SHOWNTO BE DEMOLISHED AND REPAIR FLOOR PENETRATIONS.
COORDINATE WITH STRUCTURAL.
3. MECHANICAL CONTRACTOR SHALL REMOVE OR ABANDON IN PLACEALL PIPING AND EQUIPMENT SHOWN AS DASHED. REFER TO
ARCHITECTURAL, ELECTRICAL, AND STRUCTURAL DRAWINGS FORCOORDINATION PURPOSES.
4. ABANDONED PIPING SHALL BE PLUGGED WITH CONCRETE AND
CAPPED BELOW GRADE.
5. REUSE EXISTING PIPES WHERE POSSIBLE. VIDEO SCOPE ALL EXISTINGPIPING PROPOSED FOR REUSE.
PLUMBING LEGENDDEMOLISHED SANITARY
EXISTING SANITARY
GREASE INTERCEPTOR TO BEREMOVED
CLEANOUT
DRAWING NOTE#
8'
HUSSMANN
ZEP
WIL
L CA
LLCA
BINE
T (N
)
DIGITAL T
V
(2) A
GED
MEA
TDI
SPLA
Y(D
ETAI
LS T
.B.C
.)
TD
HD
HD
HD
FDC
TD-2
10
FDA
FDA
FDA
HDHD
U470 2
HD
HD
HD
HD
W825
TD-2
W825
TD-1
BWV
4"
Q470 2
S470 2
HD
4"
FDB
W804
HD
HD
HD
HD
HD
HDHD
HD
HD
HD
HD
HD
HD
HD
HD
HD
HD
HD
TD-1
GI-2
CHD
B470
W825
2
7
HD
HD
HD
HD
HD
HD
TD-1
TD-1
W825 7
GI-2
H4702
HD
SI-1
M470 2FDB
W804
BWV
M470 2
GI-1
GI-1
GI-1
HD
W825TD-1
BWV
HD
HD
HD
HD
2"
HD
HD
HD
HDHD
X4702
GI-1
FDA
BWV
HD
TD-1
TD-1
3"
BWV
CHD
FDA
BWV
FDB
HD
CHD
CHD
CHD
HD
CHD
HD
HD
HD
HD
2"
BWV
BWV
BWV
FDA
HD
1
3
3
4
5
6
7
7
W8257
GI-1
FDA
3"
3"
2"
4"4"4"
3"
EXISTING
EXISTINGEXISTING
EXISTING
4"
4"
4"
4"4"
4"
4"
4"
4"
4"
4"
3"
3"
4"
4"
4"4"
2"
4"
4"
4" 3"
HD
HD
HD
HD
HD
HD
HD
NO. 12
REF PIT
NO. 11
REF PIT
2"
4"
4"4"
4"
2"
3"
4"
4"
HD
BWV
TD-2
4"
GI-2
4"
FDA
BWV
FDA
4"
BWV
4"
4"
4"
4"
EXISTING CATCH BASINRIM ELEV. = 1200mm B.F.F.
S.E. INV. = 2720mm B.F.F.BWV
CHD
BWV
NO. 02
REF. PIT
NO. 01
REF. PIT
EXISTING STORM SEWER
TO REMAIN.
W804
4"
4"
4"
4"
4"
4"
4"
4"
4"
EXISTING 3"
W825 7
NO. 04
REF. PIT
NO. 08
REF. PITNO. 07
REF. PIT
NO. 06
REF. PITFDA
EXISTING 4"
EXISTING 6"
EXISTING 6"
EXISTING 6"
EXISTING 8"SANITARY LINE
EXISTING 4"
EXISTING 4"
EXISTING 4"
EXISTING 4"
4"
NO. 14
REF. PIT
NO. 13
REF. PIT
HD
4"
EXISTING 6"
BWV
FDA
BWV
EXISTING 4"
EXISTING 4"
BWV
EXISTING 4"
NO. 15
REF. PIT
NO. 16
REF. PIT
NO. 21
REF PIT
NO. 22
REF PIT
NO. 23
REF PIT
P470 2
EXISTING 4"
2"
4"
4"
W825 7
2"
NO. 05
REF. PIT
W825
W825
6"
4"Ø
6"
3"
STSTST
FDA
BWV
W825 7
BWV
TD-1
BWV
W825 7
W825 7
TD-1
HD
ST
8
8
11
HD
HD
HD
HD
HD
4"
4" @ 1:100
4" @ 1:100
3"
3"
4" @ 1:100
4" @ 1:100
3"
NO. 03
REF. PIT
HD
HD
HD
HD
HD
4"
4"
4"
NO. 09
REF. PIT
NO. 10
REF. PIT
NO. 17
REF PIT
NO. 18
REF PIT
NO. 19
REF PIT
NO. 20
REF PIT
6"
6"
6"
6"
6"
6"
6"
6"
6" 6"
6"
6"
3"
EW-1
2-54 Adelaide Street Winnipeg Manit aob R3A 0V7
P 204 947 3775 F 204 947 3789 www.nejmark.mb.ca
N E J M A R KA R C H I T E C T
PROJECT TITLE:
SHEET TITLE:
COMMISSION NUMBER: SHEET NUMBER:
SOBEYS VARSITY COMMONS
1550- 8 St. E, SASKATOON,
SASKATCHEWAN
Drawings and specifications, as instruments of service are the property of the architect, the
copyright in the same being reserved to them. No reproduction may be made without the
permission of the architects, and when made, must bear their names. All prints to be returned.
The contractor is to verify dimensions and date noted herein with conditions on the site and is
held responsible for reporting discrepancy to the architects for adjustment.
DRAWN BY:
PRINTING DATE:
STAMP
No. ISSUED FOR DATE BY
1607
PSG2016.03.09
PERMIT AND TENDER1
JA
2016.03.09
2-472 STRADBROOK AVENUE
W I N N I P E G , M B R 3 L 0 J 9
( 2 0 4 ) 2 7 2 - 3 2 5 5
J O B :
FOUNDATION PLAN -
PLUMBING RENOVATION
M1.2
DRAWINGS NOTES - FOUNDATION
PLAN PLUMBING RENOVATION
CONFIRM EXACT LOCATION AND INVERT ON SITE AND WITH
OUTSIDE SERVICES CONTRACTOR. REFER TO CIVIL DRAWINGS FOR
CONTINUATION.
TIE INTERCEPTOR VENTING INTO SANITARY VENT SYSTEM AS PER
MANUFACTURER'S WRITTEN INSTRUCTIONS. 4" INLET AND OUTLET
CONNECTIONS TO INTERCEPTOR.
EXISTING SANITARY SERVING MEZZANINE FLOOR DRAINS DOWN TO
LOW LEVEL.
EXISTING SANITARY DRAIN FROM MEZZANINE FIXTURES DOWN TO
LOW LEVEL WITHIN WALL.
PROVIDE TWO HUB DRAINS FOR CHICKEN ROTISSERIE, OVER FLOW
DRAIN SHALL CONNECT TO THE GREASE INTERCEPTOR AND AUTO
CLEAN DRAIN SHALL CONNECT DIRECTLY TO THE SANITARY SEWER.
EXTEND SANITARY LINE FOR EVAPORATOR CONDENSATE DOWN
WITHIN WALL.
COORDINATE EXACT LOCATION OF TRENCH DRAIN WITH COOLER
SHOP DRAWINGS.
EXTEND 34" PEX-A DCW, 3 4" PEX-A DHW, 34" PEX-A DHWR WITHIN PVCSLEEVE BENEATH SLAB.
12" PEX-A DCW AND 12" PEX-A DHW AND 3 4" PEX-A DHWR WITHIN PVCSLEEVE BENEATH SLAB.
EXTEND 3
4" DCW, DHW, DHWR LINES AND GAS LINE DOWN WITHINWALL. EXTEND PEX-A PIPING WITHIN PVC SLEEVE BELOW SLAB TO
SINK AND DISHWASHER. EXTEND FLEXIBLE GAS TUBING WITHIN PVC
SLEEVE TO GAS RANGE.
PVC SLEEVE TO RISE C/W LONG RADIUS ELBOWS. EXTEND 12" DCW, 12"
DHW AND 3 4" DHWR PEX-A LINES WITHIN SLEEVE TO SERVE SINK.
1
2
3
4
5
6
7
8
9
10
11
GENERAL NOTES - PLUMBING
1. CONTRACTOR SHALL BE FAMILIAR WITH, REFER TO, AND COMPLY WITH ALLLOCAL CODES. ALL MECHANICAL WORK SHALL COMPLY IN EVERY RESPECT
WITH THE LATEST EDITIONS OF THE NATIONAL, PROVINCIAL AND MUNICIPAL
BUILDING CODES, NFPA, ASHRAE, SMACNA, AND ANY ADDITIONALREQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION.
2. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHALL NOT BE SCALED. THEY
ESTABLISH DESIGN INTENT AND ARE NOT INTENDED TO BE DETAILED
INSTALLATION DOCUMENTS. MECHANICAL CONTRACTOR SHALL ALLOW IN
THEIR CONTRACT PRICE ALL COMPONENTS REQUIRED TO PROVIDE ACOMPLETE AND FUNCTIONAL MECHANICAL INSTALLATION.
3. ANY OMISSIONS OR DISCREPANCIES IN THE DRAWINGS SHALL BE BROUGHT
TO THE IMMEDIATE ATTENTION OF THE CONSULTANT FOR CLARIFICATION.
COMPENSATION FOR ADDITIONS TO THE CONTRACT AFTER BID CLOSING
WILL BE REJECTED.
4. JOB SITE SHALL BE INSPECTED PRIOR TO COMMENCEMENT OF WORK ANDAPPROPRIATE PROVISIONS MADE FOR ALL SITE CONDITIONS. EXACT
PLACEMENT OF MECHANICAL EQUIPMENT AND SIZING/ROUTING OF
MECHANICAL SYSTEMS SHALL BE SITE CONFIRMED AND COORDINATED WITHTHE ARCHITECTURAL, ELECTRICAL, AND STRUCTURAL DRAWINGS AND
TRADES. REROUTE/RESIZE PIPING AND RELOCATE EQUIPMENT AND
COMPONENTS AS REQUIRED.
5. ALLOW FOR ANY MODIFICATIONS OR REBALANCING OF EXISTING SYSTEMS
AND COMPONENTS AS REQUIRED TO COMPLETE RENOVATION WORK.
6. CAREFULLY EXAMINE THE DRAWINGS OF OTHER TRADES. COORDINATE THEELECTRICAL REQUIREMENTS OF ALL MECHANICAL EQUIPMENT WITH THE
ELECTRICAL CONTRACTOR. AN APPROVED FIRE STOP SYSTEM SHALL BE
APPLIED AT ALL PENETRATIONS OF WALLS OR FLOORS DENOTED TO BE FIRESEPARATIONS ON THE ARCHITECTURAL DRAWINGS. REFER TO
ARCHITECTURAL ELEVATIONS FOR MOUNTING HEIGHTS OF FIXTURES.
7. A MEANS OF BALANCING EACH BRANCH OF HYDRONIC SYSTEMS AND
COMPONENT SHALL BE PROVIDED. ISOLATION VALVES SHALL BE PROVIDED AS
REQUIRED TO SERVICE OR REPLACE EACH PIECE OR GROUP OF EQUIPMENT.
8. ACCESS DOORS SHALL BE PROVIDED AS REQUIRED TO SERVICE VALVES ANDMECHANICAL EQUIPMENT.
9. ALL PIPING AND EQUIPMENT SHALL BE INSULATED TO THE REQUIREMENTS OF
THE LATEST EDITION OF ASHRAE 90.1 AND FOR NEW CONSTRUCTION, TO
THE REQUIREMENTS OF THE NATIONAL ENERGY CODE OF CANADA. ALL VENT
PIPES WITHIN 10' (3M) OF THERMAL ENVELOPE PENETRATION SHALL BETHERMALLY INSULATED.
10. ALL CUTTING AND/OR PATCHING OF ROOFS, WALLS OR FLOORS SHALL BE BY
THE GENERAL CONTRACTOR UNLESS SPECIFICALLY INDICATED OTHERWISE.
11. ALL DRAIN STUB UPS WITHIN CURB ADJACENT COOLER/FREZZERS TO BE AT 2"
A.F.F. UNLESS OTHERWISE NOTED.
12. ALL DRAINS TO BE INDIVIDUALLY TRAPPED UNLESS SHOWN OTHERWISE. ALL
TRAPS TO BE PRIMED OR EQUIPPED WITH WADE TRAP GUARDS EXCEPT FORDRAINS THAT ARE EXPECTED TO REGULARLY RECEIVE CONDENSATE.
13. ALL TRENCH DRAINS TO HAVE HEAVY DUTY GRATES (GRATE TYPES VARY).
REFER TO SCHEDULES.
14. ALL GREASE INTERCEPTORS TO BE RECESSED IN SLAB, WITH COVERS INSTALLED
FLUSH WITH FINISHED FLOOR.
15. EXACT LOCATIONS AND QUANTITY OF FLOOR DRAINS, HUB DRAINS
(INCLUDING PIPES THROUGH FLOOR) AND TRANSIT PITS TO BE CONFIRMEDBY SOBEYS REFRIGERATION CONTRACTOR PRIOR TO INSTALLATION.
16. ALL HUB DRAINS (PIPES THROUGH FLOOR) THAT ARE NOT USED ARE TO
CAPPED.
