IFC CONVERSION ISSUEMEP HVAC– Methodology
1. Create sample project and extract infoe.g Families, Element ID, System Classification, Dim ension, Quantity
2. Conversion of native .rvt file into IFC
3. View IFC file from Solibri
4. View IFC file from Revit MEP 2012
5. View IFC file from EDModel Server
6. Convert IFC into .rvt file.
Trade Tested :
Cold Water, Sanitary, Fire Protection
Tested By : Jeremy Loh
IFC CONVERSION ISSUEMEP – Plumbing (Domestic Water & Sanitary) & Fire Pro tection
Revit (.rvt) Solibri (.ifc)EDM Model Server (.ifc)
Revit (.ifc)
Domestic Water
Sanitary
Fire Protection
IFC CONVERSION ISSUE
MEP – Plumbing (Domestic Water & Sanitary) & Fire Pr otection
Observation #1: IFC does not specifically points out a ‘family’ parameter.Instead, Family, Type and Element ID is clumped into aparameter called “name”
Native .rvt Solibri .ifc EDM Model Server .ifc
Family Type Name Name
M_Elbow - Generic StandardM_Elbow -
Generic:Standard:Standard:568140
M_Elbow -Generic:Standard:Standard:568140
M_Split Case Pump - Horizontal
31.55 LPS - 15.8 Meter Head
M_Split Case Pump -Horizontal:31.55 LPS - 15.8 Meter
Head:31.55 LPS - 15.8 Meter Head:566469
M_Split Case Pump - Horizontal:31.55 LPS - 15.8 Meter Head:31.55 LPS -
15.8 Meter Head:566469
M_Multi-Purpose Valve - Straight - 80-300 mm -
Flanged80 mm
M_Multi-Purpose Valve -Straight - 80-300 mmm -
Flanged:80 mm: 80 mm:612492
M_Multi-Purpose Valve - Straight -80-300 mm - Flanged:80 mm: 80
mm:612492
MEP – Plumbing (Domestic Water & Sanitary) & Fire Pr otection
IFC CONVERSION ISSUE
Observation #2: Category names for models changes when exported to IFC and viewed in Solibri or EDM MS.
All categories (in IFC) when viewed in Revit becomes Generic Models
Revit (.rvt) Solibri (.ifc) EDM MS (.ifc) Revit (.ifc)
Pipes Pipe Flow Segment Generic Model
Pipe Fittings Pipe Fitting Flow Fitting Generic Model
Pipe Accessories Valve Flow Controller Generic Model
Plumbing Fixture / Sprinklers
Flow Terminal Flow Terminal Generic Model
Mechanical Equipment
ObjectBuilding Element
ProxyGeneric Model
IFC CONVERSION ISSUEMEP – Plumbing (Domestic Water & Sanitary) & Fire Pr otection
Observation #3: IFC in Revit loses all data while family and type parametersfollows the name of the object / model as seen in Solibri / EDM MS.
The Element ID in Revit (.ifc) has also changed from its original ID.
Revit (.rvt) Solibri (.ifc)EDM ModelServer (.ifc)
Revit (.ifc)
Family Type Element ID
Name Type Name Object Type
Family Type Element ID
M_Sink -Scrub Floor
760 mmx560
mm561632 A* Undefined A*
M_Sink -Scrub
Floor:760 mmx560
mm
A* A* 557475
M_Flange -Slip-on -
Steel - Class 300
Standard 586513 B* Standard B* Standard B* B* 557590
A* : M_Sink - Scrub Floor:760 mmx560 mm:760 mmx560 mm:561632B* : M_Flange - Slip-on - Steel - Class 300:Standard:Standard:586513
IFC CONVERSION ISSUEMEP – Plumbing (Domestic Water & Sanitary) & Fire Pr otection
Observation #4: Pipe types when in –
Solibri : Follows the name of the first similar type of pipe which was drawn in Revit
EDM Model Server : Shows the Element ID of the pipe type
Revit Solibri EDM Model Server Remarks
Family Type Element ID
Name Type Name Object Type
Pipe Types
PVC (261488)
603708Pipe
Types:PVC:603708Pipe
Types:PVC:603708Pipe
Types:PVC:603708 261488First PVC
pipe drawn in Revit.
Pipe Types
PVC (261488)
610317Pipe
Types:PVC:610317Pipe
Types:PVC:603708Pipe
Types:PVC:610317 261488
IFC CONVERSION ISSUEMEP – Plumbing (Domestic Water & Sanitary) & Fire Pr otection
Observation #5: There is no colour control when viewing in Solibri / EDM Model Server.
Solibri (.ifc) EDM Model Server (.ifc)
Domestic Water
1) Pipes & Pipe Fittings– Orange
2) Plumbing Fixtures / Sprinklers & Valves – Pink
3) Mech. Equipment – Gray
1) Pipes – Green
2) Pipe Fittings – Blue
3) Valves – Orange
4) Plumbing Fixtures / Sprinklers – Light Brown
5) Mech. Equipment – Dark Brown
Sanitary
Fire Protection
IFC CONVERSION ISSUEMEP – Plumbing (Domestic Water & Sanitary) & Fire Pr otection
Observation #6: Graphical representation of insulation is missing. Insulation data is still intact (except when viewing ifc in Revit).