17. CAREFULLY EXAMINE ALL DRAWINGS OF OTHER TRADES. COORDINATE THE
EXACT SIZES, LOCATIONS AND INVERTS OF ALL SEWERS WITH CIVILDRAWINGS AND ON SITE.
18. ALL DRAINAGE SYSTEMS AND TRAPS SHALL BE VENTED. ALL VENTING SHALL BE
INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL,
PROVINCIAL AND MUNICIPAL BUILDING CODES AND ANY ADDITIONALREQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION. SYSTEM
SHALL BE INSTALLED SUCH THAT ABOVE-GRADE VENTS ARE LOCATED IN
INCONSPICUOUS LOCATIONS WHERE POSSIBLE.
19. DWV PIPING AND ELECTRICAL/CONTROL WIRING INSTALLED WITHIN H.V.A.C.
PLENUMS SHALL HAVE A FLAME SPREAD RATING NOT EXCEEDING 25 AND ASMOKE DEVELOPED RATING NOT EXCEEDING 50 WHEN TESTED IN
ACCORDANCE WITH ASTM E84 (UL 723).
20. PROVIDE DIELECTRIC COUPLINGS WHERE COMPONENTS OF DISSIMILAR METAL
ARE JOINED.
21. ENSURE THAT ALL TRAPS SERVING FLOOR DRAINS ARE PRIMED OR FITTED
WITH WADE TRAPS GUARDS.
22. PROVIDE AUTOMATIC AIR VENTS AT ALL HIGH POINTS OF THE SYSTEM.
23. GAS PIPING SHALL BE BLACK STEEL TO ASTM A-53 SCHEDULE 40, 150 LB.
STANDARD BLACK MALLEABLE IRON SCREW FITTING FOR SIZES BELOW 212".
ALL MATERIALS AND INSTALLATION SHALL CONFIRM TO ALL REQUIREMENTS
OF THE LATEST EDITION OF CSA B149.1 NATURAL GAS AND PROPANE
INSTALLATION CODE AND ALL LOCAL GAS NOTICES.
PLUMBING LEGENDSANITARY BELOW GRADE
STORM BELOW GRADE
PLUMBING VENT
PVC SLEEVE BELOW GRADE
GREASE INTERCEPTORS
SOLIDS INTERCEPTOR
TRANSIT PIT
BACK WATER VALVE
TRENCH DRAIN
CLEANOUT
FLOOR DRAIN
HUB DRAIN
FUNNEL FLOOR DRAIN
REFRIGERATION PIT TAG
EQUIPMENT TAG
DRAWING NOTE
ST
BWV
HD
FFD
REF. PIT
NO. ##
#
EQP
#
SCALE:M1.2N
FOUNDATION PLAN - PLUMBING RENOVATION1/8"=1'-0"
1
8'
HUSSMANN
ZEP
WIL
L CA
LLCA
BINE
T (N
)
DIGITAL T
V
(2) A
GED
MEA
TDI
SPLA
Y(D
ETAI
LS T
.B.C
.)
15'-4 5/8"
3'-3 1/8"
9'-7 1
/8"
3'-3 1/8"
11'-4 5
/8"
16'-7 1
/8"
12'-2 1/4"
4'-9 3
/8"
14'-8"
12'-11 3/8"
4'-9 1
/4"
3'-0 1
/2"
19'-11 3
/8"
5'-6 5/8"
0"
9'-4 5/8"
4'-11 3/4"
2'-3 1
/2"
1'-8 1/2"
13'-9 1
/8"
10'-9 7/8"
12'-10 1/4"
14'-10 3
/4"
4'-4"
4'-1 1/4"
10'-7 1
/8"
13'-6 5/8"
11'-1 1
/8"
9'-7 3/8"
10'-7 3
/4"
15'-6 1/4"
1'-10 5
/8"
9'-2"
2'-9 1
/2"
4'-6 7
/8"
21'-5 1/8"
21'-5 1/8"
15'-3 3
/8"
6'-11 3/8"
13'-1 3
/4"
1'-8 3
/4"
2'-9 5/8"
6'-5"
7'-10 1
/4"
9'-10"
12'-4 1
/4"
8'-9 3/4"5'-1 5
/8"
11'-9"
7'-8 5
/8"
21'-1 1/4"
14'-4"
10'-1 3/8"
7'-3 5
/8"
4'-8 1/8"
14'-8 1
/4"
14'-8 1
/4"
7'-0 5/8"
5'-0 3
/8"
22'-10 1/8"
3'-3 1/8"
14'-2 1
/8"
14'-2 7/8"
13'-1 7
/8"
13'-6"
3'-3 1/8"
14'-9 7
/8"
12'-8 7
/8"
17'-11 3/4"
5'-3 5/8"
13'-1 7
/8"
8'-8 1/8"
3'-2 5
/8"
4'-4 5
/8"
1'-1 1/8"
10'-3 1
/8"
22'-7 1/4"
8'-6 7
/8"
16'-8 3/4"8"
10'-7 5
/8"
11'-8 7/8"
4'-9 1
/4"
21'-1"
11 7
/8"
22'-2 5/8"
5'-7"
18'-4 1/2"
1'-0 7
/8"
25'-10 5
/8"
7'-7 1/4"4'-11"
11'-7 1
/8"
8'-2 3/8"
9 7
/8"
15'
18'
25'-0 1/4"
9'-0 5/8"
6'-9 7
/8"
7 1
/4"
7'-8 1/8"
9'-3 3/8"
7'-5 5
/8"
9'-0 5/8"
10'-4 3
/8"
15'-3"
22'-1 1/4"
9'
15'-7"
17'-8 3/8"
3 5
/8"
8'-8 3/8"
6 5
/8"
2 1
/2"
14'-3 1/8"
27'-1"
4'-2 1
/4"
2'-0 1/4"
12'-0 3
/8"5
'-3 1
/4"
16'-2 3/4"
8'-7"
11'-4 3
/8"
2'-10 3
/4"
1'-10 3/8"
11'-7"
7'-0 1
/8"
9'-5 1
/8"
5'-9 1/8"
9'-6 3
/8"
9'-5 5/8"
17'-1"
4'-7 5/8"
5'-7 3
/8"
3'-0 7/8"
13'-9 5/8"8'-7 1
/4"
4'-6 3/4"
3'-3 1
/8"
2'-8 1
/4"
14'-6"
6'-1 7
/8"
16'-11 7/8"
NO. 12
REF PIT
NO. 11
REF PIT
13'-8 3/4"
7'-6 7
/8"
8'-4 5/8"
2'-3 3
/8"
5'-9 1
/2"
22'-5 1/4"
15'-9 3/8"6'-8 1
/2"
NO. 02
REF. PIT
NO. 01
REF. PIT
6'-5"
13'-3"
2'-4 5
/8"
12'-3 5
/8"
10'-8 5
/8"
9'-5 1/2"
NO. 04
REF. PIT
NO. 08
REF. PITNO. 07
REF. PIT
NO. 06
REF. PIT
NO. 14
REF. PIT
NO. 13
REF. PIT
2'-7 7
/8"
1'-4 3/8"
NO. 15
REF. PIT
NO. 16
REF. PIT
NO. 21
REF PIT
NO. 22
REF PIT
NO. 23
REF PIT
NO. 05
REF. PIT
26'-8 3/4"
9'-0 1
/4"
6 1/8"
2'-9 3
/4"
5'-1 3
/8"
22'-11 5/8"
20'-9 1/2"
5'-1 3
/8"
11'-4 5
/8"
13'-5 1/8"
3'-5 1/2"
2'-6"5'-5"
5 1/4"
5'-4 7/8"
6'-8 7
/8"
11'-4"
11'-8 3/4"
9'-1 1/4"
9'-6 3
/8"
7'-2 7
/8"
8 1/8"
2'-7 7
/8"
4 1/8"
22'-1 3/8"8'-10"
8'-2 5
/8"
3'-5 1/4"
13'-10 3
/8"
16'
9'-4"
14'-9 5/8"
8'-4 1/8"
8'-3 5
/8"
1'-9 1
/2"
3 7/8"
20'-7 3/4"
5'-1 1/4"
3 1/8"
3'-10"
3'-8 3
/4"
13'-8 3/8"
NO. 03
REF. PIT
NO. 09
REF. PIT
NO. 10
REF. PIT
NO. 17
REF PIT
NO. 18
REF PIT
NO. 19
REF PIT
NO. 20
REF PIT
3'-8 1
/8"
7 5/8"
15'-6 1/8"
12'-10 1
/2"
1'-6 3
/8"
11'-6 7/8"11'-6 7/8"
4'-8 1
/4"
9'-11 1/8"
9'-11 1/8"
8'-9 3/4"
12'-6 1
/2"
7'-2 1/8"
9'-7 7
/8"
3'-6 5
/8"
15'-9 1/2"
4'-9 1
/8"
25'-1"
10'-9 7/8"4'-9 1
/8"
11'-3"
6'-3 3
/8"
14'-3 5/8"
18'-6 7/8"
14'-7 7
/8"
14'-3 5/8"
8'-10 3
/4"
5'-8 1/2"
1'-3 3
/8"
2'-2 7/8"
3'-7 3
/4"
4'-7 3/4"
11 1
/8"
2'-8 7/8"
7'-8 3
/4"
10'-0 3
/8" 18'-5 5/8"
14'-2 1/8"
15'-3 3
/8"
16'-1 7/8"
11'-11 5/8"
13'-0 7
/8"
15'-7 1
/4"
18'-4 1/4"
2-54 Adelaide Street Winnipeg Manit aob R3A 0V7
P 204 947 3775 F 204 947 3789 www.nejmark.mb.ca
N E J M A R KA R C H I T E C T
PROJECT TITLE:
SHEET TITLE:
COMMISSION NUMBER: SHEET NUMBER:
SOBEYS VARSITY COMMONS
1550- 8 St. E, SASKATOON,
SASKATCHEWAN
Drawings and specifications, as instruments of service are the property of the architect, the
copyright in the same being reserved to them. No reproduction may be made without the
permission of the architects, and when made, must bear their names. All prints to be returned.
The contractor is to verify dimensions and date noted herein with conditions on the site and is
held responsible for reporting discrepancy to the architects for adjustment.
DRAWN BY:
PRINTING DATE:
STAMP
No. ISSUED FOR DATE BY
1607
PSG2016.03.09
PERMIT AND TENDER1
JA
2016.03.09
2-472 STRADBROOK AVENUE
W I N N I P E G , M B R 3 L 0 J 9
( 2 0 4 ) 2 7 2 - 3 2 5 5
J O B :
FOUNDATION PLAN - DRAINS,
PITS AND SLEEVES
M1.3
REFRIGERATION PIT SCHEDULE
REFRIGERATIONPIT NO.:
DIMENSIONS NOTES
REF. PIT NO. 01 24"X24" PLASTIC INSERTS
REF. PIT NO. 02 24"X24" PLASTIC INSERTS
REF. PIT NO. 03 36"X36" PLASTIC INSERTS
REF. PIT NO. 04 24"X24" PLASTIC INSERTS
REF. PIT NO. 05 24"X24" PLASTIC INSERTS
REF. PIT NO. 06 24"X24" PLASTIC INSERTS
REF. PIT NO. 07 24"X24" PLASTIC INSERTS
REF. PIT NO. 08 24"X24" PLASTIC INSERTS
REF. PIT NO. 09 24"X24" PLASTIC INSERTS
REF. PIT NO. 10 24"X24" PLASTIC INSERTS
REF. PIT NO. 11 24"X24" PLASTIC INSERTS
REF. PIT NO. 12 24"X24" PLASTIC INSERTS
REF. PIT NO. 13 24"X24" PLASTIC INSERTS
REF. PIT NO. 14 24"X24" PLASTIC INSERTS
REF. PIT NO. 15 24"X24" PLASTIC INSERTS
REF. PIT NO. 16 24"X24" PLASTIC INSERTS
REF. PIT NO. 17 24"X24" PLASTIC INSERTS
REF. PIT NO. 18 24"X24" PLASTIC INSERTS
REF. PIT NO. 19 24"X24" PLASTIC INSERTS
REF. PIT NO. 20 24"X24" PLASTIC INSERTS
REF. PIT NO. 21 24"X24" PLASTIC INSERTS
REF. PIT NO. 22 24"X24" PLASTIC INSERTS
REF. PIT NO. 23 24"X24" PLASTIC INSERTS
SCALE:M1.3N
FOUNDATION PLAN - DRAINS PITS AND SLEEVES1/8"=1'-0"
1
GENERAL NOTES - FOUNDATION PLAN
1. REFRIGERATION IN-FLOOR ACCESS PIT C/W 6"X6" PVC JUNCTION BOX(TYPICAL). COORDINATE ALL REQUIREMENTS WITH REFRIGERATION
CONTRACTOR PRIOR TO INSTALLATION OF PIPING. CONDUIT TYPESINDICATED ON DRAWING ARE TO BE INSTALLED AS FOLLOWS:
A. PVC TRANSIT LINE (REFRIGERATION) - BY MECHANICALB. 2" PVC (ELECTRICAL) LINE VOLTAGE - BY ELECTRICAL
C. 2" ABS (ELECTRICAL) LOW LINE VOLTAGE - BY ELECTRICAL
SUPPLY OF PIT BY GENERAL CONTRACTOR. INSTALLATION OF PIT BYMECHANICAL CONTRACTOR. INSTALLATION OF JUNCTION BOXES BY
ELECTRICAL CONTRACTOR. TRANSIT LINES TO SLOPE AT 116" PER FOOTTOWARD COMPRESSOR ROOM. REFER TO DETAIL ON DETAIL DRAWING.
12Ø
EXISTING HWT TO REMAIN
1
2
112"
112"
112"
12"
12"
34"
34"
34"
1"
12"
114"
34"
114"
34"
114"
112"
12"
114"
112"
12"
114"
112"
12"
34"
114"
12"
34"
1"
12"
34"
34"
12"
34"
34"
12"
12"
12"
34"
12"
12"
12"
34"
34"
34"
34"
34"
34"
34"
34"
34"
34"
12"
12"
12"
12"
34"
34"
34"
34" 3
4"3
4"
1"
1"
34"
34"
34"
34"
34"
34"
114"
114"
34"
34"
12"
34"
12"
112"
34"
12"
112"
34"
12"
12"
12"
34"
112"
34"
12"
12"
1"
112"
12"
1"
112"
12"
12"
12"
12"
12"
12"
12"
12"
34"
34"
34"
12"
34"
34"
G 34"
114"
E4
UH
E5
UH
G3
4
5
6
7
8
9
2-54 Adelaide Street Winnipeg Manit aob R3A 0V7
P 204 947 3775 F 204 947 3789 www.nejmark.mb.ca
N E J M A R KA R C H I T E C T
PROJECT TITLE:
SHEET TITLE:
COMMISSION NUMBER: SHEET NUMBER:
SOBEYS VARSITY COMMONS
1550- 8 St. E, SASKATOON,
SASKATCHEWAN
Drawings and specifications, as instruments of service are the property of the architect, the
copyright in the same being reserved to them. No reproduction may be made without the
permission of the architects, and when made, must bear their names. All prints to be returned.
The contractor is to verify dimensions and date noted herein with conditions on the site and is
held responsible for reporting discrepancy to the architects for adjustment.
DRAWN BY:
PRINTING DATE:
STAMP
No. ISSUED FOR DATE BY
1607
PSG2016.03.09
PERMIT AND TENDER1
JA
2016.03.09
2-472 STRADBROOK AVENUE
W I N N I P E G , M B R 3 L 0 J 9
( 2 0 4 ) 2 7 2 - 3 2 5 5
J O B :
SCALE:M1.4N
MAIN FLOOR PLAN - PLUMBING DEMOLITION1/8"=1'-0"
1
MAIN FLOOR PLAN -
PLUMBING DEMOLITION
M1.4
PLUMBING LEGENDDOMESTIC WATER DEMO
EXISTING DOMESTIC COLD WATER
PIPE ELBOW DROP
PIPE ELBOW RISE
PIPE TEE DROP
ISOLATION VALVE
DRAWING NOTE
EQUIPMENT TAG
#
#
EQP
DRAWINGS NOTES - PLUMBINGDEMOLITION
EXISTING 6" INCOMING WATER SERVICE UP TO EXISTING SPRINKLER
TREE AND WATER METER TO REMAIN. UPON COMPLETION OFRENOVATION WORK, DEMOLISH EXISTING DOMESTIC COLD WATER
MAIN BELOW GRADE. REFER TO PLUMBING RENOVATION DRAWINGSFOR CONTINUATION.
EXISTING WATER LINE EXTENDING BELOW SLAB TO TRAP PRIMERS.
DETERMINE ROUTING ON SITE AND CAP ALL LINES SERVINGDEMOLISHED PRIMED TRAPS.
EXISTING GAS LINE DOWN FROM ROOF SERVING OVENS TO REMAIN
FOR EXTENSION TO RELOCATED OVENS.
RETAIN WATER AND SANITARY LINES SERVING EXISTING MEZZANINE
FIXTURES FOR RECONNECTION.
EXISTING GAS LINE DOWN FROM ROOF SERVING HWT AND UNIT
HEATERS TO REMAIN.
TEMPORARILY DISCONNECT GAS LINES SERVING RELOCATED UNIT
HEATERS.
RETAIN DOMESTIC WATER LINES UP TO HOT WATER HEATER
MOUNTED ABOVE STAIRWELL FOR RECONNECTION TO NEW WATERSERVICES.
RETAIN EXISTING WATER LINE SERVING EXTERIOR HOSE BIBB FOR
RECONNECTION TO NEW WATER PIPING
EXISTING RAIN WATER THROUGH SLAB TO REMAIN. REFER TO
PLUMBING RENOVATION DRAWINGS FOR CONTINUATION.
1
2
3
4
5
6
7
8
9
GENERAL NOTES - PLUMBINGDEMOLITION
1. MECHANICAL DESIGN IS BASED ON INFORMATION AVAILABLE FROM
RECORD DRAWINGS AND SITE VISIT, FOR REFERENCE. MECHANICALCONTRACTOR TO REMOVE OR ABANDON IN PLACE ALL DOMESTIC
WATER LINES SERVING DEMOLISHED AND RELOCATED FIXTURESAND EQUIPMENT.
2. ALL EXISTING BELOW GRADE DOMESTIC WATER PIPING SHALL BE
ABANDONED UPON COMPLETION OF WORK AS SHOWN.
3. COORDINATE PHASING OF DEPARTMENT SHUT DOWNS WITHGENERAL CONTRACTOR AND PROJECT MANAGER. EXISTING
UNDERGROUND WATER SUPPLIES TO EXISTING DEPARTMENTS TOREMAIN OPERATIONAL AT ALL TIMES.
4. STAFF MEZZANINE DOMESTIC WATER AND SANITARY PIPING TO BE
RETAINED FOR RECONNECTION TO NEW PLUMBING SYSTEM.
5. ALL BELOW GRADE PIPING SHOWN TO BE DEMOLISHED SHALL BECAPPED BELOW GRADE AND ABANDONED.
6. CONTRACTOR SHALL BE FAMILIAR WITH, REFER TO, AND COMPLY
WITH ALL LOCAL CODES. ALL MECHANICAL WORK SHALL COMPLYIN EVERY RESPECT WITH THE LATEST EDITIONS OF THE NATIONAL,
PROVINCIAL AND MUNICIPAL BUILDING CODES, NFPA, ASHRAE,SMACNA, AND ANY ADDITIONAL REQUIREMENTS OF THE LOCALAUTHORITY HAVING JURISDICTION.
7. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHALL NOT BE SCALED.
THEY ESTABLISH DESIGN INTENT AND ARE NOT INTENDED TO BEDETAILED INSTALLATION DOCUMENTS. MECHANICAL CONTRACTOR
SHALL ALLOW IN THEIR CONTRACT PRICE ALL COMPONENTSREQUIRED TO PROVIDE A COMPLETE AND FUNCTIONAL
MECHANICAL INSTALLATION.
8. ANY OMISSIONS OR DISCREPANCIES IN THE DRAWINGS SHALL BEBROUGHT TO THE IMMEDIATE ATTENTION OF THE CONSULTANT
FOR CLARIFICATION. COMPENSATION FOR ADDITIONS TO THECONTRACT AFTER BID CLOSING WILL BE REJECTED.
9. JOB SITE SHALL BE INSPECTED PRIOR TO COMMENCEMENT OF WORK
AND APPROPRIATE PROVISIONS MADE FOR ALL SITE CONDITIONS.
EXACT PLACEMENT OF MECHANICAL EQUIPMENT ANDSIZING/ROUTING OF MECHANICAL SYSTEMS SHALL BE SITE
CONFIRMED AND COORDINATED WITH THE ARCHITECTURAL,ELECTRICAL, AND STRUCTURAL DRAWINGS AND TRADES.REROUTE/RESIZE PIPING AND RELOCATE EQUIPMENT AND
COMPONENTS AS REQUIRED.
10. ALLOW FOR ANY MODIFICATIONS OF EXISTING SYSTEMS ANDCOMPONENTS AS REQUIRED TO COMPLETE RENOVATION WORK.
11. CAREFULLY EXAMINE THE DRAWINGS OF OTHER TRADES.
COORDINATE THE ELECTRICAL REQUIREMENTS OF ALL MECHANICALEQUIPMENT WITH THE ELECTRICAL CONTRACTOR. AN APPROVED
FIRE STOP SYSTEM SHALL BE APPLIED AT ALL PENETRATIONS OFWALLS OR FLOORS DENOTED TO BE FIRE SEPARATIONS ON THE
ARCHITECTURAL DRAWINGS. REFER TO ARCHITECTURALELEVATIONS FOR MOUNTING HEIGHTS OF FIXTURES.
12. ALL CUTTING AND/OR PATCHING OF ROOFS, WALLS OR FLOORS
SHALL BE BY THE GENERAL CONTRACTOR UNLESS SPECIFICALLYINDICATED OTHERWISE.
13. CAREFULLY EXAMINE ALL DRAWINGS OF OTHER TRADES.
COORDINATE THE EXACT SIZES, LOCATIONS AND INVERTS OF ALLSEWERS WITH CIVIL DRAWINGS AND ON SITE.
CASE
CASE
CASE
CASE
CASE
CASE
CASE
8'
HUSSMANN
WIL
L CA
LLCA
BINE
T (N
)
(2) A
GED
MEA
TDI
SPLA
Y(D
ETAI
LS T
.B.C
.)
B320B321
HW CW HWCW
S-2
S408
S321
S320
12"
8
S321S320
CW
HW
S-5S-4
B321
B320
34 "
CW
HW
CW
HW
4
B321
CW
HW
LAV-1
U-1
WC-1
18
D321 D321
X320
G50517
G415
10S-7
CW
HW
4
S-6
CW
HW
G22
1"
1"
1"12"
HW CW HW CW
X321
H410
H409
H408
G
7
11
12
H407 13
H405 14
34"
GAS
GAS
GAS
HW
112" GAS
CW
RO 27H415
H320
H321
12 "
4
H321
3"
23
3"
MIXMIXMIXMIX
W81920
12 "
U320
U321
H407
CW
S-8
HW
CW
F321
F500
MIX
MIX
MIX
MIX
MIX
MIX
MIX
MIX
MIX
MIX
MIX
W8192012"
W81920
W81920
W822
MIX-212 "
P321
25
P321
4
34 "
34" GAS
WC-1
LAV-2
12"
34 "
5
5
5
2
M 3
B420
B421
6
6
B421 6
GAS
GAS
ROS
ROS
ROS
12"
114" GAS
12"
44
G
P320
9
4
HW
CW
B320
GAS
RECONNECT EXISTING
NON-FREEZE WALLHYDRANT
W819 20
12" 12"
MIX
MIX
MIX
MIX
MIX
MIX
MIX
12"
34"
12"
EXTEND 3 4" DCW,DHW AND DHWR
UNDER CASES
WC-1
WC-1
1"
12 "
12 "
1"
W82316
26
HW
CW
1"
MIX-1
X321
12 "
CW
HW
RO
RO
RO
RO
RO
RO
EXTEND 3 4" DCW,DHW AND DHWRUNDER CASES
EXISTING ROS MACHINE
S-3
S-3
RO RO
RO
RO
34" PEX
12"
34"
W81920
W81920
MIX-1
MIXMIXMIXMIXMIXMIXMIXMIXMIXMIXMIXMIXMIXMIXMIXMIXMIXMIXMIXMIXMIXMIX
LAV-1
STST
STST
STST
ST
STST
STST
STST
ST
STST
STST
STST
ST
STSTSTSTSTSTSTSTSTSTSTSTSTSTSTSTSTSTSTSTST
STST
ST
G
RORO
W82316
RORORORO
RO
RO
RO
RO
RO
RORO
RO
RO
RO
RO
RO
34"
CW
HW
CW
HW
HW
CW
B321
HW CW
MIX
MIX
MIX
MIX
MIX
MIX
MIX
MIX
MIX
MIXMIX
MIX
MIX
MIX
MIX
MIX
12 "
34 "
12"
W819 20
12"
W819
RO
RO
RO
P321 15
58" PEX
34"
34"
34"
12"
R1
UH
R2
UH
1
4
4
4
25
10
15
GGGGG
19
MIX 1
2"
DROP TO 7'-6" AFF AND
EXTEND ALONG CASES
34 "
21 31
28
20
12"
STSTSTSTSTSTSTSTSTSTSTSTSTSTSTSTSTSTSTSTST
U321
STST
34 "
EXISTING HWT
112"
34"
34"
114"
34"
114"
34"
112"
2"
12"
12"
114"
34"
M
1"
1"
112"
34"
34"
2"
34 "
34"
1"
1"
2"3
4"
1"
2"
2"
212"
34"
1"
2"
34"
1"
2"
34"
1"
2"
34"
1"
2"
MIX
MIX
34"
34"
34"
12"
34"
34"
34"
34"
12"
34"
34"
34"
34"
1"
34"
2"
2"
34"
2"
2"
34"
2"
2"
34"
2"
2"
12" 3
4"
34"
112"
2"
34"
112"
2"
114"
34"
34"
34"
12 "
34"
34"
34"
34"
112"
34"
34"
114"
34"
1"
34"
1"
1" 34"
1"
2"
1"
34"
2"
34"
2"
112"
34"
112"
34"
34" GAS
112" GAS
114"
34"
E4
UH
E5
UH
G
29
4
10
W819 20
1"
DROP LINES BENEATHMEZZANINE
DROP LINES BENEATHMEZZANINE
30
34"
15
4
W81920
30
4
4
112" GAS
4" @ 1:100 4" @ 1:100
4" @ 1:100
3" @ 1:50
3" @ 1:50
3" @ 1:50
24
24
DROP LINES BENEATH
MEZZANINE
DROP LINESBENEATH
MEZZANINE
EXISTING HWT
ON MEZZANINE
2"112"
29
2"
23
3"
24
3232
TMV-1EW-1
34"
2-54 Adelaide Street Winnipeg Manit aob R3A 0V7
P 204 947 3775 F 204 947 3789 www.nejmark.mb.ca
N E J M A R KA R C H I T E C T
PROJECT TITLE:
SHEET TITLE:
COMMISSION NUMBER: SHEET NUMBER:
SOBEYS VARSITY COMMONS
1550- 8 St. E, SASKATOON,
SASKATCHEWAN
Drawings and specifications, as instruments of service are the property of the architect, the
copyright in the same being reserved to them. No reproduction may be made without the
permission of the architects, and when made, must bear their names. All prints to be returned.