(.rvt) Revit
(.ifc)Solibri
(.ifc)EDM Model Server
(.ifc) Revit
*notice how the pipe elbow has a insulation cover and the rest doesn’t
PWOI
PWI
PWOI
PWI
PWOI
PWOI – Pipe without InsulationPWI – Pipe with Insulation
IFC CONVERSION ISSUEMEP – Plumbing (Domestic Water & Sanitary) & Fire Pr otection
Observation #7: Parameters relating to pipe connectors are automatically converted from metric to imperial
Parameters Revit (.rvt) Solibri (.ifc)EDM Model Server (.ifc)
Tank Radius 289 mm 289 mm 289 mm
Tank Height 889 mm 889 mm 889 mm
Outlet Radius 25 mm 0.082 ‘ 0.082021‘
Outlet Diameter 50 mm 0.164 ‘ 0.164045‘
Leg Height 401 mm 401 mm 401 mm
Handrail Length 305 mm 305 mm 305 mm
Handrail Distance 305 mm 305 mm 305 mm
Cap Radius 321 mm 321 mm 321 mm
Bottom Radius 578 mm 578 mm 578 mm
Bottom Height 77.4 mm 77.44 mm 77.437317 mm
*M_Mixing Tank_Bottom Dish was used as an example
IFC CONVERSION ISSUEMEP – Plumbing (Domestic Water & Sanitary) & Fire Pr otection
Observation #8: Electrical Data & Flow Pressure (where applicable) has beenconverted to an unknown unit, th
Flow rate is converted from metric to imperial.
Family : M_Hose Reel Cabinet – Surface MountedType : 25 mm
Revit (.rvt) Solibri (.ifc) EDM MS (.ifc)
Flow Pressure 34400.00 Pa 10,485.12 10485.12
Flow Rate 2.52 L/s 0.089 ft3/s 0.088993 ft3/s
Family : M_Split Case Pump - HorizontalType : 31.55 LPS – 15.8 Meter Head
Revit (.rvt) Solibri (.ifc) EDM MS (.ifc)
Apparent Load 81000.00 VA 871876.744 871876.743753
Voltage 460 V 4951.399 4951.398792
Pump Speed 1150 RPM 1150 RPM 1150 RPM
IFC CONVERSION ISSUEMEP – Plumbing (Domestic Water & Sanitary) & Fire Pr otectionObservation #9: Plumbing fixtures loses all data except Family, Type (EDM
Model Server), & Element ID when exported to IFC
A typical model would have such data as shown on the left.
(Continue to next slide…)
IFC CONVERSION ISSUEMEP – Plumbing (Domestic Water & Sanitary) & Fire Pr otection
Observation #9: Plumbing fixtures loses all data except Family, Type (EDM Model Server), & Element ID when exported to IFC
Data such as PSET_Revit_Type_Identity Data and others go missing.
*Viewing in Solibri(Continue to next slide…)
IFC CONVERSION ISSUEMEP – Plumbing (Domestic Water & Sanitary) & Fire Pr otection
Observation #9: Plumbing fixtures loses all data except Family, Type (EDM Model Server), & Element ID when exported to IFC
*Viewing in EDM Model Server
The only data available for plumbing fixtures.
IFC CONVERSION ISSUEMEP – Plumbing (Domestic Water & Sanitary) & Fire Pr otection
Observation #10: Drain outlet hosted at L2 Slab is shown as a L1 item in Solibri and EDM MS.
Viewing in Revit (.rvt)
(Continue to next slide…)
IFC CONVERSION ISSUEMEP – Plumbing (Domestic Water & Sanitary) & Fire Pr otection
Observation #10: Drain outlet hosted at L2 Slab is shown as a L1 item in Solibri and EDM MS.
Viewing in Solibri (.rvt) Viewing in EDM MS (.rvt)
IFC CONVERSION ISSUEMEP – Plumbing (Domestic Water & Sanitary) & Fire Pr otection
Observation #11: EDM MS has an extra set of data that Solibri does not havewhich refers to the type parameter (in Revit).
Viewing in Solibri
(Continue to next slide…)
IFC CONVERSION ISSUEMEP – Plumbing (Domestic Water & Sanitary) & Fire Pr otection
Observation #11: EDM MS has an extra set of data that Solibri does not havewhich refers to the type parameter (in Revit).
Viewing in EDM MS
IFC CONVERSION ISSUEMEP – Plumbing (Domestic Water & Sanitary) & Fire Pr otection
Conclusion In relation to Observation #
1 2 3 4 5 6 7 8 9 1 0 1 1
1) Loss of data when exporting to IFC is minimal. Loss of data during importing IFC into Revit is extensiove.
x x x x
2) EDM Model Server has a slightly better mapping method than Solibri in which the type of the model is mapped correctly.
x x
3) IFC files are not good for Mechanical / Electrical analysis x x
4) Revit’s mapping of IFC data (both importing and exporting) requires more improvement, thus rendering it especially useless in importing IFC data.
x x x x
5) Viewing all models in IFC may be confusing as there is no colour control available to differentiate based on system.
x
6) Each IFC viewer has their own method of mapping IFC data. Therefore, this method should be explained by the vendor.
x x
7) Training to understand how IFC works and how a certain program maps IFC data is essential in order to ensure parameter is channeled to the right data.
x x x x x x x x x x x