The contractor is to verify dimensions and date noted herein with conditions on the site and is
held responsible for reporting discrepancy to the architects for adjustment.
DRAWN BY:
PRINTING DATE:
STAMP
No. ISSUED FOR DATE BY
1607
PSG2016.03.09
PERMIT AND TENDER1
JA
2016.03.09
2-472 STRADBROOK AVENUE
W I N N I P E G , M B R 3 L 0 J 9
( 2 0 4 ) 2 7 2 - 3 2 5 5
J O B :
SCALE:M1.5N
MAIN FLOOR PLAN PLUMBING RENOVATION1/8"=1'-0"
1
MAIN FLOOR PLAN -
PLUMBING RENOVATION
M1.5
PLUMBING LEGENDEXISTING DOMESTIC COLD WATER
EXISTING NATURAL GAS
EXISTING STORM ABOVE GRADE
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RECIRC
NATURAL GAS
SANITARY ABOVE GRADE
STORM ABOVE GRADE
PLUMBING VENT
REVERSE OSMOSIS
MIXED WATER
THERMAL INSULATION
PIPE ELBOW DROP
PIPE ELBOW RISE
PIPE TEE DROP
ISOLATION VALVE
FLOOR DRAIN
ROOF DRAIN
PUMP
NON-FREEZE WALL HYDRANT
HOSE BIBB
WATER METER
GAS METER
FIRE DEPARTMENT CONNECTION
CLEANOUT
DRAWING NOTE
EQUIPMENT TAG
G
ST
G
ST
RO
MIX
M
M
#
#
EQP
DRAWINGS NOTES - PLUMBING
RENOVATION
EXISTING WATER METER, BACKFLOW ASSEMBLY AND SPRINKLER TREE TO REMAIN.EXTEND NEW 2" DOMESTIC COLD WATER MAIN TO HIGH LEVEL FOR
DISTRIBUTION.
EXISTING NATURAL GAS METER & PRV TO REMAIN.
EXISTING NATURAL GAS LINE UP BUILDING TO ROOF ALONG EXTERIOR OF
BUILDING. EXTEND NEW 112" NATURAL GAS LINE TO ROOF ADJACENT TO
EXISTING GAS MAIN.
CONNECT DHWR LINE TO DHW LINE AT LOW LEVEL, WITHIN CLOSE PROXIMITY
TO FIXTURE(S).
EXTEND 3 4" PEX-A DCW, 3 4" PEX-A DHW AND 3 4" PEX-A DHWR WITHIN PVCSLEEVE BENEATH SLAB.
EXTEND 3 4 " PEX-A REVERSE OSMOSIS LINE TO PROOFER RETARDER. EXTEND 3 4"
PEX-A REVERSE OSMOSIS AND 114 " GAS TO ROTATING DOUBLE RACK OVEN.
EXTEND GAS LINE FROM ROOF DOWN WALL TO LOW LEVEL TO SERVE COOKINGEQUIPMENT. PROVIDE VALVED AND THREADED GAS CONNECTION FOR
KITCHEN APPLIANCES C/W ULC/CSA LISTED 48" LONG BRAIDED S/S FLEXIBLE GAS
HOSE C/W QUICK CONNECTION (TYPICAL). COORDINATE FIRE SUPPRESSION
REQUIREMENTS, INCLUDING BUT NOT LIMITED TO AUTOMATIC GAS VALVE,WITH SUPPRESSION SYSTEM SUPPLIER.
EXTEND 12" PEX-A REVERSE OSMOSIS LINE AND 12" DCW LINE DOWN WITHINWALL TO HOSE BIBBS SERVING LOBSTER STEAMER AND LOBSTER TANK FILL.
DROP WATER LINES FROM HIGH LEVEL TO ABOVE CEILING IN INCONSPICUOUS
LOCATION, OUT OF COSTUMERS VIEW.
INSTALL AIR ADMITTANCE VALVE ON SINK VENT. PROVIDE 3"Ø INCONSPICUOUS
OPENING WITHIN CABINET FOR AIR TRANSFER.
114 " NATURAL GAS LINE TO GAS RANGE AND OVEN.
114" NATURAL GAS LINE TO GAS BROILER.
12 " DHW AND 3 4" NATURAL GAS LINES TO ROTISSERIE.
34" ROS PEX-A LINE AND 34" DCW LINE TO COMBI OVEN.
INSTALL 34" PEX-A CAPPED REVERSE OSMOSIS LINE ABOVE T-BAR FOR MISTINGSYSTEM BY OTHERS.
34" DCW LINE TO NON-FREEZE HOSE BIBB C/W BACK FLOW PREVENTION IN
RECESSED LOCKABLE CABINETS MOUNTED FLUSH WITH WALL AT 24" A.F.F.
ENSURE HOSE BIBB PLUMBING IS TOTALLY CONCEALED WITHIN WALL.
EXTEND GAS LINE DOWN WITHIN WALL AND THROUGH PVC SLEEVE WITH
LONG RADIUS ELBOWS BENEATH SLAB TO COMMUNITY ROOM RANGE. PROVIDE
FLEXIBLE GAS CONNECTION TO RANGE.
PROVIDE 2" SANITARY LINE C/W PRIMED TRAP FOR EVAPORATOR CONDENSATE.EXTEND TO LOW LEVEL WITHIN WALL. REFER TO FOUNDATION PLAN FOR
CONTINUATION.
PROPOSED LOCATION OF RELOCATED FIRE DEPARTMENT CONNECTION (TO BECONFIRMED BY SPRINKLER TRADE).
QUICK CONNECT TO TEMPERED WATER SUPPLY VALVE AND REGULATOR, 12"LINE, MOUNTED 6" ABOVE CASES BEHIND FASCIA OR 60" A.F.F. FOR CASE WASHDOWN. FINAL CONNECTIONS TO REFRIGERATION CASE WATER SPRAY HOSE BY
REFRIGERATION CONTRACTOR.
EXTEND 12" DCW AND 12" DHW TO NOODLE BAR EQUIPMENT BENEATH SLABTHROUGH PVC SLEEVE WITH LONG RADIUS ELBOWS. CONFIRM EXACT
REQUIREMENTS ON SITE PRIOR TO INSTALLATION.
EXTEND 12" DCW, 12" DHW AND 3 4" DHWR LINES DOWN WITHIN WALL. EXTENDPEX-A PIPING WITHIN PVC SLEEVE BELOW SLAB TO SINK AND DISHWASHER.PROVIDE BACK FLOW PREVENTION ON DISHWASHER CONNECTION. EXTEND
FLEXIBLE GAS TUBING WITHIN PVC SLEEVE TO GAS STOVE.
OFFSET 3" INSULATED AND HEAT TRACED RAIN WATER LEADER WITHIN CANOPY
BACK TO BUILDING, DROP DOWN WALL TO LOW LEVEL C/W CLEAN OUT ATLOW LEVEL. PROVIDE AND INSTALL HEAT TRACE FOR PORTION OF RAIN WATER
LEADER WITHIN CANOPY. HEAT TRACING SHALL BE: SERGE BARIL 6CCAA-2BA, 6
WATTS/FT SELF REGULATING HEATING CABLE WITH POWER CONNECTION KIT
AND SEALS. THERMOSTAT IN NEMA ENCLOSURE. PIPE TO BE WRAPPED WITH FOILFACED INSULATION. COORDINATE ELECTRICAL REQUIREMENTS WITH
ELECTRICAL. REFER TO FOUNDATION PLAN FOR CONTINUATION.
EXTEND RAIN WATER LEADER TO LOW LEVEL C/W CLEANOUT WITH RETAINING
STRAP AT BASE. REFER TO FOUNDATION PLAN FOR CONTINUATION
EXTEND 12" PEX-A DCW, 12" PEX-A DHW AND 34" DHWR WITHIN PVC SLEEVEBENEATH SLAB.
PROVIDE BARBEQUE OUTLET CONNECTION MOUNTED AT 24" A.F.F.
EXTEND DOMESTIC WATER LINES AND ROS PEX-A LINE DOWN WITHIN WALL
AND CONNECT TO FIXTURES AND APPLIANCES AS REQUIRED.
CONNECT DCW TO COFFEE BREWER AS PER MANUFACTURER'S WRITTEN
INSTRUCTIONS.
CONNECT NEW DOMESTIC WATER LINES TO EXISTING HOT WATER TANK(S)ABOVE STAIRS / IN COMPRESSOR MEZZANINE.
EXTEND EXISTING NATURAL GAS LINE TO RELOCATED UNIT HEATER.
CONNECT NEW 4" RAIN WATER LEADER TO EXISTING 6" RAIN WATER LEADER ATHIGH LEVEL.
OFFSET SANITARY DRAIN SERVING EXISTING COMPRESSOR ROOM FLOOR DRAINAT HIGH LEVEL AND EXTEND TO LOW LEVEL FOR RECONNECTION TO EXISTING
SANITARY DRAIN. REFER TO FOUNDATION PLAN DRAWING FOR
CONTINUATION.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
GENERAL NOTES - PLUMBINGRENOVATION
1. CONTRACTOR SHALL BE FAMILIAR WITH, REFER TO, AND COMPLYWITH ALL LOCAL CODES. ALL MECHANICAL WORK SHALL COMPLY
IN EVERY RESPECT WITH THE LATEST EDITIONS OF THE NATIONAL,
PROVINCIAL AND MUNICIPAL BUILDING CODES, NFPA, ASHRAE,
SMACNA, AND ANY ADDITIONAL REQUIREMENTS OF THE LOCALAUTHORITY HAVING JURISDICTION.
2. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHALL NOT BE SCALED.
THEY ESTABLISH DESIGN INTENT AND ARE NOT INTENDED TO BE
DETAILED INSTALLATION DOCUMENTS. MECHANICAL CONTRACTORSHALL ALLOW IN THEIR CONTRACT PRICE ALL COMPONENTS
REQUIRED TO PROVIDE A COMPLETE AND FUNCTIONAL
MECHANICAL INSTALLATION.
3. ANY OMISSIONS OR DISCREPANCIES IN THE DRAWINGS SHALL BE
BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONSULTANTFOR CLARIFICATION. COMPENSATION FOR ADDITIONS TO THE
CONTRACT AFTER BID CLOSING WILL BE REJECTED.
4. JOB SITE SHALL BE INSPECTED PRIOR TO COMMENCEMENT OF WORK
AND APPROPRIATE PROVISIONS MADE FOR ALL SITE CONDITIONS.
EXACT PLACEMENT OF MECHANICAL EQUIPMENT ANDSIZING/ROUTING OF MECHANICAL SYSTEMS SHALL BE SITE
CONFIRMED AND COORDINATED WITH THE ARCHITECTURAL,
ELECTRICAL, AND STRUCTURAL DRAWINGS AND TRADES.REROUTE/RESIZE PIPING AND RELOCATE EQUIPMENT AND
COMPONENTS AS REQUIRED.
5. ALLOW FOR ANY MODIFICATIONS OR REBALANCING OF EXISTING
SYSTEMS AND COMPONENTS AS REQUIRED TO COMPLETE
RENOVATION WORK.
6. CAREFULLY EXAMINE THE DRAWINGS OF OTHER TRADES.
COORDINATE THE ELECTRICAL REQUIREMENTS OF ALL MECHANICALEQUIPMENT WITH THE ELECTRICAL CONTRACTOR. AN APPROVED
FIRE STOP SYSTEM SHALL BE APPLIED AT ALL PENETRATIONS OF
WALLS OR FLOORS DENOTED TO BE FIRE SEPARATIONS ON THEARCHITECTURAL DRAWINGS. REFER TO ARCHITECTURAL
ELEVATIONS FOR MOUNTING HEIGHTS OF FIXTURES.
7. A MEANS OF BALANCING EACH BRANCH OF HYDRONIC SYSTEMS
AND COMPONENT SHALL BE PROVIDED. ISOLATION VALVES SHALL BE
PROVIDED AS REQUIRED TO SERVICE OR REPLACE EACH PIECE ORGROUP OF EQUIPMENT.
8. ACCESS DOORS SHALL BE PROVIDED AS REQUIRED TO SERVICE
VALVES AND MECHANICAL EQUIPMENT.
9. ALL PIPING AND EQUIPMENT SHALL BE INSULATED TO THE
REQUIREMENTS OF THE LATEST EDITION OF ASHRAE 90.1 AND FOR
NEW CONSTRUCTION, TO THE REQUIREMENTS OF THE NATIONALENERGY CODE OF CANADA. ALL VENT PIPES WITHIN 10' (3M) OF
THERMAL ENVELOPE PENETRATION SHALL BE THERMALLY INSULATED.
10. ALL CUTTING AND/OR PATCHING OF ROOFS, WALLS OR FLOORS
SHALL BE BY THE GENERAL CONTRACTOR UNLESS SPECIFICALLY
INDICATED OTHERWISE.
11. CAREFULLY EXAMINE ALL DRAWINGS OF OTHER TRADES.COORDINATE THE EXACT SIZES, LOCATIONS AND INVERTS OF ALL
SEWERS WITH CIVIL DRAWINGS AND ON SITE.
12. ALL PLUMBING SYSTEMS AND EQUIPMENT SHALL BE VENTED. ALL
VENTING SHALL BE INSTALLED TO THE REQUIREMENTS OF THE
NATIONAL, PROVINCIAL AND MUNICIPAL BUILDING CODES ANDANY ADDITIONAL REQUIREMENTS OF THE LOCAL AUTHORITY
HAVING JURISDICTION.
13. DWV PIPING AND ELECTRICAL/CONTROL WIRING INSTALLED
WITHIN H.V.A.C. PLENUMS SHALL HAVE A FLAME SPREAD RATING
NOT EXCEEDING 25 AND A SMOKE DEVELOPED RATING NOTEXCEEDING 50 WHEN TESTED IN ACCORDANCE WITH ASTM E84 (UL
723).
14. PROVIDE DIELECTRIC COUPLINGS WHERE COMPONENTS OF
DISSIMILAR METAL ARE JOINED.
15. ENSURE THAT ALL TRAPS SERVING FLOOR DRAINS ARE PRIMED OR
FITTED WITH WADE TRAPS GUARDS.
16. PROVIDE AUTOMATIC AIR VENTS AT ALL HIGH POINTS OF THE
SYSTEM.
17. GAS PIPING SHALL BE BLACK STEEL TO ASTM A-53 SCHEDULE 40, 150
LB. STANDARD BLACK MALLEABLE IRON SCREW FITTING FOR SIZES
BELOW 212". ALL MATERIALS AND INSTALLATION SHALL CONFIRM TO
ALL REQUIREMENTS OF THE LATEST EDITION OF CSA B149.1 NATURAL
GAS AND PROPANE INSTALLATION CODE AND ALL LOCAL GAS
NOTICES.
18. COORDINATE REVERSE OSMOSIS WATER REQUIREMENTS WITHPROJECT MANAGER.
19. THERMALLY INSULATE ALL HORIZONTAL RAIN WATER LEADERS ATHIGH LEVEL INCLUDING DRAIN BODIES.
20. PROVIDE APPROVED BACK FLOW PREVENTION AT ALL
CONNECTIONS TO HAZARDOUS FIXTURES AND EQUIPMENT.
21. PROVIDE PLUMBING CONNECTIONS AS REQUIRED TO ALL OWNER
SUPPLIED EQUIPMENT SHOWN ON THE PLANS.
50
12x12
S4
530
24x24
SE1
x8
530
24x24
SE3
x8
415
24x24
SE1
x7
12"Ø
8"Ø
12"Ø 12"Ø
12"Ø
12"Ø 12"Ø
12"Ø 12"Ø
20"Ø
20"Ø
16"Ø
16"Ø
12"Ø
12"Ø 12"Ø
12"Ø
12"Ø 12"Ø
12"Ø 12"Ø
20"Ø
20"Ø
16"Ø
16"Ø
R15
CF
R18
CF
R19
CF
E6
RTUR16
CF
R13
CF
E11
CF
R12
CF
R10
CF
R20
CFR14
CF
R7
CF
R8
CF
R1
CF
E2
CF E3
CF
E4
CF
R5
CF
E6
CF
510
24x24
SE1
x8
200
24x24
S2
S
E5
RTU
E4
RTU
12"Ø
12"Ø
12"Ø 12"Ø
20"Ø
16"Ø
250
24x24
S2
x8
12"Ø
12"Ø
20"Ø
16"Ø
12"Ø
530
24x24
SE1
x8
12"Ø
S
D9
CF
E3
RTU
530
24x24
SE1
x8
12"Ø
12"Ø 12"Ø
12"Ø
12"Ø 12"Ø
12"Ø 12"Ø
20"Ø
EXISTING 20"Ø
EXISTING 16"Ø
16"Ø
SS
T
TT
T
-
24x24
RE1
x14
12"Ø12"Ø
16"Ø20"Ø
12"Ø
12"Ø
E1
RTU
12"Ø12"Ø12"Ø12"Ø
20"Ø
16"Ø
S
12"Ø
12"Ø
500
72x4
SE2
x12
12"Ø
12"Ø
12"Ø
12"Ø32x20
12"Ø
12"Ø
12"Ø 12"Ø
12"Ø
12"Ø
16x12
50
12x12
S4
140
12x12
S4
x8
6"Ø 6"Ø
6"Ø6"Ø
12"Ø
6"Ø
6"Ø
6"Ø 6"Ø
6"Ø
6"Ø
12x10 TRANSFER
DUCT
8X8 TRANSFERDUCT
8X8 TRANSFERDUCT
6"Ø6"Ø
110
24X24
EE1
x2
-
12x12
RE1
x2
D12
EF
BB-E1
D9
RTU
S
32x20
F
FD AT TOP OFFIRE RATED SHAFT
-
48x32
RE2
LOW LEVEL
500
72x4
SE2
x3
12"Ø
20"Ø
12"Ø 12"Ø
10"Ø
10"Ø
10"Ø
10"Ø
10"Ø20"Ø
DUCT WORK DROPSUNDER MEZZ,
CONCEALED IN CEILING
DUCT WORK DROPSUNDER MEZZ, CONCEALED
IN BULKHEAD
REMOVE GREASEDUCT FROM DONUT
HOOD AND EF ONROOF
BB-E1FF-E1
E10
RTU
S
E2
RTU
S
D3
EF
ROOF
D2
EF
ROOF
E8
RTU
SEE MEZZ OFFICEAREA PLAN
12"Ø12"Ø
12"Ø
410
24x24
SE1
x6
16"Ø
16"Ø
12"Ø
12"Ø
12"Ø
20x16
D1
MUA
REMOVE GREASE DUCT
FROM CHICKENROTISSERIE TO EF-D13
ON ROOF
D13
EF
ROOF
REMOVE PVCEXHAUST
VENT ANDEF-D1 ON
ROOF
D1
EF
ROOF8"Ø
R3
EF
ROOFR2
EF
ROOF
OVEN GREASE
EXHAUST TOEF-R2 ON ROOF OVEN GREASE
EXHAUST TO
EF-R3 ON ROOF
E7
RTU
SEE MEZZ STAFF
AREA PLAN FORCONTINUATION
D4
EF
12"Ø
D5
EF
REMOVE EXHAUSTFAN CONNECTED
TO UNDER-SLAB
DUCT WORK
FF-E2
R1
UH
R2
UH
R2
UH
D8
EF
D9
EF
REMOVE EXHAUSTDUCT AND
ASSOCIATED FANS
D7
EF
EF AT HIGH LEVEL
CONNECTED TOUNDER-SLAB
DUCT WORK
D10
EF
REMOVE EXHAUST
DUCT UP TO
ROOF CAP
E11
EF
E4
UH
E5
UH
T
R17
CF
20"Ø
5 TR
INTAKEVENTILATOR
E19
EF
ROOFT
17
E7
RTU
E7
RTU
8"Ø
8"Ø
8"Ø
10"Ø
E15
EF
EXISTING EXHAUST
DUCT UP TO ROOF CAP
E16
EF
EXISTING EXHAUST DUCTUP TO ROOF CAP
300
24x24
SE1
x2
320
24x24
EE1
x2
8x8TRANSFER
DUCT
12x8TRANSFER
DUCT
235
24x24
SE1
x6
-
24x24
RE1
x4
8x8TRANSFERDUCT
12x8TRANSFER
DUCT8"Ø
8"Ø
8"Ø
8"Ø
S
EXISTING
10"Ø
E17
EF
EXISTING17
D14
EF
E8
RTU
8"Ø
8"Ø-
12x12
RE1
x5
BB-E1 BB-E1
235
24x24
SE1
x5
8x8TRANSFER
DUCT
12x8TRANSFER
DUCT
12x8TRANSFER
DUCT
12x8
TRANSFERDUCT
12x8TRANSFERDUCT
S
H.V.A.C. DEMOLITION
M2.1
2-54 Adelaide Street Winnipeg Manit aob R3A 0V7
P 204 947 3775 F 204 947 3789 www.nejmark.mb.ca
N E J M A R KA R C H I T E C T
PROJECT TITLE:
SHEET TITLE:
COMMISSION NUMBER: SHEET NUMBER:
SOBEYS VARSITY COMMONS
1550- 8 St. E, SASKATOON,
SASKATCHEWAN
Drawings and specifications, as instruments of service are the property of the architect, the
copyright in the same being reserved to them. No reproduction may be made without the
permission of the architects, and when made, must bear their names. All prints to be returned.
The contractor is to verify dimensions and date noted herein with conditions on the site and is
held responsible for reporting discrepancy to the architects for adjustment.
DRAWN BY:
PRINTING DATE:
STAMP
No. ISSUED FOR DATE BY
1607
PSG2016.03.09
PERMIT AND TENDER1
JA
2016.03.09
2-472 STRADBROOK AVENUE
W I N N I P E G , M B R 3 L 0 J 9
( 2 0 4 ) 2 7 2 - 3 2 5 5
J O B :
SCALE:M2.1N
MAIN FLOOR PLAN - H.V.A.C. DEMOLITION 1/8"=1'-0"
1
SCALE:M2.1N
OFFICE MEZZANINE FLOOR PLAN - H.V.A.C. DEMOLITION 1/8"=1'-0"
2
SCALE:M2.1N
COMPRESSOR ROOM MEZZANINE FLOOR PLAN - H.V.A.C. DEMOLITION 1/8"=1'-0"
3
SCALE:M2.1N
STAFF MEZZANINE FLOOR PLAN - H.V.A.C. DEMOLITION 1/8"=1'-0"
1
GENERAL NOTES - H.V.A.C.
1. MECHANICAL DESIGN IS BASED ON INFORMATION AVAILABLE FROM
RECORD DRAWINGS AND PRELIMINARY SITE VISIT. EXACT ROUTING ANDSIZING OF DUCT WORK AND LOCATION OF EQUIPMENT TO BE CONFIRMED
ON SITE. MODIFY SYSTEM DESIGN AS REQUIRED TO SUIT SITE CONDITIONS.
2. CONTRACTOR SHALL BE FAMILIAR WITH, REFER TO, AND COMPLY WITH ALLLOCAL CODES. ALL MECHANICAL WORK SHALL COMPLY IN EVERY RESPECT
WITH THE LATEST EDITIONS OF THE NATIONAL, PROVINCIAL ANDMUNICIPAL BUILDING CODES, NFPA, ASHRAE, SMACNA, AND ANY
ADDITIONAL REQUIREMENTS OF THE LOCAL AUTHORITY HAVINGJURISDICTION.
3. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHALL NOT BE SCALED. THEYESTABLISH DESIGN INTENT AND ARE NOT INTENDED TO BE DETAILED
INSTALLATION DOCUMENTS. MECHANICAL CONTRACTOR SHALL ALLOW INTHEIR CONTRACT PRICE ALL COMPONENTS REQUIRED TO PROVIDE A
COMPLETE AND FUNCTIONAL MECHANICAL INSTALLATION.
4. ANY OMISSIONS OR DISCREPANCIES IN THE DRAWINGS SHALL BE BROUGHTTO THE IMMEDIATE ATTENTION OF THE CONSULTANT FOR CLARIFICATION.
COMPENSATION FOR RELATED ADDITIONS TO THE CONTRACT AFTER BIDCLOSING WILL NOT BE CONSIDERED.
5. INSPECT JOB SITE SHALL PRIOR TO COMMENCEMENT OF WORK ANDALLOW FOR PROVISIONS MADE FOR ALL SITE CONDITIONS. EXACT
PLACEMENT OF MECHANICAL EQUIPMENT AND SIZING/ROUTING OFMECHANICAL SYSTEMS SHALL BE SITE CONFIRMED AND COORDINATED
WITH THE ARCHITECTURAL, ELECTRICAL, AND STRUCTURAL DRAWINGSAND TRADES. REROUTE/RESIZE DUCT WORK AND RELOCATE EQUIPMENT
AND COMPONENTS AS REQUIRED.
6. ALLOW FOR ANY MODIFICATIONS OR REBALANCING OF EXISTING SYSTEMSAND COMPONENTS AS REQUIRED TO COMPLETE RENOVATION WORK.
7. CAREFULLY EXAMINE ALL DRAWINGS OF OTHER TRADES. COORDINATE
THE ELECTRICAL REQUIREMENTS OF ALL MECHANICAL EQUIPMENT WITH
THE ELECTRICAL CONTRACTOR. TYPE B OR C DYNAMIC FIRE DAMPERSSHALL BE INSTALLED AT ALL PENETRATIONS OF WALLS OR FLOORS
DENOTED TO BE FIRE SEPARATIONS ON THE ARCHITECTURAL DRAWINGS.
8. A MEANS OF BALANCING ALL SUPPLY AND EXHAUST TERMINALS USINGDUCT MOUNTED BALANCING DAMPERS SHALL BE PROVIDED. A TERMINAL
BALANCING DAMPER SHALL BE PERMITTED WHEN A DUCT MOUNTEDDAMPER WOULD BE INACCESSIBLE OR UNDESIRABLE.
9. THE USE OF FLEXIBLE DUCT WORK SHALL BE U.L.C. LISTED AND LIMITED TO
ONLY CONNECTIONS BETWEEN DUCT BRANCHES AND DIFFUSERS, AND
CONNECTIONS BETWEEN DUCT BRANCHES AND VARIABLE AIR VOLUMETERMINAL UNITS AND SHALL HAVE A MAXIMUM LENGTH OF 5 FT WHENFULLY STRETCHED.
10. ACCESS DOORS SHALL BE PROVIDED AS REQUIRED TO SERVICE DAMPERS
AND MECHANICAL EQUIPMENT.
11. THE FINAL LOCATIONS OF GRILLES, REGISTERS AND DIFFUSERS SHALL BECOORDINATED ON SITE WITH THE FINAL CEILING LAYOUT AND THE
EQUIPMENT OF OTHER TRADES.
12. A RETURN OR RELIEF GRILLE SHALL BE INSTALLED IN EACH SPACE THAT IS
PROVIDED WITH SUPPLY AIR.
13. ELECTRICAL OR CONTROL WIRING INSTALLED WITHIN ALL PLENUMS SHALLBE FT-6 RATED AND HAVE A FLAME SPREAD RATING BELOW 25 AND A
SMOKE DEVELOPED RATING BELOW 50 WHEN TESTED IN ACCORDANCE
WITH ASTM E84 (UL 723) ALL CONTROL WIRING SHALL BE INSTALLED IN 34"EMT CONDUIT WHEN RUNNING EXPOSED VERTICALLY.
14. ALL DUCT WORK AND EQUIPMENT SHALL BE INSULATED TO THEREQUIREMENTS OF THE LATEST EDITION OF ASHRAE 90.1. ALL DUCT WORK
WITHIN 10' (3M) OF THERMAL ENVELOPE PENETRATION AND ALL DUCTWORK CONTAINING OUTSIDE AIR SHALL BE THERMALLY INSULATED.
15. ALL SIZES OF DUCTWORK INDICATED ON THE DRAWINGS DENOTE THEINTERNAL OPEN DUCT DIMENSIONS. ALLOWANCES SHALL BE MADE FOR
ANY INTERNAL INSULATION INDICATED ON THE DRAWINGS OR REQUIREDIN THE SPECIFICATIONS.
16. ALL CUTTING AND/OR PATCHING OF ROOFS, WALLS OR FLOORS SHALL BE
BY THE GENERAL CONTRACTOR UNLESS SPECIFICALLY INDICATEDOTHERWISE.
17. ALL DUCTWORK SHALL BE INSTALLED IN CONFORMANCE WITH THE LATEST
RELEVANT ASHRAE AND SMACMA STANDARDS FOR LOW PRESSURE
DUCTWORK.
18. ALL DUCTWORK C/W CLASS 'C' SEALS PER SMACNA STANDARDS.
19. INSTALL DUCTWORK IN JOINT SPACE OR TIGHT TO UNDERSIDE OFJOIST/BEAMS.
H.V.A.C. LEGEND
GRILLE/REGISTER/DIFFUSER
RETURN AIR GRILLE
EXHAUST AIR GRILLE
SUPPLY DUCT RISE / DROP
RETURN DUCT RISE / DROP
EXHAUST DUCT RISE / DROP
ROUND DUCT RISE / DROP
THERMAL INSULATION
ACOUSTIC INSULATION
DEMOLISHED DUCT
EXISTING DUCT TO REAMAIN
H.V.A.C. CONTROL
THERMOSTAT
BALANCING DAMPER
BACK DRAFT DAMPER/ MOTORIZEDDAMPER
DIFFUSER TAG
ELECTRIC HEAT TAG
EQUIPMENT TAG
DRAWING NOTE
T T
B M F S
FLOW
SIZE
TYPE
TAG
CAP.
#
EQP
3
8'
HUSSMANN
WIL
L CA
LLCA
BINE
T (N
)
(2) A
GED
MEA
TDI
SPLA
Y(D
ETAI
LS T
.B.C
.)
20"Ø
20"Ø
16"Ø
16"Ø
20"Ø
20"Ø
16"Ø
16"Ø
E6
RTU
R15
CF
E2
CF E3
CF
E4
CF
E6
CF
S
E5
RTU
E4
RTU
S
E3
RTU
20"Ø
EXISTING 20"Ø
EXISTING 16"Ø
16"Ø
T
TT
T
16"Ø20"Ø
E1
RTU
20"Ø
BB-E1
E10
RTU
E2
RTU
E8
RTU
E7
RTU
SEE MEZZ STAFFAREA PLAN FOR
CONTINUATION
FF-E2
E11
EF
E4
UH
E5
UH
T
R13
CF
R14
CFR11
CF
R8
CF
R10
CF
R7
CF
R12
CF
R18
CF
R17
CF
R9
CF
R19
CF
R16
CF
R2
EF
R3
EF
1
UH
R3
UH
R1
UH
R2
UH
1
RTU
-
24x24
R1
305
24x24
S2
x2
80
12X12
S1
10"Ø
10"Ø
-
6x6
R1
-
6x6
R1
TO RTU-1
11
6"Ø
525
18x8
S1
x8525
18x8
S1
x8
2
RH
1
RH
3
RH
150
8x8
E1
150
24x12
E1
x7
12"Ø
10"Ø
16"Ø
8"Ø
14"x14"
300
24x24
S2
2
MUA
R1
CF
525
18x8
S1
x8
5
EF
4
EF
9
8"Ø
100
8x8
E1
R5
CF
150
8x8
E1
50
8x8
E1
2
EF
20"Ø
26"Ø
20"Ø
16"Ø
20"Ø
525
18x8
S1
x7
1050
28X12
S1
5 TR
1
AC
16"Ø
1500
40x12
S1
x3
32"x20"
20"Ø
3
16"Ø
750
24x8
S1
x2
STO RTU-E10
11
200
24x24
S2
10"Ø
10"Ø
200
24x24
S2
x2
200
24x24
S2
8"Ø
10"Ø
8"Ø
8"Ø
775
22x10
S1
x4
775
22x10
S1
x4
14"Ø
28"Ø
24"Ø
18"Ø
18"Ø
300
10x8
S1
x4
12"Ø
16"Ø
S
S
SS
S
6"Ø8"Ø
10"x10"1
EF3
RTU
750 W
EBB-1
1.5 KW
EBB-1
8"Ø6"Ø
5"Ø
8"Ø
500 W
EBB-1
500 W
EBB-1
100
12x12
S2
x2
8"Ø
6"Ø
6"Ø
120
24x24
S2
110
24x24
S2
90
12x12
S2
15
15x15
S2
65
12x12
S2
2 KW
EBB-1
16"x16"12"Ø
12"Ø
6
EF
6"Ø
670
24x24
S2
325
24x24
S2
x4
350
24x24
S2
x4
470
24x24
S2
x2
12"Ø
14"Ø 16"Ø10"Ø10"Ø
10"Ø
10"Ø
12"Ø
18"Ø
S
10"Ø
10"Ø
S
12"x12"
20"x20"
2
RTU
875
18"Ø
S3
x4
500
24x24
S2
8"Ø
3
EF
1
MUA1
20"x20"
1
2
4
4
1
EV
20"x20"
4
5
7
-
64x30
R1
8 -
6x6
S1
10
10
11
-
6x6
R1
TYPICAL
13
14
14
15
15
15
-
24x24
R1
x2
8"Ø
110
12x12
S2
7
7
7
7
TYPICAL
6
6
15
11
16
16
16
32"x20"
15
S
INTAKEVENTILATOR
E19
EF
ROOFT
17
E7
RTU
E7
RTU
8"Ø
8"Ø
8"Ø
10"Ø
E15
EF
EXISTING EXHAUSTDUCT UP TO ROOF CAP
E16
EF
EXISTING EXHAUST DUCTUP TO ROOF CAP
300
24x24
SE1
x2
320
24x24
EE1
x2
8x8TRANSFER
DUCT
12x8TRANSFER
DUCT
235
24x24
SE1
x6
-
24x24
RE1
x4
8x8TRANSFERDUCT
12x8TRANSFER
DUCT8"Ø
8"Ø
8"Ø
8"Ø
S
EXISTING
10"Ø
E17
EF
EXISTING17
H.V.A.C RENOVATION
M2.2
2-54 Adelaide Street Winnipeg Manit aob R3A 0V7
P 204 947 3775 F 204 947 3789 www.nejmark.mb.ca
N E J M A R KA R C H I T E C T
PROJECT TITLE:
SHEET TITLE:
COMMISSION NUMBER: SHEET NUMBER:
SOBEYS VARSITY COMMONS
1550- 8 St. E, SASKATOON,
SASKATCHEWAN
Drawings and specifications, as instruments of service are the property of the architect, the
copyright in the same being reserved to them. No reproduction may be made without the
permission of the architects, and when made, must bear their names. All prints to be returned.
The contractor is to verify dimensions and date noted herein with conditions on the site and is
held responsible for reporting discrepancy to the architects for adjustment.
DRAWN BY:
PRINTING DATE:
STAMP
No. ISSUED FOR DATE BY
1607
PSG2016.03.09
PERMIT AND TENDER1
JA
2016.03.09
2-472 STRADBROOK AVENUE
W I N N I P E G , M B R 3 L 0 J 9
( 2 0 4 ) 2 7 2 - 3 2 5 5
J O B :
SCALE:M2.2N
MAIN FLOOR PLAN - H.V.A.C. RENOVATION 1/8"=1'-0"
1
SCALE:M2.2N
OFFICE MEZZANINE FLOOR PLAN - H.V.A.C. RENOVATION 1/8"=1'-0"
1
SCALE:M2.2N
COMPRESSOR ROOM MEZZANINE FLOOR PLAN - H.V.A.C. RENOVATION 1/8"=1'-0"
3
GENERAL NOTES - H.V.A.C.
1. CONTRACTOR SHALL BE FAMILIAR WITH, REFER TO, AND COMPLY WITH ALLLOCAL CODES. ALL MECHANICAL WORK SHALL COMPLY IN EVERY RESPECT
WITH THE LATEST EDITIONS OF THE NATIONAL, PROVINCIAL AND
MUNICIPAL BUILDING CODES, NFPA, ASHRAE, SMACNA, AND ANYADDITIONAL REQUIREMENTS OF THE LOCAL AUTHORITY HAVING
JURISDICTION.
2. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHALL NOT BE SCALED. THEYESTABLISH DESIGN INTENT AND ARE NOT INTENDED TO BE DETAILED
INSTALLATION DOCUMENTS. MECHANICAL CONTRACTOR SHALL ALLOW INTHEIR CONTRACT PRICE ALL COMPONENTS REQUIRED TO PROVIDE A
COMPLETE AND FUNCTIONAL MECHANICAL INSTALLATION.
3. ANY OMISSIONS OR DISCREPANCIES IN THE DRAWINGS SHALL BE BROUGHT
TO THE IMMEDIATE ATTENTION OF THE CONSULTANT FOR CLARIFICATION.COMPENSATION FOR RELATED ADDITIONS TO THE CONTRACT AFTER BID
CLOSING WILL NOT BE CONSIDERED.
4. INSPECT JOB SITE SHALL PRIOR TO COMMENCEMENT OF WORK ANDALLOW FOR PROVISIONS MADE FOR ALL SITE CONDITIONS. EXACT
PLACEMENT OF MECHANICAL EQUIPMENT AND SIZING/ROUTING OFMECHANICAL SYSTEMS SHALL BE SITE CONFIRMED AND COORDINATED
WITH THE ARCHITECTURAL, ELECTRICAL, AND STRUCTURAL DRAWINGSAND TRADES. REROUTE/RESIZE DUCT WORK AND RELOCATE EQUIPMENT
AND COMPONENTS AS REQUIRED.
5. ALLOW FOR ANY MODIFICATIONS OR REBALANCING OF EXISTING SYSTEMSAND COMPONENTS AS REQUIRED TO COMPLETE RENOVATION WORK.
6. CAREFULLY EXAMINE ALL DRAWINGS OF OTHER TRADES. COORDINATETHE ELECTRICAL REQUIREMENTS OF ALL MECHANICAL EQUIPMENT WITH
THE ELECTRICAL CONTRACTOR. TYPE B OR C DYNAMIC FIRE DAMPERSSHALL BE INSTALLED AT ALL PENETRATIONS OF WALLS OR FLOORS
DENOTED TO BE FIRE SEPARATIONS ON THE ARCHITECTURAL DRAWINGS.
7. A MEANS OF BALANCING ALL SUPPLY AND EXHAUST TERMINALS USINGDUCT MOUNTED BALANCING DAMPERS SHALL BE PROVIDED. A TERMINAL
BALANCING DAMPER SHALL BE PERMITTED WHEN A DUCT MOUNTEDDAMPER WOULD BE INACCESSIBLE OR UNDESIRABLE.
8. THE USE OF FLEXIBLE DUCT WORK SHALL BE U.L.C. LISTED AND LIMITED TOONLY CONNECTIONS BETWEEN DUCT BRANCHES AND DIFFUSERS, AND
CONNECTIONS BETWEEN DUCT BRANCHES AND VARIABLE AIR VOLUMETERMINAL UNITS AND SHALL HAVE A MAXIMUM LENGTH OF 5 FT WHEN
FULLY STRETCHED.
9. ACCESS DOORS SHALL BE PROVIDED AS REQUIRED TO SERVICE DAMPERSAND MECHANICAL EQUIPMENT.
10. THE FINAL LOCATIONS OF GRILLES, REGISTERS AND DIFFUSERS SHALL BE
COORDINATED ON SITE WITH THE FINAL CEILING LAYOUT AND THE
EQUIPMENT OF OTHER TRADES.
11. A RETURN OR RELIEF GRILLE SHALL BE INSTALLED IN EACH SPACE THAT ISPROVIDED WITH SUPPLY AIR.
12. ELECTRICAL OR CONTROL WIRING INSTALLED WITHIN ALL PLENUMS SHALL
BE FT-6 RATED AND HAVE A FLAME SPREAD RATING BELOW 25 AND A
SMOKE DEVELOPED RATING BELOW 50 WHEN TESTED IN ACCORDANCE
WITH ASTM E84 (UL 723) ALL CONTROL WIRING SHALL BE INSTALLED IN 3 4"EMT CONDUIT WHEN RUNNING EXPOSED VERTICALLY.
13. ALL DUCT WORK AND EQUIPMENT SHALL BE INSULATED TO THE
REQUIREMENTS OF THE LATEST EDITION OF ASHRAE 90.1. ALL DUCT WORKWITHIN 10' (3M) OF THERMAL ENVELOPE PENETRATION AND ALL DUCT
WORK CONTAINING OUTSIDE AIR SHALL BE THERMALLY INSULATED.
14. ALL SIZES OF DUCTWORK INDICATED ON THE DRAWINGS DENOTE THE
INTERNAL OPEN DUCT DIMENSIONS. ALLOWANCES SHALL BE MADE FORANY INTERNAL INSULATION INDICATED ON THE DRAWINGS OR REQUIRED
IN THE SPECIFICATIONS.
15. ALL CUTTING AND/OR PATCHING OF ROOFS, WALLS OR FLOORS SHALL BEBY THE GENERAL CONTRACTOR UNLESS SPECIFICALLY INDICATED
OTHERWISE.
16. ALL DUCTWORK SHALL BE INSTALLED IN CONFORMANCE WITH THE LATEST
RELEVANT ASHRAE AND SMACMA STANDARDS FOR LOW PRESSUREDUCTWORK.
17. ALL DUCTWORK C/W CLASS 'C' SEALS PER SMACNA STANDARDS.
18. INSTALL DUCTWORK IN JOINT SPACE OR TIGHT TO UNDERSIDE OFJOIST/BEAMS.
H.V.A.C. LEGEND
GRILLE/REGISTER/DIFFUSER
RETURN AIR GRILLE
EXHAUST AIR GRILLE
SUPPLY DUCT RISE / DROP
RETURN DUCT RISE / DROP
EXHAUST DUCT RISE / DROP
ROUND DUCT RISE / DROP
THERMAL INSULATION
ACOUSTIC INSULATION
NEW DUCT
H.V.A.C. CONTROL
THERMOSTAT
BALANCING DAMPER
BACK DRAFT DAMPER/ MOTORIZEDDAMPER
DIFFUSER TAG
ELECTRIC HEAT TAG
EQUIPMENT TAG
DRAWING NOTE
T T
B M F S
FLOW
SIZE
TYPE
TAG
CAP.
#
EQP
3
DRAWINGS NOTES - H.V.A.C.
TRANSITION FROM MUA S/A CONNECTION TO ACOUSTICALLY LINEDPLENUM, TERMINATING IN FACTORY-SUPPLIED 4-WAY DIFFUSER BOX
INSTALLED APPROXIMATELY 6" BELOW BOTTOM CHORD JOIST. EMSCONTRACTOR TO SET UP AND VERIFY FACTORY-INSTALLED DOUBLE
REVERSE INTERLOCK BETWEEN MUA AND GREASE HOOD EXHAUSTFAN(S).
UNIT HEATER SUPPLIED AND INSTALLED BY MECHANICAL
CONTRACTOR. TEMPERATURE SENSOR (BY EMS CONTRACTOR) TO BEMOUNTED 60" A.F.F. C/W LEXAN COVER. INSTALL VERTICAL SEPARATED
COMBUSTION AIR KIT AS PER MANUFACTURER'S WRITTENINSTRUCTIONS.
AIR CURTAIN MOUNTED ABOVE DOOR AS PER MANUFACTURER'S
WRITTEN INSTALLATION INSTRUCTIONS. COORDINATE INSTALLATIONWITH STRUCTURE ON SITE.
EXTEND MINIMUM 16 MSG CONTINUOUSLY WELDED CARBON STEEL
EXHAUST DUCT FROM HOOD TO EXHAUST FAN ON ROOF. PROVIDEACCESS DOOR AT EACH CHANGE OF DIRECTION AND AT LEAST ONE
EVERY 12' OF HORIZONTAL RUN TO NFPA-96 STANDARDS. MAINTAIN18" CLEARANCE FROM COMBUSTIBLES AND 3" CLEARANCE FROM
LIMITED COMBUSTIBLES. REFER TO DETAILS FOR CLEARANCE
REDUCTION NOTES.
PROVIDE AND INSTALL WALL-MOUNTED EVAPORATOR FOR USE WITHCONDENSING UNIT C/W CONDENSATE DRAIN AND WALL MOUNTED
THERMOSTAT. COORDINATE MOUNTING LOCATION W/ CABINETRYON SITE.
RECONNECT RELOCATED DESTRATIFICATION FAN TO EXISTING
CONTROLLERS AS PER MANUFACTURER'S WRITTEN INSTALLATIONINSTRUCTIONS. CONFIRM EXISTING INSTALLATION OF CONTROLLERS
ON SITE, AND PROVIDE NEW CONTROLLERS AS REQUIRED.
ACOUSTICALLY LINED RETURN AIR ELBOW C/W BELL MOUTH FITTINGSIZED TO MATCH UNIT CONNECTION.
REFER TO ARCHITECTURAL ELEVATION FOR EXACT PLACEMENT OFRETURN AIR GRILLE.
EXTEND 6"Ø EXHAUST DUCT FROM GAS COOK TOP CONNECTION,BENEATH SLAB (USE PVS 18 GAUGE SURE SEAL SPIRAL DUCT AND
FITTINGS, AND SLOPED W/ CLEAN OUT AT LOW POINT) AND UPTHROUGH ROOF, AS PER MANUFACTURER'S WRITTEN INSTALLATION
INSTRUCTIONS.
RECONNECT 8" OVEN GREASE DUCT UP TO RELOCATED EXHAUST FANON ROOF.
SUGGESTED LOCATION OF TEMPERATURE SENSOR FOR RTU (BY EMSCONTRACTOR).
ACOUSTICALLY-LINED RETURN AIR PLENUM FROM CEILING RETURNGRILLE.
EXTEND 6" STAINLESS STEEL B-VENT FROM OVEN STEAM CONNECTION
THROUGH ROOF, AS PER MANUFACTURER'S WRITTEN INSTALLATIONINSTRUCTIONS.
UTILITY CABINET FOR CONTROLS AND FIRE SUPPRESSION.
ELECTRIC BASE BOARD HEAT SUPPLIED AND INSTALLED BY ELECTIRCAL.
NEW ROOF TOP UNIT TO BE CONNECTED INTO EXISTING EMS SYSTEMBY EMS CONTRACTOR.
EXISTING H.V.A.C. SYSTEM AND ASSOCIATED CONTROLS TO REMAIN.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
G
G G G G G G G G G G G G G G G G G G G G G G G G
GG
GG
G
G
GG
GG
GG
GG
GG
G
G
GG
G
G
G
EXISTING 34"
EXISTING 34"
EXISTING 2"
EXISTING 2"
EXISTING 2"
EXISTING 3 4"
EXISTING 2"EXISTING 2"
EXISTING 34"
EXISTING 2"
EXISTING 34"EXISTING 34"
EXISTING 34"
EXISTING 2"
EXISTING 1"
EXISTING 3 4"
EXISTING 34"
EXISTING 1"
EXISTING 112"
EXISTING 34"
EXISTING 3 4"
EXISTING 3 4"
EXISTING 34"
EXISTING 112"EXISTING 11
2"
EXISTING 114"
EXISTING 114"
EXISTING 1"
EXISTING 114"
EXISTING 34"
EXISTING 34"
EXISTING 3 4"
EXISTING 34"
EXISTING 34"
EXISTING 112"
EXISTING 3 4"
EXISTING 34"
EXISTING 3 4"
EXISTING 34" EXISTING 114"
EXISTING 1"
EXISTING 3 4"
EXISTING 3 4"
GG
G
G
R2
EF
R3
EF
D1
EF
D3
EF
D2
EF
D3
EF
RD-E1
RD-E1
RD-E1 RD-E1
RD-E1RD-E1
E17
EF
EXISTINGINTAKE
VENTILATOR E19
EF
EXISTING
REFRIGERATIONEQUIPMENT
G G G G G
#5
#12
#17
#6
#9
#8
ISOLATION VALVE
50Ø
32Ø
E6
RTU
E5
RTU
E4
RTU
E3
RTU
E1
RTU
D9
RTU
E2
RTU
E8
RTU
D1
MUA
E7
RTU
235 MBH
235 MBH
235 MBH235 MBH
235 MBH
125 MBH
78 MBH
400 MBH
E10
RTU
296 MBH
75 MBH
250 MBH
78 MBH
PRV-E1
PRV-D2
325 MBH
78 MBH
PRV-E3
235 MBH
PRV-E4
235 MBH
PRV-E5
235 MBH
PRV-E7
235 MBH
PRV-D6
120 MBH
PRV-E8
75 MBH
PRV-E9
510 MBH
PRV-D10
120 MBH
PRV-E11
235 MBH
235 MBH
PRV-E12
400 MBH
PRV-E13
78 MBH
PRV-E14
296 MBH
PRV-D15
80 MBH
PRV-E16
235 MBH
PRV-E17
580 MBH
EXISTING 3 4"
EXISTING 1"
#7
580 MBH
#1
DEMO
EXISTING 34"
3
2 1
2
6
3
2
3
2
5
5
4 4
6
#17
PRV-E18
125 MBH
2
7
ROOF PLAN - DEMOLITION
M3.1
SCALE:M3.1N
ROOF PLAN - DEMOLITION 1/8"=1'-0"
1
2-54 Adelaide Street Winnipeg Manit aob R3A 0V7
P 204 947 3775 F 204 947 3789 www.nejmark.mb.ca
N E J M A R KA R C H I T E C T
PROJECT TITLE:
SHEET TITLE:
COMMISSION NUMBER: SHEET NUMBER:
SOBEYS VARSITY COMMONS
1550- 8 St. E, SASKATOON,
SASKATCHEWAN
Drawings and specifications, as instruments of service are the property of the architect, the
copyright in the same being reserved to them. No reproduction may be made without the
permission of the architects, and when made, must bear their names. All prints to be returned.
The contractor is to verify dimensions and date noted herein with conditions on the site and is
held responsible for reporting discrepancy to the architects for adjustment.
DRAWN BY:
PRINTING DATE:
STAMP
No. ISSUED FOR DATE BY
1607
PSG2016.03.09
PERMIT AND TENDER1
JA
2016.03.09
2-472 STRADBROOK AVENUE
W I N N I P E G , M B R 3 L 0 J 9
( 2 0 4 ) 2 7 2 - 3 2 5 5
J O B :
GENERAL NOTES - ROOF PLAN
1. CONTRACTOR SHALL BE FAMILIAR WITH, REFER TO, AND COMPLYWITH ALL LOCAL CODES. ALL MECHANICAL WORK SHALL COMPLY IN
EVERY RESPECT WITH THE LATEST EDITIONS OF THE NATIONAL,PROVINCIAL AND MUNICIPAL BUILDING CODES, NFPA, ASHRAE,
SMACNA, AND ANY ADDITIONAL REQUIREMENTS OF THE LOCALAUTHORITY HAVING JURISDICTION.
2. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHALL NOT BE SCALED.
THEY ESTABLISH DESIGN INTENT AND ARE NOT INTENDED TO BEDETAILED INSTALLATION DOCUMENTS. MECHANICAL CONTRACTOR
SHALL ALLOW IN THEIR CONTRACT PRICE ALL COMPONENTSREQUIRED TO PROVIDE A COMPLETE AND FUNCTIONAL MECHANICAL
INSTALLATION.
3. ANY OMISSIONS OR DISCREPANCIES IN THE DRAWINGS SHALL BE
BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONSULTANT FORCLARIFICATION. COMPENSATION FOR ADDITIONS TO THE CONTRACT
AFTER BID CLOSING WILL BE REJECTED.
4. INSPECT JOB SITE SHALL PRIOR TO COMMENCEMENT OF WORK ANDALLOW FOR PROVISIONS MADE FOR ALL SITE CONDITIONS. EXACT
PLACEMENT OF MECHANICAL EQUIPMENT AND SIZING/ROUTING OFMECHANICAL SYSTEMS SHALL BE SITE CONFIRMED AND COORDINATED
WITH THE ARCHITECTURAL, ELECTRICAL, AND STRUCTURALDRAWINGS AND TRADES.
5. CAREFULLY EXAMINE ALL DRAWINGS OF OTHER TRADES.
COORDINATE THE ELECTRICAL REQUIREMENTS OF ALL MECHANICALEQUIPMENT WITH THE ELECTRICAL CONTRACTOR.
6. ALL CUTTING AND/OR PATCHING OF ROOFS SHALL BE BY THEGENERAL CONTRACTOR UNLESS SPECIFICALLY INDICATED OTHERWISE.
7. PROVIDE DIELECTRIC COUPLINGS WHERE COMPONENTS OF DISSIMILARMETAL ARE JOINED.
8. GAS PIPING SHALL BE BLACK STEEL TO ASTM A-53 SCHEDULE 40, 150 LB.STANDARD BLACK MALLEABLE IRON SCREW FITTING FOR SIZES BELOW
212". ALL MATERIALS AND INSTALLATION SHALL CONFIRM TO ALL
REQUIREMENTS OF THE LATEST EDITION OF CSA B149.1 NATURAL GAS
AND PROPANE INSTALLATION CODE AND ALL LOCAL GAS NOTICES.
DRAWINGS NOTES - ROOF PLAN
REMOVE ROOF TOP UNIT FROM SITE. GENERAL CONTRACTORTO REPAIR ROOF OPENING.
REMOVE BRANCH GAS PIPING AND CAP AT MAIN.
GENERAL CONTRACTOR TO PATCH ABANDONED PITCH BOX.
TEMPORARILY REMOVE EXHAUST FAN AND ASSOCIATED
CONTROLS. RETAIN FOR REINSTALLATION. REFER TO H.V.A.C.AND ROOF RENOVATION PLANS.
REMOVE EXHAUST FAN AND ASSOCIATED ACCESSORIES FROMSITE. GENERAL CONTRACTOR TO REPAIR ROOF OPENING.
REMOVE GOOSENECK FROM SITE. GENERAL CONTRACTOR TOREPAIR ROOF OPENING.
REMOVE MAKE UP AIR UNIT FROM SITE. GENERAL CONTRACTORTO REPAIR ROOF OPENING.
1
2
3
4
5
6
7
ROOF LEGENDDEMOLISHED NATURAL GAS
NATURAL GAS
ISOLATION VALVE
UNION
ROOF DRAIN
DRAWING NOTE
EQUIPMENT TAG
G
#
#
EQP
G
G G G G G G G G G G G G G G G G G G G G G G G G
GG
GG
G
G
GG
GG
GG
GG
GG
G
G
GG
G
G
G
G
G G G G G G G G G G G G
EXISTING 2"
EXISTING 2"
EXISTING 2"
EXISTING 3 4"
EXISTING 2"EXISTING 2"
EXISTING 3 4"
EXISTING 2"
EXISTING 34"EXISTING 3 4"
EXISTING 3 4"
EXISTING 2"
EXISTING 1"
EXISTING 34"
EXISTING 3 4"
EXISTING 1"
EXISTING 34"
EXISTING 112"EXISTING 11
2"
EXISTING 114"
EXISTING 114"
EXISTING 1"
EXISTING 114"
EXISTING 34"
EXISTING 34"
EXISTING 3 4"
EXISTING 3 4"
EXISTING 3 4"
EXISTING 112"
EXISTING 34"
EXISTING 34"
EXISTING 34"
EXISTING 114"
EXISTING 34"
EXISTING 34"
6
EF
5
EF
4
EF
1
RTU
GG
G
G
R2
EF
R3
EF
G G G
GG
GG
315 MBH
60 MBH
GG
GG
114" @ 7" WC
112" @ 7" WC
436 MBH
2
5
RD-E1
1" @ 2 PSI
34" @ 2 PSI
GG
G
RD-E1
RD-E1 RD-E1
RD-E1RD-E1
34" @ 2 PSI
1" @ 7" WC
114" @ 7" WC
34 " @ 7" WC
1 " @ 7" WC
2" @ 2 PSI
2" @ 7" WC
1" @ 2 PSI
114" @ 2 PSI
E17
EF
EXISTINGINTAKE
VENTILATOR E19
EF
EXISTINGREFRIGERATION
EQUIPMENT
G G G G G
452 MBH
#5
#12
#17
#9
#8
ISOLATION VALVE
50Ø
32Ø
RD-2
150 MBH
3.4 IN HEAD
2.8 HR DDT
14 GPM
2050 SQ FT
6" RISE
1 NOTCH
RD-1
5.5 IN HEAD
3.9 HR DDT
19.6 GPM
4120 SQ FT
6" RISE
1 NOTCH
RD-1
1.4 IN HEAD
2.6 HR DDT
8.5 GPM
988 SQ FT
6" RISE
1 NOTCH
RD-1
E6
RTU
E5
RTU
E4
RTU
E3
RTU
E1
RTU
E2
RTU
E8
RTU
E7
RTU
2
MUA
3
RTU
2
RTU
1
MUA
235 MBH
235 MBH
235 MBH235 MBH
235 MBH
125 MBH
78 MBH
400 MBH
E10
RTU
75 MBH
250 MBH
PRV-E1
325 MBH
PRV-E3
235 MBH
PRV-E4
235 MBH
PRV-E5
235 MBH
PRV-E7
235 MBH
PRV-E8
75 MBH
PRV-E9
510 MBH
PRV-E11
235 MBH
235 MBH
PRV-E12
400 MBH
PRV-E13
78 MBH
PRV-E16
235 MBH
PRV-E17
580 MBH
EXISTING 1"
#7
GG
GG
GG
G
G G G G G G G G G G
60 MBH
150 MBH
580 MBH
34" @ 7" WC 3
4" @ 2 PSI
#1
114" @ 2 PSI 11
4" @ 2 PSI 112" @ 2 PSI
112" @ 2 PSI
112" @ 2 PSI
112" @ 2 PSI
1
22
2
2
3
4
6
666
7
88
8
1
CU9
RD-3
10
11
8
13
12
12
#17
PRV-E18
125 MBH
PRV-1
60 MBH
PRV-2
318 MBH
PRV-3
452 MBH
PRV-4
315 MBH
PRV-5
436 MBH
PRV-6
150 MBH
RD-28
ROOF PLAN - RENOVATION
M3.2
SCALE:M3.2N
ROOF PLAN - RENOVATION1/8"=1'-0"
1
2-54 Adelaide Street Winnipeg Manit aob R3A 0V7
P 204 947 3775 F 204 947 3789 www.nejmark.mb.ca
N E J M A R KA R C H I T E C T
PROJECT TITLE:
SHEET TITLE:
COMMISSION NUMBER: SHEET NUMBER:
SOBEYS VARSITY COMMONS
1550- 8 St. E, SASKATOON,
SASKATCHEWAN
Drawings and specifications, as instruments of service are the property of the architect, the
copyright in the same being reserved to them. No reproduction may be made without the
permission of the architects, and when made, must bear their names. All prints to be returned.
The contractor is to verify dimensions and date noted herein with conditions on the site and is
held responsible for reporting discrepancy to the architects for adjustment.
DRAWN BY:
PRINTING DATE:
STAMP
No. ISSUED FOR DATE BY
1607
PSG2016.03.09
PERMIT AND TENDER1
JA
2016.03.09
2-472 STRADBROOK AVENUE
W I N N I P E G , M B R 3 L 0 J 9
( 2 0 4 ) 2 7 2 - 3 2 5 5
J O B :
GENERAL NOTES - ROOF PLAN
1. CONTRACTOR SHALL BE FAMILIAR WITH, REFER TO, AND COMPLYWITH ALL LOCAL CODES. ALL MECHANICAL WORK SHALL COMPLY IN
EVERY RESPECT WITH THE LATEST EDITIONS OF THE NATIONAL,PROVINCIAL AND MUNICIPAL BUILDING CODES, NFPA, ASHRAE,
SMACNA, AND ANY ADDITIONAL REQUIREMENTS OF THE LOCALAUTHORITY HAVING JURISDICTION.
2. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHALL NOT BE SCALED.THEY ESTABLISH DESIGN INTENT AND ARE NOT INTENDED TO BE
DETAILED INSTALLATION DOCUMENTS. MECHANICAL CONTRACTORSHALL ALLOW IN THEIR CONTRACT PRICE ALL COMPONENTS
REQUIRED TO PROVIDE A COMPLETE AND FUNCTIONAL MECHANICALINSTALLATION.
3. ANY OMISSIONS OR DISCREPANCIES IN THE DRAWINGS SHALL BE
BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONSULTANT FORCLARIFICATION. COMPENSATION FOR ADDITIONS TO THE CONTRACT
AFTER BID CLOSING WILL BE REJECTED.
4. INSPECT JOB SITE SHALL PRIOR TO COMMENCEMENT OF WORK AND
ALLOW FOR PROVISIONS MADE FOR ALL SITE CONDITIONS. EXACTPLACEMENT OF MECHANICAL EQUIPMENT AND SIZING/ROUTING OF
MECHANICAL SYSTEMS SHALL BE SITE CONFIRMED AND COORDINATEDWITH THE ARCHITECTURAL, ELECTRICAL, AND STRUCTURALDRAWINGS AND TRADES.
5. CAREFULLY EXAMINE ALL DRAWINGS OF OTHER TRADES.COORDINATE THE ELECTRICAL REQUIREMENTS OF ALL MECHANICAL
EQUIPMENT WITH THE ELECTRICAL CONTRACTOR.
6. ALL CUTTING AND/OR PATCHING OF ROOFS SHALL BE BY THEGENERAL CONTRACTOR UNLESS SPECIFICALLY INDICATED OTHERWISE.
7. PROVIDE DIELECTRIC COUPLINGS WHERE COMPONENTS OF DISSIMILAR
METAL ARE JOINED.
8. GAS PIPING SHALL BE BLACK STEEL TO ASTM A-53 SCHEDULE 40, 150 LB.STANDARD BLACK MALLEABLE IRON SCREW FITTING FOR SIZES BELOW
212". ALL MATERIALS AND INSTALLATION SHALL CONFIRM TO ALL
REQUIREMENTS OF THE LATEST EDITION OF CSA B149.1 NATURAL GAS
AND PROPANE INSTALLATION CODE AND ALL LOCAL GAS NOTICES.
DRAWINGS NOTES - ROOF PLAN
EXTEND NEW 112" @ 2 PSI GAS LINE UP BUILDING ADJACENT TO
EXISTING 2" @ 2 PSI NATURAL GAS PIPE. CONNECT NEW GAS
LINE TO GAS MAIN IMMEDIATELY DOWNSTREAM OF EXISTING 2"MAIN. CONFIRM ADEQUACY OF EXISTING GAS METER WITH
LOCAL UTILITY AND COORDINATE REPLACEMENT IF NECESSARY.TAKE OUT REQUIRED PERMIT AND PAY ALL ASSOCIATED FEES.
EXISTING GAS PIPING THROUGH EXISTING PITCH BOX TOREMAIN.
NEW GAS PIPING THROUGH NEW PITCH BOX TO SERVE NEWHMR EQUIPMENT.
NEW GAS PIPING THROUGH NEW PITCH BOX TO SERVE NEWUNIT HEATER.
GAS PIPE THROUGH ROOF WITHIN PITCH BOX TO SERVEBARBECUE CONNECTION AND GAS RANGE.
EXPANSION LOOP.
CONCENTRIC COMBUSTION AIR AND VENT PIPES SERVING UNITHEATER THROUGH ROOF. COORDINATE EXACT LOCATION ON
SITE. INSTALL AS PER MANUFACTURER'S WRITTEN INSTALLATIONINSTRUCTIONS.
THERMALLY INSULATE RAIN WATER LEADER FROM ROOF DRAIN
AND ROOF DRAIN BODY. REFER TO PLUMBING DRAWING FORCONTINUATION.
PROVIDE AND INSTALL CONDENSING UNIT FOR USE WITH
ASSOCIATED EVAPORATOR .
B-VENT FROM PIZZA OVEN THROUGH ROOF IN ACCORDANCE
WITH MANUFACTURER'S WRITTEN INSTALLATIONINSTRUCTIONS AND TO THE REQUIREMENTS OF THE
AUTHORITY HAVING JURISDICTION.
COMMUNITY ROOM VENT THROUGH ROOF IN ACCORDANCE
WITH MANUFACTURER'S WRITTEN INSTALLATIONINSTRUCTIONS.
REINSTALL RELOCATED OVEN EXHAUST FAN ON NEW ROOFCURB.
THERMALLY INSULATE AND HEAT TRACE RAIN WATER LEADER
FROM ROOF DRAIN AND INSULATED ROOF DRAIN BODY. REFERTO PLUMBING DRAWING FOR CONTINUATION.
1
2
3
4
5
6
7
8
9
10
11
12
13
ROOF LEGENDNATURAL GAS
ISOLATION VALVE
UNION
ROOF DRAIN
DRAWING NOTE
EQUIPMENT TAG
G
#
#
EQP